Phase 1 - Plans - Amd 0007.pdf
PDF 4 MB Posted
- Solicitation number
- W912DS25BA004
About this file
These architectural and engineering design plans detail a manufacturing lab addition and renovation project for Buildings 331 and 332 at Joint Base McGuire-Dix-Lakehurst in Lakehurst, New Jersey. The comprehensive set of technical drawings covers multiple disciplines including civil, structural, architectural, mechanical, plumbing, and electrical systems for an additive manufacturing laboratory expansion. Key components include a new high-bay laboratory space with specialized infrastructure for compressed air, nitrogen, and argon gas systems, HVAC equipment with precise environmental controls, rooftop mechanical units, and comprehensive utility modifications to support advanced manufacturing research and development activities.
The design documents specify detailed technical requirements for the lab, including specific equipment installations, utility connections, fire protection systems, and integrated mechanical systems. Notable features include specialized ventilation for particulate containment, multiple gas supply systems with regulators and quick-connect interfaces, rooftop mechanical platforms, and precise environmental control systems. The project involves carefully coordinating new construction with existing building infrastructure, ensuring minimal disruption to ongoing operations while implementing advanced laboratory capabilities. The plans are marked as final submittal for construction, dated January 2025, with the most recent amendment dated 28 May 2025, indicating an ongoing design refinement process.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O
N C
R
ETE
BUILDING 332
C O
N C
R
ETE
BUILDING 332T
BUILDING 331
X
X X
X
XXX
X X
X
X
ELECTRIC
CONCRETE
PAD
PAVED
PARKING LOT
PLAN
TER
WOODEN RAMP
GV
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G
G
G
G
G
G
G
G
G
G
GGGGGG
G
G G
G
G G
G G
G G
G G
G G
G G
G G
G G
G G
G G
TR
EN
C H
D R
AIN
CONCRETE
BARRIERS
H O
U G
H
TO
N R
O
AD
CO
CO
AC UNIT
ON RAISED
CONCRETE
AC UNITS
AC UNIT
ON RAISED
CONCRETE
AC UNIT
AC UNIT
T
T
VENTS
GAS METER
GAS METER
EQUIPMENT
FIRE PHONE
FIRE PHONE
FIRE PHONE
FIRE PHONE
4" PVC
15" R
C P
15" RCP
SILL90.14
SILL90.15
SILL90.12
SILL90.18
FF90.16
AC UNIT
COMPENSATED
AIR DISCHARGE
ROOF DRAIN
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
W W
W W
W W
W W
W W
W W
W W
W W
F F
F
F F F F F F F F
C C C C C C C
C
C C C C C C C C C C C C
W
W W
W W
W W
W W
W W
W
S
S S
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E
E
E
E
E
E
E
E E
E E
E E
E E
E E
E
E E E E E E E E
E
E
E E
E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E E E E E E E E E E E E E E
E E E E E E E
E E
E E
E
E
E
E E
E E
E E
E E
E E
E E
E
E
E
E
E
E E
E E
E E
E
E E
E E
E E
E
C C
C C
C C
C C C C C C C
C
C C
C C
C
C C C C C
C C
C C
C C
C C
C C
C C
C C
C C
C
E E
E E
G
C
LEN
D
EN
IN
G
STR
EET
INLET GRT 89.22
IN 4" INV 87.1
OUT 15" INV 86.4
MH RIM 89.85
INV 84.7
INLET TRENCH 89.75
INV 89.1
BSM-3
SPIKE & TAG ON CURB
N:434652.21 E:543861.89
ELEV:85.94'
ROOF DRAIN ROOF DRAIN
ROOF DRAIN
PLAN
TER
87 88 89
ROOF
DRAIN
ROOF
DRAIN
17 17
20 20
GV
G G
E E
E
E
E
E
E
E
E
E
E
G
G
G
GV
W
W
W
W
PLAN
NORTH
LA
KE
H U
R
ST
, N J
FA
D
JA
N
U
AR
Y
JO
IN
T-
BA
SE
M C
G U
IR
E-
D
IX
-L
AK
EH
U
R
ST
, L
AK
EH
U
R
ST
N J
AD
D
IT
IT
VE
L
AB
A
D D
IT
IO
N
FA
D
FI
N
AL
S
U
BM
IT
TA
L
- I
SS
U
ED
F
O R
C O
N
ST
R U
C
TI
O N
SHEET ID
AI
R
F O
R C
E C
IV
IL
E N
G
IN
EE
R
IN
G
C
EN
TE
R
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
Au to de sk
D oc s:
//0
9-
-J
BM
D
L B3
B
2/
-0 3C
D
1.
dw g
A1 EXISTING CONDITIONS AND DEMOLITION PLAN
SCALE: 1" = 10'
GENERAL SHEET NOTES
1. ALL EXISTING INFORMATION SHOWN HEREON IS BASED ON THE CAD FILE
PROVIDED BY BORBAS SURVEYING & MAPPING, LLC. THIS IS NOT A BOUNDARY
OR TOPOGRAPHIC SURVEY. THE CERTIFICATION ON THIS SHEET IS INTENDED
ONLY TO CERTIFY THE DEMOLITION SHOWN, NOT THE EXISTING CONDITIONS.
2. THE HORIZONTAL DATUM IS THE NEW JERSEY STATE PLANE COORDINATE
SYSTEM NAD83 (2011) DETERMINED BY DIFFERENTIAL GPS ON JULY 11, 2022
USING THE NGS CORS SYSTEM, REFERENCE STATION NJOC.
3. THE VERTICAL DATUM IS THE NORTH AMERICAN VERTICAL DATUM OF 1988
(NAVD88) GEOID12A VERIFIED BY DIFFERENTIAL GPS OBSERVATIONS FROM THE
NGS CORS NETWORK ON JULY 11, 2022. BENCHMARK: REFERENCE STATION
NJOC (ORTHOMETRIC HEIGHT=81.4629').
4. THIS BASE MAP DEPICTS LIMITED PHYSICAL IMPROVEMENTS AS THEY EXISTED
ON JULY 11, 2022. NO ATTEMPT HAS BEEN MADE TO DETERMINE THE LOCATION
OF PROPERTY LINES, EASEMENTS OR RIGHT-OF-WAY LINES.
5. ALL COORDINATES AND ELEVATIONS SHOWN HEREON ARE IN U.S. SURVEY FEET
IN THE HORIZONTAL AND VERTICAL DATUMS LISTED ABOVE.
6. THE UTILITIES SHOWN HAVE BEEN LOCATED FROM EVIDENCE OBSERVED ON
THE SURFACE ONLY. THE SURVEYOR MAKES NO GUARANTEES THAT THE
UTILITIES SHOWN COMPRISE ALL SUCH UTILITIES IN THE AREA, EITHER
IN-SERVICE OR ABANDONED. THE SURVEYOR FURTHER DOES NOT WARRANT
THAT THE UNDERGROUND UTILITIES SHOWN ARE IN THE EXACT LOCATION
INDICATED. THE SURVEYOR HAS NOT PHYSICALLY LOCATED THE
UNDERGROUND UTILITIES.
7. COMMUNICATIONS, ELECTRICAL POWER, WATER, FIRE WATER, SANITARY
SEWER, AND NATURAL GAS UNDERGROUND UTILITIES HAVE BEEN SHOWN ON
THESE PLANS BASED ON GIS INFORMATION PROVIDED BY THE BASE.
CONTRACTOR SHALL LOCATE ALL UNDERGROUND UTILITIES PRIOR TO
DEMOLITION AND CONSTRUCTION.
SHEET KEYNOTES
1. REMOVE BUILDING DOWNSPOUTS
2. REMOVE AC UNIT AND CONCRETE PAD, RE: MECHANICAL
3. REMOVE METAL PLATFORM AND GAS TANKS ALONG WITH CONCRETE PAD
4. SAWCUT ASPHALT
5. REMOVE ASPHALT
6. REMOVE LIGHT POLE, RE: ELECTRICAL
7. REMOVE LIGHTING FEEDS BACK TO NEAREST HANDHOLE OR LIGHT POLE
8. REMOVE VAULT
9. REMOVE SHELTER STRUCTURE
10. NOT USED
11. REMOVE PLANTERS
12. REMOVE ELECTRICAL EQUIPMENT AND CONCRETE PADS, RE: ELECTRICAL
13. REMOVE NATURAL GAS METER AND SERVICE LINE BACK TO MAIN, CUT AND CAP
SERVICE, CONTACT NJNG CO TO MOVE NATURAL GAS LINES, RE: PLUMBING
14. REMOVE WATER LINE, CUT AND CAP
15. REMOVE SANITARY SEWER CLEANOUT AND SERVICE LINE, CUT AND CAP AT
MAIN
16. CUT AND CAP STEAM PIPES (APPROXIMATE LOCATION), RE: PLUMBING
17. REMOVE EXTERNAL ELECTRICAL CONDUIT, RE: ELECTRICAL
18. REMOVE EXISTING COMPRESSED AIR, STEAM, AND CONDENSATE PIPES
19. RELOCATE CONCRETE BARRICADE
20. REMOVE MISCELLANEOUS UTILITY EQUIPMENT
21. SAWCUT, DEMOLISH AND REMOVE CURB
AM
EN
D
M
EN
T
M
AY
A.
S
EA
L
A.
Y
AR
N
EL
L
N . L
EA
G
U E
D . C
AV
IN
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
AN
D D
EM
O
LI
TI
O N
P
LA
N
CD101A10' 20'0
5/
/2
:5
AM
MATCHLINE, SEE DETAIL A17 THIS SHEET
MATCHLINE SEE PLAN THIS SHEET
A16 FIRE SERVICE DETAIL
SCALE: 1"=10' 10' 20'0
08/01/202324 JUNE 202428 MAY 2025
J1
S-510A
1 3 4
B
A
C
D
E
F
G
16' - 0" 14' - 5" 11' - 7"
J1
S-510A
J7
S-510A
J7
S-510A
W10X54 W10X54
W10X54
W10X54W10X33W10X54
W10X33
W10X33
W10X54 W10X54
W10X54
W10X54 W10X54
W10X33
W10X33
W10X33
W10X33
2 24
H12
S-201A
H1
S-201A
F7 F9
F8
F8 F4 F8
F5
F5
F5
F5
F5
F5
F6 F6
F9 F6
F5
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP1
BP2BP2
BP2
BP2
BP1
HSS4X4X1/4
BP4
S-401A
H1 ABOVE
1' - 5"
4' - 0"
A1
S-201A
6' - 10"
4' - 0"
(FIELD
VERIFY)
(FIELD
VERIFY)
G1
S-202A
A8
S-201A
A1
S-201A
SIM.
BP3
SEE NOTE 4
16' - 6"
A1
S-502A
TYP. AT NEW
DOORWAYS
A1
S-502A
SIM.
TYP.
TYP.
4' - 8" 3' - 4" 3' - 0" 4' - 0"
3' - 4" 4' - 8"
A1
S-202A
S L O
P E
D O
W N
J12
S-510A
TYP.
SIM.
SLOPE
DOWN
SLOPE
DOWN
/8
/1
4' - 0"
SLOPE
DOW
N
INDICATES SPREAD FOOTING DESIGNATION. SEE
SCHEDULE ON SHEET S-601A FOR FOOTING INFORMATION.
INDICATES BASE PLATE DESIGNATION. SEE S-508A FOR
BASE PLATE DESIGNS.
1. SLAB ON GRADE IN NEW ADDITION SHALL BE 12" THICK
REINFORCED WITH #5 AT 14" O.C. EACH WAY, TOP AND
BOTTOM. THICKEN SLAB EDGE PER J7 / S-510A EVERYWHERE
SLAB EDGE MEETS EXTERIOR GRADE OR STOOPS (NOT
WHERE SLAB EDGE MEETS EXISTING B331/B332 SLABS).
2. EXISTING SLAB ON GRADE IN B331 AND B332 (TO REMAIN).
3. ROLL-UP DOOR THRESHOLD. SEE DETAIL J13 / S-502A.
4. COLUMN ISOLATION JOINT (TYP.). SEE DETAILS J1 AND J7
ON SHEET S-502A. SEE DETAIL E1 / S-501A FOR TYPICAL RE-
ENTRANT CORNER REINFORCING FOR SLAB.
5. 4" CONCRETE STOOP WITH #4 AT 16" O.C. AT MID-DEPTH OF
CONCRETE. SEE J7 / S-501A FOR TYPICAL STOOP DETAIL.
SLOPE 1/8" PER FOOT MINIMUM AND 3/8" PER FOOT MAXIMUM
TO ENSURE MARRY UP TO CIVIL PAVING.
6. EQUIPMENT PAD. SEE DETAIL K1 / S-503A AND COORDINATE
SIZE WITH EQUIPMENT CUT SHEET.
7. 6" CONCRETE PAD REINF. WITH #4 AT 16" O.C. AT MID-DEPTH
OF CONCRETE. SEE J13 / S-502A FOR DETAIL AT JOINT.
USE 1/8" PER FOOT MIN. TO 3/8" PER FOOT MAX. SLOPE IN
THREE DIRECTIONS AS SHOWN AND VERIFY IN FIELD THAT
CONCRETE PAD WILL MARRY UP TO SIDEWALK PAVING AT
LOW END.
8. CONSTRUCTION OR CONTRACTION JOINT IN 6" SLAB. SEE
DETAILS J14 AND D8 ON SHEET S-501A. 6" SLAB TO SLOPE
NORTH FROM OH DOOR, EAST FROM PEDESTRIAN DOOR AT
WEST SIDE AND WEST FROM PEDESTRIAN DOOR AT EAST
END OF 6" SLAB.
9. PIPE BOLLARD EMBEDDED THROUGH NEW 6" SLAB, EXISTING
5" SLAB, OR EXISTING 4" STOOP (SEE K7 ON S-508A).
10. PIPE BOLLARD SURFACE MOUNTED TO 12" MAT SLAB (SEE A1
ON S-508A).
11. DEMO 12" CMU BLOCK BELOW (1) EXISTING 2'-0"H x 3'-0"W
WINDOW TO CREATE PEDESTRIAN DOOR AND DOOR
THRESHOLD (SEE ARCH. ELEVATIONS).
12. DEMOLISH EXISTING 5" THICK REINFORCED CONCRETE SLAB
(AREA APPROXIMATELY 9'-0" BY 7'-0") IN NEW RESTROOM.
REPLACE SLAB IN KIND AFTER NEW PLUMBING IS INSTALLED.
SEE P-401B FOR MORE INFORMATION. SEE DETAIL G1 / S-503A
FOR SLAB REPAIR DETAIL. SLOPE CONCRETE SLAB TO DRAIN.
SEE MECH. FOR DRAIN LOCATION.
13. DUST CONTROL PLATES AT BASE OF COLUMN, SEE
DETAIL A12 / S-515A.
14. SLOPE SLAB ON GRADE 1/8" PER FOOT TO DRAIN IN FILTER
ROOM (SEE MECH. FOR LOCATION OF DRAIN).
15. OVERHEAD DOOR CENTERLINE (SEE ARCH.). DOOR HEADER
AND RAIL SUPPORTS ARE LIGHT GAGE STUDS AND ARE A
DELEGATED DESIGN. DESIGN OVERHEAD DOOR AT
STOREFRONT FOR COMPONENTS AND CLADDING WINDS
SHOWN ON S-701A AND DESIGN INTERIOR OVERHEAD DOOR
FOR PARTITION LOADS. COORDINATE WITH DOOR
MANUFACTURER FOR DOOR DEAD AND LIVE LOADS.
16. EXTERIOR CONCRETE PAVING. SEE CIVIL.
17. THICKEN SLAB EDGE PER J7 / S-510A AT THIS EDGE.
18. FOUNDATION FOR 1500 GAL. ARGON TANK AND EQUIPMENT.
SEE K1 / S-503A FOR TYPICAL DETAIL. SEE CIVIL FOR
LOCATION.
19. FOUNDATION FOR GENERATOR. SEE K1 / S-503A FOR TYPICAL
DETAIL. SEE CIVIL FOR LOCATION.
1. TOP OF FINISHED FLOOR EL. 0'-0" U.N.O.
2. SEE DETAIL C13 / S-502A FOR REINFORCING AT DOOR
OPENINGS AND J7 / S-501A FOR TYPICAL STOOP DETAIL.
3. TOP OF SPREAD FOOTING ELEVATION SHALL BE -2'-0"
UNLESS NOTED OTHERWISE.
4. 12" MAT SLAB DOES NOT REQUIRE CONSTRUCTION OR
CONTRACTION JOINTS.
5. SEE MECHANICAL, ELECTRICAL, AND CIVIL DRAWINGS FOR
LOCATIONS OF EQUIPMENT PADS AND HOUSEKEEPING
PADS. SEE DETAILS K1 / S-503A FOR EXTERIOR
EQUIPMENT PAD DETAIL AND A1 / S-501A FOR
HOUSEKEEPING PAD DETAIL.
6. SEE ARCH. DRAWING AD-201A FOR LOCATIONS OF
EXISTING WINDOWS TO BE REMOVED AND REPLACED
WITH 12" CMU BLOCK INFILL. NEW BLOCK INFILL IS
UNREINFORCED AND CUT TO FIT.
7. ALL EXTERIOR CONCRETE PAVING AND STOOPS SHALL BE
SLOPED AT 1/4" PER FOOT UNLESS NOTED OTHERWISE.
EXTERIOR STOOPS AT PEDESTRIAN AND OVERHEAD
DOORS DROP 1/4" AT THE THRESHOLD.
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s /0
-0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n S
.r v t
/2
/2
:0
:4
P
M
S-101A
F O
U N
D A
T
IO
N P
L A
N
J B
M D
L L a k e h u rs t, N
J A
M
A G
IN
N
IS
A M
A G
IN
N
IS
C T
R A
N
J A
N U
A R
Y
F A
D
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
1/8" = 1'-0"A1
FOUNDATION PLAN
0 4' 8' 16'
PLAN NORTH
GENERAL SHEET NOTES
LEGEND
FX
BPX
SHEET KEYNOTES
A
M E
N D
M E
N T
M
A Y
UPUP
A6
AE202A
1 4
G
F
E
D
C
B
A
A4
AE301A
F6
AE301A
K10
AE301A
A7
AE304A
A10
AE303A
A1
AE304A
4" / 1'-0" 4" / 1'-0" 1/2" / 1'-0"1/2" / 1'-0"
1 1
DS
DS
DS
DS
DS
DS
DS
DS
DS DS
TYP
4 4
A5
AE302A
BELOW
10 10
H1
AE505A
A4
AE201A
E6
AE201A
K4
AE201A
TYP
EPDM ROOF
ROOF LEGEND
STANDING SEAM METAL ROOF
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s /0
-0
-J
B M
D L B
B
/J
B M
D L
L a b E x p a n s io n A
.r v t
/2
/2
:3
:1
P
M
AE120A
R O
O F
P L A
N
J O
IN
T
B A
S E
M C
G U
IR
E
-D
IX
-L A
K E
H U
R S
T L A
K E
H U
R S
T N
J D
R E
M Y
M R
O B
IN
S
O N
Q R
E M
Y
J A
N U
A R
Y
M S
B L
-4
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
1/8" = 1'-0" A3
ROOF PLAN
0' 2' 4' 8' 16'
PLAN NORTH
SHEET KEYNOTES
1 PREFINISHED METAL GUTTER
2 LOW SLOPE STANDING SEAM METAL ROOF ENTRY
3 STANDING SEAM METAL ROOF
4 EPDM ROOF
5 ROOF ACCESS LADDER WITH PERSONAL FALL
ARREST SYSTEM
6 GALVANIZED MECHANICAL PLATFORM AND LADDER
BY MANUFACTURER
8 MECHANICAL EQUIPMENT, RE: MECHANICAL
9 REMOVABLE RAIL
10 PIPING, RE: PLUMBING
11 SNOW GUARDS BY MANUFACTURER
GENERAL SHEET NOTES
1 EXISTING BUILDING 331 AND EXISTING BUILDING 332
WILL BE OCCUPIED DURING CONSTRUCTION.
CONTRACTOR MUST TAKE APPROPRIATE PRECAUTION
TO PROTECT THESE FACILITIES, EQUIPMENT, AND
PERSONNEL DURING CONSTRUCTION.
3 MECHANICAL EQUIPMENT IS SUPPORTED BY A ROOF
CURB BY MANUFACTURER, RE: MECHANICAL. THE
OPENINGS FOR ROOF MOUNTED MECHANICAL
EQUIPMENT MUST BE COORDINATED WITH THE LIGHT
GAUGE TRUSS MANUFACTURER, RE: STRUCTURAL.
TRUSS MANUFACTURER MUST ACCOUNT FOR THE
LOADING OF THE SYSTEMS, RE: STRUCTURAL.
4 THE MECHANICAL PLATFORM SYSTEM IS ONLY
INTENDED TO SUPPORT THE LOAD OF THE
MAINTENANCE PERSONNEL AND THEIR TOOLS,
FILTERS, ETC. IT IS NOT INTENDED TO BEAR THE
WEIGHT OF THE MECHANICAL SYSTEMS. THE BASIS
OF DESIGN FOR THE MECHANCIAL PLATFORM
SYSTEM IS TO ATTACH TO THE VERTICAL SEAM OF THE
STANDING SEAM METAL ROOF. DUE TO THE SENSITIVITY
OF THIS TYPE OF FACILITY, THIS SYSTEM WAS
SELECTED TO MINIMIZE ROOF PENETRATIOSN AND TO
REDUCE MAINTENANCE AND MITIGATE THE POTENTIAL
FOR LEAKS. ACTUAL ATTACHMENT DETAILS ARE BY
MANUFACTURER SELECTED. CONTRACTOR MUST
COORDINATE THE MECHANICAL PLATFORM SYSTEM
WITH THE ROOFING MANUFACTURER/INSTALLER.
5 SNOW GUARDS SHOWN FOR BIDDING PURPOSES ONLY.
FINAL LAYOUT TO BE BY MANUFACTURER SELECTED.
A
M E
N D
M E
N T
M
A Y
EL. 12'-4"
332 JOIST BEARING
EXISTING ROOF DECK
EXISTING CMU WALL
EXISTING ROOF JOIST
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
6" CH METAL STUD FRAMING
R-19 BATT INSULATION
1" MOISTURE/MOLD
RESISTANT SHAFT LINER
COMPOSITE METAL PANEL ON
THERMAL BREAK ATTACHMENT
SYSTEM (TYPICAL)
1 1/2" RIGID INSULATION
5/8" GLASS MAT SHEATHING
2" PREFORMED JOINT SEAL
EXPANSION JOINT
EPDM MEMBRANE
1/2" GLASS MAT COVER BOARD
6" RIGID INSULATION
1/2" PLYWOOD
FLUID APPLIED MEMBRANE AIR
BARRIER
METAL TRIM FLASHING
METAL COUNTERFLASHING
EL. 16'-6"
331 JOIST BEARING
EXISTING ROOF DECK
EXISTING ROOF JOIST
EXISTING CMU WALL
1/2" PLYWOOD
6" RIGID INSULATION
1/2" GLASS MATCOVER BOARD
EPDM MEMBRANE
COMPOSITE METAL PANEL ON THERMAL
BREAK ATTACHMENT SYSTEM (TYPICAL)
1 1/2" RIGID INSULATION
FLUID APPLIED MEMBRANE AIR BARRIER
5/8" GLASS MAT SHEATHING
2" PREFORMED JOINT SEAL
EXPANSION JOINT
1" MOISTURE/MOLD
RESISTANT SHAFT LINER
6" CH METAL STUD FRAMING
R-19 BATT INSULATION
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
METAL TRIM FLASHING
METAL COUNTERFLASHING
PROVIDE CRICKET FOR POSITIVE DRAINAGE
INSULATED CURB BY MFR,
PREFINISHED TO MATCH
ADJACENT ROOF COLOR
2" STANDING SEAM METAL ROOF, ON SLIP
SHEET, ON SELF-ADHERING UNDERLAYMENT,
ON 1/2" HD POLYISO, ON 6" RIGID
INSULATION, ON 5/8" GLASS MAT SHEATHING,
ON 1 1/2" METAL DECK
8" MIN. CURBING ABOVE THE SURFACE OF THE ROOF
MECHANICAL EQUIPMENT, RE: MECHANICAL
MECHANICAL PLATFORM SYSTEM
HELD OFF CURB PER
MANUFACTURER. STANDING SEAM
CLAMP ATTACHMENT PER
MANUFACTURER.
MECHANICAL DUCT, RE: MECHANICAL
BENT PLATE
PRE-ENGINEERED LIGHT
GAUGE STEEL TRUSS, RE:
STRUCTURAL FOR LOADING
SMALL FRAMING AT DECK OPENING
BY TRUSS MANUFACTURER, RE:
STRUCTURAL
THROUGH ROOF PIPE. EXTEND TO
ACCOMODATE NEW ROOF THICKNESS
PIPE FLASH CUT TO PIPE SIZE IN FIELD
SO THAT FLASHING FITS SNUGGLY
AROUND PIPE. SET BASE IN
CONTINUOUS BEAD OF APPROVED
SEALANT
3/16" BLIND RIVETS W/ SEALING WASHERS
@ 2" O.C. FASTENED TO THE PANEL ONLY
AND NOT INTO THE ROOF SUBSTRATE TO
ALLOW THE PANEL TO MOVE THERMALLY
PRIOR TO SLIDING PIPE FLASH DOWN
OVER PIPE, PLACE A CONTINUOUS BEAD
OF APPROVED SEALANT AROUND PIPE
AT THE HEIGHT OF THE BOOT SO THAT
WHEN THE BOOT IS IN PLACE THE TOP
OF THE BOOT ENGAGES THE SEALANT
NOTES:
1. ADEQUATE CLEARANCE MUST BE LEFT BETWEEN THE PIPE AND THE PANEL TO ALLOW FOR THERMAL MOVEMENT WITHOUT
INTERFERENCE.
2. THE PIPE MUST BE CENTERED IN THE PANEL TO ALLOW ADEQUATE CLEARANCE FOR INSTALLATION OF THE PIPE FLASH WITHOUT
INTERFERENCE WITH THE PANEL RIBS. IF THIS IS NOT POSSIBLE USE DETAIL AT RIB
3.
4.
PIPES LARGER THAN 6" IN DIAMETER MAY REQUIRE A CURB DEPENDING ON PANEL WIDTH & PIPE LOCATION. THIS IS TO BE VERIFIED
IN FIELD
ALL FLASHINGS TO CONTINUE A MINIMUM OF 8" ABOVE THE ROOF DECK
*SNUGGLY MEANS NO WATER CAN PENETRATE BETWEEN TOP OF BOOT & PIPE.
SEALANT
CLAMPING RING
PRE-MANUFACTURED FLEXIBLE
STANDING SEAM METAL ROOF
PIPE FLASHING TO 8" MIN
ABOVE ROOF, WEATHERPROOF
COLOR TO MATCH ROOF.
VENT PIPE COLOR TO
MATCH ROOF, RE: MECH.
1" M
IN
STANDING
SEAM METAL
ROOF
8" M
IN
CLAMPING RING
CLAMPING RING
PRE-MANUFACTURED FLEXIBLE PIPE
FLASHING, WEATHERPROOF. COLOR
TO MATCH STANDING SEAM METAL
ROOF
GUY WIRE
EPDM ROOF
PRE-MANUFACTURED METAL CLIP
ROOF VENT
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
D R
E M
Y
A u to d e s k D o c s /0
-0
-J
B M
D L B
B
/J
B M
D L
L a b E x p a n s io n A
.r v t
/2
/2
:2
:3
P
M
AE503A
R O
O F
D E
T A
IL
S
J O
IN
T
B A
S E
M C
G U
IR
E
-D
IX
-L A
K E
H U
R S
T L A
K E
H U
R S
T N
J D
R E
M Y
M R
O B
IN
S
O N
Q R
E M
Y
J A
N U
A R
Y
M S
B L
-4
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
3" = 1'-0" A1
ADDITIVE LAB SHAFT WALL TO B332
EPDM ROOF DETAIL
3" = 1'-0" A10
ADDITIVE LAB SHAFT WALL TO B331
EPDM ROOF DETAIL
1 1/2" = 1'-0" K1
TYPICAL CURB DETAIL 3" = 1'-0"
K14
PIPE PENETRATION DETAIL AT RIB
1 1/2" = 1'-0" A16
ROOF - VENT DETAIL
0' 0.5' 1'1 1/2" 3" 0' 0.5' 1'1 1/2" 3"
0' 0.5' 1'1 1/2" 3"
0' 1' 2'3" 6"
0' 1' 2'3" 6"
1 1/2" = 1'-0" F16
TYPICAL ROOF PIPE PENETRATION
DETAIL
0' 1' 2'3" 6"
A
M E
N D
M E
N T
M
A Y
F
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
6" CH METAL STUD
FRAMING
COMPOSITE METAL PANEL
ON THERMAL BREAK
ATTACHMENT SYSTEM
(TYPICAL)
R-19 BATT INSULATION
5/8" MOISTURE/MOLD
RESISTANT GYP BOARD
6" METAL STUD
FRAMING
1 1/2" RIGID INSULATION
5/8" GLASS MAT
SHEATHING
1" MOISTURE/MOLD
RESISTANT SHAFT LINER
2" PREFORMED JOINT
SEAL EXPANSION JOINT
FLUID APPLIED
MEMBRANE AIR
BARRIER
PREFINISHED METAL
PARAPET CAP (BELOW)
EPDM ROOF (BELOW)
EPDM MEMBRANE
FLASHING
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
1" MOISTURE/MOLD
RESISTANT SHAFT
LINER
COMPOSITE METAL PANEL ON
THERMAL BREAK ATTACHMENT
SYSTEM (TYPICAL)
2" PREFORMED JOINT
SEAL EXPANSION JOINT
R-19 BATT INSULATION
6" CH METAL STUD
FRAMING
1 1/2" RIGID INSULATION
5/8" GLASS MAT SHEATHING
1" GLASS FIBER GYP BOARD SHAFT LINER
FLUID APPLIED MEMBRANE
AIR BARRIER
EPDM MEMBRANE FLASHING
PREFINISHED METAL
PARAPET CAP (BELOW)
EPDM ROOF (BELOW)
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD RESISTANT
GYP BOARD
1" MOISTURE/MOLD
RESISTANT SHAFT LINER
COMPOSITE METAL PANEL ON
THERMAL BREAK
ATTACHMENT SYSTEM
(TYPICAL)
2" PREFORMED JOINT
SEAL EXPANSION JOINT
R-19 BATT INSULATION
5/8" GLASS MAT GYP
BOARD
6" METAL STUD
FRAMING
1 1/2" RIGID INSULATION
5/8" GLASS MAT
SHEATHING
FLUID APPLIED
MEMBRANE AIR BARRIER
PREFINISHED METAL
PARAPET CAP (BELOW)
EPDM ROOF (BELOW)
EPDM MEMBRANE
FLASHING
6" CH METAL STUD FRAMING
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
1" MOISTURE/MOLD
RESISTANT SHAFT
LINER
COMPOSITE METAL
PANEL ON THERMAL
BREAK ATTACHMENT
SYSTEM (TYPICAL)
2" PREFORMED JOINT
SEAL EXPANSION JOINT
R-19 BATT INSULATION
6" CH METAL STUD
FRAMING
1 1/2" RIGID INSULATION
5/8" GLASS MAT SHEATHING
FLUID APPLIED MEMBRANE
AIR BARRIER
EPDM MEMBRANE
FLASHING
PREFINISHED METAL
PARAPET CAP (BELOW)
EPDM ROOF (BELOW)
EL. 12'-4"
332 JOIST BEARING
1/2" GLASS MAT COVER BOARD
COMPOSITE METAL PANEL
ON THERMAL BREAK
ATTACHMENT SYSTEM
(TYPICAL)
6" RIGID INSULATION
PREFINISHED METAL
GUTTER
1/2" PLYWOOD SHEATHING
EXISTING CONCRETE ROOF
DECK
EXISTING CMU WALL
EXISTING ROOF JOIST
EPDM MEMBRANE
WOOD BLOCK NAILER
PREFINISHED METAL
DOWNSPOUT
5/8" GLASS MAT SHEATHING
LIGHT GAUGE METAL
FRAMING, RE: STRUCTURAL
FOR LOADING
ROOFTOP BAR RAIL
STEEL ANGLE,
ANCHORED TO EPDM
WELDED ANGLE TO
COMPOSITE METAL PANEL
3 LAYERS 5/8" TYPE X -
MOISTURE/MOLD
RESISTANT GYP BOARD
6" CH METAL STUD
FRAMING
R-19 BATT INSULATION
1" MOISTURE/MOLD
RESISTANT SHAFT LINER
2" PREFORMED JOINT
SEAL EXPANSION JOINT
METAL TRIM FLASHING
COMPOSITE METAL PANEL ON
THERMAL BREAK ATTACHMENT
SYSTEM (TYPICAL)
5/8" GLASS MAT
SHEATHING
FLUID APPLIED
MEMBRANE AIR BARRIER
1 1/2" RIGID INSULATION
METAL
COUNTERFLASHING
EPDM MEMBRANE
1/2" GLASS MAT COVER BOARD
6" RIGID INSULATION
1/2" PLYWOOD
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
D R
E M
Y
A u to d e s k D o c s /0
-0
-J
B M
D L B
B
/J
B M
D L
L a b E x p a n s io n A
.r v t
/2
/2
:2
:2
P
M
AE505A
R O
O F
D E
T A
IL
S
J O
IN
T
B A
S E
M C
G U
IR
E
-D
IX
-L A
K E
H U
R S
T L A
K E
H U
R S
T N
J D
R E
M Y
M R
O B
IN
S
O N
Q R
E M
Y
J A
N U
A R
Y
M S
B L
-4
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
3" = 1'-0" H15
ADDITIVE LAB SHAFT WALL TO B331
EPDM ROOF EXPANSION JOINT PLAN
DETAIL
3" = 1'-0" A15
ADDITIVE LAB SHAFT WALL TO B331
EPDM ROOF EXPANSION JOINT PLAN
DETAIL
3" = 1'-0" H8
ADDITIVE LAB SHAFT WALL TO B332
EPDM ROOF EXPANSION JOINT PLAN
DETAIL
3" = 1'-0" A8
ADDITIVE LAB SHAFT WALL TO B332
EPDM ROOF EXPANSION JOINT PLAN
DETAIL
3" = 1'-0" A1
TYPICAL EPDM ROOF EAVE DETAIL
0' 0.5' 1'1 1/2" 3" 0' 0.5' 1'1 1/2" 3" 0' 0.5' 1'1 1/2" 3"
0' 0.5' 1'1 1/2" 3"0' 0.5' 1'1 1/2" 3"3" = 1'-0" H1
MECHANICAL PLATFORM LADDER TO
EPDM ROOF
0' 0.5' 1'1 1/2" 3"
A
M E
N D
M E
N T
M
A Y
E
AC-2
E
AC-1
1 2 3 4
A
B
C
D
E
F
1/8" = 1'-0"C3
HVAC DEMOLITION PLAN
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s
/0 -0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:4
:2
P
M
MD101A
H V
A C
D E
M O
L
IT
IO
N
P L A
N
J B
M D
L L a k e h u rs t, N
J D
H
E R
N A
N D
E Z
M T
A Y
L O
R
M A
B
U S
B Y
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
EXISTING AIR COMPRESSOR - SEE
PLUMBING DRAWINGS
EXISTING AIR HANDLING UNIT THAT
SUPPLIES AIR TO B332 IS TO BE REMOVED
ALONG WITH ALL PIPING, SUPPORTS, AND
ELECTRICAL CONNECTIONS AND WIRING.
EXISTING GAS METER AND GAS LINE TO
BE REMOVED - SEE CIVIL DRAWINGS.
DURING PHASE 1 AND 2, ENTIRETY OF
BUILDING 332 IS TO BE MAINTAINED IN
OPERATION AND WILL REQUIRE THAT
TEMPORARY COOLING AND HEATING
IS PROVIDED BY THE CONTRACTOR TO
MAINTAIN TEMPERATE AND HUMIDITY
CONTROL IN THE SPACE.
CONTRACTOR CAN REUSE EXISTING
DUCTWORK LOCATED IN THE MECHANCAL
ROOM (HATCHED) IF POSSIBLE AND CONNECT
ONLY TO TEMPORARY UNIT IF POSSIBLE.
EXISTING AIR COMPRESSOR TO
REMAIN - SEE PLUMBING
DRAWINGS
EXISTING AIR HANDLING UNIT THAT
SUPPLIES AIR TO B331 TO REMAIN
ALONG WITH ALL PIPING, SUPPORTS, AND
ELECTRICAL CONNECTIONS AND WIRING.
EXISTING AIR
COMPRESSOR
RECEIVER TANK.
0 4' 8' 16'
PLAN NORTH
NEW PLUMBING FIXTURES - SEE
PLUMBING DRAWINGS
A
M M
E N
D M
E N
T
M
A Y
F13
M-301A
F13
M-301A
RG-1
500 CFM
SD-1
260 CFM
SD-1
275 CFM
(TYP. 8)
(TYP. 3)
(TYP. 3)
(TYP. 4)
SD-1
255 CFM
(TYP. 5)
VAV-8
V A
V -7
V A
V -6
A
V A
V -6
B
(TYP. 4)
CU-2 CU-1
SS-2 SS-1
T
T
T
T
24"ø SA
"ø
S A
"x
R A
"x
S A
"ø
O A
"ø
S A
"ø
S A
20"ø SA
"ø
S A
12"ø SA
"ø
S A
"ø
S A
"ø
S A
14"ø SA 8"ø SA
10"ø SA
"ø
R A
10"ø SA
10"ø SA
"ø
S A
"ø
R A
24"ø RA
1 2 3 4
A
B
C
D
E
F
5 5
3 3
6 18"ø OA
A13
M-301A
A13
M-301A
30"x18" SA
20"ø SA
3 HR RATED FIRE
DAMPER (TYP.)
O2
O2
O2
O2
F3
M-301A
F3
M-301A
A3
M-301A
A3
M-301A
10"ø SA
8 8
SD-2
630 CFM
"ø
R A
3 HR RATED FIRE
DAMPER (TYP.)
"ø
R A
260 CFM
FG-1
3000 CFM
LV-1
UH-1
M
OPTOMEC
CONTAINMENT
MECHANICAL
COMM
ELEC
POWDER
HANDLING
SD-3
100 CFM
(TYP. 4)
ADDITIVE LAB
ADD
EF-2
ADD
EF-1
260 CFM
FG-1
ADDITIVE LAB
(PARTICULATE
CONTAINMENT)
102FILTER CLOSET
12"ø EA
16"ø EA
RG-2
1600 CFM
"x
R A
10"ø SA
SD-1
255 CFM
10"ø SA
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s
/0 -0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:1
:5
P
M
M-101A
H V
A C
P L A
N
J B
M D
L L a k e h u rs t, N
J D
H
E R
N A
N D
E Z
M T
A Y
L O
R
M A
B
U S
B Y
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
1/8" = 1'-0"B5
HVAC PLAN
GENERAL NOTES
SHEET KEYNOTES
1. REFER TO M-001A FOR MECHANICAL ABBREVIATION AND
NOTES.
2. ALL WORK SHOWN ON THIS SHEET IS INTENDED TO BE
COMPLETED DURING ADDITION CONSTRUCTION. ENSURE ANY
MECHANICAL COMPONENTS TO BE USED FOR FUTURE
CONSTRUCTION PROJECTS ARE PROTECTED, AND ANY
DUCTWORK NOT USED TO SERVE THIS PORTION OF THE
BUILDING SHALL BE CAPPED.
3. THERMOSTATS AND OXYGEN SENSORS AND ALARMS ARE TO
BE EXPLOSION PROOF WHEN LOCATED IN CLASS 2 DIV 1
SPACES, "ADDITIVE LAB (PARTICULATE CONTAINMENT) 102".
REFER TO ELECTRICAL DRAWINGS FOR INFORMATION ON
AREAS AFFECTED.
4. DUCTWORK REQUIREMENTS
ROUND AND RECTANGULAR (SUPPLY AND RETURN)
EXPOSED - OCCUPIED AREAS - DOUBLE WALL G90 INNER AND
OUTER, INTERSTITIAL SPACE WITH 1" FIBERGLASS , 0.75 PCF.
MAXIMUM PRESSURE = 6 (IN WC) SEAL CLASS A
ROUND AND RECTANGULAR (SUPPLY AND RETURN)
CONCEALED- OCCUPIED AREAS - G90 GALVANIZED STEEL,
WITH 2" FIBERGLASS DUCT WRAP, 3.0 PCF.
MAXIMUM PRESSURE = 6 (IN WC) SEAL CLASS A
EXHAUST - ROUND AND RECTANGULAR
G90 GALVANIZED STEEL. NO INSULATION.
MAXIMUM PRESSURE = NEGATIVE 2 (IN WC) SEAL CLASS B
1. DUCTWORK PAST THIS POINT FOR FUTURE WORK. CAP ANY
OPEN DUCTS AND PENETRATIONS. PROVIDE PENETRATIONS
THROUGH FIRE RATED WALLS WITH 3 HR RATED FIRE
DAMPER.
2. DUCTWORK PAST THIS POINT WILL BE EXTENDED PAST WALL
PENETRATION, SIZED, AND CAPPED FOR FUTURE
CONNECTION. ALSO, CAP NEW OUTSIDE AIR DUCT FOR
FUTURE CONNECTION. PROVIDE PENETRATIONS THROUGH
FIRE RATED WALLS WITH 3 HR RATED FIRE DAMPER. SEAL
AROUND DUCTS WITH FIRE RATED SEALANT.
3. SUPPLY AND RETURN DUCTWORK TRAVELS UP TO RTU-A.
4. SUPPLY AND RETURN DUCTWORK TRAVELS UP TO RTU-B.
5. SUPPLY AND RETURN DUCTWORK TRAVELS UP TO RTU-C.
6. SUPPLY DUCTWORK TRAVELS UP TO DOAS-1.
7. LOW OXYGEN SENSORS TO BE WIRED TO BUILDING
CONTROLS.
8. PROVIDE EQUIPMENT PAD. REFER TO DETAIL K1 ON SHEET
S-503A FOR ADDITIONAL INFORMATION.
9. LV-1 TO HAVE MOTOR DAMPER TO CLOSE DURING
UNOCCUPIED CONDITIONS.
10. FILTER GRILLE FOR HIGH PARTICULATE , BOX UNIT WITH
FILTER AND HOLDING FRAME. UNIT TO MOUNT IN 24X24 GRID,
STAINLESS STEEL FRAME WITH KNURLED THUMBSCREWS
AND FOR USE WITH 2" FILTERS.
0 4' 8' 16'
PLAN NORTH
EPO
EPO
A
M M
E N
D M
E N
T
M
A Y
331 JOIST BEARING
116' - 6"
HIGH BAY ROOOF
BEARING
122' - 0"
6"ø OA
20"ø SA
24"ø RA
10"ø SA
SD-3
90 CFM
SD-1
275 CFM
14"ø SA
SUPPLY AND RETURN
FROM RTU-B, REFER TO
M-101A FOR
CONTINUATION.
PROVIDE 3 HR RATED FIRE
DAMPER.
BOD 9'-2" AFF
BOD
13'- 0" AFF
BOD
16'-2" AFF
BOD
16'-2" AFF
BOD 11'-5" AFF
HIGH BAY ROOOF
BEARING
122' - 0"
RTU-C DOAS-1
1 1
GAS PIPE ON ROOF,
SWING ELBOW OVER
ROOF.
PITCHED
CURB -
TYP. OF
ALL
RTU'S
RTU-A
"x
R A
"ø
S A
"ø
S A
"x
R A
1 3
RTU-B
GAS PIPE ON ROOF,
SWING ELBOW OVER
ROOF.
FINISHED FLOOR
100' - 0"
331 JOIST BEARING
116' - 6"
HIGH BAY ROOOF
BEARING
122' - 0"
332 JOIST BEARING
112' - 4"
SUPPLY AND RETURN DUCTS
FROM RTU-C. REFER TO
M-101A FOR CONTINUATION
30"x18" SA
14"ø OA
PROVIDE 3 HR RATED
FIRE DAMPER FOR DUCT
ENTERING EXISTING 332
(TYP. 3)
BOD
13'-9" AFF
BOD
16'-6" AFF
BOD
18'-10" AFF
BOD (3 DUCTS)
10'-0"AFF
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s
/0 -0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:1
:0
P
M
M-301A
H V
A C
S E
C T
IO
N
S
J B
M D
L L a k e h u rs t, N
J D
H
E R
N A
N D
E Z
M T
A Y
L O
R
J S
O L A
N O
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
1/4" = 1'-0"A13
MECHANICAL SECTION
0 2' 4' 8'
0 2' 4' 8'1/4" = 1'-0"F3
MECHANICAL ROOF SECTION
1/4" = 1'-0"A3
MECHANICAL ROOF SECTION
0 2' 4' 8'
1/4" = 1'-0"F13
MECHANICAL SECTION
0 2' 4' 8'
GENERAL NOTES
SHEET KEYNOTES
1. REFER TO M-001A FOR MECHANICAL ABBREVIATION AND
NOTES.
1. PROVIDE ROOFTOP UNITS WITH 24" MINIMUM HEIGHT ROOF
CURB (SEPERATE FROM ARCHITECTURAL ROOFTOP
PLATFORM) THAT MATCH THE SAME PITCH AS THE ROOF.
ROOF CURB SHALL BE VERIFIED TO BE COMPATIBLE WITH RTU
AND DOAS MANUFACTURER.
2. ROOF OPENINGS FOR ROOF TOP EQUIPMENT DUCTWORK
SHALL BE COORDINATED WITH JOIST /STRUCTURAL
COMPONENTS MANUFACTURER, TO PROVIDE PROPER
PLACEMENT AND REINFORCEMENT TO OPENING.
3. ROOF TOP IS FOR FUTURE INSTALLATION, AND WILL BE
CAPPED. CURB IS INSTALLED AS SHOWN.
A
M M
E N
D M
E N
T
M
A Y
VAV TERMINAL UNITS WITH ELECTRIC REHEAT
PLAN AIRFLOW UNIT ELECTRIC REHEAT TEMPERATURE (F) MINIMUM DESIGN
MARK RANGE SIZE AIRFLOW AIRFLOW
(CFM) VOLTS PHASE KW ENTERING/LEAVING (CFM) (CFM) REMARKS
VAV-6A 215 - 1840 10 120 1 5.5 55 / 85 600 1750 1
VAV-6B 215 - 1840 10 120 1 5.5 55 / 85 600 1750 1
VAV-7 215 - 1840 10 120 1 5.5 55 / 85 600 1700 1
VAV-8 125 - 1100 8 120 1 5.5 55 / 85 450 1000 1
REMARKS:
1. PROVIDE MIN 36" CLEARANCE TO VAV CONTROL PANEL.
DUCTLESS SPLIT-SYSTEM AIR CONDITIONING UNIT SCHEDULE
LOCATION INDOOR UNIT DATA OUTDOOR UNIT ELECTRIC DATA REMARKS
PLAN MARK
AIR COOLING
PLAN MARK
MINIMUM
CIRCUIT
AMPACITY (A)
VOLT/PH/HZ
FLOW MIN MAX
MAX. CAPACITY CAPACITY
(CFM) (BTU/HR) (BTU/HR)
SS-1 ADD LAB COMM 427 3000.0 15,000 CU-1 12.5 208/1/60 1
SS-2 ADD LAB ELECT 579 7500.0 23,884 CU-2 20.0 208/1/60 1
REMARKS:
1. PROVIDE TIE DOWN BOLTS AND RUBBER ISOLATION PADS (SEE DETAIL K-1 IN SHEET S503A).
2. UNITS WILL BE PROVIDED WITH 4" THICK CONCRETE PADS (SEE STRUCTURAL).
3. PROVIDE INDOOR UNITS WITH MOUNTING KITS, AND DRAIN KITS.
4. SECURE PIPING TO EXTERIOR WALL AND PROVIDE LINESET COVER KIT TO MATCH EXTERIOR.
5. PROVIDE DISCONNECT SWITCH WITH UNIT.
REMARKS:
1. ALL SELECTIONS BASED ON A SITE ELEVATION OF 131 METERS
2. UNIT TO BE CONTROLLED BY THE BUILDING AUTOMATION SYSTEM.
3. AHRI 360 CERTIFIED / ASHRAE 90.1 -2016 COMPLIANT
4. INVERTER OR VARIABLE SPEED COMPRESSORS
5. ALUMINUM MICROCHANNEL CONDENSER COIL / COPPER TUBE W/ AL FINS.
6. VAV FAN MOTOR DRIVES.
7. MERV 8/ MERV 13 FILTERS.
8. HOT GAS REHEAT.
9. UNIT MATCHED ROOF CURB WITH SLOPING CURB TO MATCH ROOF, 14" MIN.
10. NON FUSED DISCONNECT, PROVIDE SINGLE POINT POWER CONNECTION TO UNITS.
11. UNIT MOUNTED SERVICE RECEPTACLE.
12. PROVIDE UNIT WITH PRESSURE RELIEF TO AVOID OVERPRESSURIZATION IN SPACE.
13. SMOKE DETECTORS INSTALLED ON SUPPLY AND RELIEF DUCTS TO UNITS.
14. TRANE MFG EQUIPMENT PER J &A.
FAN SCHEDULE
PLAN TYPE SERVICE UNIT DUCT ESP FAN RPM REMARKS
MARK WEIGHT AIRFLOW (IN. W.C.) MOTOR VOLT/PH/HZ
(LBS) (CFM) SIZE
(HP)
ADD EF-1 IN-LINE FAN OPTOMEC ROOM 60 200 0.25 1,205 0.10 208/1/60 1,2,3,4
ADD EF-2 IN-LINE FAN MECH RM/COMP AIR 110 2,500 0.30 1,160 1/2 208/1/60 1,2,3,4
REMARKS:
1. ALL SELECTIONS BASED ON A SITE ELEVATION OF 131 METERS
2. UNIT TO BE CONTROLLED BY THE BUILDING AUTOMATION SYSTEM.
3. PROVIDE SINGLE POLE OR PLUG-IN MODULE DISCONNECT SWITCH.
4. DUCTWORK WILL BE EXTENDED UP TO ROOF MOUNTED CAP.
LOUVER SCHEDULE
PLAN SERVICE SYSTEM AIR SIZE MIN. FREE PRESSURE
MARK FLOW WIDTH HEIGHT AREA DROP REMARKS
(CFM) (IN) (IN) (SQ. FT.) (IN. W.G.)
LV-1 INTAKE MECH RM 2500 24 36 3.1 0.15 1, 2, 3, 4
REMARKS:
1. PROVIDE BIRD AND INSECT SCREEN.
2. PROVIDE MOTOR OPERATED DAMPER.
3. MOUNTING HEIGHT SHALL BE NO LESS THAN 10'-0" ABOVE FINISHED GRADE OR ADJACENT SIDEWALK.
4. DRAINABLE HEAVY GAUGE 6063 ALUMINUM BLADES.
ROOFTOP UNIT SCHEDULE
PLAN AIRFLOW SUPPLY FAN AIR FILTER DATA GAS PREHEATING
MARK MIN
ESP (WG)
VOLT/P
H
TYPE MAX. TYPE MAX PERFORMANCE
SETBACK HP PLEATED APD PLEATED APD EAT DB (DEG
F)
LAT DB
(DEG
F)
TOTAL
CAP. (MBH)
MAX APD
(DIRTY)
(WG)
AIRFLOW (DIRTY) (DIRTY)
(CFM) PRE (WG) FINAL (WG)
RTU-A 5,875 3 3.0 460/3 8 0.25 13 0.25 65.0 73.0 59 0.14
RTU-C 1,800 2 3.0 460/3 8 0.25 13 0.25 55.0 73.0 40 0.10
ROOFTOP UNIT SCHEDULE CONT'D
PLAN
MARK
COOLING COIL DATA
REFRIGERANT MIN COOLING PERFORMANCE
TYPE EAT EAT LAT LAT
SENSIBLE CAP. (MBH)
TOTAL CAP.
(MBH)
REMARKS
DB WB DB WB
(DEG F) (DEG F) (DEG F) (DEG F)
RTU-A 410 73.5 62.0 60.0 57.6 145 152 1 THRU 14
RTU-C 410 73.5 62.0 59.8 56.5 90 101 1 THRU 14
GAS HEATING
100% OUTSIDE AIR UNIT SCHEDULE
PLAN MARK
SUPPLY DX COIL AIR FILTER DATA
REMARKS
FLOW (CFM) ESP (IN WG)
MOTOR (HP)
VOLT/PH/HZ
EAT DB (DEG
F)
EAT WB (DEG
F)
LAT DB (DEG
F)
TOTAL CAP. (MBH) INPUT (MBH) PRE FINAL
DOAS-1 2,930 2 3 460/3/60 90.3 74.5 57.9 160.0 460/3/60 MERV 8 MERV 13 1 THRU 13
REMARKS
1. INVERTER OR VARIABLE SPEED COMPRESSOR. 7. ACCESS PANELS FOR COILS, FILTERS, AND FAN SECTION. 13. UNIT BY TRANE MFG, PER J&A
2. DIRECT EXPANSION COOLING AND GAS HEATING. 8. SOUND PERFORMANCE IN ACCORDANCE WITH AHRI 260.
3. SEALED PANEL DOUBLE WALL. 9. MOUNTED ON MATCHING ROOF CURB FROM SAME MANUFACTURER.
4. 2" MERV-8 PLEATED PRE-FILTER, MERV-13 FINAL FILTER. 10. SMOKE DETECTOR MOUNTED ON SUPPLY AND RETURN DUCTWORK.
5. ALUMINUM FINS W/ COPPER TUBES.. 11. UNIT WILL HAVE SINGLE POINT POWER CONNECTION AND SERVICE RECEPTACLE
6. STARTERS AND DISCONNECTS PROVIDED BY UNIT MANUFACTURER. 12. UNIT WILL HAVE SLOPING ROOF CURB TO MATCH ROOF.
ELECTRIC UNIT HEATER SCHEDULE
PLAN TYPE AREA EAT FAN ELECTRIC FAN REMARKS
MARK SERVED HEAT MOTOR POWER
(DEG F) (CFM) (kW) (WATTS) AMPs VOLT/PH/HZ
UH-1 SUSPENDED MECH 104 10 400 5 FRAC 6.2 480/3/60 1,2,3,4,5.
REMARKS:
1. HEAVY GUAGE WELDED STEEL, POWDER COATED BEIGE UNIT HEATER SUSPENDED FROM ACCESSORY WALL BRACKET.
2. COPPER CLAD STEEL SHEATH ELEMENT, WITH OVERHEAT PORTECTION WITH AUTOMATIC RESET LIMIIT CONTROL.
3. ADJUSTABLE LOUVER WITH UP TO 15 DEGREE DEFLECTION FROM HORZIONTAL.
4. ETL AGENCY RATING.
5. LOW VOLTAGE THERMOSTAT.
DIFFUSER, REGISTER AND GRILLE SCHEDULE
PLAN
MARK
DUTY DESCRIPTION
MODULE SIZE
(IN X IN)
NECK SIZE (IN) MATERIAL FINISH REMARKS
SD-1 SUPPLY 4-WAY DIFFUSER 24" X 24" MATCH DUCT SIZE ALUMINUM WHITE 1,2
SD-2 SUPPLY SIDEWALL DIFFUSER 18" X 12" 18" X 12" ALUMINUM WHITE 1.2
SD-3 SUPPLY SIDE WALL DIFFUSER 6" X 6" 6" X 6" ALUMINUM WHITE 1,2
SD-4 SUPPLY SIDE WALL DIFFUSER 8" X 8" 8" X 8" ALUMINUM WHITE 1,2
SD-5 SUPPLY SIDE WALL DIFFUSER 10" X 10" 10" X 10" ALUMINUM WHITE 1,2
SD-6 SUPPLY SIDE WALL DIFFUSER 12" X 12" 12" X 12" ALUMINUM WHITE 1,2
SD-7 SUPPLY 4-WAY DIFFUSER 24" X 24" 8" Ø ALUMINUM WHITE 1,2
RG-1 RETURN RETURN GRILLE 24" X 24" 12" X 12" ALUMINUM WHITE 1,2
RG-2 RETURN SIDEWALL RETURN GRILLE 12" X 12" 12" X 12" ALUMINUM WHITE 1,2
EG-1 EXHAUST EXHAUST GRILLE 12" X 12" 6" Ø ALUMINUM WHITE 1,2
REMARKS:
1. REFER TO ARCHITECTURAL DRAWINGS FOR TYPE OF CEILING AND/OR SUSPENSION SYSTEM, OR DUCT TO PROVIDE NECESSARY MOUNTING FRAMES
AND BRACKETS. SIDEWALL MOUNTS PROVIDED WITH EXTRACTORS.
2. MAXIMUM NC SHALL BE 20.
3. REFER TO FLOOR PLAN DRAWINGS FOR DIFFUSERS AND GRILLES USED.
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e sk
D o c s:
-0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:1
:0
P
M
M-601A
H V
A C
S C
H E
D U
L E
S
J B
M D
L L a k e h u rs t, N
J D
H
E R
N A
N D
E Z
M T
A Y
L O
R
M A
B
U S
B Y
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
A M
M E
N D
M E
N T
M
A Y
E
AC-1
1-1/2" CW TO
LINE AT EXTERIOR
REMOVE AND
PROVIDE NEW PLUMBING
FIXTURES, 1-1/2" CW TO
LINE AT EXTERIOR
1 2 3 4
A
B
C
D
E
F
FCO
3" ø S
AN
"ø
C A
3"ø SAN
4"ø SAN
1 1/4"ø DCW
CA HOSE
REEL
50' (TYP.)
F
F
F
F
F
1 1/2"ø CA
1"ø CA
1"ø CA
F
F F
1 1/2"ø CA
3"ø CA
F
1 1/2"ø CA
3"ø CA 1"ø CA
N2
Ar
N2
N2
N2
A r
N2
Ar
Ar
Ar
A r
A r
1/2"ø AR
1/2"ø AR
1/2"ø N2
3"ø CA
3"ø CA
1"ø CA
1 1/2"ø CA
1"ø CA
1 1/2"ø CA
1"ø CA
1"ø CA
1 1/2"ø CA
1 1/2"ø CA
1 1/2"ø CA
1 1/2"ø CA
3/4"ø CA
1"ø CA
1 1/2"ø AR
1/2"ø N2
1/2"ø N2
1/2"ø AR
1/2"ø AR
1/2"ø N2
3/4"ø N2
2"ø N2
3/4"ø N2
3/4"ø AR
3/4"ø N2
3/4"ø AR
1"ø CA
1 1/2"ø N2
1 1/2"ø AR
3/4"ø N2
3/4"ø AR
3/4"ø AR 3/4"ø N2
3/4"ø AR
3/4"ø AR
8 8
10 10
1/2"ø AR1/2"ø AR
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
B R
E N
O V
A T
IO
N
A u to d e s k D o c s
/0 -0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:1
:0
P
M
P-101A
P L U
M B
IN
G
P L A
N
J B
M D
L L a k e h u rs t, N
J D
W
H
IT
A K
E R
D W
H
IT
A K
E R
D H
E R
N A
N D
E Z
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
1/8" = 1'-0"B8
PLUMBING PLAN
GENERAL NOTES
1. REFER TO P-001A FOR PLUMBING ABBREVIATION AND NOTES.
2. REFER TO P-402A FOR PLUMBING COMPRESSED AIR
ISOMETRIC DIAGRAM.
3. COMPRESSED AIR OUTLETS ARE TO BE REGULATED AND
WHERE NOTED SHOW BE PROVIDED WITH PARTICULATE
FILTERS FOR CLEAN AIR CONNECTION TO EQUIPMENT AS
NOTED WITH "F".
4. NITROGEN AND ARGON DROPS WILL BE REGULATED AND
PROVIDED WITH VALVES AND QUICK CONNECTS.
5. THE CONTRACTOR SHALL FIELD VERIFY WITH ELECTRICAL,
MECHANICAL, AND FIRE PROTECTION, AND STRUCTURAL
EQUIPMENT CONTRACTORS AND INSTALLATION, TO AVOID
CONFLICTS WITH ROUTING OF EQUIPMENT, AND
COMPONENTS.
6. THE CONTRACTOR SHALL ACCOUNT FOR ADDITIONAL
ACCESSORIES REQUIRED FOR EQUIPMENT (SUCH AS
FILTERS, VALVES, ETC.) AND SHALL INSTALL EQUIPMENT TO
MAINTAIN ANY EQUIPMENT WARRANTIES
7. GAS METER NOTE:
AMRS COMPATIBLE GAS METER SPECIFICATIONS
• ACCURATELY SCALED OUTPUT PULSES
• PROPERLY SIZED COMPONENTS ACCORDING TO PEAK
DEMAND
• COORDINATE WITH BASE PERSONNEL TO OBTAIN ALL
NECESSARY INFORMATION TO BUILD SYSTEM THAT
SATISFIES REQUIREMENTS AND MEETS FOLLOWING
SPECIFICATION REQUIREMENTS.
1. PULSE KIT MUST BE ABLE TO PRODUCE 2 WIRE
(FORM A) PULSE OUTPUT VIA EXTERIOR RATED
RS485 CABLE IN CONDUIT.
2. GAS METER OR ATTACHED PULSE KIT MUST
INLCUDE A VISUAL REGISTER OR DIAL.
3. GAS METER SHALL INCLUDE UPSTREAM
GASKET STRAINERS.
4. ALL METER LABELS SALL BE WHITE ON BLACK
PHENOLIC.
5. ALL CABLING SHALL BE PROTECTED BY
CONDUIT.
PROVIDE NEW 4"
SANITARY LINE AND
RECONNECT TO
EXISTING FIXTURES
NEW GAS METER AND
REGULATOR (SEE GENERAL NOTES)
WITH NEW GAS LINE UP TO
ROOF TO SUPPLY
NEW ROOF UNITS
EXISTING AIR COMPRESSOR
AND ASSOCIATED EQUIPMENT
REMAINS, ALONG WITH AIR PIPING
0 4' 8' 16'
PLAN NORTH
SHEET KEYNOTES
1. COMPRESSED AIR HOSE REEL (50 Ft. HOSE CAPACITY) WITH
FULL PORT BALL VALVE, DIRT LEG, AND FILTER /REGULATOR.
SEE DETAIL SHEET FOR ADDITIONAL INFORMATION.
2. FILTERS ARE TO BE PROVIDED AT ALL INSTANCES NOTED ON
DRAWINGS WITH "F" SYMBOL, THE INSTALLATION AT THESE
LOCATIONS WILL REQUIRE REPLACEMENT ELEMENT
DESICCANT DRYER, 1 MICRON FILTER (OR AS NOTED PER
SERVICED EQUIPMENT), AND DESIGNATED FILTER.
3. COMPRESSED AIR SYSTEMS; PROVIDED BY GOVERNMENT
AND FACILITY. SYSTEM WILL INCLUDE COMPRESSOR, AIR
DRYER, AND RECEIVER TANK. COMPRESSOR AND DRYER ON
PLATFORM IN MECHANICAL ROOM. RECEIVER LOCATED
DIRECTLY BELOW, MOUNTED ON FLOOR.
4. PROVIDE A VALVED AND CAPPED COMPRESSED AIR SERVICE
LINE EXTENDS TO EXISTING B332, TO BE USED FOR FUTURE
CONNECTION.
5. 3/4" CW LINE TO DROP IN WALL AND STUB OUT TO HOSE BIBB
WITH VACUUM BREAKER. 2" VENT UP THROUGH WALL.
6. 3/4" CW LINE DROP IN WALL AND TO WALL HYDRANT FOR USE
WITH HOSED CONNECTION AT WATER USE TANKS, AND JETS.
7. 3/4" COMPRESSED AIR DROP TO FINISHER (WW).
8. FUTURE CONNECTION DROPS FOR ARGON AND NITROGEN
TO EQUIPMENT, PROVIDE CAPPED END, WITH REGULATOR
AND VALVE.
9. PROVIDE NITROGEN AND ARGON DROPS WITH REGULATOR
AND VALVE, AND QUICK CONNECT FOR HOSE CONNECTION
TO EQUIPMENT.
10. PROVIDE ARGON DROPS IN POWDER ROOM - TYPICAL OF 2.
11. NITROGEN GENERATOR IS GOVERNMENT PROVIDED
EQUIPMENT.
12. PROVIDE LINE SIZE REGULATOR, PRESSURE RELIEF AND
SHUTOFF VALVE AT EXTERIOR PAD LOCATION. 1500 GALLON
TANK IS TO BE LOCATED ON PAD AT EXTERIOR (SEE CIVIL
DRAWINGS). PAD SHALL HOUSE VAPORIZER AND TANK AND
ALL APPURTENANCES TO PROVIDE 200 PSIG GAS TO FACILITY.
CONCRETE PAD FOR 1500 GALLON
TANK AND VAPORIZER
A
M M
E N
D M
E N
T
M
A Y
6" MIN.
DIRT LEG UNION (TYP.)
ISOLATION VALVE (TYP.)
THREADED CAP
FITTING
GAS PIPE
EQUIPMENT
1" RELIEF VENT
THRU EXTERIOR WALL
MEDIUM PRESSURE GAS
LOW PRESSURE GAS
SUPPLIED AT APPLIANCE
PRESSURE
NOTE:
REFER TO DRAWINGS FOR PIPE SIZES.
GAS PRESSURE REGULATOR
FINISHED GRADE
4" CONCRETE PAD
TEE W/ BUSHING
AND 3/8" PLUG
GAS PRESSURE
REGULATOR
INSULATING UNION
PLUGGED TEE W/ BUSING
AND 3/8" PLUG
GAS COCK (TYP.)
ANNODELESS RISER
TO BUILDING
SUPPLY AT 0.5 PSIG
PROVIDE 1/2"
CONDUIT FOR MECS
WIRING
AF GAS METER WITH PULSE OUTPUT. PULSE KIT MUST PRODUCE 2 WIRE (FORM A) PLUSE
OUTPUT VIA EXTERIOR RATED RS485 CABLE. MUST INCLUDE A VISUAL REISTER OR DIAL.
METER SHALL INCLLUDE UPSTREAM GASKET STRAINERS. LABELS SHALL BE WHITE ON BLACK
PHENOLIC.CABLING SHALL BE PROTECTED BY CONDUIT.
TOTAL GAS LOAD OF 500 MBH
CONTRACTOR SHALL PROVIDE 2 METERS, ONE METER IS THE NJNG CO METER, AND THE
SECOND IS THE AF PULSE METER KIT, DESCRIBED ON SHEET P101A (GENERAL NOTES).
PIPE COLLAR
A A
PLAN
SECTION A - A
PIPE COLLAR
ASTM E814 RATING
T = 3 F = 3
1" X1-1/4" TAPCON (TM)
SCREWS. TYP 3
CONCRETE FLOOR/
MASONRY WALL
MAXIMUM 4" PLASTIC
PIPING
ANNULAR SPICING
MIN. 0" - MAX 1/2"
NO FILL MATERIAL REQUIRED
NOTES
1 IF PIPING IS INSULATED, STOP INSULATION AT FLOOR MAX. 1/2" ABOVE
PENETRATION AND RESUME ON OTHER SIDE MAX 1/2" FROM BOTTOM OF SLAB
INSTALLATION INSTRUCTIONS
THESE INSTRUCTIONS ARE FOR THE INSTALLATION OF THROUGH-PENETRATION FIRE
STOP SYSTEM IN A MINIMUM 4 1/2" THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150
PCF) CONCRETE OR HOLLOW-CORE FLOORS AS LISTED BY UNDERWRITERS
LABORATORIES INC. REFER TO ABOVE DRAWINGS AND SYSTEM CONFIGURATION
INFORMATION FOR COMPONENT DETAILS.
STEP PROCEDURE
1. CUT HOLE IN CONCRETE FLOOR IN REQUIRED SIZE TO ACCOMMODATE PIPE
PENETRATION AND ALLOWABLE ANNULAR SPACING. DO NOT EXCEED MAXIMUM
SPECIFIED HOLE DIAMETER.
2. INSTALL UP TO 4" I.D. ABS OR PVC/CPVC(FOAM OR SOLID CORE) VENTED (DWV) OR
CLOSED (PRESSURE) PIPE. SUPPORT PIPE RIGIDLY ON BOTH SIDES OF FLOOR.
3. CLEAN ALL HOLE AND PIPE SURFACES IN PENETRATION AREA TO REMOVE LOOSE
DEBRIS, DIRT, OIL, WAX, GREASE, OLD CAULKING, ETC.
4. INSTALL APPROPRIATE SIZE PIPE COLLAR FOR CORRESPONDING PLASTIC PIPE
DIAMETER ON BOTTOM SIDE OF FLOOR. SECURE COLLAR IN PLACE THROUGH
ANCHOR TABS WITH 1/4"X1 1/4" TAPCON(TM) CONCRETE ANCHOR SCREWS.
2 THIS NOTE FOR PLASTIC PIPING WITH COLLAR ONLY. FOR METALIC PIPING
PENETRATIONS, ANNULAR SPACE SHALL BE FILLED WITH AN APPROVED
FLEXIBLE FIRE STOP MATERIAL PER SPECIFICATIONS
3 COLLAR SHALL BE TESTED AND UL LISTED AS A FIRESTOP DEVISE ON ABS,CPVC,
PVC, AND PP PIPING SYSTEMS. COLLAR SHALL BE LISTED FOR UP TO A 3 HOUR
RATED FLOOR AND WALL ASSEMBLIES. COLLAR SHALL MEET USGBC GUIDELINES
FOR ADHESIVES AND SEALANTS. BASIS OF DESIGN: PFP PARTNERS PPC COLLAR
BALL VALVE
TYPE "K" COPPER
TUBING NO JOINTS
BELOW FLOOR
WRAP TUBING IN
CONCRETE WITH
PROTECTIVE
SLEEVE.
WATER MAIN PIPE
1/2" COPPER PIPE (TYP.)
TRAP PRIMER
FLOOR DRAIN
FINISHED FLOOR
FULL PORT
BALL VALVE
DRIP LEG DRAIN
CLEAR SIGHT CUP
DRIP LEG DRAIN FILTER UNIT
HOSE QUICK
DISCONNECT FITTING
GENERAL PURPOSE REGULATOR
UNIT TO PROVIDE MAX. 45 SCFM
CFM AT 5 TO 150 PSI RANGE
NOTE: ARRANGEMENT MAY MIRROR IN SOME LOCATIONS.
HOSEREEL
INLET SWIVEL
JOINT
MOUNT TO WALL
125 FT. OF 1" DIAMETER HOSE
FLEXIBLE
CONNECTOR
FULL PORT
BALL VALVE
CA DROP ALONG WALL
GENERAL PURPOSE FILTER
WITH REGULATOR AND PRESSURE GAUGE.
UNIT TO PROVIDE 5 TO 150 PSIG RANGE.
6" MINIMUM
DIRT LEG
UNION (TYP.)
FULL PORT
BALL VALVE
HOSE QUICK
DISCONNECT FITTING
GENERAL PURPOSE REGULATOR
UNIT TO PROVIDE MAX. 45 SCFM
CFM AT 5 TO 150 PSI RANGE
NOTES:
1. ARRANGEMENT MAY MIRROR IN SOME LOCATIONS.
2. DEVICES MAY BE INSTALLED IN VERTICAL CONFIGURATION.
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
E N
T E
R
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R
A D
D
IT
IV
E
L A
B A
D D
IT
IO
N
A u to d e s k D o c s
/0 -0
-J
B M
D L B
B
/0
-0
-J
B M
D L -B
B
L a b E x p a n s io n M
.r v t
/2
/2
:4
:3
P
M
P-501A
P L U
M B
IN
G
D E
T A
IL
S
J B
M D
L L a k e h u rs t, N
J D
W
H
IT
A K
E R
D W
H
IT
A K
E R
D H
E R
N A
N D
E Z
J A
N U
A R
Y
F
IN
A L
S U
B M
IT
T
A L
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
-0
D C
A V
IN
NTSK1
GAS CONNECTION TO EQUIPMENT DETAIL
NTSK9
GAS METER DETAIL
NTSF17
FIRE STOP DETAIL
NTSA1
TRAP PRIMER IN FLOOR DRAIN DETAIL
NTSF9
COMPRESSED AIR REGULATOR AND
LUBRICATOR DETAIL
NTSA9
COMPRESSED AIR HOSE REEL DETAIL
1/2" = 1'-0"F1
NITROGEN DROP DETAIL
A
M M
E N
D M
E N
T
M
A Y
| CD101A - EXISTING CONDITIONS AND DEMOLITION PLAN |
| S-101A - FOUNDATION PLAN |
| AE120A - ROOF PLAN |
| AE503A - ROOF DETAILS |
| AE505A - ROOF DETAILS |
| MD101A - HVAC DEMOLITION PLAN |
| M-101A - HVAC PLAN |
| M-301A - HVAC SECTIONS |
| M-601A - HVAC SCHEDULES |
| P-101A - PLUMBING PLAN |
| P-501A - PLUMBING DETAILS |