This package includes construction drawings and specifications for repair work at Power Building 4016 (J-Plant) at the BMEWS radar site in Thule, Greenland. The project involves repairing the Power Building, including replacement of the HEMP shielding. Key project elements include repairing the existing power J-Plant building; installing a new HEMP shield for the mechanical room, generator room, and other areas; and performing electrical upgrades. The specifications provide requirements for structural work, foundations and slabs, mechanical systems like generators and supporting equipment, and electrical systems. Relevant details are also included regarding codes and standards to be followed.
The opportunity is a solicitation issued by the US Army Corps of Engineers Engineering District New York. It requests proposals for repairing Building 4016 and replacing the HEMP shielding at the BMEWS radar site in Thule, Greenland.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN CRITERIA
1. THE FOLLOWING CODES AND STANDARDS, AS MODIFIED BY THE REFERENCED UFC PUBLICATIONS, INCLUDING ALL
SPECIFICATIONS REFERENCED, APPLY TO THE DESIGN OF THIS PROJECT:
A. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS WITH CHANGE 1 (1 OCTOBER 2020)
B. UFC 3-301-01 STRUCTURAL ENGINEERING (1 OCTOBER 2019)
C. IBC 2018, INTERNATIONAL BUILDING CODE
D. ASCE/SEI 7–16, MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES
E. ACI 318-14, AMERICAN CONCRETE INSTITUTE, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND
COMMENTARY
F. AISC 360-16, SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS.
CONSTRUCTION REQUIREMENTS
1. REVIEW AND VERIFY AS-BUILT CONDITIONS AND ACTUAL EQUIPMENT DIMENSIONS USING APPROVED
MANUFACTURER/VENDOR DRAWINGS PRIOR TO SUBMISSION OF SHOP DRAWINGS.
2. REVIEW AND VERIFY LOCATION OF CHASES, INSERTS, OPENINGS, SLEEVES, FINISHES, DEPRESSIONS, PADS, AND WALL
OPENINGS. COORDINATE WITH OTHER DISCIPLINE SHEETS.
3. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING CONSTRUCTION AND/OR SUBMITTING SHOP
DRAWINGS. REPORT ANY DISCREPANCIES TO THE COR.
4. DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS.
5. DO NOT STORE OR STACK CONSTRUCTION MATERIALS ON FLOORS/ROOFS IN EXCESS OF 80 PERCENT OF LIVE LOAD.
6. PROVIDE BRACING AND SHORING TO MAINTAIN THE STABILITY OF, AND TO AVOID OVER-LOADING THE STRUCTURE DURING DEMOLITION AND CONSTRUCTION. THE STRUCTURE IS DESIGNED FOR THE COMPLETED CONDITION ONLY. PROVIDE TEMPORARY SUPPORT TO MAINTAIN STABILITY/AVOID OVER-LOADING BEFORE COMPLETION. ENSURE BRACING IS PLACED PRIOR TO REMOVAL OF EXISTING CONCRETE SLAB ON GROUND AND LATERAL FORCE RESISTING ELEMENTS.
7. DO NOT CUT HOLES IN STRUCTURAL MEMBERS WITHOUT APPROVAL FROM THE COR.
8. PROTECT EXISTING AND NEW UTILITIES, STRUCTURAL MEMBERS, FINISHES, ETC. ASSUME FULL RESPONSIBILITY FOR DAMAGE DURING CONSTRUCTION. RESTORE DAMAGED AREAS TO THE SATISFACTION OF THE COR AT NO COST TO THE
GOVERNMENT.
EXISTING CONSTRUCTION
1. ALL INFORMATION SHOWN ON THESE DRAWINGS THAT RELATES TO THE EXISTING CONSTRUCTION HAS BEEN BASED ON THE FOLLOWING DRAWINGS AND FIELD OBSERVATIONS. THE INFORMATION IS DEEMED RELIABLE BUT ACTUAL FIELD CONDITIONS MAY VARY. NOTIFY THE COR OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK
THULE AIR FORCE BASE GREENLAND BMEWS POWER PLANT ADDITION, METCALF & EDDY ARCHITECTS - ENGINEERS, 28
OCTOBER 1966
2. EXISTING CONCRETE COMPRESSIVE STRENGTH AND REINFORCEMENT YIELD STRENGTH ASSUMED 30 MPa AND 275 MPa
RESPECTIVELY.
3. EXISTING STRUCTURAL STEEL YIELD STRENGTH ASSUMED TO BE 250 MPa.
4. DO NOT REMOVE OR CUT ANY BEAMS, COLUMNS, OR OTHER BUILDING COMPONENTS UNLESS INDICATED ON THESE
DRAWINGS OR APPROVED BY THE COR IN WRITING.
5. DO NOT DAMAGE EXISTING STRUCTURES UNLESS ELEMENT IS INDICATED ON THESE DRAWINGS TO BE REMOVED/
DEMOLISHED.
DRAWING ORGANIZATION
1. ELEVATIONS NOTED ON THE STRUCTURAL DRAWINGS ARE RELATIVE TO FIRST/GROUND FLOOR SLAB ELEVATION OF 0000.
SEE CIVIL FOR ACTUAL TOP OF FIRST/GROUND FLOOR ELEVATION (MEAN SEAL LEVEL DATUM).
2. DETAILS LABELED "TYPICAL DETAILS" OR DETAILS ON "TYPICAL DETAILS" SHEETS APPLY TO SITUATIONS THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY DETAILED. SUCH DETAILS AND DIMENSIONS APPLY WHETHER OR NOT DETAILS
ARE REFERENCED AT EACH LOCATION.
3. ALL DIMENSIONS WITHOUT A DECIMAL ARE IN MILLIMETERS (mm) AND ALL DIMENSIONS WITH A DECIMAL ARE IN METERS
(m) UON.
DELEGATED DESIGN
DESIGN MUST BE PERFORMED BY LICENSED PROFESSIONAL ENGINEER. PROVIDE DRAWINGS AND CALCULATIONS FOR
APPROVAL PRIOR TO INSTALLATION.
1. STRUCTURAL STEEL CONNECTIONS NOT SPECIFICALLY DETAILED ON DRAWINGS
2. WATER TANK AND WATER TANK FOUNDATION
3. EXTERIOR SUPPORT OF PULLBOX AND CONDUITS
4. METAL STAIR SYSTEMS, COMPONENTS AND ATTACHMENTS
5. RAILING SYSTEMS, COMPONENTS AND ATTACHMENTS
6. TEMPORARY POWER SYSTEM ENCLOSURE
7. STRUCTURAL SUPPORT FOR EXHAUST MUFFLERS/SILENCERS
STRUCTURAL TESTS AND INSPECTIONS
1. PROVIDE STRUCTURAL TESTS AND INSPECTIONS CONFORMING TO THE REQUIREMENTS OF UFC 3-301-01, IBC 2018, CHAPTER 17, AND PROJECT SPECIFICATIONS.
DESIGN LOADS
1. BUILDING RISK CATEGORY III
2e 3e
2n
3r2r3r
2n
3e
3r
3e 3e
3r 3r
3r
3e
2n
3e2e3e
3e 2e 1
2r
2e
2n
ROOF
a a a a a a a a a a a a a a
WALLS
BUILDING COMPONENTS & CLADDING WIND PRESSURE (KPA)
AREA ZONE
EFFECTIVE WIND AREA (SQ M)
ROOF
2e
2n
2r
3e
3r
WALLS
0.9 1.9 4.6 9.3
+2.5 / -7.5
+2.5 / -7.5
+2.5 / -11.0
+2.5 / -11.0
+2.5 / -11.0
+2.5 / -13.0
+4.1 / -4.4
+4.1 / -5.5
+2.3 / -7.5
+2.3 / -7.5
+2.3 / -9.5
+2.3 / -9.5
+2.3 / -9.5
+2.3 / -11.2
+3.9 / -4.3
+3.9 / -5.1
+1.9 / -4.6
+1.9 / -4.6
+1.9 / -7.5
+1.9 / -7.5
+1.9 / -7.5
+1.9 / -8.7
+3.7 / -4.0
+3.7 / -4.6
+1.7 / -2.4
+1.7 / -2.4
+1.7 / -6.1
+1.7 / -6.1
+1.7 / -6.1
+1.7 / -6.8
+3.5 / -3.8
+3.5 / -4.3
1. WIDTH OF PRESSURE COEFFICIENT ZONE MUST BE a = 3050 mm IN ACCORDANCE WITH ASCE 7-16 CHAPTER 26.
2. FOR CLADDING FASTENERS, THE EFFECTIVE WIND AREA MUST NOT BE GREATER THAN THE AREA THAT IS TRIBUTARY TO
AN INDIVIDUAL FASTENER.
3. WIND PRESSURES ARE THE GROSS WIND PRESSURE FOR COMPONENTS AND CLADDING (SUM OF THE INTERNAL AND EXTERNAL PRESSURES) APPLIED NORMAL TO THE CLADDING SURFACE. THE MAGNITUDES DO NOT INCLUDE COMPONENT
SELF WEIGHTS.
4. WIND PRESSURE MAGNITUDES ARE FACTORED/ULTIMATE (LRFD) VALUES. MULTIPLY BY 0.6 FOR WORKING/STRESS
VALUES.
5. POSITIVE VALUES INDICATE PRESSURE TOWARDS THE SURFACE AND NEGATIVE VALUES INDICATE PRESSURE AWAY
FROM THE SURFACE.
a
GROUND LEVEL
LOW ROOF
HIGH ROOF
TYP BUILDING CORNER a a a a
ROOF RIDGE
ROOF RIDGE
2. SNOW
A. GROUND SNOW LOAD: 1.2 kN/m2
B. FLAT-ROOF SNOW LOAD: 1.1 kN/m2
C. SNOW LOAD IMPORTANCE FACTOR: 1.1
D. THERMAL FACTOR: 1.2
E. SNOW DRIFT SEE DIAGRAM THIS SHEET
F. UNBALANCED & SLIDING SNOW SEE DIAGRAM THIS SHEET
3. WIND
A. ULTIMATE DESIGN WIND SPEED: 246 km/hr
B. WIND EXPOSURE: D
C. INTERNAL PRESSURE COEFFICIENT: +/- 0.18
D. MWFRS DESIGN BASE SHEAR:
a. EAST-WEST: 930 kN
b. NORTH-SOUTH: 1780 kN
4. SEISMIC
A. SEISMIC IMPORTANCE FACTOR: 1.25
B. MAPPED RESPONSE ACCELERATION PARAMETERS
a. SS: 0.39
b. S1: 0.18
C. SITE CLASS: C
D. DESIGN RESPONSE ACCELERATION PARAMETERS
a. SDS: 0.34
b. SD1: 0.18
E. SEISMIC DESIGN CATEGORY: C
F. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
DESIGN LOADS (CONTINUED)
6. SNOW LOADS
SNOW SURCHARGE
MAX (kPa) MIN (kPa) A
BUILDING SNOW DRIFT SURCHARGE LOADS
LOAD
TYPE
2.42 0 3580
1. SURCHARGE LOADS LISTED IN THE ABOVE TABLE ARE TO BE ADDED TO THE FLAT ROOF SNOW LOAD.
REFER TO DESIGN LOADS FOR ADDITIONAL SNOW LOADING CRITERIA.
2. THE MAX SNOW DRIFT LOAD INDICATED IS THE PEAK VALUE ADJACENT TO THE VERTICAL FACE.
3. IN AREAS WITH MULTIPLE SNOW SURCHARGE LOADS, USE THE LARGER SNOW LOAD.
HATCH
DRIFT A
A
MIN DRIFT SURCHARGEMAX DRIFT
SURCHARGE
DRIFT B 0
SLIDING C N/A
3.78 5580
0.77 7920
UNBALANCED D N/A0.97 3830
F L
A T
R O
O F
S N
O W
L O
A D
MAX SURCHARGE
F L
A T
R O
O F
S N
O W
L O
A D
MAX SURCHARGE
A
A
S N
O W
L O
A D
.3 x F
L A
T R
O O
F
F L
A T
R O
O F
S N
O W
L O
A D
MAX SURCHARGE
MAX SURCHARGE
UNBALANCED SNOW LOAD
SLIDING SNOW LOAD
DRIFT SNOW LOAD
DESIGN LOADS (CONTINUED)
4. SEISMIC
A. EXISTING STRUCTURE
• SEISMIC FORCE-RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
• SEISMIC RESPONSE COEFFICIENT, CS: 0.141
• RESPONSE MODIFICATION COEFFICIENT, R: 3
• DESIGN BASE SHEAR: 565kN
B. HEMP SHIELD - HIGH BAY/PRIMARY
• SEISMIC FORCE-RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
• SEISMIC RESPONSE COEFFICIENT, CS: 0.141
• RESPONSE MODIFICATION COEFFICIENT, R: 3
• DESIGN BASE SHEAR: 300kN
C. HEMP SHIELD - GENERATOR ROOM
• SEISMIC FORCE-RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
• SEISMIC RESPONSE COEFFICIENT, CS: 0.141
• RESPONSE MODIFICATION COEFFICIENT, R: 3
• DESIGN BASE SHEAR: 50kN
D. HEMP SHIELD - MECHANICAL ROOM
• SEISMIC FORCE-RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
• SEISMIC RESPONSE COEFFICIENT, CS: 0.141
• RESPONSE MODIFICATION COEFFICIENT, R: 3
• DESIGN BASE SHEAR: 60kN
E. SECOND FLOOR ADDITION
• SEISMIC FORCE-RESISTING SYSTEM: STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE
• SEISMIC RESPONSE COEFFICIENT, CS: 0.141
• RESPONSE MODIFICATION COEFFICIENT, R: 3
• DESIGN BASE SHEAR: 465kN
5. WIND COMPONENTS & CLADDING LOADS DIAGRAM
3e 3e aa
3e
3r
2n a a
2e
2r a
1 5 7 12
G
A
B
E
F
5.5 13
C.5
SNOW DRIFT PLAN
A
A
H
1 5 7 12
G
A
B
E
F
5.5 13
C.5
UNBALANCED SNOW LOAD PLAN
A
A
A
A A
H
D.6
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
34919
S-001
G E
N E
R A
L S
T R
U C
T U
R A
L N
O T
E S
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
T T
E S
F A
Y E
T T
E S
F A
Y E
A P
O Z
O L O
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
A
D D
E N
D U
M
/0
/2
1 2 3 4 5 6 7 8 9 10 11 12
G
A
B
C
D
E
F
11.510.59.58.56.5
D.9
B.1
5.54.53.52.51.1
4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E)
E
E
E
E
E
E
D.8
B.2
11.9
C.5
1.5
4880 4880 4880 4880 4370
4186 4794 4880 5650
6.41.3
B.5
C.3
C.8
D.5
A1
S-301
OF
1000250415
OF
A1
S-302
A1
S-310
S-420
A1
S-410
A1
S-401
B1
F1700 [-300]
8WF24^
BP8
P600 [-127]
F1700 [-600]
8WF24^
BP8
P600 [-127]
F1700 [-300]
8WF24^
BP8P600
[-127]
F1700 [-300]
8WF24^
BP4
P600 [-127]
F1700 [-300]
8WF24^
BP4
F1700 [-300]
8WF24^
BP4
P600 [-127]
F1700 [-300]
8WF24^
BP4
P600 [-127]
F1700 [-300]
8WF24^
BP8
P600 [-127] F1700
[-300]
8WF24^
BP8
P600 [-127]
E O
S
EOS
E O
S
O F
O F
EOS
A4
S-310
TYP
11 1
W460X128
BP2
F1500 [-300]
W460X128
BP2
F1500 [-300]
W460X128
BP2
F1500 [-300]
W360X101
BP6
W460X128
BP2
W360X101
BP3
W360X101
BP6
TYP
O
F
O F
T/CONC EL 0
T/CONC EL 0
T/CONC EL 0
D1
S-301
H W200X35.9
BP8
F1400 [-300]
W200X35.9
BP8
F1400 [-300]
W200X35.9
BP8
F1400 [-300]
D.6
W200X35.9
BP12
F3400 [-610]
W200X35.9
BP10
F2500x2000 [-450]
W200X35.9
BP9
F1400 [-700]
HSS203.2X101.6X9.5
BP11
HSS203.2X203.2X9.5
BP15
F1100x2200 [-450]
36052590
A1
S-312
D9
S-311
P600 [-127]
O
F O
F
O F
O F
A3
S-312
TYP
W360X101
BP3
W360X101
BP3
FV
[-610]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FII
[-152]
FV
[-610]
FV
[-610]
FI
[-610]
FVIII
[-300]
FI
[-610]
FI
[-610]
FI
[-610]
FV
[-610]
FV
[-610]
FVI
[-610]
FVI
[-610]
FVI
[-610]
FVI
[-610]
FV
[-610]
FV
[-610]
FIII
[-152]
FIII
[-152]
FIII
[-152]
FVIX
[-610]
FIII
[-152]
FIII
[-152]
FIII
[-152]
P600 [-150]
P1220 [-150]
P1220 [-150]
P1220 [-150]
P1220 [-150]
P1220 [-150]
15 15
BP13
BP14
BP13
BP13
BP14
16 16
16 16 16
17 TYP
G9
S-501
TYP
G9
S-501
E O
S
G9
S-501
EOS
7.6
191919
20TYP
UON
18 22
F3
S-502
14141414
23232323
CC150x150
CC150x150
CC150x150
CC150x150
CC150x150CC385x150
CC150x150
CC150x150
CC150x150
CC150x150
CC150x150
CC150x150
CC410x150
CC150x150
CC150x150
24 24
T/FTG EL [ -610 ]
T/FTG EL [ -152 ]
T/FTG EL [ -152 ]
T/FTG EL [ -600 ]
10001140
T/FTG EL [ -152 ]
T/FTG EL [ -650 ]
T/FTG EL [ -152 ]2424
E O
S
E O
S
EOS
EOS
E O
S
TYP
F3
S-502 SIM
TYP
EOS
E O
S
E O
S
T/SOG [ -65 ]
EOS
7.5
A7
S-310
TYP
CL
CL
HSS203.2X203.2X9.5
BP15
CL CL
E O
S
29 29
29 29
29 29 29
N
TRUE NORTH
WIND
PLAN NORTH
0 5,000mm 10,000mm
SCALE 1:100 (MILLIMETERS)THIS DRAWING DEPICTS HARDNESS CRITICAL ITEMS (HCI'S)
AND (OR) HARDNESS CRITICAL PROCESSES (HCP'S). ALL
CHANGES TO OR PROPOSED SUBSTITUTIONS OF HCI'S
AND (OR) HCP'S MUST BE EVALUATED FOR HARDNESS
IMPACTS AND APPROVED BY THE CONTRACTING OFFICER.
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
34934
S-101
S L
A B
A N
D F
O U
N D
A T
IO
N
P L
A N
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
T T
E S
F A
Y E
T T
E S
F A
Y E
A P
O Z
O L O
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
22 EXISTING W12 COLUMN.
23 REFER TO DETAIL E6/S-510 FOR BASE PLATE ANCHORAGE.
24 STEPPED FOOTING, REFER TO TYPICAL DETAILS.
25 230 DEEP TRENCH, REFER TO TYPICAL DETAILS. COORDINATE LOCATION WITH
PLUMBING DRAWINGS.
26 SLAB DEPRESSION FOR WALKOFF MAT, COORDINATE LOCATION WITH ARCH
DRAWINGS.
27 300mm THK CONCRETE FOUNDATION CENTERED ON TANK. 5015kg MAX WEIGHT OF SINGLE TANK. MINIMUM 2500mm X 4000mm FOUNDATION. SUBMIT SHOP
DRAWINGS OF STACKED TANK FOR VERIFICATION OF FOUNDATION PRIOR TO
PLACEMENT OF CONCRETE. COORDINATE WITH MECHANICAL DRAWINGS.
28 FLOOR DRAIN THROUGH HEMP FLOOR PLATE. REFER TO A1/S-531 AND
COORDINATE SIZE AND LOCATION WITH PLUMBING.
29 FLOOR DRAIN, REFER TO D3/S-502 AND COORDINATE SIZE AND LOCATION WITH
PLUMBING.
12 THICKENED SLAB AT BASE OF STAIR, REFER TO TYPICAL DETAIL.
13 760mm THK CONCRETE MAT FOUNDATION W/ T/FDN EL = [-610] UON. CAST
AROUND EXISTING FOOTINGS AND REINFORCE WITH #22 @ 250 OC T&B EW.
REFER TO TYPICAL DETAIL FOR CONNECTION TO EXISTING FOOTINGS.
14 405mm THK CONCRETE MAT FOUNDATION W/ T/FDN EL = [-152] UON. CAST
BETWEEN EXISTING FOOTINGS AND REINFORCE WITH #16 @ 250 OC T&B EW.
REFER TO TYPICAL DETAIL FOR CONNECTION TO EXISTING FOOTINGS.
15 CONCRETE PEDESTAL BENEATH EXISTING COLUMN, REFER TO DETAILS ON
S-510.
16 455mm THK CONCRETE MAT FOUNDATION W/ T/FDN EL = [-152] UON. CAST
BETWEEN EXISTING FOOTINGS AND REINFORCE WITH #16 @ 250 OC T&B EW.
REFER TO TYPICAL DETAIL FOR CONNECTION TO EXISTING FOOTINGS.
17 CHANNEL AT DOOR OPENING, SEE ELEVATIONS.
18 EXISTING W8 COLUMN.
19 EXISTING W10 COLUMN.
20 EXISTING W21 COLUMN.
21 EXISTING W16 COLUMN.
1 CONCRETE GENERATOR FOUNDATION. REFER TO SECTIONS FOR MORE INFO.
2 HEMP SHIELD, 6mm THK CONT STEEL PLATE.
3 PROVIDE TYPE A COLUMN REINFORCEMENT - REFER TO TYPICAL DETAILS.
4 EXISTING TUNNEL TO PASSAGEWAY.
5 ALIGN EDGE OF SLAB WITH EXISTING EDGE OF SLAB.
6 CONCRETE SLAB-ON-GROUND ATOP 12mm THK STEEL PLATE AND MUD MAT.
REFER TO TYPICAL DETAIL "SLAB-ON-GROUND W/ HEMP SHIELD". SUBMIT SHOP
DRAWINGS FOR LAYOUT OF HEMP SHIELD PLATE/JOINT AND SELDS TESTING
PVC CONDUITS. COORDINATE WITH SHIELDED FLOOR SELDS TESTING DETAIL
ON ELEC DWGS.
7 TYPICAL CONCRETE SLAB-ON-GROUND, REFER TO TYPICAL DETAIL
"SLAB-ON-GROUND".
8 HEMP VESTIBULE, REF ENLARGED PLAN ON S-404.
9 150 THK CONCRETE EQUIPMENT PAD, REFER TO TYPICAL DETAILS FOR
REINFORCEMENT. COORDINATE LOCATION AND DIMENSIONS WITH EQUIPMENT.
10 SEWAGE EJECTOR PIT.
11 EXISTING FOOTING, VIF ELEVATION AND SIZE.
1 : 100B1
SLAB AND FOUNDATION PLAN
SHEET NOTES
1. DIMENSIONS AND ELEVATIONS DEPICTING EXISTING CONDITIONS ARE
APPROXIMATE. FIELD VERIFY AND NOTIFY COR IMMEDIATELY IF CONDITIONS DIFFER
FROM THOSE DEPICTED IN DESIGN DOCUMENTS.
2. 40kN MAXIMUM ALLOWABLE FORKLIFT WHEEL REACTION ON SOG. MAXIMUM REACTION BASED ON 10300mm2 CONTACT AREA.
KEYED NOTES
A
D D
E N
D U
M
/0
/2
1 2 3 4 5 6 7
A
B
6.5
B.1
5.54.53.52.51.1
B.2
1.5
S-411
A1
S-411
D1
S-412
A1
2051 4880 4880 4880 4880 4880
E
301 2500 2500 2500 2500 2500 2500 2500 2500 2500 1340 1860 760 1740
4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E)
SIM SIM
S-412
A5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S X
.6
X .5
H S
S .4
X .6
X .5
H S
S .4
X .6
X .5
H S
S .4
X .6
X .5
H S
S .4
X .6
X .5
H S
S .4
X .6
X .5
HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5
HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5 HSS127X76.2X9.5HSS127X76.2X9.5
HSS127X76.2X9.5
TYP
EQ
TYP
EQ
H S
S .4
X .6
X .5
HSS127X76.2X9.5
HSS76.2X76.2X9.5
HSS127X101.6X9.5 HSS127X101.6X9.5
B/PL EL 4000
B/PL EL 4000
HSS127X76.2X9.5
HSS76.2X76.2X9.5
HSS127X76.2X9.5
H S
S X
.6
X .5
HSS127X101.6X9.5
HSS127X101.6X9.5
HSS127X101.6X9.5
790 840 870
H S
S X
.6
X .5
H S
S X
.6
X .5
X-112
E1
X-112
E6
X-112
F1
X-112
F6
HSS127X76.2X9.5
HSS76.2X76.2X9.5
HSS76.2X76.2X9.5
H S
S .2
X .2
X .5
A1
S-313
A1
S-313
A1
S-313
A1
S-313
A1
S-313
A1
S-313
HSS76.2X76.2X9.5 HSS76.2X76.2X9.5 HSS76.2X76.2X9.5
HSS76.2X76.2X9.5
B/PLATE EL 4230
1 2 3 4 5 6 7
A
B
6.5
B.1
5.54.53.52.51.1
B.2
1.51.3
S-411
A1
S-411
D1
S-412
A1
2051 4880 4880 4880 4880 4880
4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E) 4877 (E)
D1
S-311
S-412
A5
D1
S-311
D6
S-311 D3
S-311
700 2500 2500 2500 2500 2500 2500 2500 2500 2500 3200 760 1740
HSS101.6X76.2X9.5
TYP UON 2
TYP
X-111
B1
X-112
E1
X-112
E6
X-112
F1
X-112
F6
FIII
[-152]
FIII
[-152]
FIII
[-152]
FIII
[-152]
FIII
[-152]
FIII
[-152]
CL
CL
CL
CL
6 7 7 7 7 7 7
8 8 8 8 8 8
TYP
T/CONC EL 0
EOS
A1
S-311
SIM
THIS DRAWING DEPICTS HARDNESS CRITICAL ITEMS (HCI'S)
AND (OR) HARDNESS CRITICAL PROCESSES (HCP'S). ALL
CHANGES TO OR PROPOSED SUBSTITUTIONS OF HCI'S
AND (OR) HCP'S MUST BE EVALUATED FOR HARDNESS
IMPACTS AND APPROVED BY THE CONTRACTING OFFICER.
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
34964
S-410
E N
L A
R G
E D
P L
A N
S
M E
C H
A N
IC
A
L H
E M
P
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
T T
E S
F A
Y E
T T
E S
F A
Y E
A P
O Z
O L O
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1 : 50D1
ENLARGED FRAMING PLAN - MECHANICAL HEMP
1 : 50A1
ENLARGED GROUND FLOOR PLAN - MECHANICAL HEMP
SHEET NOTES
1 HEMP PLATE, 12mm THK CONT STEEL PLATE. REFER
TO HEMP TYPICAL DETAILS.
2 HEMP POST, REFER TO DETAIL ON SHEET S-531 FOR
CONNECTION TO FLOOR.
3 HEMP FLOOR, 12mm THK CONT STEEL PLATE
BEARING ON SLAB-ON-GROUND. REFER TO HEMP
TYPICAL DETAILS. SUBMIT SHOP DRAWINGS FOR
LAYOUT OF HEMP SHIELD PLATE/JOINT AND SELDS
TESTING PVC CONDUITS. COORDINATE WITH
SHIELDED FLOOR SELDS TESTING DETAIL ON ELEC
DWGS.
4 HEMP SHIELD, 6mm THK CONT STEEL PLATE.
5 EXISTING W16 COLUMN.
6 CONCRETE PEDESTAL BENEATH EXISTING COLUMN,
REFER TO DETAILS ON S-510.
7 EXISTING W21 COLUMN.
8 EXISTING W12 COLUMN.
9 ISOLATION JOINT, REFER TO TYPICAL DETAILS.
10 FLOOR DRAIN THROUGH HEMP FLOOR PLATE. REFER
TO A1/S-531 AND COORDINATE SIZE AND LOCATION
WITH PLUMBING.
KEYED NOTES
1. DIMENSIONS AND ELEVATIONS DEPICTING EXISTING CONDITIONS
ARE APPROXIMATE. FIELD VERIFY AND NOTIFY COR IMMEDIATELY
IF UNUSUAL CONDITIONS ARE ENCOUNTERED.
A
D D
E N
D U
M
/0
/2
9 10 11
B
11.5
10.59.58.5
B.1
B.2
S-421
A1
S-421
C1
S-421
A7
4877 (E) 4877 (E)
4794 4880
F1
S-311
F6
S-311
2364 2450 2450 2450 2450 2354
F1
S-311
F1
S-311
14518
F6
S-311
F6
S-311
E
S-421
C7
1 TYP
F1500 [-300]
W460X128
BP2
F1500 [-300]
W460X128
BP2
F1500 [-300]
W460X128
BP2
W460X128
BP2
T/CONC EL [ -150 ]
T/CONC EL 0
CC320x150
C C x
CC320x150 C
C x
S-420
A6
TYP
HSS127X127X9.5
TYP UON
HSS127X76.2X9.5
F1
S-311
S-421
E1
X-113
B8
X-113
B1
X-113
B5
X-113
D1
55 F3
S-311
6 6
CC320x150
IF
IF1
IF1
IF
9 10 11
A
B
11.5 10.59.58.5
B.1
B.2
S-421
A1
S-421
C1
S-421
A7
4877 (E) 4877 (E)
4794 4880 5650
2364 2450 2450 2450 2450 2365
16007
E
F6
S-312 D6
S-312
A6
S-312
A6
S-312
F6
S-312
F6
S-312
S-421
C7
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
HSS127X127X6.4
HSS127X127X6.4HSS127X127X6.4HSS127X127X6.4HSS127X127X6.4HSS127X127X6.4 HSS127X127X6.4
HSS127X127X6.4 HSS127X127X6.4HSS127X127X6.4 HSS127X127X6.4 HSS127X127X6.4
S-420
D6
HSS127X127X6.4
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
HSS127X127X6.4
HSS127X127X6.4
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
H S
S X
X
.5
A6
S-312
A8
S-312 S-421
E1
H S
S X
X
.5
H S
S X
X
.5
TYP
TYP
TYPB/PLATE EL 2626
D50+135
B/DECK EL 2390
TYP
EQ
TYP
EQ
B
B.1
D6
S-311
F6
S-311
HSS76.2X76.2X6.4
HSS76.2X76.2X6.4 HSS76.2X76.2X6.4
HSS76.2X76.2X6.4
T/CONC EL 0
F9
S-311
D6
S-311
SIM
SIM
B
B.1
F6
S-312
HSS76.2X76.2X9.5
H S
S .2
X .2
X .5
HSS76.2X76.2X9.5
H S
S .2
X .2
X .5
G1
S-312
B/PLATE EL 2200
9 10 TYP
THIS DRAWING DEPICTS HARDNESS CRITICAL ITEMS (HCI'S)
AND (OR) HARDNESS CRITICAL PROCESSES (HCP'S). ALL
CHANGES TO OR PROPOSED SUBSTITUTIONS OF HCI'S
AND (OR) HCP'S MUST BE EVALUATED FOR HARDNESS
IMPACTS AND APPROVED BY THE CONTRACTING OFFICER.
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
34967
S-420
E N
L A
R G
E D
P L
A N
S
G E
N E
R A
T O
R R
O O
M H
E M
P
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
T T
E S
F A
Y E
T T
E S
F A
Y E
A P
O Z
O L O
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1 : 50A1
ENLARGED GROUND FLOOR PLAN - GENERATOR ROOM
HEMP
1 : 50D1
ENLARGED FRAMING PLAN - GENERATOR ROOM HEMP
SHEET NOTES
1 SLAB REENTRANT CORNER REINFORCEMENT, REFER
TO TYPICAL DETAIL.
2 EXISTING W12 COLUMN.
3 HEMP SHIELD, 6mm THK CONT STEEL PLATE.
4 HEMP SHIELD MOVEMENT JOINT, REFER TO TYPICAL
DETAIL.
5 CONCRETE SLAB ATOP 12mm THK STEEL PLATE AND
CONCRETE SLAB-ON-GROUND. REFER TO TYPICAL
DETAIL "SLAB-ON-GROUND @ GENERATOR HEMP
SHIELD". SUBMIT SHOP DRAWINGS FOR LAYOUT OF
HEMP SHIELD PLATE/JOINT AND SELDS TESTING PVC
CONDUITS. COORDINATE WITH SHIELDED FLOOR
SELDS TESTING DETAIL ON ELEC DWGS.
6 EXISTING W21 COLUMN.
7 PLATE PENETRATION, COORD LOCATIONS WITH MEP
DWGS. REFER TO HEMP PENETRATION PLAN.
8 12mm THK HEMP STEEL PLATE ABOVE CONCRETE ON
METAL DECK. REFER TO SECTIONS.
9 HEMP PLATE, 12mm THK CONT STEEL PLATE. REFER
TO HEMP TYPICAL DETAILS.
10 HEMP WALL, 6mm THK CONT STEEL PLATE. REFER TO
HEMP TYPICAL DETAILS.
KEYED NOTES
1. DIMENSIONS AND ELEVATIONS DEPICTING EXISTING CONDITIONS ARE
APPROXIMATE. FIELD VERIFY AND NOTIFY COR IMMEDIATELY IF UNUSUAL
CONDITIONS ARE ENCOUNTERED.
1 : 25A6
HEMP CHASE - FLOOR PLAN
1 : 25D6
HEMP CHASE - FRAMING PLAN
A
D D
E N
D U
M
/0
/2
CONCRETE SPREAD FOOTING SCHEDULE
MARK
SIZE
LENGTH WIDTH DEPTH LONG1 SHORT
1400F1400 1400 500 5#19 -
NOTES:
1. FOR SQUARE FOOTINGS, PLACE LONG REINFORCEMENT EACH WAY.
2. UNLESS NOTED OTHERWISE, PLACE REINFORCEMENT AT THE BOTTOM OF THE FOOTING.
REINFORCEMENT
LONG1 SHORT
5#19 - -
REMARKSTOP BOTTOM
1500F1500 1500 500 5#19 - 5#19 - -
2800F2800x1800 1800 600 7#19 11#19 7#19 11#19 -
3700F3700 3700 750 18#19 - 18#19 - -
3400F3400x2000 2000 750 10#19 17#19 10#19 17#19 -
4600F4600x2000 2000 750 10#19 22#19 10#19 22#19 -
4300F4300x2000 2000 750 10#19 21#19 10#19 21#19 -
5200F5200x2000 2000 750 10#19 25#19 10#19 25#19 -
4800F4800x2000 2000 750 10#19 23#19 10#19 23#19 -
1700F1700 1700 600 5#19 - 5#19 - -
3400F3400 3400 750 17#19 - 17#19 - -
2500F2500x2000 2000 750 10#19 12#19 10#19 12#19 -
4600F4600x1800 1800 750 9#19 22#19 9#19 22#19 -
2200F1100x2200 1100 500 4#19 8#19 4#19 8#19 -
COL
"D E
P T
H
S E
E S
C H
E D
75 CLR, TYP
SCHEDULED FTG
SCHEDULED
BOT FTG REINF7
C
L R
T/FTG EL
SEE PLAN
NOTES:
1. SEE SCHEDULE FOR FOOTING SIZE AND REINFORCING
2. ALL FOOTINGS MUST BE CENTERED ON COLUMNS, UON
SCHEDULED
PEDESTAL,
SEE
PEDESTAL
REINFORCEMENT
SCHEDULED
TOP FTG REINF
STD HOOK, TYP
/C5 S-501
C
L R
P E
D E
S T
A L S
C H
E D
U L E
T
IE
S S
P A
C E
D P
E R
SCHEDULED
PEDESTAL
SCHEDULED
PEDESTAL
REINFORCEMENT
BLOCK-OUT FOR
SHEAR LUG
WHERE REQUIRED
SCHEDULED TIES
PLAN SECTION
BRACE
W/2 W/2
W /2
W /2
P E
D E
S T
A L
W
ID
T H
W
W/2
W /2
W /2
P E
D E
S T
A L
W
ID
T H
W
NOTES:
1. CENTER SQUARE PEDESTALS ON COLUMN GRID INTERSECTION.
2. LONGSIDE OF RECTANGULAR PEDESTAL GOES IN DIRECTION OF BRACE.
COLCOL
COL COL
SCHEDULED
BASE PLATE
SCHEDULED
BASE PLATE
CONCRETE PEDESTAL SCHEDULE
MARK REMARKSSIZE (mm) VERTICAL
REINF
TIES
600x600P600 8#25 #10@400 OC ADDITIONAL TIES AT TOP OF PEDESTAL, REF
1200x1200P1200 24#29 #13@300 OC ADDITIONAL TIES AT TOP OF PEDESTAL, REF
/A7 S-501
/A7 S-501
T
CONTRACTION JOINT @
4200 MAX SPACING T
/4
EQUIPMENT
ISOLATION PAD AS REQUIRED BY
MFR'S INSTALLATION INSTRUCTIONS
12 DIA ANCHOR BOLT W/ MIN 90
EMBED, OR AS REQUIRED BY MFR'S
INSTALLATION INSTRUCTIONS
150 THK SLAB
#10M @ 450 OC EW
HEMP SHIELD FLOOR PLATE
75 THK MUD MAT
100 THK DRAINAGE COURSE
VAPOR RETARDERSELDS TESTING PVC
CONDUIT LOCATE AT
FLOOR PLATE WELD SEAMS
FLOOR PLATE JOINT
SEE DETAIL ON S-530
SEE PLAN
EOS
T/SLAB EL
SEE PLAN
COL
(2) #16 CONT BARS
TYP SLAB REINF, SEE TYP DETAIL
CONC CURB, SEE PLAN
AND SCHEDULE
IMP ANGLE BY IMP
MANUFACTURER,
REF TO ARCH
150 THK SLAB
#10M @ 450 OC EW
100 THK DRAINAGE
COURSE
VAPOR RETARDER
CONCRETE WALL SEE
PLAN
SLAB ISOLATION JOINT SEE
TYP DETAIL
(3) #10M TOP BARS @ 50 OC
C
LR
25 SLAB
TYP
#10M @ 450
(5) #10M CONT
T H
K
S L A
B
SLAB REINF
SEE PLAN
STAIR SYSTEM AND CONNECTION
BY CONTRACTOR'S DESIGNATED
SPECIALTY ENGINEER
SLAB REINF
SEE PLAN
150 THK SLAB ABOVE AND
BELOW HEMP SHIELD
#10M @ 450 OC EW
HEMP SHIELD FLOOR PLATE
100 THK DRAINAGE COURSE
VAPOR RETARDERSELDS TESTING PVC
CONDUIT LOCATE AT
FLOOR PLATE WELD SEAMS
FLOOR PLATE JOINT
SEE DETAIL ON S-530
SEE PLAN
EOS
T/SLAB EL
SEE PLAN
COL TYP SLAB REINF, SEE
TYP DETAIL
COORD RECESS WITH
ARCH AND DOOR
MANUFACTURER
T
1 1/2" DEEP SAWCUT JOINT
FILLED WITH TRAFFIC
GRADE SEALANT
CUT REINF EACH
SIDE OF JOINT
50 50
ROUGHEN SURFACE
TO 1/4" AMPLITUDE
(3) #10M TOP BARS @ 50 OC
EDGE OF SLAB
CONCRETE
WALL
ISOLATION
JOINT
C
LR
P L A
N
S E
E
C
L R
SEE NOTE
20 CHAMFER,
TYP
ANCHOR PER REQUIREMENTS OF
EQUIPMENT, REFER TO EQUIP
SHOP DRAWINGS FOR TYPE, SIZE,
PROJECTION AND LOCATION. MIN
90 EMBEDMENT INTO SLAB.
EQUIPMENT PAD W/ #13
@ 300 OC EW
ROUGHEN TO 6
AMPLITUDE & APPLY
BONDING AGENT
NOTES:
COORDINATE PAD LOCATION AND SIZE WITH MECH, PLUMBING AND ELEC
DRAWINGS AND EQUIP MFR'S RECOMMENDATIONS.
SOG, SEE PLAN AND DETAILS
150 MIN
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
34969
S-501
D E
T A
IL
S
F
O U
N D
A T
IO
N
S A
N D
S L
A B
S
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
T T
E S
F A
Y E
T T
E S
F A
Y E
A P
O Z
O L O
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
NTSA1
CONCRETE SPREAD FOOTING SCHEDULE
NTSA5
SPREAD FOOTING
W/ PEDESTAL
NTSA7
CONCRETE PEDESTAL
REINFORCEMENT
NTSC8
CONCRETE PEDESTAL PLAN
NTSC5
CONCRETE PEDESTAL SCHEDULE
NTSG3
SLAB-ON-GROUND
CONTRACTION JOINT
NTSE7
TYPICAL EQUIPMENT
ANCHORAGE
NTSG1
SLAB-ON-GROUND
W/ HEMP SHIELD
NTSG9
TYP EDGE OF SLAB
NTSG5
SLAB-ON-GROUND
NTSE1
SLAB REENTRANT
CORNER BARS
NTSC1
THICKENED SLAB
AT STAIR
NTSG7
SLAB-ON-GROUND W/
GENERATOR HEMP SHIELD
NTSE9
SLAB RECESS AT
EXTERIOR PERIMETER
DOOR
NTSE3
SLAB-ON-GROUND
CONSTRUCTION JOINT
NTSC3
SLAB-ON-GROUND
REINFORCING AT DOOR
NTSE5
INTERIOR EQUIPMENT PAD
A
D D
E N
D U
M
/0
/2
FIRST FLOOR
PROVIDE WAVEGUIDE
ARRAY AT DUCT
PENETRATION THRU
HEMP SHIELD (REFER
TO E-8/X-141)
G ABCDE
G-2
AHU-2
PROVIDE WAVEGUIDE
ARRAY AT DUCT
PENETRATION THRU HEMP
SHIELD
DT-2
PROVIDE WAVEGUIDE ARRAY AT
EXHAUST PIPE PENETRATION THRU
HEMP SHIELD (REFER TO A-4/X-141)
R-2
PROVIDE WAVEGUIDE ARRAY AT AFTERCOOLER PIPE
PENETRATION THRU HEMP SHIELD (REFER TO E-1/X-142)
AREA CLEAR FOR
HOIST BEAM
3 3 m m
G E
A
600mm - GEA
EF-2
GENERATOR INLET AIR
FILTER HOUSE (1 OF 2
PER GENERATOR)
500mm - GIA
F
50mm CA
80mm HWR
80mm HWS
50mm HWR 50mm HWS
600mm x 2150mm RA
1000mm x 1700mm RA
1200mm x 1800mm OA
1000mm x 1600mm RA
1000mm x 1600mm EA
1500mm x 1800mm SA
550mm x 3500mm SA
FLEXIBLE CONNECTION
IH-2
EH-2
400mm x 350mm SA TO
OIL STORAGE RM 107
GENERATOR COOLING WATER
EXPANSION TANK (G-2)
200mm FOV
80mm FOV
BALANCING DAMPER
m m x m m R
A
250mm x 300mm SA
GENERATOR
AREA
OPEN AREA
GENERATOR
MECH RM
RADIATOR
ROOM
INTR AREA
RADIATOR ROOM
SERVICE
CLEARANCE
SERVICE
CLEARANCE
20mm ACR
LUBE OIL AND GLYCOL FILL AND WASTE LINES TO
BE CONNECTED TO GENERATOR WITH
REMOVABLE HOSES ONLY DURING MAINTENANCE
ACTIVITY (TYP OF G-1 THRU G-4).
m m G
S m m G
R m m L
O R m m L
O S
80mm FOV 80mm FOV
80mm FOO
80mm FOS
20mm FOS/R
TO UH-16
200mm FOV
32mm FOS
32mm FOR
32mm FOS
50mm FOO
NOTE: PIPING AND INTAKE/EXHAUST
CONNECTIONS TYPICAL OF G-1 THRU G-4.
1500mm x 1800mm SA
25mm DRAIN (TERMINATE IN
RADIATOR ROOM 112)
TOP OF GENERATOR EXHAUST @
12325mm A.F.F.
1000mm x 1600mm RA
FLEXIBLE CONNECTION
150mm FLEXIBLE CONNECTION
PROVIDE HIGH-WIND GENERATOR EXHAUST
CAP (TYP OF EACH GENERATOR)
PROVIDE FLEXIBLE CONNECTION
FOR GENERATOR INTAK AND
EXHAUST (TYP)
PROVIDE MINIMUM 900mm
CLEARANCE FROM ROOF TO
BOTTOM OF HOOD OPENING (TYP
OF EXHAUST AND INTAKE
HOODS))
PROVIDE MINIMUM
950mm FROM ROOF
TO TOP OF RADIATOR
LOUVER OPENING
MUFFLER7
0 2,500MM 5,000MM
SCALE 1:50 (MILLIMETERS)
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349213
M-301
G E
N E
R A
T O
R A
N D
S U
P P
O R
T
IN
G E
Q U
IP
M
E N
T T
Y P
IC
A
L B
U
IL
D
IN
G S
E C
T
IO
N
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
S A
L M
O N
D
L T
A T
E
J L E
M E
N S
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1:50B1
GENERATOR AND SUPPORTING EQUIPMENT TYPICAL
BUILDING SECTION
DRAWING NOTES:GENERAL NOTES:
1. REFER TO M-001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
1. OUTDOOR INLET AIR LOUVERS FOR REMOTE RADIATOR COOLING AIR.
2. REMOTE RADIATOR EXHAUST AIR LOUVER THROUGH ROOF.
3. REMOTE RADIATOR CLEARANCE REQUIREMENT FOR FAN AND MOTOR
REMOVAL.
4. REMOTE RADIATOR HOT AIR EXHAUST PATH.
5. REMOTE RADIATOR COLD OUTDOOR AIR SUPPLY PATH.
6. MUFFLER SUPPORT STRUCTURE BY DELIGATED DESIGN. CONTRACTOR TO
DESIGN AND INCLUDE SHOP DRAWINGS WITH CALCULATIONS OF MUFFLER
STAND DESIGN.
7. CONTRACTOR TO SUPPLY A MUFFLER/SILENCER THAT WILL REDUCE
SOUND EMISSIONS FROM THE GENERATOR EXHAUST BY 40 TO 60
DB. MUFFLER SUPPLIED MUST BE SIZED TO COMPLY WITH THE BACK
PRESSURE LIMIT RANGE OF THE GENERATOR MANUFACTURER. INCLUDE
BACK PRESSURE CALCULATIONS IN MUFFLER SUBMITTAL WHICH WILL
INCLUDE THE WAVE GUIDE THROUGH THE HEMP SHIELD, MUFFLER AND
ALL PIPE/FITTINGS TO SHOW THE COMPLIANCE WITH THE GENERATOR
MANUFACTURER REQUIREMENTS.
D
D E
N D
U M
/5
/2
F B
F
B
F B
F
B
F B
F
B
FB1 FB1
F B
F
B
F B
F
B
F B
F B
F
B
F B
FB3 FB3FB3 FB3 FB3 FB3 FB3 FB3 FB3 FB3 FB3 FB3
F B
F
B
F B
FB3FB3 FB3FB3FB3FB3FB3FB3FB3FB3FB3FB3
F B
F
B
F B
F
B
F B
F
B
F B
F
B
F B
F
B
FB3 FB3FB3 FB3
FB1
7 8 9 10 11 12
A
B
C
D
UH-21
UH-26
UH-31
EF-10
DT-1
DT-2
DT-3
DT-4
G-1 G-2 G-3 G-4
HX-1 HX-2 HX-3 HX-4
UH-16
LOT-1
LOT-2
GT-1
GT-2
GP-2
LOP-2
LOP-1
GP-1
80 mm LOS
80 mm LOR
80 mm LOF
80 mm LOS
80 mm LOR
80 mm GR 80 mm GS
AT-1B AT-2B AT-3B AT-4B
80 mm GF
80 mm LOF
80 mm GR
80 mm GS
200 mm ACS
200 mm ACR
200 mm - FOV (TYP. 4)
200 mm - FOV (TYP. 4)
80 mm - FOV (TYP. 4)
GENERATOR
AREA
OIL STORAGE RM
GENERATOR
MECH RM
111RADIATOR
ROOM
EXIT
STAIR #2
INTR AREA
INTR AREA
INTR AREA
25 mm - HWR (25 mm - HWS BELOW)
20 mm - HWS/R
(TYP. 4)
(TYP 4)
(TYP. 4)
AT-1A AT-2A
G-4
AT-3A AT-4A
(TYP 8)
20mm HWS & HWR
UP AND DN
400mm x 350mm SA-UP (TO OIL STORAGE 107) 250mm x 300mm SA-DN
80mm NORMAL VENT (DT-4)
200mm PRIMARY TANK EMERGENCY VENT(DT-2)
200mm SECONDARY TANK EMERGENCY VENT (DT-2)
250mm x 300mm SA-DN (TO
GEN. MECH ROOM 111)
40 mm FOS
40 mm FOR
40 mm FOS
40 mm FOR
40 mm FOS
40 mm FOR
40 mm FOS
40 mm FOR
450mm x 350mm SA
40mm FOS
40mm FOR
40mm FOS 50mm FOO
20mm HWR 20mm HWS
40mm FOR 40mm FOS
40mm FOS 50mm FOO
50mm FOO 40mm FOS
40mm FOR 40mm FOS
50mm FOO 40mm FOS
40mm FOR 40mm FOS
300mm x 250mm EA
20 mm HWS 20 mm HWR
400mm x 350mm SA
(ABOVE ACS/R PIPING)
200 mm ACS200 mm ACS
200 mm ACR
200 mm ACR
80 mm GR 80 mm GS
200mm PRIMARY TANK EMERGENCY VENT(DT-1)
200mm PRIMARY TANK EMERGENCY VENT(DT-4)
200mm SECONDARY TANK EMERGENCY VENT (DT-4)
80mm NORMAL VENT (DT-2)
200mm SECONDARY TANK EMERGENCY VENT (DT-3)
200mm PRIMARY TANK EMERGENCY VENT(DT-3)
80mm NORMAL VENT (DT-3)
200mm SECONDARY TANK EMERGENCY VENT (DT-1)
80mm NORMAL VENT (DT-1)
20 mm HWS 20 mm HWR
80 mm HWS
80 mm HWR
DECOUPLER (TYP)
250mm x 300mm SA
UH-37
UH-13
FD
(BELOW GT-2)
(BELOW LOT-2)
80 mm LOF
80 mm LOR
80 mm GR 80 mm GS
EF-12
CONNECT 300mm x 300mm
EA TO EH-12 (REFER TO
A-605 & A7/M-501 FOR
MORE INFORMATION)
300mm X 300mm EA
UH-38
25mm HWS
25mm HWR
25mm HWS
25mm HWR
CONTROL
PANEL
250mm x 300mm SA FROM AHU-7
FD
NOTE: NOTE: GLYCOL AND
LUBE OIL TANKS SUPPORT
STRUCTURE BY TANK
MANUFACTURER.
CONTRACTOR TO DESIGN
AND INCLUDE SHOP
DRAWINGS WITH
CALCULATIONS OF TANK
STAND DESIGN.
50mm CA 50mm CA
(BELOW)
50mm CA
50mm CA 50mm CA
(BELOW)
50mm CA
50mm CA 50mm CA
(BELOW)
50mm CA
50mm CA 50mm CA
(BELOW)
50mm CA
T
T
T
200 mm ACR
200 mm ACS
CONNECT 300mm x 250mm EA TO EH-10 (REFER TO
A-605 FOR MORE INFORMATION) (BELOW DT VENTS)
T
T
7 7 7
400mm x 350mm SA-UP
TO OIL STORAGE RM
EH-12
EH-10
200 mm ACS-UP TO R-1 200 mm ACR-UP TO R-1
200 mm ACS-UP TO R-2
200 mm ACR-UP TO R-2
200 mm ACS-UP TO R-3
200 mm ACR-UP TO R-3
200 mm ACS-UP TO R-4
200 mm ACR-UP TO R-4
EMCS CONTROL
PANEL
T
PROVIDE ATMOSPHERIC FUEL OIL VENT ABOVE ROOF
LINE AND INSULATED DRAIN AT BOTTOM OF VENT PIPE
(TYP OF ALL FUEL VENTS)(REFER TO C6/M-504)
KEY PLAN
N
TRUE NORTH
WIND
PLAN NORTH
0 2,500MM 5,000MM
SCALE 1:50 (MILLIMETERS)
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349218
M-404
M E
C H
A N
IC
A
L
G E
N E
R A
T O
R B
A Y
A N
D D
A Y
T A
N K
R O
O M
E N
L A
R G
E D
P L
A N
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
S A
L M
O N
D
L T
A T
E
J L E
M E
N S
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1 : 50B1
MECHANICAL - GENERATOR BAY AND
DAY TANK ROOM ENLARGED PLAN
DRAWING NOTES:GENERAL NOTES:
1. REFER TO M-001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL ROOM FINAL THERMOSTAT AND SENSOR LOCATION TO BE FINALIZED
WITH THE FIELD CONTRACTING OFFICER REPRESENTATIVE "COR" AND
DESIGNER OF RECORD "DOR".
1. WAVEGUIDE ARRAY AT EXHAUST PENETRATION THROUGH HEMP
SHIELD. (REFER TO E-8/X-141).
2. WAVEGUIDE ARRAY AT FUEL TANK VENT LINE PENETRATION THOUGH
HEMP SHIELD CEILING. (REFER TO E-7/X-142).
3. GENERATOR MECH ROOM 111 PROVIDED WITH SPILL CONTAINMENT
CURB BY LOWERING FLOOR. SEE STRUCTURAL DRAWINGS.
4. GENERATOR CLEARANCE REQUIREMENT.
5. FUEL TANK CLEARANCE REQUIREMENT.
6. GENERATOR COOLING WAVEGUIDE BELOW CUTOFF THROUGH HEMP
SHIELD. (REFER TO E-1/X-142).
7. LUBE OIL AND GLYCOL FILL AND WASTE LINES TO BE CONNECTED TO
GENERATOR WITH REMOVABLE HOSES ONLY DURING MAINTENANCE
ACTIVITY.
8. LUBE OIL AND GLYCOL PIPING WAVEGUIDE THROUGH HEMP SHIELD.
(REFER TO E-4/X-141).
9. ARCTIC RATED HOOD (160 KMH WIND SPEED RESISTANT).
D E
N D
U M
/5
/2
8 9 10 11 12
B
C
R-1 R-2 R-3 R-4
200 mm - ACR
150mm ACR
(TYP 4)
(TYP 4)
200 mm - ACS
(TYP 4)
(TYP 4)
(TYP 4)
(TYP 4)
GENERATOR
COOLING WATER
EXPANSION TANK
(TYP. 4)
420mm ACR-DN TO 200mm ACR (TYP 4)
800mm GEA
(TYP 4)
600mm GEA
600mm GEA
600mm GEA
600mm GEA
600mm GEA
600mm GEA
600mm GEA
600mm GEA
150mm ACS
(TYP 4)
150mm ACS
400mm x 350mm SA
450mm x 450mm SA
TO OIL STORAGE
ROOM 107
800mm GEA 800mm GEA 800mm GEA 800mm GEA
FD
400mm x 350mm SA
400mm x 350mm SA-DN (BELOW 800mm GEA)
RADIATOR ROOM
OIL STORAGE
450mm x 450mm SA
MUFFLER
(TYP) 1
1 1 1 1
5 5 5 5 5 5 5 5
KEY PLAN
N
TRUE NORTH
WIND
PLAN NORTH
0 2,500MM 5,000MM
SCALE 1:50 (MILLIMETERS)
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349220
M-406
M E
C H
A N
IC
A
L
G E
N E
R A
T O
R E
X H
A U
S T
A N
D R
A D
IA
T
O R
R O
O M
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
S A
L M
O N
D
L T
A T
E
J L E
M E
N S
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1 : 50B1
MECHANICAL - GENERATOR EXHAUST
AND RADIATOR ROOM
DRAWING NOTES:GENERAL NOTES:
1. REFER TO M-001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL ROOM FINAL THERMOSTAT AND SENSOR LOCATION TO BE FINALIZED
WITH THE FIELD CONTRACTING OFFICER REPRESENTATIVE "COR" AND
DESIGNER OF RECORD "DOR".
1. GENERATOR EXHAUST DUCT.
2. WAVEGUIDE ARRAY AT GENERATOR EXHAUST DUCT PENETRATION
THROUGH HEMP SHIELD. (REFER TO A-4/X-141).
3. PROVIDE MAINTENANCE ACCESS FOR REMOTE RADIATOR WITH CATWALK
ABOVE CENTER OF RADIATORS. SEE STRUCTURAL DRAWING S-102.
4. WAVEGUIDE ARRAY AT OIL STORAGE ROOM SUPPLY AIR DUCT
PENETRATION THROUGH HEMP SHIELD. (REFER TO E-1/X-141).
5. CONTRACTOR TO SUPPLY A MUFFLER/SILENCER THAT WILL REDUCE
SOUND EMISSIONS FROM THE GENERATOR EXHAUST BY 40 TO 60
DB. MUFFLER SUPPLIED MUST BE SIZED TO COMPLY WITH THE BACK
PRESSURE LIMIT RANGE OF THE GENERATOR MANUFACTURER. INCLUDE
BACK PRESSURE CALCULATIONS IN MUFFLER SUBMITTAL WHICH WILL
INCLUDE THE WAVE GUIDE THROUGH THE HEMP SHIELD, MUFFLER AND
ALL PIPE/FITTINGS TO SHOW THE COMPLIANCE WITH THE GENERATOR
MANUFACTURER REQUIREMENTS.
D E
N D
U M
/5
/2
ACCESS DOOR
PROVIDE MANUAL VOLUME
DAMPER WITH LOCKING
QUADRANT AT ALL BRANCH
TAKEOFFS TO PROPERLY
BALANCE SYSTEM.
RECTANGULAR TO
RECTANGULAR BRANCH
CONNECTIONS MUST
UTILIZE 45° ENTRY TAP
FITTINGS.
CONCENTRIC TRANSITION:
MAXIMUM ANGLE FOR
DIVERGING FLOW =45°.
MAXIMUM ANGLE FOR
CONVERGING FLOW = 60°.
PROVIDE TURNING
VANES IN
RECTANGULAR AND
MITERED ELBOWS.
FLEXIBLE DUCT MAXIMUM
LENGTH MUST NOT EXCEED
1524 MM. NO FLEXIBLE DUCT
MUST BE ALLOWED IN RETURN
OR EXHAUST SYSTEMS.
EXCEPT WHERE INDICATED.
ROUND ELBOWS
MUST BE 1.5 RADIUS
UNLESS OTHERWISE
NOTED.
RECTANGULAR TO ROUND
BRANCH CONNECTIONS
MUST UTILIZE BELL MOUTH
TAP FITTINGS. ROUND TO
ROUND CONNECTIONS MUST
UTILIZE 45° OVAL TO ROUND
TAP FITTINGS.
PROVIDE PROPORTIONAL
FITTINGS FOR PARALLEL
FLOW RANCHES.
MINIMUM WIDTH MUST
BE 102 MM. PROVIDE
VOLUME DAMPER IN
EACH BRANCH. DUAL
RADIUS ELBOWS ARE
OPTIONAL.
ECCENTRIC TRANSITION:
MAXIMUM ANGLE = 30°
NOTE:
DUCT, FITTINGS, MATERIAL AND SUPPORT MUST BE AS
SPECIFIED IN ACCORDANCE WITH SMACNA "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE."
ANGLE
ANGLE
LAY-IN SUPPY AIR DIFFUSER
WITH ROUND NECK AND
BALANCE DAMPER
FLEX DUCT WITH 50 MM
EXTERNAL INSULATION AT
MAX. LENGTH 1500 MM
NYLON DRAW BAND
METAL BAND SUPPORT
TIE OFF TO ROOF
STRUCTURE
SUPPLY AIR DUCT
SPIN-IN TAP FITTING WITH
AIR SCOOP AND DAMPER
CEILING
DUCT
SEISMIC RESTRAINT
CABLE (TYP.)
BEAM CLAMP
STEEL BEAM
SECURE STRAP HANGER
TO STRUCTURE
CONNECT/MOUNT ON
BOTTOM CHORD OF
STEEL JOIST
SLAB
SEISMIC BRACING MUST
BE SELECTED AND SIZED
UNDER DELEGATED
DESIGN
WALL
PACK WITH FIBROUS
MATERIAL
SEAL BOTH SIDES WITH
RESILIENT ACOUSTICAL
SEALANT AND BACKER
ROD
DUCT OR PIPE
EQUIPMENT
EQUIPMENT BASE
100 MM EQUIPMENT PAD
FLOOR
ADHESIVE ANCHOR BOLT (SIZE AND
QUANTITY DETERMINED BY MANUFACTURER)
NOTE:
ANCHOR BOLT SIZE AND QUANTITY FOR
SEISMIC BRACING MUST BE SELECTED
UNDER DELEGATED DESIGN
STRUCTURAL STEEL CHANNEL
WELDED TO BEAMS (TYP.)
SLAB
SEISMIC RESTRAINT CABLE
(TYP.)
DUCT
FLEXIBLE CONNCTION (TYP.)
DOUBLE LOCKNUTS TORQUED
TOGETHER BELOW
SUSPENSION CLIP (TYP.)
SPRING ISOLATORS (TYP.)
SUSPENSION CLIPS ON SIDE OF
FAN (PROVIDED WITH FAN)
TRANSITION
STRUCTURAL BEAM
FAN
EXISTING STEEL BEAM
NOTE:
SEISMIC BRACING MUST BE SELECTED AND
DESIGNED UNDER DELEGATED DESIGN
CONNECTION TO STEEL BEAMS CONNECTION TO SPREADERS BETWEEN STEEL BEAMS
STEEL BEAM CLAMP
MACHINE BOLT AT END
OF BRACE
FILLER PLATE AS
REQUIRED
3600 MM MAX. BETWEEN BEAMS
CENTERLINE OF SPREADER OR
BRACE
MACHINE BOLT AT END
OF BRACE
SPREADER
VERTICAL AND DIAGONAL BRACESWELDED CONNECTION TO
EXISTING STEEL BEAM
(TYPICAL EACH END)
AIR HANDLING UNIT
EQUIPMENT PAD (SEE
MANUFACTURER'S
INSTRUCTIONS)
CONDENSATE DRAIN SLOPED
AT 2.1% (TERMINATE @
FLOOR DRAIN)
PLENUM FAN SECTION
RETURN AIR
OPENING
HOT WATER COIL
SECTION
NOTE: PROVIDE FLEXIBLE CONNECTIONS FOR
SUPPLY/RETURN/OUTSIDE AIR DUCTS TO AHU.
OUTSIDE AIR
OPENING
SUPPLY AIR
OPENING STAINLESS STEEL
ATMOSPHERIC FUEL VENT WITH
INTERNAL WIRE SCREEN (SIZE
ACCORDING TO DAY TANK
VENTING REQUIREMENTS OR
TWO SIZES GREATER THAN
VENT SIZE, WHICHEVER IS
LARGER)
FUEL OIL VENT.
REFER TO PLANS
FOR SIZE AND
CONTINUATION.
DRAIN SPOUT
ROOF
CONSTRUCT VENT
STACK COLLECTION
SUMP INSULATED
DRAIN FASTENED TO
BUILDING AND OPEN
TO SPLASH BLOCK
BUILDING
EXTENTS
STAINLESS STEEL
FUEL VENT
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349224
M-504
M E
C H
A N
IC
A
L D
E T
A
IL
S
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
S A
L M
O N
D
L T
A T
E
J L E
M E
N S
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
N.T.S.C1
TYPICAL DUCT DETAIL
N.T.S.E4
SUPPLY AIR DIFFUSER DETAIL
N.T.S.A1
DUCT HANGER AND SUPPORT DETAIL
N.T.S.C4
DUCT AND PIPING PENETRATION THRU
PARTITION DETAIL
N.T.S.C7
EQUIPMENT SEISMIC SUPPORT DETAIL
N.T.S.A4
IN-LINE FAN DETAIL
N.T.S.A7
SEISMIC BRACING TO STEEL DETAIL
D E
N D
U M
/5
/2
NTSF8
AIR HANDLING UNIT DETAIL
N.T.S.C6
FUEL OIL VENT DETAIL
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349226
M-601
M E
C H
A N
IC
A
L S
C H
E D
U L
E S
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
S A
L M
O N
D
L T
A T
E
J L E
M E
N S
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
RADIATOR SCHEDULE
UNIT NO.
COOLANT TYPE
HEAT
REJECTION
(kW)
COOLANT
FLOW (L/m) PD (kPa)
ENTERING
WATER TEMP
(DEG. C)
LEAVING
WATER TEMP
(DEG. C)
AMBIENT AIR
TEMP (DEG. C) FAN QTY AIRFLOW (L/s) dBA @ 7
METERS
MOTOR
NOTES
kW (PER FAN) RPM V PH Hz
R-1 ETHYLENE
GLYCOL
2160 1560 36 73 50 11.1 4 50026 81 11.2 1200 460 3 60 1, 2, 3, 4
R-2 ETHYLENE
GLYCOL
2160 1560 36 73 50 11.1 4 50026 81 11.2 1200 460 3 60 1, 2, 3, 4
R-3 ETHYLENE
GLYCOL
2160 1560 36 73 50 11.1 4 50026 81 11.2 1200 460 3 60 1, 2, 3, 4
R-4 ETHYLENE
GLYCOL
2160 1560 36 73 50 11.1 4 50026 81 11.2 1200 460 3 60 1, 2, 3, 4
NOTES:
PROVIDE DISCONNECT.
UNIT PERFORMANCE RATED FOR 50% ETHYLENE GLYCOL/WATER MIXTURE.
PROVIDE WITH AIR SEPARATOR AND AN EXPANSION TANK SIZED AND PROVIDED BY THE MANUFACTURER. AIR SEPARATOR/EXPANSION TANK MUST MEET
THE REQUIREMENTS OF THE RECOMMENDATIONS FROM THE GENERATOR MANUFACTURER.
RADIATOR TO BE PROVIDED WITH DUAL COOLING CIRCUITS WITH INDIVIDUAL TEMPERATURE CONTROLS. ONE CIRCUIT WILL BE FOR THE ENGINE JACKET WATER AND THE OTHER FOR THE LUBE OIL COOLER/AFTER COOLER. REFER TO P&IDS, SEQUENCE OF OPERATIONS, AND THE SPECIFICATION 26 32 15 FOR
SPECIFIC INFORMATION.
FUEL STORAGE TANK SCHEDULE
UNIT
NO.
WEIGHT (kg)
EMPTY FULL
REMARKSSERVICE CONFIGURATION OVERALL
VOLUME (L)
MAXIMUM
STORAGE (L)
OUTER TANK DIMENSIONS (mm)
NOTES:
DT-1 GENERATOR DAY TANK
HORIZONTAL
RECTANGULAR 4164
SECONDARY
CONTAINMENT
VOLUME (L)
LENGTH WIDTH HEIGHT
CARBON
STEEL 1633
1.
2.
DOUBLE WALL CONSTRUCTION - HOT ROLLED STEEL PRIMARY & SECONDARY CONTAINMENT (UL 142).
3.
RUPTURE BASIN SWITCH.
4.
NFPA 30 COMPLIANT STORAGE TANK FOR JP-8 FUEL.
5.
PROVIDE WITH NFPA WARNING DECALS.
45461778 1322 18293748 1,2,3,4,5
TANK
MATERIAL
DT-2 GENERATOR DAY TANK
HORIZONTAL
RECTANGULAR 4853163345461778 1322 1829 1,2,3,4,5
DT-3 GENERATOR DAY TANK
HORIZONTAL
RECTANGULAR 163345461778 1322 1829 1,2,3,4,5
DT-4 GENERATOR DAY TANK
HORIZONTAL
RECTANGULAR 163345461778 1322 1829 1,2,3,4,5
DT-5 BOILER FUEL TANK
HORIZONTAL
RECTANGULAR 568 7611207 762 1257511.0 1,2,3,4
DT-6 BOILER FUEL TANK
HORIZONTAL
RECTANGULAR 568 7611207 762 1257511.0 1,2,3,4
DT-7 BOILER FUEL TANK
HORIZONTAL
RECTANGULAR 568 7611207 762 1257511.0 1,2,3,4
CARBON
STEEL
CARBON
STEEL
CARBON
STEEL
CARBON
STEEL
CARBON
STEEL
CARBON
STEEL
295 735
295 735
295 735
LUBE OIL STORAGE TANK SCHEDULE
UNIT
NO.
WEIGHT (kg)
EMPTY FULL
REMARKSSERVICE CONFIGURATION OVERALL
VOLUME (L)
MAXIMUM
STORAGE (L)
OUTER TANK DIMENSIONS (mm)
LOT-1 GENERATOR LUBE OIL TANK
HORIZONTAL
CYLINDRICAL
LENGTH WIDTH HEIGHT
CARBON
STEEL 1134
TANK
MATERIAL
LOT-2 GENERATOR LUBE OIL TANK
HORIZONTAL
CYLINDRICAL 1134
CARBON
STEEL
FOOT-1 OVERFLOW TANK
HORIZONTAL
CYLINDRICAL 1,2,3,4,5CARBON
STEEL
GLYCOL STORAGE TANK SCHEDULE
UNIT
NO.
WEIGHT (kg)
EMPTY FULL
REMARKSSERVICE CONFIGURATION OVERALL
VOLUME (L)
MAXIMUM
STORAGE (L)
OUTER TANK DIMENSIONS (mm)
GT-1 GENERATOR GLYCOL TANK HORIZONTAL
CYLINDRICAL
LENGTH WIDTH HEIGHT
5015CARBON
STEEL
TANK
MATERIAL
GT-2 GENERATOR GLYCOL TANK HORIZONTAL
CYLINDRICAL
CARBON
STEEL
3028 2725.4 2692 1245 1829 3482 839 3186
NOTES:
1. DOUBLE WALL CONSTRUCTION - HOT ROLLED STEEL PRIMARY & SECONDARY CONTAINMENT (UL 142).
2. TANK MANUFACTURER TO PROVIDE TANK STAND. REFER TO DRAWING M-101.
NOTES:
1. ASME BPVC SEC VIII, DIV 1, U-STAMPED.
2. TANK MANUFACTURER TO PROVIDE TANK STAND. REFER TO DRAWING M-101.
PROVIDE WITH POSITIVE DISPLACEMENT OVERFLOW PUMP RATED AT 2.02 L/SEC, 34.5 kPa TDH, 1750 RPM, 1.12 KW MOTOR. PROVIDE API 676 STANDARD PUMP. REFER TO DIVISION 33 IN SPECIFICATIONS.
4012 4012 3658 1219 1524 1,2
4012 4012 3658 50158451219 1524 1,2
1,2
1,2
D E
N D
U M
/5
/2
4164 3748
4164 3748
4164 3748
1.
2.
3.
4.
76 8 9 10 11
B
C
D
E
H
F
G
Passageway, Bldg. 4000
R E
F E
R T
O D
W G
E P
MASTER CONTROL PANEL
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
FRONT
FRONT
4 3 2 1
(ABB)
5KV SERVICE SWITCHGEAR
FRONT
N
TRUE NORTH
WIND
PLAN NORTH
0 2,500MM 10,000MM
SCALE 1:50 (MILLIMETERS)
BATTERY RM
TEMP POWER SYSTEM
I/O CABINETS
T I E
T I E
T I E
T I E
5KV SWGR - BUS C 5KV SWGR - BUS D
5KV SWGR - BUS A 5KV SWGR - BUS B
FRONT
5KV SWGR 4012A
G
TO UNIT SUB
B4012F
M A I N
P T
F D R
A
F D R
B
SPLICE
BOX 001
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349267
EP105
B L
D G
E
L E
C T
R
IC
A L
R O
O M
P O
W E
R P
L A
N
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
A A
N S
O N
J C
A T
H C
A R
T
D S
H
IF
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
1 : 50A1
FIRST FLOOR PLAN -
4012 ELECTRICAL ROOM
1. REFER TO E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS, GENERAL NOTES
AND DEMOLITION NOTE.
2. REFER TO E-702 FOR FEEDER, TRANSFORMER AND BRANCH CIRCUIT
SCHEDULES.
3. CONTRACTOR MAY UTILIZE EXISTING CABLE TRAY SYSTEMS FOR THE
TEMPORARY POWER SYSTEM 5 KV POWER AND CONTROL WIRING
GENERAL NOTES:
EXISTING SLIDING DOOR FOR REAR ACCESS TO ABB 5 KV SERVICE
SWITCHGEAR.
REMOVE ALL EXISTING OUT OF SERVICE WIRING AND EQUIPMENT BETWEEN
COL 10 AND 11, INCLUDING THE NEUTRAL GROUNDING RESISTOR CABINET
AND WALL MOUNTED EQUIPMENT. REFER TO DETAIL E2 DWG E-504.
PERFORM AS-FOUND SURVEY FOR ALL PROTECTIVE RELAYS FOR THE 5 KV
CIRCUIT BREAKERS IN THE ABB SERVICE SWITCHGEAR, AND THE 5 KV
DISTRIBUTION SWITCHGEAR .
GROUND 5 KV SWITCHGEAR 4012A GROUND BUS TO COLUMN 10 WITH
120 mm2 CONDUCTOR USING EXOTHERMIC WELD.
ALL ACTIVE EXISTING 5 KV CIRCUIT BREAKERS “CLOSE” AND “TRIP”
CONTROLS NOW REMOTELY OPERATED FROM BLDG. 4016 CONTROL ROOM
SHALL BE REROUTED FROM THE 5 KV SWITCHGEAR TO THE TEMPORARY
POWER SYSTEM CONTROL BOAD VIA THE TEMP. PWR. SYSTEM I/O CABINETS.
REFER TO E-612 - TEMPORARY POWER SINGLE LINE DIAGRAM 2 AND EP107 –
TEMPORARY POWER SYSTEM.
REFER TO E-615 DETAIL C2 FOR SINGLE LINE DIAGRAM
KEY NOTES:
D E
N D
U M
/0
/2 e3enmrt3 Line e3enmrt3 Typewritten Text
EXISTING HEMP SPLICE BOX
E
SWGR B4012
BUS A
REFER TO
DWG E-612
MV23
500KVA
AA
DRY TYPE
PRI 4.16KV
SEC 480/277V
S P P
800A
SST
3P
400A 3P
600A 3P
225A 3P
70A 3P
70A 3P
PNL
R4012-1
150A
MCB
T45
XFMR
480V- 208/120V
480V, 800A, 3P, 4W, 14KAIC SWBD 4012F
UNIT SUB B4012F BOILER ROOM
50E
600A
5KV SWGR B4012A
125E
600A
F
UNIT SUB B4012D
ALT SOURCE
REFER TO
DWG E-612
MV22
MV21
4160V, 600A, 3P, 3W, 31.5KA
600AF
600AS
PNL
P 4013
1-1 400A
MCB
TBD E
600A
CONSTRUCTION
POWER
(MAX 500KVA)
SPARE
CONTROL RM
BLDG 4012
70AF
100AS
TEMPORARY POWER SYSTEM
480V AUXILIARY POWER
BLDG 4013
42Y 62Y
4 4
PNL
P4090-1
350A
MCB
RADAR BRIDGE
BY B4090
PNL
R4090-1
150A
MCB
T45
XFMR
480V- 208/120V
42Y
30A 3P
4Y
6 7
WATER
TANK
30AF
60AS
WP
400:5
400:5
50:5
T4012D
225KVA
480/277
SWITCH CLOSED
TO FEEDER 5
N.O.
BUS A (BLDG 4012) BUS B
BLDG
2000:5
US Army Corps of Engineers ®
SHEET OF
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
DISTRIBUTION OF THESE DRAWING IS SUBJECT TO THE LIMITATIONS STATED ON THE COVER SHEET.
349300
E-615
M
IS
C E
L L
A N
E O
U S
S
IN
G L
E L
IN
E
D
IA
G R
A M
S
T H
U L
E A
B
G R
E E
N L
A N
D
F
E D
E R
A L
P L
A Z
A N
E W
Y O
R K
N
Y
A A
N S
O N
J C
A T
H C
A R
T
D S
H
IF
M
A Y
--F
IR
S T
T
IT
L E
S E
C O
N D
T
IT
L E
FINAL SUBMISSION
R E
P A
IR
B
M E
W S
P O
W E
R
J
P L
A N
T B
N E
W Y
O R
K D
IS
T
R
IC
T
SCALE NOT TO SCALEB2
BLDG 4012 PARTIAL
SINGLE LINE DIAGRAM
SCALE NOT TO SCALEB6
BLDG 4012 PARTIAL
DEMO SINGLE LINE DIAGRAM
1. REFER TO E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS, GENERAL NOTES
AND DEMOLITION NOTE.
2. REFER TO E-702 FOR FEEDER, BRANCH CIRCUIT SCHEDULES AND LOW VOLTAGE
INDOOR DRY-TYPE TRANSFORMER SCHEDULE FOR SECONDARY FEEDER AND
GROUND CONDUCTOR SIZES.
3. THE EXISTING 5KV SWGR BUS B CIRCUIT BREAKER NO.14 SERVING SUB 4012D
FUSED PRIMARY TRANSFER SWITCH SHALL BE RE-CIRCUITED TO UNIT SUB B4012.
REFER TO DWG EP-104 AND DWG EP-105.
GENERAL NOTES:
CONTRACTOR MAY UTILIZE 5 KV SWITCH FOR CONSTRUCTION POWER FOR
BLDG. 4016. CONTRACTOR IS TO PROVIDE ALL OTHER REQUIRED EQUIPMENT
AND PROVIDE FOR THE DESIGN, ROUTING AND SECONDARY DISTRIBUTION
SYSTEM AND OPERATION OF THE CONSTRUCTION POWER.
REMOVE EXISTING 5 KV FEEDER, COORDINATE SECHDULED OUTAGE OF UNIT
SUB 4012D WITH GOVERMENT
PROVIDE A FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL KIT IN NEMA 1
ENCLOSURE.
CONTRACTOR MAY PROVIDE JACKETED ARMORED CABLE IN LIEU OF WIRE
AND CONDUIT, ROUTE WHERE POSSIBLE THRU EXISTING CABLE TRAY
SYSTEM OR SUPPORT AS REQUIRED BY NEC. REFER TO ES102 FOR ROUTING
PATH.
GROUND TRANSFORMER TO LOCAL STEEL.
PROVIDE A 30 AMPERE 480 VOLT FEEDER TO WATER TANK HEATER. EXACT
LOCATION FOR FUSED DISCONNECT SWITCH SHALL BE COORDINATED IN
FIELD.
ROUTE THE 480 VOLT ARMORED FEEDER CABLE ON EXISTING CABLE TRAY
SYSTEM IN BUILDING 4012 AND ON GRADE OUTSIDE BUILDING. ROUTE UNDER
ACCESS ROAD THRU A COLVERT.
KEY NOTES:
A
D D
E N
D U
M
/0
/2
| Sheets |
| M-404 - MECHANICAL - GENERATOR BAY AND DAY TANK ROOM ENLARGED PLAN |
| M-504 - MECHANICAL DETAILS |
| M-504 - RFI 041.pdf |
| Sheets |
| M-404 - MECHANICAL - GENERATOR BAY AND DAY TANK ROOM ENLARGED PLAN |
| M-504 - MECHANICAL DETAILS |
| FX001_AMEND 001.pdf |
| Sheets |
| FX001 - FIRE SUPPRESSION GENERAL NOTES AND SYMBOLS |
| M-406 |
| Sheets |
| M-301 - GENERATOR AND SUPPORTING EQUIPMENT TYPICAL BUILDING SECTION |
| M-406 - MECHANICAL - GENERATOR EXHAUST AND RADIATOR ROOM |
| M-301 |
| Sheets |
| M-301 - GENERATOR AND SUPPORTING EQUIPMENT TYPICAL BUILDING SECTION |
| M-406 - MECHANICAL - GENERATOR EXHAUST AND RADIATOR ROOM |
| EP105 |
| Sheets |
| EP105 - BLDG 4012 ELECTRICAL ROOM POWER PLAN |
| S-sheets |
| Sheets |
| S-001 - GENERAL STRUCTURAL NOTES |
| S-101 - SLAB AND FOUNDATION PLAN |
| S-410 - ENLARGED PLANS - MECHANICAL HEMP |
| S-420 - ENLARGED PLANS - GENERATOR ROOM HEMP |
| S-501 - DETAILS - FOUNDATIONS AND SLABS |
File details come from the government source that posted it. Updated .