Appendix_A_-SOW_Attachment_2_-_AMRS_Meter_Specifications_dated_28_January_2016.pdf

PDF 111 KB Posted

Attached to
KC 46A Two Bay General Purpose MX Hangar Federal contract opportunity
Solicitation number
W912DS-19-R-0001
Issued by
Department of the Army Corps of Engineers Engineering District New York

About this file

Appendix A

View the file

Other files for this federal contract opportunity

Other files attached to KC 46A Two Bay General Purpose MX Hangar, newest first.
File Type Posted
Amendment_0009.pdf PDF
Amendment_0007.pdf PDF
Amendment_0008.pdf PDF
Amendment_0008_Plan.pdf PDF
Amendment_0008_Spec.pdf PDF
hangar_site_visit_sign_in_12.27.18.pdf PDF
Amendment_0006_-_2-Bay_MX_Hangar_Plans.docx.pdf PDF
Appendix_Q_-_KC46_2-Bay_Hangar_Soil_Erosion_Plans.pdf PDF
Amendment_0006_-_2-Bay_MX_Hangar_Specs.pdf PDF
Amedment_0006.pdf PDF
Amendment_0005.pdf PDF
Amendment_0004.pdf PDF
Amendment_0003_-KC46_2-Bay_Hangar_-_Specs.pdf PDF
Amendment_0003.pdf PDF
Amendment_0003_-KC46_2-Bay_Hangar_-_Plans.pdf PDF
Appendix_P_-_Site_Visit_14_NOV_2_Bay_Hanger.pdf PDF
W912DS19R0001-0002.pdf PDF
Amendment_0001.pdf PDF
Appendix_G_-_KC46_2-Bay_Hangar_CADD_Files_(Aval_After_Award).pdf PDF
Appendix_B_-_As-Built_Drawings_For_Buildings_1801_and_1823.pdf PDF
Package_2_-_KC46_-_2-Bay_Hangar_-_Specifications.pdf PDF
Package_4_-_KC46_-_2-Bay_Hangar_-_FFE.pdf PDF
Pages_from_Package_1_-_KC46_-_2-Bay_Hangar_-_Plans-1.pdf PDF
Package_3_-_KC46_-_2-Bay_Hangar_-_CID.pdf PDF
Pages_from_Package_1_-_KC46_-_2-Bay_Hangar_-_Plans_2.pdf PDF
Appendix_O_-_Hangar_Acceptance_Test_Procedures_AFCEC.pdf PDF
Appendix_F_-_USACE_Joint_Base_MDL_HazMat_Assessment_Report_5-8-18_(KM).pdf PDF
Appendix_I_-_SOO-KC-46A_Beddown.pdf PDF
Appendix_C_-_Sustainability_Checklists_and_References.pdf PDF
W912DS19R0001.pdf PDF
Appendix_N_-_KC-46A_MOB_4_Public_FEIS_ExecSumm_June_2018.pdf PDF
Appendix_M_-_Soil_Contamination_Maps.pdf PDF
Appendix_E_-_McGuire_KC-46A_Two-Bay_MX_Hangar_Geotech_Report.pdf PDF
Appendix_J_-_ATFP_Flightline_Securitypdf.pdf PDF
Appendix_B_-_As-Built_Drawings_For_Buildings_1801_and_1823.pdf PDF
Appendix_K_-_KC46_-_Apron_and_Fuel_Hydrant_Relocation.pdf PDF
Appendix_H_-_JB_MDL_-_Pavement_Evaluation_Report_North_of_1837.pdf PDF
Appendix_D_-_Hydrant_Flow_Test.pdf PDF
Appendix_L_-__McGuire_Environmental_Survey_of_B1801_and_B1823_(September_1999).pdf PDF
Show all 39

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMRS Meter Specifications 28 January 2016

SOW Attachment 2

FA3002-0X-D-00XX-4CXX Page 1 or 4

Table of Contents

1.0 Meters Compatible with AMRS

1.1 New / Replacement Meter Installations

1.2 Existing Meters

2.0 AMRS Electric Meter Specifications

3.0 AMRS/UFGS Water, Gas and Steam Meter Specifications

4.0 Typical AMRS Electric Meter Profile

5.0 Typical Stored Data

AMRS Meter Specifications SOW Attachment 2

SOW Attachment 2 - AMRS Meter Specifications dated 28 January 2016 Page 2 of 4

1.0 Meters Compatible with AMRS

1.1 New / Replacement Meter Installations

The following list of meters, or equivalent meters meeting the AMRS meter specification, are

UFGS compatible and will function with the AMRS platform. The AMRS native Data Access

(DA) communication protocol is MODBUS/TCP.

1. Schneider Electric ION 8600/8650 meter product series.

2. EIG Nexus 1262/1272 meter product series.

All new and replacement meter installations, shall be provided with voltage and current safety disconnect devices or equivalent, so that the meter assembly can be worked on safely over the life of the meter installation and not require utility outages for servicing.

1.2 Existing Meters

The following list of meters, or equivalent, can be modified to allow compatibility with the

AMRS platform. These meters are not UFGS compliant and shall not be used for new or replacement installations. These meters may be AMRS compliant with hardware upgrades.

1. The EIG Shark 200 meter product series.

2. The E-mon D-mon Class 5000 meter.

2.0 AMRS Electric Meter Specifications

The AMRS / UFGS Compliant Electric Meter shall meet the following requirements:

UFGS 2007 Compliant (UFGS 2011 supersedes previous versions but is currently not AF approved)

Utility Grade, 0.2% Accuracy or better

Poly Phase (3 voltages and 3 currents)

Transformer grade (Three five (5) Amp Current Transformer (CT) inputs)

Form 9S Socketed Meter

Internal Storage for Recording 2 values or channels for 90 Days, configurable using manufacture supplied configuration software. Must support Interval consumption (15

Minute) and Demand (15 minute Block Average)

Clear and concise manufacture’s published procedure or method for extracting the internally recorded values, register sets (buffer) or channel data via Modbus and Ethernet

Shall support Time of Use Recording

Onboard Ethernet Communications, Base 10/100 with RJ45 connector or pigtail with receptacle connector

MODBUS/TCP communication protocol is required.

Front Display with ability to display all measured values

ANSI Optical Type 2 Communications Port for Meter Configuration and Manual Data

Retrieval

Meter internal real time clock that can be set via the Ethernet Network

Minimum of two external dry contact inputs that will count pluses from other devices

Minimum of one (1) external RS485 serial port (not including the optical serial RS232 port) for communicating to wired MODBUS RTU Slave Meters on this external serial bus.

The above requirements are for new, replacement or upgrade installations.

SOW Attachment 2 - AMRS Meter Specifications dated 28 January 2016 Page 3 of 4

3.0 AMRS/UFGS Water, Gas and Steam Meter Specifications

This AMRS Water, Gas and Steam Meter Specification defines the measurement and communications components for use with the AMRS and must also be compliant to the UFGS as stated below for the mechanical side of the Meter and must meet the following requirements:

UFGS 2013 Compliant for Mechanical Dated November 2011; UFGS – 33 12 33.00 30

Dry Contact Relay (Open Collector Transistor, Open Drain FET) un-wetted pulse output

MODBUS/TCP Communications Protocol for Measured Values from a Pulse Counter

Device wit Integral Ethernet. Device must have ability to wet the input.

MODBUS/TCP Communications Protocol for Measured Values from a Tridium Jace

Programmable Logic Controller with Integral Ethernet. Device must have ability to wet the input.

Insertion, In-Line, Rotor, Electromagnetic, Vortex, & Ultrasonic Meter types are acceptable.

Where plumbing infrastructure is old and risk exists where extensive repairs would be required if piping is disturbed a non-intrusive measurement method is recommended like externally installed ultrasonic devices. New meter installations shall be installed in the building’s mechanical room or inside the facility near the point of entry. In either case, the water meter shall be installed to measure all the potable water entering the facility. If necessary, install multiple meters to assure all potable water is measured.

The above requirements are for new, replacement or upgrade installations.

4.0 Typical AMRS Electric Meter Profile

Measured Parameter Meter-Typical AMRS Namespace

Voltage Phase A-N or A-B, Typical settings

Volts AB VOLTS_PH_AB

Voltage Phase B-N or B-C, Typical settings

Volts BC VOLTS_PH_BC

Voltage Phase C-N or C-A, Typical settings

Volts CA VOLTS_PH_CA

Current Phase A IA CUR_PH_A

Current Phase B IB CUR_PH_B

Current Phase C IC CUR_PH_C

Current Phase N, Neutral, Calculated INc CUR_NEUT

Power (Real) or Active, Total Watts Total PWR_WATTS_POLY

Power Reactive, Total VAR Total PWR_VAR_POLY

Power (Volts Amps) or VA, Total VA Total PWR_VA_POLY

Power Factor Total, COS PF PF_POLY

Frequency in HZ Frequency FREQ

Demand, Block Average (15 Minute) (BWA) KW DEMAND_KW

Energy, KWH (Active or Real) WH Quadrant 1 or

(1+4)

ENERGY_KWH

Pulse Aggregation, Unscaled Aggregator 1 Pulse_1_raw

SOW Attachment 2 - AMRS Meter Specifications dated 28 January 2016 Page 4 of 4

Pulse Aggregation, Unscaled Aggregator 2 Pulse_2_raw

Pulse Aggregation, Unscaled Aggregator 3 Pulse_3_raw

Pulse Aggregation, Unscaled Aggregator 4 Pulse_4_raw

5.0 Typical Stored Data

Measured Parameter Meter-Typical AMRS Namespace

Consumption Interval (15-minutes) Interval Calculated (delta value

Internal to CEM object)