This document provides details for a federal solicitation seeking construction services for reservoir maintenance and improvements. The U.S. Army Corps of Engineers, Baltimore District is soliciting competitive, firm-fixed-price bids via an Invitation for Bid to complete work at the Second High Reservoir in Washington D.C. The project aims to address operational and sanitary issues previously identified to improve water quality and distribution system operation. Specific work includes replacing the brick Sample Building, replacing the 24-inch drain line, installing mechanical mixers, sealing all interior joints and cracks, installing a spread spectrum radio communications antenna, installing a roof sub-drainage system, and replacing the perimeter fence. The reservoir outage period is restricted due to its critical role in the water distribution system. Bids are due by May 25, 2022, with award planned for July 2022 and work expected to be complete by September 2023.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
16' - 0"16' - 0"16' - 0"16' - 0"
INSIDE FACE IF RESERVOIR
EXTERIOR WALL
FLOOR CONSTRUCTION
JOINT GRID PATTERN (TYP)
CL 20" SQ CONCRETE
COLUMN (TYP)
WATERPROOF
MEMBRANE PATCH OVER
ALL FLOOR JOINTS
REPAIR ALL BOTTOM SLAB
CRACKS PER DETAIL 4/S-10
EXTERIOR WALL
REPAIR ALL BOTTOM
SLAB JOINTS PER
DETAIL 3/S-10
TYPE I - NON-LEAKING CRACKS
FACE OF EXISTING CONCRETE
PATCH VOID FLUSH WITH EPOXY CRACK
BINDER IN ACCORDANCE WITH SPECIFICATION
SECTION 03 01 35 - CONCRETE REPAIRS.
EXISTING CONCRETE
TYPE II - LEAKING CRACKS
(WATERPROOF INJECTION GROUT)
DRILL AND INSTALL INJECTION
POINTS PER MANUFACTURER
RECOMMENDATIONS (TYP)
SEAL CRACK SURFACE PER
MANUFACTURE RECOMMENDATIONS
EXISTING CONCRETE
FACE OF EXISTING CONCRETE
45.00°
EXISTING
FACE OF EXISTING CONCRETE
EXISTING CONSTRUCTION JOINT FILLER
AND SEALANT TO REMAIN
EXISTING CONCRETE
NEW
FACE OF EXISTING CONCRETE
12" WIDE WATERPROOF MEMBRANE PATCH
OVER ALL JOINTS IN MAT SLAB ONLY
EXISTING CONCRETE
EXISTING
REMOVE UNSOUND MATERIALS
BY APPROVED MEANS AND
CLEAN SUBSTRATE
EXISTING CRACK
EXISTING CONCRETE
PROPOSED
SEAL JOINT PER TYPICAL CRACK
REPAIR DETAIL II
EPOXY BONDING AGENT, TYP
EXISTING
CONCRETE
REPAIR MORTAR, SEE
SPECIFICATIONS, (TYP)
SAWCUT AROUND PERIMETER
TO PROVIDE 1/2" MIN MATERIAL
DEPTH
PACK JOINT WITH APPROVED SPONGE RUBBER
OR CORK EXPANSION JOINT MATERIAL AS
REQD BY THE EPOXY AND MORTAR
MANUFACTURER FOR WIDTH OF CRACK
APPLY WATERPROOF INJECTION GROUT PER
TYPICAL CRACK REPAIR DETAIL TYPE II
.1 /2
M
IN
D
E P
T H
EXISTING
FACE OF EXISTING
CONCRETE
EXISTING CONSTRUCTION JOINT
FILLER AND SEALANT TO BE REMOVED
AT THE DIRECTION OF THE
CONTRACTOR OFFICER
EXISTING
CONCRETE
TYPE I - NON-LEAKING CRACKS
FACE OF EXISTING
CONCRETE
EXISTING CONSTRUCTION JOINT.
REMOVE JOINT SEALANT AND
EXPANSION JOINT MATERIAL TO BE
REMOVED AT THE DIRECTION OF THE
CONTRACTOR OFFICER, SEE NOTE 3
PACK JOINT WITH APPROVED SPONGE
RUBBER OR CORK EXPANSION JOINT
MATERIAL
APPLY WATERPROOF INJECTION GROUT PER
TYPICAL CRACK REPAIR DETAIL PER DETAIL 5/S-09
TYPE II - LEAKING CRACKS
(WATERPROOF INJECTION GROUT)
FACE OF EXISTING
CONCRETE
PATCH VOID FLUSH WITH
EPOXY CRACK BINDER,
SEE SPECIFICATION 03 01
PACK JOINT WITH APPROVED SPONGE
RUBBER OR CORK EXPANSION JOINT
MATERIAL
APPLY WATERPROOF INJECTION GROUT PER
TYPICAL CRACK REPAIR TYPE II PER DETAIL 5/S-09
12" WIDE WATERPROOF
MEMBRANE PATCH OVER ALL
JOINTS IN MAT SLAB ONLY
12" WIDE WATERPROOF
MEMBRANE PATCH OVER ALL
JOINTS IN MAT SLAB ONLY
GENERAL NOTES
1. CONCRETE REPAIR WORK SHALL BE PERFORMED PER SPECIFICATION 03 01 35 -
CONCRETE REPAIRS AND THE DETAILS ON THIS SHEET AND SHEET S-09.
2. THE CONTRACTOR IN CONJUNCTION WITH THE ENGINEER, SHALL DETERMINE THE
EXTENT OF CRACKED OR DETERIORATED CONCRETE TO BE REHABILITATED AND/OR
RESURFACED A SUMMARY OF WORK DETAILING QUANTITIES OF BASE BID AND
CONTINGENCY ITEMS SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO
COMMENCEMENT OF THE WORK.
3. EXISTING MATERIAL IN FLOOR CONSTRUCTION JOINTS HAS BEEN TESTED AND
DETERMINED TO CONTAIN ASBESTOS, THEREFORE, SHALL BE HANDLED AND DISPOSED
IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 13.00 10 - ASBESTOS ABATEMENT.
ANY MATERIAL THAT IS DETERMINED TO BE LEFT IN PLACE SHALL BE COVERED BY A
MEMBRANE PATCH AS INDICATED IN DETAIL 3 AND MARKED IN THE AS-BUILT AS
MATERIAL CONTAINED ASBESTOS LEFT IN PLACE.
4. FOR PAYMENT PURPOSES, THE WIDTH OF CONSTRUCTION JOINT REPAIR SHALL BE
LIMITED TO 4 INCHES MAXIMUM MEASURED EITHER WAY FROM THE CENTERLINE OF THE
JOINT. DETERIORATED CONCRETE AT A JOINT WIDER THAN 4 INCHES SHALL BE PAID AS
A SPALL REPAIR.
5. BEFORE COMMENCEMENT OF ANY CONCRETE REPAIR WORK CONTRACTOR SHALL
WATERBLAST DETERIORATED AREAS WITH PRESSURE NOT TO EXCEED 2500 PSI TO
REMOVE RESIDUAL LIME, SEDIMENT DEPOSIT AND BIOFILM FROM INTERIOR WALL
SURFACES AS DIRECTED BY THE GOVERNMENT. SEE SPECIFICATION 03 01 35 -
CONCRETE REPAIRS.
6. ALL SEDIMENT AND WASHWATER REMOVED DURING BLASTING AND CLEANING
OPERATIONS SHALL BE CONTAINED, COLLECTED, AND PROPERLY DISPOSED OF BY THE
CONTRACTOR IN COMPLIANCE WITH THE APPLICABLE PERMIT CONDITIONS.
7. TYPE II WATERPROOF CRACKS REQUIRE INJECTION GROUTING WHEN A CRACK IS
VISIBLY WET OR LEAKING.
8. FOR OVERHEAD CRACKS REQUIRING INJECTION GROUTING, CONTRACTOR SHALL PLACE
INJECTION PORTS ALONG CRACK AND SEAL THE SURFACE CRACK PRIOR TO INJECTING
THE GROUT PER MANUFACTURER RECOMMENDATIONS.
9. CONTRACTOR SHALL FIELD LOCATE ALL EXPANSION JOINTS AND MARK THEM IN THE AS-
BUILT.
10. ALL CONSTRUCTION JOINTS IN NEED OF REPAIR SHALL BE DRY FOR PROPER SEALING
WITH FLEXIBLE MEMBRANE PATCH. ANY LEAKING JOINT WILL REQUIRE REMOVAL OF THE
EXISTING MATERIAL AND REPLACEMENT WITH HYDROPHILIC GROUT.
11. IT HAS BEEN DETERMINED THAT THE RESERVOIR HAS INFILTRATION WHEN IT IS EMPTY.
THE CONTRACTOR SHALL ASSUME WET WORKING CONDITIONS INSIDE THE RESERVOIR.
Nova Consulting
REV DATE DESCRIPTION BY
U.S. ARMY ENGINEER DISTRICT, BALTIMORE
WASHINGTON AQUEDUCT
WASHINGTON, DC
SCALE: DATE:
DRAWING NUMBER PLATE
SHEET:
CORPS OF ENGINEERS
BALTIMORE, MARYLAND
SECOND HIGH RESERVOIR
MAINTENANCE AND IMPROVEMENTS
APPROVED:
A/E PRINCIPAL
SEAL:
MARCH 2022
80.2-2.7-.
US Army Corps of Engineers
STEVEN S. EAGLE, PE
S-10
CONCRETE AND JOINT REPAIR
DETAILS II
STRUCTURAL
NTS
5/2022 AMENDMENT 0002 SSE
1/8" = 1'-0"S-10
1 TYPICAL BOTTOM REPAIR PLAN REPAIRS
NTSS-10
5 TYPICAL CRACK REPAIR DETAIL
NTSS-10
3 CONSTRUCTION JOINT REPAIR AT MAT SLAB DETAIL
NTSS-10
2 CRACK REPAIR AT MAT SLAB DETAIL
NTSS-10
4 CONSTRUCTION JOINT REPAIR AT CEILING AND WALL
0 8 16
SCALE: 1/8" = 1'-0"
CONCRETE REPAIRS TABLE
PAY
ITEM DESCRIPTION
BASE BID
ITEM
OPTIONAL
BID ITEM
JOINT REPAIR
QTY (LF)
JOINT REPAIR
REFERENCE
STRUCT CRACK
REPAIR QTY (LF)
STRUCT CRACK
REPAIR REFERENCE
WATERPROOF MEMB
PATCH QTY (LF)
WATERPROOF MEMB
PATCH REFERENCE
WATERPROOF INJ ECTION
GROUT QTY (LF)
WATERPROOF INJECTION
GROUT REFERENCE
SURFACE SPALL
REPAIR QTY (CF)
SURFACE SPALL
REPAIR REFERENCE
FORMED SPALL
REPAIR QTY (CF)
FORMED SPALL
REPAIR REFERENCE
004 EXPANSION / CONSTRUCTION JOINT WITHOUT WATER PROOF INJECTION GROUTING X 14,000 4/S-10 ; 4/S-09 14,000 4/S-10 ; 4/S-09
005 EXPANSION / CONSTRUCTION JOINT WITH WATER PROOF INJECTION GROUTING X 6,000 4/S-10 ; 4/S-09 6,000 4/S-10 ; 4/S-09 6,000 5/S-10
007 CEILING REPAIR USING STRUCTURAL CRACK MATERIAL X 4,000 5/S-10
008 CRACKS REPAIRS WITH WATER PROOF INJECTION GROUTING X 500 5/S-10
010 WALL AND FLOOR SLAB REPAIR USING STRUCTURAL CRACK MATERIAL X 1,000 5/S-10 ; 2/S-10
011 WALL AND SLAB JOINT REPAIR WITH WATERPROOF INJECTION GROUT X 500 4/S-09 500 4/S-09
012 SPALL REPAIR X 50 2/S-09
013 SPALL REPAIR USING FORMED REPAIR METHOD X 30 3/S-09
014 MAT SLAB JOINT REPAIR WITH WATER PROOF MEMBRANE X 5,000 3/S-10
OrlandoAlfonso Polygon
| Sheets |
| S-09 - CONCRETE AND JOINTS REPAIR DETAILS I |
| S-10 - CONCRETE AND JOINT REPAIR DETAILS II |
| 2022-05-05T11:44:31-0400 | |
| Steven S. Eagle P.E. 43684 State of Florida |