MHAFB_Facility2215_Drawings_Part_3.pdf
PDF 29 MB Posted
- Attached to
- Repair and Minor Renovation of Squadron Operations Building 2215 at Mountain Home Air Force Base, Idaho
- Solicitation number
- W912DW19R0028
About this file
This notice announces a proposed contract action to solicit for a minor renovation project at Mountain Home Air Force Base in Idaho. The project scope includes replacing the roof and HVAC system, remodeling restrooms to meet ADA requirements, adding exterior windows and skylights, and relocating interior walls and providing new interior finishes for a 61,472 square foot building. The contract value is estimated between $5 million and $10 million. The solicitation will be limited to eligible 8(a) firms located in Idaho, Oregon, Utah, or Washington and will be posted on July 31, 2019 via the Federal Business Opportunities website under solicitation number W912DW19R0028. Interested vendors should monitor the website for any updates.
RFP W912DW19R0028 - Drawings Package 3 of 6
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
VAULT
CRYPTO
OFFICE
EXEC
OSS CC
UFC
SEC ADMINADMIN
BRF
VEST
C O
R
ID
CORRIDOR
OSK
ROOM
MOM
MEN
WOMEN
JAN
CONFERENCE
GLO
OFC
SGT
1STUMP
PLN
MSN
STOR
ADMIN
DO
COMM
SUPT
SQ
TRNG
SERE
HARMSERE
MAIN
113 114 115
106 107
119 120
122 124
126125
185 186
188 189
170 171
HARM
CVN 1
CVN 2 CVN 3
CVN 4
CVN 5
CVN 7
CVN 6
V
N
CVN 10
CVN 9
2 3 4
D e s ig n d b y h e c k e ra w a d F il te
P ro je c t
H
M
IL
L
S m o l
A p v s c ri p ti
Drawing Number:
A B C D E F G H
GUNFIGHTERS
HOME OF THE
COMBAT COMMAND
AIR
DEPARTMENT OF
MOUNTAIN HOME AFB.
THE AIR FORCE
MOUNTAIN HOME
AFB
U.S. AIR FORCE
366 CES/CECD
1030 LIBERATOR ST.
MOUNTAIN HOME AFB, ID
83648-5442
E t F t S tr e u it
-1
.d g e c je c t
B is e I d a h
-7
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:20:00 PM
SHEET of
/2
IT
Y
KEY PLAN
PLAN TRUE
A C
B D
Q
Z
-8
IR
U
T
IF
IE
IN
IG
M-118 k
IC
682783_2215M-118.dgn
682783
1/8" = 1'-0"
LINE
MATCH M-117
SHEET KEYNOTES
GENERAL NOTES
X
W
K
AREA D HVAC UPPER DUCTWORK PLAN
64 149
2TYP
2TYP
ARCHITECTURAL CEILING PLAN.
TUBE-TYPE SKYLIGHT FIXTURE. SEE 2.
M-114 FOR CONTINUATION.
DUCTWORK DOWN TO LOWER ELEVATION, SEE 1.
M300
UNUSED BY THIS CONTRACTOR. GENERAL CONTRACTOR SHALL PROVIDE IN-FILL.
DETAIL 7/M-502. IDENTIFY ALL EXISTING OPENINGS LEFT AS A RESULT OF DEMOLITION AND
BARS INSTALLED PER DETAIL 3/M-504. ALL DUCTWORK SHALL HAVE SOUND ATTENUATION PER
TO ROOF DECK. ALL DUCTWORK THROUGH THIS WALL EXCEEDING 80 SQ IN SHALL HAVE SECURITY
BOLD CENTERLINE REPRESENTS SECURED AREA BOUNDARY WITH GYPBOARD WALLS EXTENDING 4.
THRU EITHER NEW OR EXISTING OPENINGS.
DUCTWORK SHALL BE FULLY INSULATED AND AT NO REDUCTION IN FREE AREA WHEN PASSING
RUN-OUTS TO TAKE ADVANTAGE OF NEAR-BY OPENINGS IN LIEU OF PROVIDING NEW OPENINGS.
COORDINATION IS PERFORMED WITH OTHER TRADES. THIS CONTRACTOR MAY ADJUST DUCT
OPENINGS IN CMU WALLS ABOVE CEILING MAY BE REUSED BY THIS CONTRACTOR PROVIDED THAT 3.
UNUSED BY THIS CONTRACTOR. GENERAL CONTRACTOR SHALL PROVIDE IN-FILL.
DETAIL 7/M-502. IDENTIFY ALL EXISTING OPENINGS LEFT AS A RESULT OF DEMOLITION AND
BARS INSTALLED PER DETAIL 3/M-504. ALL DUCTWORK SHALL HAVE SOUND ATTENUATION PER
ROOF DECK. ALL DUCTWORK THROUGH THIS WALL EXCEEDING 80 SQ IN SHALL HAVE SECURITY
BOLD DASHED LINE REPRESENTS SECURED AREA BOUNDARY WITH CMU WALLS EXTENDING TO 2.
SOLID SHADED WALL REPRESENTS EXISTING CMU WALL UP TO ROOF DECK.1.
WALL-TYPE NOTES
CONFLICT WITH DUCT ROUTING.
EXISTING ROOF TRUSS CROSS-BRACING IS IN
COORDINATE WITH STRUCTURAL TRADES WHERE D.
DRAWING M-300 FOR DEMARCATION LINE.
LOWER HVAC DUCTWORK. REFER TO SECTION
SEE DRAWINGS M-111 THROUGH M-114 FOR C.
SEE M-500 AND M-501 FOR DETAILS.B.
SEE M-001 FOR MECHANICAL LEGEND.A.
2019-04-29T07:47:44-0600
Price, Ted INC00033148
CRYPTO
EXEC
OSS CC
UFC
SEC ADMINADMIN
BRF
WCCS AREA
SECURE
OPER
COMP
MUNS
AFE
CHEM
HAZ
BENC
MAIN SHOP
CORRIDORCORRIDOR
WALKWAY
STORAGE
AUDITORIUM
ELECTRICAL
MECHANICAL
STORAGE
FLT CHF
SAD
COMMON AREA
INTEL
PLANNING
INTEL
OSK
MOM
OFC
SGT
1STUMP
PLN
MSN
ADMIN
COMM
SQ
PHYSIO
AERO
HARMSERE
MAIN
MAN
AERO
UDM
CONTROL
CONFERENCE OPS
RANGE
103102
113 114 115
106 107
119 120
122 124
126125
2 174 175
176 178
185 186
188 189
170 171
FLT/CC
OSO
MGR
P5
CHAPLAIN
OSOTSCHED
AIR SPACE
HARM
HERITAGE
CVN 1
CVN 2 CVN 3
CVN 4
CVN 5
CVN 7
CVN 6
ROOM 1
ROOM 2
CVN 10
ROOM 3
CVN 9
PARA ROOM
TRAINING
2 3 4 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:24:40 PM
PT
682783_2215M-120.dgn
J
682783682783
1/16" = 1'-0"
OVERALL HYDRONIC PLAN
CAB-1
CAB-2
CAB-3
CAB-4
M-403
VAV-105
KEYED NOTESX
3/4" HWR
3/4" HWS
1" HWR
1" HWS
1" HWR
1" HWS
M-404
1 1/4" HWR (E)
1 1/4" HWS (E)
1 1/4" HWR (E)
1 1/4" HWS (E)
1/2" HWR (E)
1/2" HWS (E)
3/4" HWR (E)
3/4" HWS (E)
1/2" HWR (E)
1/2" HWS (E)
1 1/2" HWR
1 1/2" HWS
VAV-106
VAV-102 VAV-103
VAV-101
VAV-1008
VAV-104
14965
M-120
4" CHWR
4" CHWS
CH-1
CH-2
DB-1
EXTEND 1/2" HWS & HWR LINES TO NEW VAV LOCATIONS.8.
OF THE EXISTING PIPING.
OF AHU COIL CONNECTION. COORDINATE THE LOCATION
APPROXIMATE LOCATION. REPLACE PIPING UPSTREAM
CONNECT NEW 1 1/4" HWS & HWR LINE AT THIS 7.
HEATER.
RUN NEW HWS & HWR LINES TO THE EXISTING UNIT6.
GPM.
DETAIL 5 ON SHEET M-502. BALANCE WATER FLOW TO 3.0
REPLACE ALL PIPING TO UNIT HEATER SIMILAR TO
EXISTING UNIT HEATER TO REMAIN IN SERVICE.5.
CAP EXISTING 1" HWS & HWR LINES4.
TRANSMITTERS ON HWS & HWR.
INSTALL DIFFERENTIAL PRESSURE & TEMPERATURE 3.
SEE M-403 FOR CONTINUATION OF HYDRONIC PIPING.2.
OFFSET HWS & HWR TO ALLOW FOR THERMAL EXPANSION. 1.
HYDRONIC PIPING RUNOUT SIZES.
REFER TO VAV BOX AND CABINET HEATER SCHEDULE FORB.
CONFIRM INFORMATION BEFORE BEGINNING ANY WORK.
AVAILABLE INFORMATION. CONTRACTOR SHALL
INFORMATION SHOWN ON DRAWINGS IS BASED ON BESTA.
2019-04-29T07:48:26-0600
Price, Ted INC00033148
AFE AFE TRAINING CORRIDOR
FLT CHF
e c k e d F il je c t s c ri p ti t
S tr e it
-3 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:29:21 PM
M-300 k
682783_2215M-300.dgn
3/16"=1'-0"
SECTION
M-110
M-113
M-111
ALL
TYP
48"
NTS
HOLD STRUT TIGHT TO BOTTOM OF JOIST.
CONNECT TO EXISTING ROOF JOIST.
STRUT SUPPORT SYSTEM
TYP ALL
TYP 4 PER PLATE
3/8"x4" ANCHORS
BEHIND BOILERS AND BOILER PUMPS.
2. FOR BOILER SUPPORTS INSTALL ALONG FULL LENGTH OF WALL
1. FOR ELECTRICAL PANELS INSTALL WITH 4 TOTAL VERTICALS.
NOTES:
DOUBLE NUT
/4
IO
AND ROOF
EXISTING METAL DECKING
JOISTS
EXISTING ROOF
JOISTS
EXISTING ROOF
TO LATERAL BRACE, TYP ALL
SUPPORT. TIE-IN VERTICAL RISERS
TRUSS TO TRUSS TO PROVIDE LATERAL
EXTEND LATERAL BRACES FROM
TYP VERTICAL
P1001
EQV. TO A UNI-STRUT
TYP HORIZONTAL
P1000
EQV. TO A UNI-STRUT
AS REQUIRED
ADD ADDITIONAL STRUT
CRAWL SPACE REFER TO ARCHITECTURAL DRAWINGS.
SPRINKLER HEADS LOCATED THROUGHOUT CRAWL SPACE. FOR ACCESS TO 6.
EXTEND BENEATH MECHNCIAL ROOM. SHOWN FOR CLARITY.
BENEATH SHOWN ROOMS: 153, 154, 148, 146, AND 145, BUT DOES NOT
EXISTING DEPRESSED ACCESS FLOOR (NOT DRAWN TO SCALE). EXTENDS 5.
APPROXIMATELY 12' AFF.
INSTALL ALL WATER PIPING AT SAME ELEVATION AS EXISTING PIPING WORK, 4.
INSULATION. PROVIDE SEALANT AT ALL JOINTS TO MAKE WALL AIR TIGHT.
AROUND ALL PORTIONS OF THE DUCTWORK AND PIPING WITH FIBERGLASS
TO CMU WALL. COMPLETELY PACK THE SPACE IN THE WALL CAVITY
ON THE BUILDING SIDE. USE MINIMUM OF 20 GA SHEET METAL AND TAPCON
PROVIDE ESCUTCHEON/FLASHING ON BOTH THE MECHANICAL ROOM AND
DUCTWORK AND PIPING THAT PENETRATES THE MECHANICAL ROOM WALL.
PROVIDE GALVANIZED SHEET METAL ESCUTCHEON/FLASHING AROUND ALL 3.
EXISTING CONDITIONS. MAINTAIN ORIGINAL FREE AREA.
CONTRACTOR MAY ADJUST FROM DUCT SIZE SHOWN TO ACCOMODATE 2.
REFER TO FLOOR PLANS FOR ACTUAL DUCT SIZING AT WALL PENETRATIONS.1.
SECTION NOTES:
SEE M-120, NOTE 2
1" HWS & HWR,
SEE 9/M-502, NOTE 2
DHW, DHWR, DCW
DUCTWORK
SUPPLY/RETURN
TYPICAL FAN COIL
FIELD
WITH DUCTWORK IN THE
AND NEW CONDUIT RUNS
COORDINATE EXISTING
ELEC PANELS, TYP.
STRUCTRURAL DRAWINGS
TYP OF 2. SEE
NEW 32x48 OPENING, SEE STRUCTURAL DRWGS
HAVE DEPTH INCREASED,
(E) 42x40 OPENING TO
OPENING
(E) 72x44
9E) 44x30 OPENING TO
(E) 42x44 OPENING TO
(E) 78x52 OPENING TO
(E) 78x44 OPENING TO
WALL OPNG
(E) 208x66
(E) 80x44 OPENING TO
SEE NOTE 3 & 4 SEE NOTE 3 & 4SEE NOTE 3 & 4
14966
M-115 THRU M-118.
UPPER DUCTWORK DRAWINGS
THIS LINE IS SHOWN ON
DUCTWORK LOCATED ABOVE
M-111 THRU M-114.
LOWER DUCTWORK DRAWINGS
THIS LINE IS SHOWN ON
DUCTWORK LOCATED BELOW
AFF TO BOTTOM OF JOIST
APPROXIMATELY 16'
VERIFY LOCATION
EXISTING ROOF JOIST,
M-117
M-117
TO VAV UNITS
12"Ø OA
M-114
OF THE NUTS.
LOCTITLE TO PREVENT MOVEMENT
NUT TO BE INSTALLED WITH
MOVEMENT OF ROOF JOIST. ALL
SUPPORT TO ALLOW VERTICAL
CONNECTS BRACKET TO VERTICAL
WASHERS. TIGHTEN BOLT THAT
BOLT AND 1/16" THICK FLAT NYLON
INSTALL ANGLE BRACKET WITH
DOUBLE NUT
INSTALL AT APPROX. 10' AFF
ANCHOR WITH BASE PLATE.
EXTEND TO CMU WALL AND
BEAM
EXISTING WIDE-FLANGE
WALLS AND CEILING
CONCRETE VAULT
CONDUIT
EXISTING ELECTRICAL
WALL
SECURITY PERIMETER
FULL-HEIGHT CMU
DETAIL 3/M-504
DUCTWORK PER
USED FOR NEW
IN CMU WALL TO BE
EXISTING OPENING
DETAIL 3/M-504
DUCTWORK PER
USED FOR NEW
IN CMU WALL TO BE
EXISTING OPENING
ROOF ROOF ROOF
TO ERU-1
34x20 EA
CEILING
2019-04-29T07:52:35-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-4 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:33:12 PM
M-400 k
682783_2215M-400.dgn
IP
G
ENLARGED MECHANICAL ROOM EQUIPMENT LAYOUT PLAN
1/4"=1'-0"
ENLARGED MECHANICAL ROOM EQUIPMENT LAYOUT PLAN
FC-10
FC-12
FC-13
FC-24
FC-22
FC-23
FC-17
FC-27FC-18
FC-28
FC-26
FC-14FC-15
HU-1 HU-2
ET-2
GMU-2
PUMP 2A
PUMP 2B
PUMP 1A
GMU-1
ET-1
BOIL-1
BOIL-2
BOIL-3
FC-6
FC-2
FC-7
FC-1
FC-5
FC-8
FC-3
FC-9
ERU-1
FC-25
FC-11
FC-16
FC-21
FC-19
PUMP 1B
PUMP-1DHW
SEE DETAIL 2 & 3 ON SHEET M-500.
ALL FAN COIL UNITS TO SET ON AN EQUIPMENT FRAME. A.
AND 3/M-500
CLARITY SEE 2/M-500,
TYP 7, ENLARGED FOR
EQUIPMENT FRAME
EXISTING 80x24 LOUVER
" 10
TYP, 4
PANELS
DDC
TYP 4
ELECTRICAL
1/M-300.
SIMILAR TO DETAIL
CONSTRUCT IN MANOR
BOILER EQUIPMENT
UNISTRUT RACK FOR
(OVERHEAD)
AS-2
SEE F-110 TO F-901
EXISTING FIRE RISER
SERVICE AREA, TYP
PF-6
FC-4
67 149
M-505
15'-5"7'-10 1/2 "12'-3"21'-10 1/4 "12'-3"7'-10 1/2 "5'-5"
SERVICE AREA, TYP
/4
6'-9" 6'-9"
12'-4 1/2 "12'-8 1/2 "
(OVERHEAD)
AS-1
6'-0"
RPBP-1
6'-8 1/4 " 7'-8 3/4 " 2'-6"
4'-7 1/2 " 6'-9"
4'-7 1/2 "
WATER, SEE P-113
EXISTING INCOMING
NEW WATER METER
11 11
FC-20
MD-6
DESIGN SHOWN IN EQUIPMENT SCHEDULES, TYPICAL.
AROUND MECHANICAL EQUIPMENT PER BASIS OF
DIMENSION SHOWN PROPOSED IS PROPOSED ACCESS 11.
CONTROL PANELS.
COORDINATE PANEL LAYOUT WITH ELECTRICAL & HVAC
SEE DETAIL 1/M-300 FOR CONSTRUCTION DETAILS.
FROM UNISTRUT BY THE MECHANICAL CONTRACTOR.
ELECTRICAL & HVAC PANEL WALL TO BE CONSTRUCTED 10.
FACED FIBERGLASS INSULATION.
AND INSULATE WITH 4 INCHES OF RIGID ALUMINUM
SEAL EXISTING LOUVER OPENINGS WITH SHEET METAL 9.
PANELS. COORDINATE WITH ARCHITECTURAL PLANS.
EXISTING LOUVER TO BE INFILLED WITH TRANSLUCENT 8.
EXISTING LOUVER IS 48x32.
FC-10 WHEN UNIT IS OPERATING IN ECONOMISER-MODE.
NEW 2-POSITION DAMPER TO BE INTERLOCKED WITH 7.
EXISTING UNIT HEATER (OVERHEAD)TO REMAIN.6.
EXISTING HOUSE VACUUM TO REMAIN.5.
AT THE NEW LOCATION.
EXISTING COMPRESSOR TO REMAIN IN SERVICE, SHOWN 4.
NEW LOCATION.
EXISTING STORAGE TANK TO BE RELOCATED TO THIS 3.
LOCATION.
EXISTING RO UNIT TO BE RELOCATED TO THIS NEW 2.
POSSIBLE.
A.2 ON SHEET M-103. REUSE AS MUCH PIPING AS
RECIRCULATION PUMP, PUMP-1DHW. REFER TO PHOTO
BE REPLACED WITH NEW WATER HEATER WH-1 AND
EXISTING WATER HEATER AND RECIRCULATION PUMP TO 1.
AND 3/M-500
CLARITY SEE 2/M-500,
TYP 5, ENLARGED FOR
EQUIPMENT FRAME
CLEARNACES
MAINTAIN REQUIRED
TRANSFORMER,
EXISTING ELECTRICAL
2019-04-29T07:53:36-0600
Price, Ted INC00033148
144CORRIDOR
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:34:23 PM
M-401 k
682783_2215M-401.dgn
PROVIDE A 30" DEEP PLENUM
EXISTING 80x24 LOUVER
SG24
ON EXISTING LOUVER
PROVIDE A 30" DEEP PLENUM
"Ø
FC-15
FC-14 FC-12
FC-18
FC-17 FC-28
FC-27
x1 x x1 x x x x x x
SG22-8
RG12
RG12
x x x
DDC CONTROL
FROM ERU-1
24x24 EXHAUST
THROUGH LOUVER
EXHAUST AIR, ROUTE
18x18 RA
18x16 SA x x x
16x16 RA
12x12 SA
12x14 RA
12"Ø RA 12"Ø RA
30x20 RA
(BELOW)
28x20 SA
24x24 EA x
TO FC-4
x x
14x14 SA x
A 2 x x
ENLARGED MECHANICAL ROOM LOWER DUCTWORK PLAN
ENLARGED MECHANICAL ROOM LOWER DUCTWORK PLAN
(BELOW)
22x22 SA
630 CFM
SG22
220 CFM
OVER PLENUM
ROUTE SUPPLY DUCT
9(TYP)
(TYP) 10
18x14 RA x x x
12 1113
8x8 SA
8"Ø SA
HC-114 14CC-1
COILS, SEE SCHEDULE.
DUCT-MOUNTED HEATING AND COOLING HYDRONIC 14.
TRANSITION TO 24x24 AND EXTEND UP.
2-POSITION LOW-LEAK MOTORIZED DAMPER.
EXHAUST AIR OUTLET AT UNIT WITH FACTORY 13.
LOW-LEAK MOTORIZED DAMPER. TRANSITION TO 42x28.
OUTSIDE AIR INLET AT UNIT WITH FACTORY 2-POSITION 12.
LAYOUT AND MAXIMIZE CLEARANCE AT FLOOR.
ERU-1. PROVIDE OFFSET FITTINGS TO MINIMIZE DUCT
EXTEND EA PLENUM DOWN TO EA CONNECTION ON 11.
BASED ON BUILDING OCCUPANCY SCHEDULE.
RETURN AIR DUCTWORK FOR OPEN/CLOSED CONTROL
MOTORIZED DAMPER AT OUTSIDE AIR CONNECTION TO 10.
OUTSIDE AIR SYSTEM BALANCING.
MANUAL VOLUME DAMPER AT BRANCH TAKE-OFF FOR 9.
INSTALL DUCT AT 12' AFF.8.
THE FAN COIL UNIT.
24x24 SA DOWN TO FC-10. TRANSITION TO OUTLET OF 7.
3 ON M-504.
DEMOLITION. PROVIDE NEW SECURITY BARS PER DETAIL
EXISTING SECURITY BARS TO BE REMOVED DURING 6.
LOUVER AS A BARMETRIC RELIEF.
SEE NOTE 7 ON SHEET M-400 FOR USE OF EXISTING 5.
AVERAGING THERMOSTAT.4.
DUCT/STRUCTURE CLEARANCE.
ELBOW DOWN TO LOWER ELEVATION TO ACHIEVE 3.
INSTALL THERMOSTAT ON RIGID INSULATION BOARD.2.
8x8 TRANSFER DUCT, INSTALL HIGH IN THE WALL.1.
TO SECTION DRAWING M-300 FOR DEMARCATION LINE.
SEE DRAWINGS M-402 FOR UPPER DUCTWORK. REFER C.
THE ORGINAL FREE AREA.
TWICE THE SPECIFIED LINING THICKNESS TO MAINTAIN
SHALL INCREASE THE OVERALL DUCT DIMENSIONS BY
DUCT LINER OR INSULATION IS USED CONTRACTOR
MINIMUM FREE AREA REQUIRED. WHERE INTERNAL
CLEAR INSIDE DIMENSIONS AND REPRESENT THE
DUCTWORK DIMENSIONS INDICATED ON DRAWINGS ARE B.
SUPPLY DUCTWORK DOWNSTREAM OF HUMIDIFIERS.
OF SOUND LINING, EXCEPT NO INTERNAL LINING OF
MECHANICAL ROOM SHALL BE INSTALLED WITH 1 INCH
ALL RECTANGULAR SUPPLY AND RETURN DUCTWORK IN A.
2019-04-29T07:54:15-0600
Price, Ted INC00033148
143 ROOM
e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:36:05 PM
M-402 k
682783_2215M-402.dgn
11 2
1 2 1 x
A 2 x x x x x x x x x x x x x x x
16x14 SA
18x14 SA
20x14 RA
16x14 SA
14969
16x14 RA
ENLARGED MECHANICAL ROOM UPPER DUCTWORK PLAN
ENLARGED MECHANICAL ROOM UPPER DUCTWORK PLAN
14x12 SA
14x14 RA
16x16 SA
18x16 RA x x x
TURN-DOWN AND BIRD SCREEN.
NEW ROOF CURB AND TERMINATE WITH A GOOSENECK
OPENING. VERIFY SIZE AND LOCATION. PROVIDE WITH
EXTEND 42x28 OA DUCTWORK UP TO EXISTING ROOF 4.
DUCT/STRUCTURE CLEARANCE.
ELBOW DOWN TO LOWER ELEVATION TO ACHIEVE 3.
UNIT.
COMBINE SA DUCTWORK FROM DUAL OUTLET FAN COIL 2.
SEE M-401 FOR CONTINUATION.
EXTEND SA/RA DUCTWORK DOWN TO FAN COIL UNIT. 1.
WITH DUCT ROUTING.
EXISTING ROOF TRUSS CROSS-BRACING IS IN CONFLICT
COORDINATE WITH STRUCTURAL TRADES WHERE E.
SECTION DRAWING M-300 FOR DEMARCATION LINE.
SEE DRAWING M-401 FOR LOWER DUCTWORK. REFER TO D.
GRILLES AND DISTRIBUTION NOTATION.
SEE DRAWING M-401 FOR GENERAL HVAC DUCTWORK, C.
THE ORGINAL FREE AREA.
TWICE THE SPECIFIED LINING THICKNESS TO MAINTAIN
SHALL INCREASE THE OVERALL DUCT DIMENSIONS BY
DUCT LINER OR INSULATION IS USED CONTRACTOR
MINIMUM FREE AREA REQUIRED. WHERE INTERNAL
CLEAR INSIDE DIMENSIONS AND REPRESENT THE
DUCTWORK DIMENSIONS INDICATED ON DRAWINGS ARE B.
SUPPLY DUCTWORK DOWNSTREAM OF HUMIDIFIERS.
OF SOUND LINING, EXCEPT NO INTERNAL LINING OF
MECHANICAL ROOM SHALL BE INSTALLED WITH 1 INCH
ALL RECTANGULAR SUPPLY AND RETURN DUCTWORK IN A.
2019-04-29T07:54:52-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:37:30 PM
M-403 k
682783_2215M-403.dgn
PUMP 2A
PUMP 2B
3/4"
CONNECT TO EXISTING
ENLARGED MECHANICAL ROOM PIPING PLAN
ENLARGED MECHANICAL ROOM PIPING PLAN
HU-1 HU-2
WH-1
SEE M-600
1"
2" 2 1/2"
1 1/4"
2 1/2"
PUMP-1-DHW
UNIT HEATER
EXISTING
SEE M-601
FOR CONTINUATION
SEE SHEET M-120
1 1/4" HWS, HWR (E)
DDC CONTROL
2 1/2" 2 1/2" 3"
3" 2-1/2"
BOILER 1
BOILER 3
PUMP 1B
PUMP 1A
TO REMAIN
EXISTING VACUUM
1-1/4"
1-1/2"
3"4"
4"
1" 1" 2"
1" 1 1/4"
3"
BOILER 2
VALVES
ISOLATION
CHILLERS
4" CWR TO
4" CWS FROM CHILLERS
VALVES,
TYPICAL
2"
2 1/2"
4" 4"
1-1/4" 1"
1 1/2"
3"
2"2"
14970
1-1/2" CHWS/R 1-1/4" CHWS/R
2 1/2" CHWS/R
2" CHWS/R
1-1/4" CHWS/R
LOCATION.
COILS, CC-1 AND HC-1. SEE DRAWING M-401 FOR
EXTEND CHWS/R AND HWS/R PIPING TO DUCT-MOUNTED 10.
ACCORDINGLY.
APPROXIMATE LOCATION. ALL PIPING TO BE REROUTED
AIR COMPRESSOR TO REMAIN, BUT RELOCATED TO THIS 9.
CONTROL, SEE M-600.
DIFFERENTIAL PRESSURE TRANSMITTER FOR PUMP 8.
SEE SHEET M-300.
SUPPORT BOILERS, PUMPS ETC FROM STRUT SUPPORT, 7.
SUPPORT PUMPS FROM EXTERIOR WALL.6.
SEE P-111 AND DETAIL 1/M504.
RELOCATED EXISTING RO EQUIPMENT AND HUMIDIFIERS. 5.
TERMINATE WITH A CONCENTRIC FLUE.
EXTEND AIR INTAKE AND EXHAUST THRU ROOF. 4.
SUPPLY AND RETURN.
SEE M-404 FOR CONTINUATION OF CHILLED WATER 3.
INFORMATION.
4" PVC INTAKE AND EXHAUST. SEE M-600 FOR ROUTE 2.
PIPING RUNS AS POSSIBLE, WITHIN SAME ROOM.
TAKE-OFF AND ISOLATION VALVES AS CLOSE TO BRANCH
VALVES SHOWN OFFSET FOR CLARITY. LOCATE BRANCH 1.
2019-04-29T07:55:44-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:39:18 PM
M-404 k
682783_2215M-404.dgn
ENLARGED PIPING PLAN CHILLER AREA
1/4" = 1'-0"
P
3" CHWR
3" CHWS
INFORMATION BEFORE BEGINNING ANY WORK.
AVAILABLE INFORMATION. CONTRACTOR SHALL CONFIRM
INFORMATION SHOWN ON DRAWINGS IS BASED ON BEST A.
PUMP-2A, 2B
3" CHWR
3" CHWS
PROVIDE ISOLATION VALVE ON INSIDE OF THE BUILDING.6.
WITH EXISTING PENETRATION.
ROLL TEE UP AT A 45° ANGLE EXTEND PIPING TO ALIGN 5.
SYSTEM, AND CAP END.
EXTEND PIPING TO PROVIDE SUPPORT TO HYDRONIC 4.
APPROVED BY PUMP MANUFACTURER.
PUMP MAY BE INSTALLED IN VERTICAL POSITION IF 3.
DRAWINGS FOR MORE INFORMATION.
SHALL BE PATCHED. REFER TO ARCHITECTURAL
USE EXISTING PENETRATIONS. UNUSED PENETRATIONS 2.
BE REMOVED.
SUPPORTS WHERE POSSIBLE. UN-USED SUPPORTS TO
AVAILABLE INFORMATION. CONTRACTOR TO RE-USE
EXISTING PIPE SUPPORTS ARE BASED ON BEST 1.
PUMP-4
PUMP-5
PUMP-3
PADS (BELOW)
EXISTING EQUIPMENT
71 149
VALVES, TYP
2019-04-29T08:05:39-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-5 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:41:01 PM
HVAC DUCT CONSTRUCTION DETAILS (TYP)
GORED ELBOWS ARE NOT ALLOWED.
L=1/4 W, 4" MIN
TYPE FITTINGS WILL BE ALLOWED.
TYPE FITTING. NO BUTT TAP
CONICAL, BELLMOUTH FLANGED
TAKE OFF TO BE AN EXPANDED
SYSTEM.
TAKEOFFS ON LOW PRESSURE
BE SUBSTITUTED FOR ANGLED
AN EXPANDED CONICAL TAP MAY
FOR OFFSETS.
DO NOT USE FLEX DUCT
SQUARE TO ROUND TRANSITIONS.
RECTANGULAR DUCTWORK INCLUDING
THIS APPLIES FOR BOTH ROUND AND
CONVERGING AIR FLOWS.
22.5 FOR DIVERGING AND 30 FOR
DIMENSION "A" TO BE A MAXIMUM OF
RECTANGULAR DUCT
SQUARE ELBOW
RADIUSED ELBOW
ROUND DUCT
RADIUSED ELBOW
TAKE OFF
TRANSITION
TAKE OFF FROM
ROUND DUCT TAKE
OFF FROM
RECTANGULAR DUCTDUCT OFFSET
TRAILING EDGE.
" 4
VANES OR SINGLE WIDTH VANES WITH
TURNING VANES TO BE DOUBLE WIDTH
DUCT.
TURNING VANES IN RETURN OR EXHAUST AIR
UNLESS NOTED OTHERWISE DO NOT INSTALL
RECTANGULAR SUPPLY DUCTWORK.
PROVIDE TURNING VANES ON ALL
TURNING VANES
1.5 W
1.5 W
45°
45° MAX
W W
FLOOR DRAIN
EXTEND TO NEAREST
SLOPE 1/4" PER FOOT
SITE CONDITIONS
PULL AREA WITH
COORDINATE FILTER
FLEXIBLE DUCT COLLAR
FLEX CONNECTOR
RA
SA
REFER TO 5/M-502
WATER PIPING
HEATING AND CHILLED
VERTICAL FAN COIL UNIT
FAN COIL EQUIPMENT FRAME
L4"x4"x1/4"
L4"x4"x1/4"
6'-0" MAX BETWEEN LEGS
FOR UNIT OF DIFFERENT DEPTH
ADDITIONAL SUPPORT IF REQUIRED
AS PAIRS OR AS A SINGLE UNIT.
2. CONTRACTOR OPTION TO BUILD FRAME TO FIT UNITS INDIVIDUALLY,
1. CONTRACTOR TO VERIFY AND BUILD FRAME FOR EQUIPMENT.
TYPICAL GAS SERVICE CONNECTION
4 223
INTO BUILDING
EXISTING 2" LINE
COORDINATE FINAL LOCATION
CONNECT TO EXISTING 2" FLANGE
GRADE
FINISH
4" CONCRETE PAD
EXISTING 1" GAS LINE
EXISTING GAS COCK
UNION 2"
50 PSI TO 5.0 PSI.
PRESSURE FROM
OF 2000 CFH WITH INLET
REGULATOR CAPABLE
GAS PRESSURE
(P TRAP) REFER TO 1/M-502
CONDENSATE DRAIN
4" OF 3/4" MINUS CRUSHED BASE MATERIAL
PREPARED SUBGRADE
NOTE A
SEE
A. MINIMUM CLEARANCE BETWEEN EDGE OF CONCRETE PAD & OUTSIDE EDGE OF GAS METER SHALL BE 6" ON ALL SIDES.
LINING ON RECTANGULAR
PROVIDE 1" THICK SOUND
SEE NOTE 3
FOR DUCT SIZE
REFER TO FC SCHEDULE
FCU DIMENSIONS AS REQUIRED
CONSTRUCT FRAME TO MATCH
AS PER HVAC SUPPLY PLAN.
REQUIREMENT IS MEET TRANSITION TO SUPPLY DUCT SIZE
AT THE OUTLET. REFER TO FAN COIL SCHEDULE. ONCE THIS
LENGTH APPROXIMATELY 2.5 TIMES THE SMALLEST DIMENSION
3. MATCH MANUFACTURERS OUTLET SIZE WITH A STRAIGHT DUCT.
PROVIDE TRAPS AT EACH UNIT.
BE GANGED TO A COMMON LINE SLOPED AS INDICATED.
2. CONDENSATE DRAINS FROM ADJACENT UNITS MAY
SIZING.
1. REFER TO DRAWING SCHEDULES FOR PIPE & DUCT
PLAN
LOCATION WITH HVAC
COORDINATE TIE-IN
OA DUCT TO UNIT
FOR DUCT SIZE
REFER TO FC SCHEDULE
WELD, TYP AT CORNERS
MITERED CORNERS W/BUTT
LEVELING GROUT
NON-SHRINK
1" MIN, 2" MAX
PL 1/2"x6"x6"
ADHESIVE ANCHOR.
CONTRACTOR'S OPTION
W/ 3-1/2" EMBED OR AT
5/8" EXPANSION ANCHOR
ALL SIDES.
WITH 1/4 FILLET. WELD
WELD TO SUPPORT ANGLE
COPE ANGLE LEG AND
1-1/4" TYP
1/4
DUCT SIZE
THE METER.
MHAFB WILL SUBSEQUENTLY OWN
COORDINATE METER WITH MHAFB;
PRESSURES. CONTRACTOR SHALL
MINIMUM OF 1500 CFH AT INDICATED
METER SHALL BE RATED FOR A
MONITORING BY THE DDC SYSTEM.
WITH A PULSED OUTPUT FOR
GAS METER TO BE PROVIDED
TEE WITH PLUG
2 PSI OUTLET PRESSURE.
5 PSI INLET PRESSURE TO
CAPABLE OF 1500 CFH MAX AT
GAS PRESSURE REGULATOR
SECTION 4-29.1.4.
REFERENCE UFC 3-600-01,
METRAFLEX GASCT0200,
SERVICE. EQUIVALENT TO
SUITABLE FOR NATURAL GAS
STAINLESS STEEL, 2"x20", FLEX CONNECTOR. BRAIDED
M-500 k
682783_2215M-500.dgn
DAMPER
BALANCE
ACCESSIBILITY. EXTEND WIRING AS REQUIRED.
STARTER TO TOP/FRONT OF UNIT FOR
RELOCATE FACTORY FURNISHED MOTOR
SEE M-400
LENGTH AS REQUIRED
SEE M-400
LENGTH AS REQUIRED
72 149
DAMPER, MD-2
MOTORIZED
2019-04-29T08:07:04-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:42:31 PM
HANGER
HANGER
ALTERNATIVE - WHEN SPACE IS LIMITED
AS DUCT WORK
INSULATE SAME
STRAP HANGER
(WHEN INDICATED ON PLAN)
OPPOSED BLADE DAMPER
(WHEN INDICATED ON PLAN)
OPPOSED BLADE DAMPER
LINING
1/2" SOUND
PLENUM WITH
1.5D MIN
DUCT6.
REINFORCEMENT ANGLE5.
MASTIC SEALANT (TYP)4.
FOR LONG LEG ANGLES3.
DUCT JOINT2.
FOR SHORT LEG ANGLES1.
KEYED NOTES:
DUCT
4 3
4 5
45°
18" MIN
ANCHOR BOLT
3" MIN TO
RIGID ROUND DUCTWORK
RECTANGULAR DUCTWORK
PROVIDE STANDOFF BRACKET WHERE EXTERNAL INSULATION IS APPLIED.A.
NOTE:
SIZE TO MATCH DUCT CONNECTION TO GRILLE.A.
HANGER SIZES SHALL BE IN ACCORDANCE WITH SMACNA, LATEST EDITION.C.
SUPPORT SYSTEM MUST NOT DAMAGE DUCT, INSULATION, OR CAUSE DUCT SHAPE DEFORMATION.B.
DO NOT USE POWDER ACTUATED FASTENING SYSTEMS TO ATTACH SUPPORTS TO STRUCTURE.A.
REINFORCEMENT AND JOINT (TYP)
INSULATION AT DUCT
DUCTWORK SUPPORT (TYP)
NTS 3
FLOOR EXHAUST
ROUND VOLUME DAMPER (UP TO 14") (TYP)
LOUVER/PLENUM CONNECTION
NTS 8
TYPICAL GRILL/DIFFUSER CONNECTION
IN N
ALL-THREAD ROD8.
CONFIGURATION
ROD IN TRAPEZE THREAD
KINDORF HANGER WITH ALL 7.
PROPRIETARY CLAMP
1" MIN BAND CLAMP OR 6.
SMACNA RECOMMENDATIONS
ATTACH TO STRUCTURE PER 5.
SPIRAL SEAM DUCT4.
15, ANCHORAGE AND BRACING88
BRACE IN ACCORDANCE WITH 01 3.
NUT WITH LOCK WASHER2.
EXPANSION BOLTS
CLAMPS OR MASONRY BEAM
ATTACH TO STRUCTURE WITH 1.
STANDARDS"
CONSTRUCTION
"HVAC DUCT SMACNA
DUCT SUPPORT PER 5.
WALL4.
FINISHED FLOOR3.
1/2" GRID SST SCREEN2.
SEE PLAN FOR SIZE OF DUCT1.
END BEARING9.
GASKET8.
REGULATOR7.
LOCKNUT6.
MIN 3/8" SQ. ROD W/SET SCREWS (2 REQD)5.
INDICATING HANDLE AND LOCKING QUADRANT4.
1" WIDE x 16 GAGE GALVANIZED STRAP (2 REQD)3.
MIN 3/8" ROD2.
GALVANIZED STEEL
DIAMETER. BLADE SHALL BE 16 GAGE DUCT
DAMPER BLADE DIAMETER TO BE 1/4" LESS THAN 1.
FAN
TO CURB
FLANGE AND FAN
FASTEN SLEEVE
SLEEVE
SHEET METAL
SHOWN ON DRAWINGS
DIMENSIONS
TRANSITION TO
PROVIDE DUCT
AROUND ROOF OPENING
PROVIDE ANGLE FRAME
SLOPE TO MATCH ROOF
ROOF CURB, COORDINATE
PRE-FABRICATED
FLANGE ON SLEEVE
PROVIDE 1" MINIMUM
2.
1.
RUBBER PAD
ROOF
OPENING DETAILS.
REFER TO STRUCTURAL DRAWINGS FOR ROOF
CONSTRUCTION AND CURB FLASHING.
REFER TO ARCHITECTURAL DRAWINGS FOR ROOF
CENTRIFUGAL ROOF FAN
EXHAUST GRILLE SCHEDULE
DUCT CONNECTION, SIZE PER 6.
AS INDICATED
EXHAUST OR RETURN GRILLE 5.
07 00
1" INSULATION LINER PER 23 4.
FSD WHERE INDICATED3.
OPPOSITE WALL
FACE SOUND BOOT OPENING 2.
OPENING TO ADJACENT
WALL WITH TRANSFER 1.
EXHAUST OR RETURN GRILLE WITH SOUND BOOT
ROUND NECK ADAPTOR
FLEX SUPPLY DUCT
PROVIDE NEW
FLEX SUPPLY DUCT
PROVIDE NEW
3/4" COMPRESSED AIR LOOP ABOVE
ANCHOR STATION TO WALL
WITH GAUGE.
MODEL R18-02-D0G0
EQUIVALENT TO A WILKERSON
PRESSURE REGULATOR
JUST BELOW CEILING.
WALL MOUNTED
HOSE REEL TO BE
50" OF 1/2' DIAMETER HOSE.
HANNAY REELS MODEL 700 WITH
HOSE REEL EQUIVALENT TO A
BUMPER STOP
QUICK CONNECT
TYPICAL NEW 100 PSIG COMPRESSED AIR STATION
P111
1/2" FLEX HOSE
MOTORIZED DAMPER
MANUFACTURER
EQUIPMENT
COORDINATE WITH
EXISTING ROOF OPENING
WALL11.
FOUR SIDES OF PLENUM
ANGLE SUPPORT FRAME ON ALL 10.
SHEET METAL SCREWS TYPICAL9.
OUTSIDE
SLOPE BOTTOM TO DRAIN
PLENUM FULL SIZE OF LOUVER, 8.
MOTORIZED DAMPER
HINGED ACCESS DOOR FOR 7.
TIGHT
SEAL PERIMETER WEATHER 6.
DUCT5.
SEAL WITH SEALANT4.
NOTED.
TYPICAL UNLESS OTHERWISE
MOTORIZED LOW-LEAK DAMPER, 3.
ARCHITECTURAL DRAWINGS
FIXED LOUVER, SEE 2.
1/2" MESH BIRDSCREEN1.
M-501 k
682783_2215M-501.dgn
73 149
2019-04-29T08:07:47-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:44:02 PM
RETURN AIR DUCT
(IF SPACE ALLOWS)
TYPICAL FOR 2 OR 4 SIDES
1/2" SS MESH SCREEN
AIR DUCT AREAS
(MINIMUM OF TWO RETURN
INTAKE AREA EQUAL TO A
2.1-5
5.1-50
THAN OUTLET SIZE
* NOT SMALLER
PITCH
LOAD(TONS)
COOLING
CONNECTED
SIZE
PIPE
MIN*
ALLOW SUFFICIENT SPACE BELOW PAN FOR TRAP AND PITCH TO DRAIN.C.
SUPPORT DRAIN LINES TO PREVENT SAG.B.
MANUALLY PRIME TRAP BEFORE START UP.A.
DUCT
METAL
SHEET
MATERIAL AS DUCT
COLLAR SAME
MIN 2" ANGLE CLOSURE
AT CMU OPENINGS
MINIMIZE CLEARANCE
1" MAX CLEARANCE
SEALANT, TYP
SILICONE RUBBER
WATERPROOF
CAULK WITHWITH FIRE SAFEING
AROUND DUCT
PACK OPENING
CONDENSATE DRAIN TRAP (TYP)
DUCT WALL PENETRATION (TYP)
RETURN DUCT AIR INTAKE
NOT LESS THAN 4"
CAPACITY PLUS 2", BUT STATIC
TRAP DEPTH EQUAL TO FAN 6.
CLEAN OUT5.
1" MIN4.
PROVIDE AIR GAP AS SHOWN.
AND WASTE ROUTING. COLLECTION
REFER TO PLUMBING FOR 3.
DRAIN PAN2.
CONNECTION
SAME SIZE AS THE DRAIN PAN THE
DRAIN LINE SHALL BE AT LEAST 1.
WEIGHT TO BEAR ON WALL PENETRATION.DUCT
SUPPORT DUCT ON BOTH SIDES OF WALL. DO NOT ALLOW B.
REFER TO 23 31 13 FOR FIRE/SMOKE DAMPER INSTALLATION.A.
REDUCER AS REQUIRED
(OR EQUAL)
"WATSON McDANIEL" AV813W
AUTOMATIC AIR VENT
CONTINUATION
SEE PLAN FOR
CONTINUATION
SEE PLAN FOR
HYDRONIC PIPING - HIGH POINT VENT
TEE FITTING
BALL VALVE ISOLATION
TO NEAREST FLOOR DRAIN.
EXTEND A 1/2" DRAIN. ROUTE
COOLING AND HEATING COIL CONNECTION
UNINSULATED PIPE
INSULATED OR
C. NO FILL ON NON-RATED WALLS.
WHERE PIPING IS EXPOSED TO VIEW PROVIDE ESCUTCHEON PLATES.
KEYED NOTES
CONSTRUCTION & RATING
A. FILL ANNULAR SPACE AND FIRE CAULK PER UL ASSEMBLY TO MATCH WALL
20 GA GALVANIZED STEEL SLEEVE. INSTALL FLUSH WITH BOTH SIDES OF WALL
MECHANICAL AND FAN ROOMS.
WHERE PENETRATING OFFICE AREA OR CONFERENCE ROOM WALLS, AND AT
B. FILL ANNULAR SPACE WITH 1" SPONGE NEOPRENE AND ACOUSTICAL CAULK
PIPING PENETRATION (FRAMED WALL)
UNINSULATED PIPE
INSULATED OR
WHERE PIPING IS EXPOSED TO VIEW PROVIDE ESCUTCHEON PLATES.
SCH 40 BLACK STEEL SLEEVE FLUSH WITH WALLS.
KEYED NOTES
PIPING WALL PENETRATION (CONCRETE WALL)
C. NO FILL ON NON-RATED WALLS.
PENETRATING OFFICE AREA OR CONFERENCE ROOM WALLS
B. FILL ANNULAR SPACE WITH 15mm SPONGE NEOPRENE AND ACOUSTICAL CAULK WHERE
& RATING
A. FILL ANNULAR SPACE AND FIRE CAULK PER UL ASSEMBLY TO MATCH WALL CONSTRUCTION
N.O.
11.
12.
FL
OWAI
3.
4.
5.
6.
7.
8.
9.
10.
GAUGE COCK, TYP
COIL
VALVE AND PLUG, BELOW
STRAINER WITH BALL
RETURN
SUPPLY
BALANCING FITTING
BALANCE FITTING
FLOW MEASURING &
BALL VALVE, TYP
MANUAL AIR VENT
NOT USED
UNION, TYP
3-WAY MIXING VALVE
NOT USED
FL
OWAI
7.
8.
9.
10.MOTORIZED VALVE
VALVE
WITH ISOLATION
MANUAL AIR VENT
TEST PLUG
TEMPERATURE
PRESSURE AND
BELOW COIL
VALVE AND PLUG,
STRAINER WITH BALL
BALL VALVE, TYP
HWS
UNION,TYP
BALANCE FITTING
FLOW MEASURING &
HWR
2 WAY CONNECTION
HEATING/COOLING COIL
CONNECTION 3 WAY VALVE
HEATING/COOLING COIL
SOUND ATTENUATOR INSTALLATION
4 EXTEND INSULATION CONTINUOUS THROUGH PENETRATION.
4 EXTEND INSULATION CONTINUOUS THROUGH PENETRATION.
2-1/2" MAIN LINE
LONG SWEEP ELBOWY-FITTING
RKV90002
TO A SPENCER TURBINE
HOSE RACK - EQUIVALENT
LOCK
RECESSED FLANGE AND HOSE
TO A SPENCER VLV900099 WITH
1-1/2" WALL INLET - EQUIVALENT
HOSE IN WITH USER.
HOSE MODEL HOS90243. COORDINATE
HEAVY DUTY URETHANE SPENCER
2. HOSE EQUIVALENT TO A 2-1/2" x 1-1/2"
FOR EACH DROP.
1. FURNISH HOSE RACK AND HOSE
FLOOR
2-1/8" RUNOUT
VACUUM INLET
THE SECURED SIDE OF THE
INSTALL ATTENUATOR ON
COATED NYLON/POLYESTER FABRIC
DURODYNE EXCELON OR EQUAL, VINYL
MIN 2" WIDE, MAX 6" WIDE.
PROVIDE NON-METALIC FLEXIBLE JOINT,
THREADED ROD, TYP
DOOR
HINGED ACCESS
1" MINIMUM
MUST LAP FROM END OPENING
ANGLES @ 3" O.C. ANGLES
RETAINING ANGLE. SECURE
4" x 4" x 16 GA PERIMETER
UNISTRUT, TYP
ANGLE IRON OR
DISTRIBUTION
ENTIRE PERIMETER
FILL CLEARANCE SPACE,
USE EXPANSION FOAM TO
M-502 k
682783_2215M-502.dgn
74 149
2019-04-29T08:08:30-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:45:31 PM
REHEAT COIL
HOT WATER
VAV TERMINAL UNIT
SUPPLY AIR
VALVES
CONTROL PANEL
SUPPLY AIR INLET
TYPICAL VAV BOX PIPING DIAGRAM
HOT WATER RETURN PIPING
HOT WATER SUPPLY PIPING
REQUIRED TO INSTALL NEW VAV BOX.
DEMOLISH DUCTWORK UPSTREAM OF VAV BOX ONLY AS FAR AS IS
OF EXISTING VAV BOX OR TO FIRST FITTING.
DEMOLISH EXISTING DUCTWORK APPROXIMATELY 5' DOWNSTREAM
AND THERMOSTATS.
DEMOLISH ALL COTROL VALVES, CONTROL WIRING
ALL DOWNSTREAM PIPNG, VALVES AND FITTINGS.
CUT PIPING UPSTREAM OF ISOLATION VALVE. REMOVE
REHEAT COIL
W/HOSE COUPLING
3/4" DRAIN VALVE
SIZE AS NOTED ON SCHEDULE
HOT WATER SUPPLY PIPING
SIZE AS NOTED ON SCHEDULE
HOT WATER RETURN PIPING
UNION
VAV TERMINAL UNIT
SUPPLY AIR
TEST PLUG
TEMPERATURE & PRESSURE
BALL VALVE
BALANCING VALVE
CALIBRATED
CONTROL VALVE
2 WAY
AIR VENT VALVE W/PLUG
CONTROL PANEL
SUPPLY AIR INLET
TO MATCH INLET
PROVIDE TRANSITIONS AS REQ'D
DUCT, SIZE TO MATCH VAV INLET
MINIMUM 2'-0" OF STRAIGHT RIGID
DISCHARGED DUCT
SOUND LINED
DEMOLITION WORK
NEW WORK
NOTE 1
NOTE 1
NOTE 2
NOTE 2
NOTE 2NOTE 3
NOTE 4
INSTALL NEW THERMOSTAT AND WIRING AT LOCATION OF EXISTING THERMOSTAT.
LOCATE PIPING TO ALLOW FULL ACCESS TO CONTROL PANEL.
OR DUCTWORK.
IF SOUND LINING IS CUT WHILE INSTALLING SUPPLY DIFFUSERS
CONTRACTOR SHALL BUTTER ALL EXPOSED EDGES OF SOUND LINING
OF VAV BOX, COORDINATE WITH EXISTING DUCTWORK.
MIN 5' SECTION OF DUCT WITH 1" SOUND LINING ON DISCHARGE
VAV BOX TO BE FURNISHED WITH SOUND LINING. PROVIDE
SUPPORT TERMINALS WITH STRAP HANGERS FROM BUILDING STRUCTURE.
HOSE COUPLING AT ALL LOW POINTS.
PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS AND DRAIN VALVES W/
HGR
HGS
STARTER
SEQUENCE OF OPERATION
UNION, TYP
BALL VALVE,
BALANCE VALVE
AIR VENT
MANUAL
TEST PLUG TYP.
TEMPERATURE
PRESSURE AND
HEATER
VERTICAL UNIT
AND PLUG, BELOW HEATER
STRAINER WITH BALL VALVE
UNIT HEATER PIPING
UNIT HEATERS FAN SHALL CYCLE AS REQUIRED TO MAINTAIN THE SPACE AT 60°F.
ARE SATISFIED REVERSE THE PROCEDURE.
TO MAINTAIN SPACE TEMPERATURE SET-POINT. WHEN SPACE HEATING REQUIREMENTS
TEMPERATURE SENSOR SHALL OPEN HEATING WATER CONTROL VALVE AND START FAN
HOT WATER UNIT HEATER AUTOMATIC CONTROL: ON CALL FOR HEATING FROM THE SPACE
HOT WATER UNIT HEATER NORMAL MODE: FAN OFF AND CONTROL VALVE TO UNIT IS CLOSED.
UNIT HEATER CONTROL
VALVE WHERE INDICATED
3-WAY OR 2-WAY CONTROL
VALVE WHERE INDICATED
3-WAY BYPASS WITH BALANCE
CABINET HEATER &
B. PIPING SIMILAR FOR HORIZONTAL CABINET HEATER.
HORIZONTAL UNIT HEATER PIPING SIMILAR.
PIPING ARRANGEMENT MAY VARY TO SUIT FIELD REQUIREMENTS.
A. DETAIL GIVES REQUIRED SEQUENCE OF EQUIPMENT AND VALVES.
M-503 k
682783_2215M-503.dgn
75 149
2019-04-29T08:09:09-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:47:02 PM
TO DDC SYSTEM
HUMIDITY SENSOR
WALL MOUNTED
HUMIDITY SENSOR
AI
1/2" ICW
PRESSURE GAUGE
CHECK VALVE
STORAGE TANK
1/2" RO WATER TO
HOSE THREAD
1/2" DRAIN WITH
TO FLOOR
ANCHORED
STAND
HUMIFIDIER
NEUTRALIZING TANK AND TO DRAIN
1/2" COMBUSTION CONDENSATE TO
FLOOR DRAIN
1" DRAIN TO NEARESTR
GAS REGULATOR
3/4" GAS
FIRE RATED
HUMIDIFIER
AO
ENABLE
HU-1
GAS FIRED
NATURAL GAS
INCOMING
SOUND LINING
SUPPLY DUCT WITH
10'-0"
BUILDING
SUPPLY DUCT TO
2" STEAM SUPPLY LINE
HUMIDIFIER DETAIL
TO HU-2
1/2" RO WATER
OFFSET
4" MIN
TYP 2
HUMIDIFIER SENSORS
RO UNIT
RELOCATED
STORAGE TANK
RELOCATED
DIMS AS INDICATED ON PLAN
1-INCH SOUND LINER, INSIDE
TRANSFER AIR DUCT WITH
BUILDING PLENUM
OPEN OUTLET TO
18" MIN, TYP BOTH SIDES
TRANSFER BOOT
WHERE SPACE IS LIMITED.
AWAY FROM CEILING
SO THAT INLET FACES
ROTATE OUT OF PLANE
ABOVE ISOLATED SPACE,
OPEN INLET IN PLENUM
PLANS AND DETAILS
PARTITION, SEE ARCH
FULL-HEIGHT INTERIOR
FOR APPLICABILITY.
FOR PHYSICAL SECURITY, SEE DRAWING M-502. REFER TO PLANS
BETWEEN ADJACENT SPACES ONLY. FOR PENETRATION DETAILS
THIS DETAIL IS INTENDED FOR MAINTAINING STC-RATING2.
ALLOW DUCT WEIGHT TO BEAR ON WALL PENETRATION.
SUPPORT TRANSFER BOOT ON BOTH SIDES OF WALL. DO NOT1.
:NOTES
SEAL DUCT PENETRATION
3/4" RO WATER SUPPLYSUPPLY LINE
1/2" RO
MIN 1" CLEARANCE ALL SIDES
TYP.
FROM WALL
EXTEND +/- 4" EACH SIDE
10 GAUGE STEEL SLEEVE
UNSECURED ROOM
FILL CLEARANCE SPACE
USE HIGH EXPANSION FOAM TO
INTERSECTIONS
EACH WAY WELD AT ALL
1/2" Ø STEEL BARS AT 6" O.C.
ALL CORNERS
FULLY WELD
SCREWS @ 4" OC.
FOR WALL PENETRATIONS PROVIDE
WELD TO SLEEVE AND STEEL DECK.
3"x3"x1/4" ANGLE 1" LONG WELD @ 4" OC.
PACK WITH INSULATION
CONNECTOR,
FLEXIBLE
NON-CONDUCTIVE
WELD AREA WITH ZINC RICH PAINT.
WITH RIVETS OR BY WELDIING. IF WELDED, TOUCH UP
HINGES AND HASP SHALL BE SECURED TO DUCTWORK
USED TO SECURE HASP TO DUCTWORK.
WHEN HASP IS CLOSED HASP SHALL COVER RIVETS
SECURED ROOM
NON-REMOVABLE, TYP
PINS SHALL BE
HINGE AND HASP
THE OWNER.
EXACT DOOR LOCATION WITH
SECURITY BARS. COORDINATE
VISUAL INSPECTION OF
WITH LOCK HASP TO PROVIDE
GASKETED ACCESS DOOR
PROVIDE A HINGED AND
1.B
WATER METER
RECOMMENDATIONS TO INSURE SYSTEM ACCURACY.
ENTIRE ASSEMBLY SHALL BE LEAD FREE. INSTALL PER MANUFACTURES
THE BUILDING DDC SYSTEM. COORDINATE WITH THE BASE WATER SHOP.
FURNISH WITH SWEEP HAND REGISTRATION AND A PULSED OUTPUT TO TIE TO C.
MAINTAINING CLEARANCE REQUIREMENTS.
SUPPORT AS REQUIRED. KEEP ARRANGEMENT CLOSE TO WALL AS WELL AS B.
ALL DOMESTIC PIPING INSIDE BUILDING SHALL BE TYPE L COPPER. A.
VALVE (E)
BUTTERFLY
3x2 REDUCER
CL EL.
NOTE 9
RISER
EXISTING 3"
MAINTINANCE.
SET METER ASSEMBLY ELEVATION AT HEIGHT CONDUCIVE TO SERVICE AND9.
CHANGES OF DIRECTION IN THIS SECTION.
OF METER ASSEMBLY. THERE SHALL BE NO VALVES, REDUCERS OR VERTICAL
PROVIDE 20" OF HORIZONTAL LAYING LENGTH UPSTREAM AND DOWNSTREAM 8.
PRESSURE GAUGE.7.
TURBO 200.
2" WATER METER WITH INTEGRAL STRAINER. MODEL: BADGER RECORDALL 6.
FINISHED FLOOR.5.
FULL PORT GATE VALVE.4.
DCW TO BLDG MAKEUP WATER SUPPLY.3.
3/4" HV-1 DRAIN VALVE WITH THREADED HOSE END.2.
CW DOMESTIC WATER SUPPLY (FOR CONT. SEE PLUMBING DWGS).1.
DETAIL KEYED NOTES
SECURED WALL PENETRATION DETAIL
M-504 k
682783_2215M-504.dgn
PROVIDE P-TRAPS PER DETAIL 1/M-502.D.
SOURCE IS COMMON FOR HU-1 AND HU-2.
ARRANGEMENT SIMILAR FOR HU-2 EXCEPT RO WATER C.
SCHEDULED UNIT ARE IDENTIFIED AS METRIC THREADS.
CONNECT TO UNIT. PIPING CONNECTIONS ON
PROVIDE TRANSITIONAL PIPING NIPPLE AS REQUIRED TO B.
HUMIDIFIER WANDS.
DO NOT INSTALL ANY SOUND LINING DOWNSTREAM OF A.
76 149
PROVIDES RO WATER FOR BOTH HU-2 AND HU-1.
RO UNIT, PRESSURE SWITCH AND EXPANSION TANK
DUCTWORK SIMILAR FOR HU-2 AND HU-1. THE EXISTING
1/2" PIPING TO HU-2. HUMIDIFIER, PIPING AND 12.
SYSTEM.
HUMIDIFIER CONTROL SIGNALS FROM BUILDING DDC 11.
SENSOR TO PROVIDE ACCURATE FEEDBACK.
COORDINATE THE LOCATION OF THE ROOM HUMIDITY 10.
DUCTWORK TO NO GREATER THAN 80% RH.
HUMIDITY HIGH LIMIT TO LIMIT THE HUMIDITY IN THE 9.
HUMIDIFIER.
AIR FLOW PROVING SWITCH TO BE FURNISHED WITH 8.
DRAIN CONNECTION.
GROUND SMOOTH. USE WELDED 1/2" COUPLINGS FOR
STEEL. ALL JOINTS SHALL BE FULLY WELDED AND
10’ LENGTH OF DUCTWORK SHALL BE 304 STAINLESS 7.
MAINTAIN GOOD DRAINAGE FROM STEAM PIPING.
PIPING MORE THAN 45 DEGREES FROM VERTICAL TO
OFFSET STEAM PIPING AS REQUIRED. DO NOT OFFSET 6.
MINIMUM OF 4” DEEP.
DRAIN TO NEAREST FLOOR DRAIN. PROVIDE A P-TRAP A
P-TRAP AT CONNECTED TO STEAM HEADER. ROUTE 1/2" 5.
DEEP.
FLOOR DRAIN. PROVIDE A P-TRAP A MINIMUM OF 4”
P-TRAP AT LOW POINT. ROUTE 1/2” DRAIN TO NEAREST 4.
REQUIREMENTS WITH THE EXISTING RO UNIT.
SWITCH TO BE REPLACED. COORDINATE PRESSURE
PIPING ASSOCIATED WITH THE EXISTING PRESSURE
EXISTING PRESSURE SWITCH TO BE RELOCATED. ALL 3.
EXISTING STORAGE TANK TO BE RELOCATED.2.
THE BASE.
SET OF FILTERS AS SPARES TO BE TURNED OVER TO
SERVICE AND PROVIDE ONE COMPLETE REPLACEMENT
FILTERS IN THE UNIT PRIOR TO PUTTING BACK INTO
CONTRACTOR SHALL REPLACE ALL OF THE EXISTING
HZ: 60
VOLTS: 110
SERIAL #: 88123
MODEL: T-500-STD
MANUFACTURE: MARLO
EXISTING RO UNIT TO BE RELOCATED. 1.
2019-04-29T08:09:51-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:48:58 PM
k
682783_2215M-505.dgn
IS
ISOMETRIC RIGHT DETAIL
ISOMETRIC LEFT DETAIL
ISOMETRIC LEFT DETAIL
NTS 4
ISOMETRIC RIGHT DETAIL
LOOKING DOWNLOOKING DOWN
LOOKING UP LOOKING UP
77 149
DRAINS.
VENTS AND TO AVOID TRAPS. LOW-POINTS SHALL HAVE
BOTTOM OF PIPING MAINS TO MINIMIZE HIGH-POINT AIR
TAKE OFF HWS/R AND CHWS/R BRANCH PIPING FROM 12.
EXISTING TRUSSES OR THRU TRUSS WEBBING.
OFFSET DUCT ELEVATION AS REQUIRED TO PASS UNDER 11.
LOCATIONS IN THE FIELD.
COORDINATE TRUSS DEPTH AND WEB OPENING 10.
WALL.
COORDINATE DUCTWORK WITH OPENINGS AT MASONRY 9.
FRAME TO SUPPORT EQUIPMENT. SEE DETAIL 3/M-500.8.
CROSS-SUPPORTS AT BOTTOM OD TRUSS AS REQUIRED.
DUCT AND PIPE HANGERS WITH UNISTRUT 7.
2/M-500.
FC UNITS, SEE M-400 FOR LOCATIONS. SEE DETAIL 6.
FOR SIZES.
CHILLED WATE SUPPLY AND RETURN PIPING. SEE PLAN 5.
FOR SIZES.
HEATING WATER SUPPLY AND RETURN PIPING. SEE PLAN 4.
TAKE-OFF AND MOTORIZED DAMPER AT RA CONNECTION.
OUTSIDE AIR DUCT WITH MANUAL DAMPER AT BRANCH 3.
FITTINGS AS REQUIRED TO CONNECT TO UNIT OUTLET.
SUPPLY AIR DUCT, TYPICAL. PROVIDE TRANSITION 2.
FITTINGS AS REQUIRED TO CONNECT TO UNIT INLET.
RETURN AIR DUCT, TYPICAL. PROVIDE TRANSITION 1.
FCU-6
FCU-5
FCU-3
FCU-9
FCU-7
FCU-8
FCU-7
FCU-8
FCU-5
FCU-3
FCU-9
WITH DUCT ROUTING.
EXISTING ROOF TRUSS CROSS-BRACING IS IN CONFLICT
COORDINATE WITH STRUCTURAL TRADES WHERE B.
DRAWING M-400.
COORDINATE SERVICE CLEARANCE AREAS WITH A.
2019-04-29T08:10:46-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:51:34 PM
PER SMACNA
SIZE AND OVERLAP
FIELD WELDING
ANGLE FRAME FOR
DOOR
ACCESS
HINGED
SMACNA/MANUFACTURER
CLEARANCE PER
FIRE DAMPER WALL INSTALLATION DETAIL
WELDED TOUCH UP WELD AREA WITH ZINC RICH PAINT.
3. HINGES AND HASP SHALL BE SECURED TO DUCTWORK WITH RIVETS OR BY WELDING. IF
2. WHEN HASP IS CLOSED HASP SHALL COVER RIVETS USED TO SECURE HASP TO DUCTWORK.
1. INSTALL DAMPER IN ACCORDANCE TO MANUFACTURERS WRITTEN INSTRUCTIONS.
AS SHOWN
FIRE DAMPER HOUSING
TO ACCOMMODATE
SLEEVE SIZE
10 GAUGE STEEL
SECURED TO
FIRE DAMPER
SMACNA TYPE 1
FIRE DAMPER HOUSING
TO ACCOMMODATE
THREADED ROD THREADED ROD
UNISTRUT
4. SEE SOUND ATTENUATOR SCHEDULE FOR SIZING, M-605.
FIRE DAMPER HOUSING
TO ACCOMMODATE
FIRE DAMPER WALL INSTALLATION WITH ATTENUATOR
THREADED ROD THREADED ROD
4. SEE SOUND ATTENUATOR SCHEDULE FOR SIZING, M-605.
JOINT TYP
BREAKAWAY SLIP
UNISTRUT, TYP
WITH ATTENUATOR AND FLARED OPENNING
FIRE DAMPER WALL INSTALLATION DETAIL
TO PLENUM
FLARED OPENING
BOTH SIDES
JOINT, TYPICAL
BOTH SIDES
JOINT, TYPICAL
HINGED ACCESS DOOR
HINGED ACCESS DOOR
M-506
682783_2215M-506.dgn
78 149
2019-04-29T08:11:39-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it
-6 e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 2:59:22 PM
M-600 k
682783_2215M-600.dgn
IA
BOIL-1 BOIL-2 BOIL-3
FM
I
PUMP ALARM PUMP ENABLE
DI DO
TANK
BYPASS
CHEMICAL
-2
TO SYSTEM
TANK, TYP OF 3
NEUTRALIZING
CONDENSATE
NOTE 4 NOTE 4
FSFSFS NOTES 2&5
2&5
NOTES
2&5
NOTES
SENSOR
PRESSURE
TEMPRATURE
HEATING WATER CONTROL DIAGRAM
SPEED
PUMP
2 PSI NAT GAS
HEATING WATER SECONDARY PUMPS, PUMP-1A AND PUMP-1B
ADDITIONAL POINTS TO MONITOR
1A
1B
VESTIBULE 127
LOCATED OUTSIDE
TO HOLD 10 PSI
TRANSMITTER SET
DIFFERENTIAL
2" HWR 3" HWR
3" HWS2" HWS
NC
NC
HOT WATER SUPPLY
RETURN
TO SYSTEM
HIGH CAPACITY
VALVE & CAP
WITH HOSE
TREAD
TYP 3 BOILERS
DISTANCE FROM ERU-1 AIR INTAKE,
MINIMUM OF 20 FT HORIZONTAL
CONCENTRIC FLUE OUTLET A
THRU ROOF, TERMINATE WITH A
EXTEND AIR INTAKE AND EXHAUST
CONNECTION TO THE DDC SYSTEM OR EXTERNAL CONTROLS REQUIRED.
PUMPS ARE POWERED AND CONTROLD BY THE RESPECTIVE BOILER. NO
PRIMARY HOT WATER PUMP CONTROL:
MANUALLY RESET.
DAMPERS SHALL CLOSE. SHUTDOWN SHALL REMAIN IN EFFECT UNTIL
EXHAUST AND OUTSIDE AIR FANS SHALL SHUT DOWN AND ALL CONTROL
SHUTDOWN SWITCH, LOCATED AS SHOWN IN THE PLANS, ALL HVAC SUPPLY,
5. EMERGENCY HVAC SHUTDOWN SWITCH. UPON ACTIVATION OF ANY
4. GLOBAL OUTSIDE AIR TEMPERATURE.
3. ELECTRICAL METER: COORDINATE WITH ELECTRICAL SHOP.
2. WATER METER: COORDINATE TYPE WITH WATER SHOP.
PULSED SIGNAL TO MONITOR GAS CONSUMPTION.
1. GAS METER: COORDINATE WITH INSTALLATION OF NEW METER TO GET A
DISPLAY
METER
FLOW
2" TYP
3/4" DRAIN TYP
GAS REGULATOR
3/4" G
1-1/4" G
1" G
3/4" G
3" BYPASS
NOTE 4 NOTE 4
M-300
FOR EQUIPMENT
STRUT SUPPORT
79 149
NETWORK
NETWORK SET TO HOLD 10 GPM
BALANCING VALVE
THERMOMETER,
DIGITAL
TEMPRATURE
FROM SYSTEM
SEPARATOR
AIR VENT OF AIR
3/4", CONNECT TO
HOSE END
DRAIN WITH
WITH HOSE END
DRAIN VALVE
INCREMENTS SO THERE IS AT LEAST ONE HEATING WATER VALVE THAT IS 80%-90% OPEN.
THE TEMPERATURE DOWN TO MINIMIZE ENERGY CONSUMPTION. RESET IN 10 DEGREE
THE DDC SYSTEM SHALL PROVIDE A TEMPERATURE SETPOINT FOR THE BOILERS. RESET
TEMPERATURE RESET:
THE LEAD BOILER ON A WEEKLY BASIS.
BOILERS. BOIL-1 SHALL BE THE LEAD BOILER FOLLOWED BY BOIL-2 AND BOIL-3. ROTATE
BOILERS SHALL UTILIZE A LEAD LAG FUNCTION TO INSURE EQUAL RUN TIME ON ALL
DECREASES THE LAST BOILER ON SHALL BE THE FIRST BOILER OFF.
LOAD CONTINUES TO BE UNMET THE NEXT BOILER SHALL BE ENABLED. AS THE LOAD
BOILER, NEXT BOILER AND ASSOCIATED CIRCULATION PUMP SHALL BE ENABLED. IF THE
BE ENABLED TO MEET HEATING LOAD. IF HEATING LOAD DEMAND IS NOT MET WITH LEAD
INCREASE IN HEATING LOAD: LEAD BOILER AND ASSOCIATED CIRCULATION PUMP SHALL
STAGING OF BOILERS:
SETPOINT. FAILURE OF BOILER SHALL INITIATE AN ALARM.
RATE MODULATION AS REQUIRED TO MAINTAIN HEATING WATER TEMPERATURE
WITH COMPLETE OPERATION AND SAFETY CONTROLS INCLUDING INDIVIDUAL FIRING
THEIR OWN INTERNAL CONTROLS. THE BOILER CONTROLS SHALL PROVIDE THE BOILER
THIS SYSTEM CONSISTS OF THREE BOILERS. THE BURNERS SHALL BE CONTROLLED VIA
BOILER CONTROL:
TYP 3.
8. 3/4" CPVC CONDENSATE LINE TO FLOOR DRAIN,
FOR THE FLOW METER.
OF FLOW METER VERIFY PIPING REQUIREMENTS
FOR THE FLOW METER. BEFORE INSTALLATION
7. COORDINATE THE POWER REQUIREMENTS
VOLTAGE REQUIREMENTS.
DDC SYSTEM TO ENSURE CORRECT
COORDINATE THE CONNECTIONS TO THE
6. MECHANICAL CONTRACTOR SHALL
IF UNABLE TO POWER FROM BOILER.
CONNECT TO POWER AS REQUIRED
FROM BOILER. PROVIDE A RELAY AND
5. CIRCULATION PUMP POWER TO BE FED
OF BOILER CONTROLS.
SENSORS AND FLOW SWITCH FURNISHED AS PART
4. SUPPLY AND RETURN WATER TEMPERATURE
3. NOT USED
MANUFACTURER.
2. BOILER CIRCULATION PUMP FURNISHED BY BOILER
1. ALL SET POINTS SHALL BE USER ADJUSTABLE.
BUILDING
SPLITS TO SERVE
VALVE, BEFORE PIPING
ISOLATION BUTTERFLY
TYP 3
SWITCH,
NOTE 8 NOTE 8 NOTE 8
FLOW SHALL BE VERIFIED BY THE FLOW METER.
THE SECONDARY HEATING WATER PRESSURE SET-POINT OF 10 PSI (ADJUSTABLE).
PUMP IS MANUALLY RESET. WHEN ON, THE SPEED OF THE LEAD PUMP SHALL BE VARIED TO MAINTAIN
THE LEAD PUMP SHALL THEN REMAIN IN THE LEAD STATUS UNTIL THE ALARM STATUS FOR THE FAILED
STATUS AND THE BACKUP PUMP TO LEAD STATUS. THE NEW LEAD PUMP SHALL THEN BE ENABLED ON.
TO PROVIDE FLOW WHEN ON SHALL INITIATE AN ALARM AND ALTERNATE THE LEAD PUMP TO BACKUP
WEEKLY. THE LEAD PUMP SHALL OPERATE WHEN HEATING IS ENABLED. FAILURE OF THE LEAD PUMP
THE LAG PUMP. ONLY ONE PUMP SHALL RUN AT A TIME. LEAD AND LAG STATUS SHALL BE ALTERNATED
PUMPS SHALL OPERATE ALTERNATELY WITH ONE PUMP AS THE LEAD PUMP AND THE OTHER PUMP AS
HEATING WATER SECONDARY PUMP AUTOMATIC CONTROL: THE TWO SECONDARY HEATING WATER
ASSOCIATED VFD.
HEATING WATER SECONDARY PUMP MANUAL MODE: PUMP MAY BE CONTROLLED MANUALLY FROM THE
ONE FAN COIL OR VAV BOX FOR MORE THAN 30 MINUTES (ADJUSTABLE).
AMBIENT TEMPERATURE IS BELOW 60°F (ADJUSTABLE) OR WHEN THERE IS A CALL FOR HEAT BY ANY
HEATING WATER SYSTEM ENABLE: THE HEATING SYSTEM WILL AUTOMATICALLY START WHEN THE
NORMAL MODE: OFF, BOILERS OFF, PUMPS OFF
BOILERS BOIL-1, BOIL-2 AND BOIL-3 SEQUENCE OF OPERATION:
BOILER SOO CONT'D BOILER SOO CONT'D
2019-04-29T08:16:23-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:00:40 PM
LCD DISPLAY
FLOW METER
RATE
VFD
HANDHOLE
PUMP-2B
PUMP-2ASIGHT GLASS
WITH HOSE BIBB
3/4" DRAIN VALVE
CHILLERCHILLER
FAILURE
ON/OFF
AT CHILLERS
AT CHILLERS
- TYPICAL
CONNECTOR
FLEXIBLE
VALVE -
CT CT
TANK
BY-PASS
CHEMICAL
VALVE -
CT
COOLER
DRY BED
CHILLER PIPING DIAGRAM
DIGITAL THERMOMETER, TYP
4" BYPASS
CWR
CWS
-O
FROM CHILLED
WATER SYSTEM
ERU-1 CONTROL DIAGRAM
EXHAUST
.5
A
FAN COIL UNITS
SUPPLY AIR TO
MD-1
HOSE THREAD
3/4" DRAIN WITH
DIFFERENTIAL PRESSURE
TRANSMITTER
PT AI
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NEAR FC-22
PRESSURE TRANSMITTER
LOCATE DIFFERENTIAL
ROOF
ABOVE GRADE
APPROXIMATELY 18'
OUTSIDE AIR INTAKE
HIGH CAPACITY
WATER SYSTEM
TO CHILLED
1/2"
DAMPER
FACTORY
HC-1
CC-1
SYSTEMS
TO FAN COIL
SYSTEMS
TO VAV
TEMP
POSITION
POSITION
ILT
GAUGE
M-601 k
682783_2215M-601.dgn
CHILLER CH-1, CH-2
ENERGY RECOVERY UNIT ERU-1
80 149
AIRFLOW
SUPPLY/RETURN
FILTER
EXHAUST
SUPPLY/
70DEG F.VAV ZONES IN A MIX OF HEATING OR COOLING
72 DEG F.ALL VAV ZONES IN HEATING:
65DEG F.ALL VAV ZONES IN COOLING:
OVERLAPING (REHEATING) TO MAINAIN THE FOLLOWING LEAVING AIR TEMPERATURES:
THE HEATING AND COOLING COILS SHALL WORK TOGETHER WITHOUT
HEATING COIL (HC-1) AND COOLING COIL (CC-1)
THAT ARE FURNISHED AS PART OF THE UNIT CONTROLS SYSTEM.
ADDITIONAL CONTROL POINTS TO MONITOR OR CONTROLS
REFER TO SPECIFICATION SECTION 23 82 19.00 40 FOR4.
SHOWN IN THE DDC SYSTEM WITH THE CONTRACTING OFFICER.
CONTRACTOR SHALL COORDINATE NUMBER AND TYPE OF POINTS 3.
OUTSIDE AIR AND EXHAUST AIR FLOW RATES.
DDC SYSTEM SHALL PROVIDE AN ACTIVE DISPLAY OF THE2.
SET AT 0.5” WC (ADJUSTABLE).
DIRTY FILTER ALARM FOR OUTSIDE AIR AND EXHAUST AIR1.
CONTROL SYSTEM SHALL MONITOR THE FOLLOWING POINT:
OUTSIDE AIR DAMPERS OPEN TO AVOID PULLING BUILDING NEGATIVE.)
(CONTRACTOR SHALL COORDINATE THE NUMBER OF FC-X UNITS WITH
OCCUPIED TIME: CONTRACTOR SHALL COORDINATE WITH END USER.
THE RETURN AIR FLOW THRU THE UNIT IS ABOVE 2400 CFM.
THRU THE ERU OF 2400 CFM. DAMPER MD-1 SHALL NOT BEGIN TO OPEN UNIT
THE DAMPER MD-1 SHALL MODULATE TO MAINTAN A DIFFERENTIAL AIR FLOW
VARY THE FAN RPM TO MAINTAIN PRESSURE SET-POINTS.
DURING OCCUPIED TIMES THE EXHAUST FAN AND THE SUPPLY FAN SHALL
OCCUPIED VENTILATION EXHAUST PRESSURE: 1.0” WC (ADJUSTABLE).
OCCUPIED SUPPLY AIR PRESSURE: 0.75” WC (ADJUSTABLE).
SET-POINTS:
ACTUATORS PROVIDED WITH UNIT.
EXHAUST AND OUTSIDE AIR DAMPER SHALL CLOSE. DAMPERS AND
DAMPERS OPEN. WHEN IN OFF POSITION FANS SHALL SHUT DOWN AND
TIMES AND SHALL RUN CONTINUOUSLY AS DESCRIBED BELOW WITH
AUTO/OFF: FANS SHALL BE AUTOMATICALLY ENABLED DURING OCCUPIED
SET-POINT OF 15 PSI (ADJUSTABLE).
OF THE LEAD PUMP SHALL BE VARIED TO MAINTAIN THE SECONDARY CHILLED WATER PRESSURE
STATUS UNTIL THE ALARM STATUS FOR THE FAILED PUMP IS MANUALLY RESET. WHEN ON, THE SPEED
THE NEW LEAD PUMP SHALL THEN BE ENABLED ON. THE LEAD PUMP SHALL THEN REMAIN IN THE LEAD
STATUS.
ALARM AND ALTERNATE THE LEAD PUMP TO BACKUP STATUS AND THE BACKUP PUMP TO LEAD
COOLING IS ENABLED. FAILURE OF THE LEAD PUMP TO PROVIDE FLOW WHEN ON SHALL INITIATE AN
LEAD AND LAG STATUS SHALL BE ALTERNATED WEEKLY. THE LEAD PUMP SHALL OPERATE WHEN
TIME.
PUMP AS THE LEAD PUMP AND THE OTHER PUMP AS THE LAG PUMP. ONLY ONE PUMP SHALL RUN AT A
PUMPS SHALL OPERATE ALTERNATELY TO MAINTAIN SYSTEM DIFFERENTIAL PRESSURE WITH ONE
CHILLED WATER SECONDARY PUMP AUTOMATIC CONTROL: THE TWO SECONDARY CHILLED WATER
CHILLED WATER SECONDARY PUMP MANUAL MODE SHALL BE CONTROLLED THRU THE VFD.
CHILLED WATER SECONDARY PUMPS, PUMP-2A AND PUMP-2B
TEMPERATURE OF 42°F BY STAGING FANS OFF/ON.
THE DRY BED COOLER SHALL UTILIZE INTERNAL CONTROLS TO MAINTAIN A LEAVING WATER
SHALL BE OPENED, THE PRIMARY PUMP-6 SHALL BE ENABLED AND THE DRY BED COOLER ENABLED.
RETURN WATER TEMPERATURE THE MOTORIZED ISOLATION VALVE ASSOCIATED WITH THE COOLER
BUILDING DDC SYSTEM. WHEN THE AMBIENT TEMPERATURE IS MORE THAN 5°F COOLER THAN THE
AUTOMATIC MODE: THE DRY BED COOLER SHALL BE CONTROLLED WITH COMMUNICATION FROM THE
BE OFF.
RUN WITH A SIGNAL FROM THE DDC SYSTEM. WHEN THE SWITCH IS OFF THE DRY BED COOLER SHALL
OFF/AUTO: WHEN THE SWITCH IS IN THE AUTO POSITION THE DRY BED COOLER SHALL BE ENABLED TO
DRY BED COOLER DB-1
THE FLOW SWITCH INTERNAL TO EACH CHILLER.
ASSOCIATED ISOLATION VALVE OPENED. PRIMARY CHILLED WATER FLOW SHALL BE MONITORED BY
CHILLER IS COMMANDED TO BE ON THE ASSOCIATED PRIMARY PUMP SHALL BE ENABLED AND THE
ALARM INITIATED. THE FAILED CHILLER SHALL REMAIN LOCKED OUT UNTIL MANUALLY RESET. WHEN A
IF A CHILLER GOES INTO ALARM WHEN ENABLED THE OFFLINE CHILLER SHALL BE ENABLED AND AN
LAG CHILLER OFF WHEN EACH CHILLER IS AT APPROXIMATELY 40% OF FULL CAPACITY.
CHILLER ON WHEN THE LEAD CHILLER IS AT APPROXIMATELY 90% OF FULL CAPACITY AND CYCLE THE
TO STAGE THE LAG CHILLER ON/OFF AS REQUIRED TO MEET THE BUILDING LOAD. STAGE THE LAG
SYSTEM SHALL MONITOR THE AMP DRAW OF THE CHILLER(S) AND THE LEAVING WATER TEMPERATURE
CAPACITY SHALL VARY USING INTERNAL CONTROLS TO MEET LEAVING WATER SETPOINT. THE DDC
LEAD STATUS UNTIL THE ALARM STATUS FOR THE FAILED CHILLER IS MANUALLY RESET. CHILLER
THE NEW LEAD CHILLER SHALL THEN BE ENABLED ON. THE LEAD CHILLER SHALL THEN REMAIN IN THE
STATUS.
ALARM AND ALTERNATE THE LEAD CHILLER TO BACKUP STATUS AND THE BACKUP CHILLER TO LEAD
COOLING IS ENABLED. FAILURE OF THE LEAD CHILLER TO PROVIDE FLOW WHEN ON SHALL INITIATE AN
LEAD AND LAG STATUS SHALL BE ALTERNATED WEEKLY. THE LEAD CHILLER SHALL OPERATE WHEN
ON A CALL FOR COOLING FROM ANY ONE ZONE FOR MORE THAN 30 MINUTES (ADJUSTABLE).
CHILLERS AND ASSOCIATED PUMPS SHALL BE ENABLED AND RESPECTIVE MOTORIZED VALVE OPENED
AND DISABLED AND SHALL LEAD AND LAG OPERATION BASED ON HOURS THRU THE DDC SYSTEM.
MAINTAIN THE PRIMARY CHILLED WATER TEMPERATURE SET-POINT. THE CHILLERS SHALL BE ENABLED
SYSTEM. THE CHILLER INTERNAL CONTROLS SHALL MODULATE THE CHILLER AS REQUIRED TO
AUTOMATIC MODE: THE CHILLERS SHALL BE ENABLED WITH COMMUNICATION FROM THE BUILDING DDC
WITH A SIGNAL FROM THE DDC SYSTEM. WHEN THE SWITCH IS OFF THE CHILLER SHALL BE OFF.
OFF/AUTO: WHEN THE SWITCH IS IN THE AUTO POSITION THE CHILLERS SHALL BE ENABLED TO RUN
2019-04-29T08:17:13-0600
Price, Ted INC00033148 e c k e d F il je c t s c ri p ti t
S tr e it e c je c t is e I d a h
FILENAME: PLOT DATE: PLOT TIME:2019\04\23 3:02:01 PM
T P
RETURN AIR
(3
-F
IS
A
DISCHARGE AIR SENSOR
FURNISHED WITH FCU
MOTOR CONTROL PANEL
TO SPACE
STARTER
(3
-F
CONSTANT VOLUME VERTICAL FAN COIL CONTROL DIAGRAM
FAN COIL UNITS AND HU-1 AND HU-2
HEATING
VAV
SA
VAV'S
OTHER
TO
AIRFLOW TRACKING
TWO OR THREE WAY VALVE
TEMP
ZONE
TEMP SENSOR
DISCHARGE AIR
AO M
F AI
AI T
T AI
SEQUENCE OF OPERATION VAV BOX
TYPICAL VAV W/REHEAT COIL CONTROL DIAGRAM
FC-23 FAN COIL CONTROL DIAGRAM
IN RETURN DUCT, TYP 7
TEMPERATURE SENSOR
AIAOAOAI
DOAIAO
FROM
BOXES
TO VAV
TO SPACE
OTHER ITEMS TO CONTROL
PROVIDE A CT TRANSMITTER TO VERIFY WHEN FAN IS OPERATING.
EF-1: COORDINATE THE REINSTALLATION OF EF-1. CONNECT USING EXISTING CONTROLS.
CONNECTION AND MAP ALL AVAILABLE POINTS OF METERS.
IS A YOKOGAW PR300. CONNECT TO THE RS-485 ETHERNET
EXISTING POWER METER IN ELECTRICAL ROOM . METER
DAMPER MODULATION
POSITION SENSOR
PROVIDE INDEPENDENT VALVE
2. FC-10 SHALL UTILIZE AN AIR SIDE ECONOMIZER AS THE FIRST STAGE OF COOLING.
1. FC-10 AND FC-4 SHALL MAINTAIN THE FOLLOWING TEMPERATURE SET POINTS: 55°F HEATING TO 85°F COOLING.
EXCEPTION:
THE OUTSIDE AIR DAMPER SHALL BE OPEN DURING OCCUPIED HOURS AND CLOSED DURING UNOCCUPIED HOURS.
OUTSIDE AIR:
THE COOLING WATER VALVE SHALL BE CLOSED.
DURING HEATING MODE: HEATING WATER VALVE SHALL MODULATE TO MAINTAIN DESIRED ROOM…