DATE: 10/31/2017
TEST BY: Day of Week: Tuesday TIME OF DAY: 10:45am MIN. OF FLOW: 5
WATER SUPPLIED BY:
PURPOSE OF TEST:
DATA
FLOW HYDRANT(S) A1 A2 A3
SIZE OPENING: 2.5
COEFFICIENT: 0.91
PITOT READING: 37
GPM: 1030
TOTAL FLOW DURING TEST: 1030 GPM
STATIC READING: 65 PSI RESIDUAL: 56 PSI
RESULTS: AT 20 PSI RESIDUAL 2456 GPM AT 0 PSI 2996 GPM
ESTIMATED CONSUMPTION: 5150 GAL.
REMARKS: Flow test performed using a 2.5 inch hosemonster
McGuire Air Force Base
KC46A Hangar Design
FIRE HYDRANT FLOW TEST
HYDRANT # & LOCATION:
Jeremy W. John, PE
Along Hangar Road: Test Hydrant #1828, Flow Hydrant #1823