This document package includes construction drawings and specifications for maintenance and improvement projects at the Second High Reservoir in Washington, DC. The U.S. Army Corps of Engineers, Baltimore District is soliciting fixed-price bids to replace the brick sample building, 24-inch drain line, and perimeter fence at the reservoir and install mechanical mixers, seal interior joints and cracks, and add a roof sub-drainage system and communications antenna. The reservoir is a critical part of the water distribution system for over one million people, so the outage period for this work is restricted. Bids are due by the date specified in solicitation number W912DR22B0007.

The construction drawings provide details for the proposed repairs and upgrades, including drainage and waterproofing details, as well as notes specifying requirements for removing the existing waterproof membrane, preparing surfaces, and applying repair patches.

View the file

Other files

File Type Posted
C.04.01 Abstract of Bids W912DR22B0007 2nd High Reservoir.pdf PDF
2nd High 04222022 Site Visit Sign In Sheet.pdf PDF
PL31_M-02.pdf PDF
B.08.03 Solicitation Amendment W912DR22B0007-0002.pdf PDF
PL40_E-06.pdf PDF
PL11_C-07.pdf PDF
PL33_M-04.pdf PDF
PL05_C-01.pdf PDF
PL20_S-05.pdf PDF
PL21_S-06.pdf PDF
PL24_S-09.pdf PDF
B.08.03 RFI Responses W912DR22B0007.pdf PDF
PL10_C-06.pdf PDF
PL08_C-04.pdf PDF
PL07_C-03.pdf PDF
PL25_S-10.pdf PDF
PL03_G-03.pdf PDF
PL18_S-03.pdf PDF
PL22_S-07.pdf PDF
PL06_C-02.pdf PDF
B.08.03 Solicitation Amendment W912DR22B0007.pdf PDF
B.08.02 Attachment C - DB Wage Determination DC20220002.pdf PDF
B.08.02 Attachment B - Drawings.pdf PDF
B.08.02 Solicitation W912DR22B0007.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING

ROOF DECK

8"

1. COVER SOIL NOT SHOWN FOR CLARITY.

NOTES:

EXISTING

GRADE

VA

R

IE

S

NEW DRAINAGE

GEOTEXTILE

NEW AASHTO

NO. 57 STONE

4"Ø PERFORATED

SCH 40 PVC PIPE

2' TRENCH

EXISTING

WATERPROOFING

MEMBRANE

BACKFILL FROM

EXCAVATED SOIL

EXISTING GROUND

NEW SOD

4' ' M

IN

AASHTO NO. 57 STONE, 36" MAX DEPTH,

MAINTAIN MINIMUM DEPTHS AROUND PIPE

PERFORATED SCH 40 PVC

PIPE (SEE DRAWING C-03

FOR DIA.)

DRAINAGE GEOTEXTILE

EXISTING WATERPROOFING

MEMBRANE

EXISTING CONCRETE

ARCH ROOF

2'-6"

6''

2'-6'' MIN.

DRAINAGE

GEOTEXTILE

PERFORATED SCH 40

PVC PIPE LAID AT 0.3%

SLOPE (SEE DRAWING

C-03 FOR DIA.)

18" SQUARE

9"9"

6"

FINISH

GRADE

8" PVC RISER

AL

L

AR

O

U N

D 3/

4" C

H

AM

FE

R

1'-6" x 1'-6" SQUARE

CONCRETE PAD

FLOW

INTERIOR SLAB OR

EXTERIOR GRADE

PROVIDE A PLUG WYE

HERE IF AT BEGINNING

OF RUN

4, 6, 8" DIA PVC

SCH 40 PIPE

CLEANOUT CAP CLEANOUT WYE

CLEANOUT WYE

RAISED HEX-HEAD PVC

CLEANOUT IN YARD,

RECESSED KEY PVC

CLEANOUT IN PAVED AREAS

WATERPROOF MASTIC (TYP),

SEE MEMBRANE TERMINATION

DETAIL 5 ON THIS PAGE

6''

3-FT WIDE SELF ADHERED

WATERPROOFING

MEMBRANE (TYP)

MEMBRANE

BOOT

MEMBRANE

APRON

EXISTING

WATERPROOFING

MEMBRANE

6''

MEMBRANE

BOOT

MEMBRANE

APRON

WATERPROOF MASTIC (TYP),

SEE MEMBRANE TERMINATION

DETAIL 5 ON THIS PAGE

3-FT WIDE SELF ADHERED

WATERPROOFING

MEMBRANE (TYP)

EXISTING

WATERPROOFING

MEMBRANE

N

EW

S

TU

B C

O

LU

M N

EXISTING LOW

DENSITY CONCRETE

GRADE

FLOW

DOUBLE WYE PLAN VIEW

8" PIPE

8''x8''x8'' DOUBLE WYE

EX

IS

TI

N

G

ST

R U

C

TU

R E

MEMBRANE

APRON

STAINLESS STEEL BATTEN

STRIP (CONTINUOUS) AND

SHOT ANCHORS @12" CC

HOT AIR WELD

EXISTING WATERPROOFING

MEMBRANE

ROOF DECK

1'

1. CONTRACTOR SHALL REMOVE THE DAMAGED AREA

OF WATERPROOF MEMBRANE AND PREPARE

SURFACE TO APPLY REPAIR DETAIL.

2. SEAMING EQUIPMENT, METHODS AND SEALANT

SHALL BE APPROVED BY THE WATERPROOFING

MEMBRANE MANUFACTURER.

NOTES:

NEW WATER PROOFING

MEMBRANE

12''

MIN 12

M

IN

M

IN

M

IN

M

IN

12''

MIN

12''

MIN

12''

MIN

EXISTING 60 ML HDPE WATERPROOF

MEMBRANE

60 MIL MIN SELF-ADHERING ELASTOMETRIC

SHEET WATERPROOF MEMBRANE PATCH

RIP, TORN, OR DAMAGED EXISTING

HDPE WATERPROOF MEMBRANE

ROOF-TOP SOIL LAYER

EXPOSE 12-INCHES OF EXISTING MEMBRANE

BEYOND PROPOSED HDPE PATCH

(TYP AROUND ALL SIDES OF PATCH)

NEW PIPE

CONCRETE WALL

PIPE Ø PLUS 6''

NON-SHRINK GROUT

H O

LE

T

O

TA

L D

IA

M

ET

ER

0.

2.

4.

6.

8.

0.

EXISTING AREA TO

BE REPAIRED

AP

PR

O X.

5'

APPROX. 25'

AA

PERMANENT EROSION GEOTEXTILE

BLANKET ANCHOR TOP AND BOTTOM.

STAKE/PIN AS RECOMMENDED BY

MANUFACTURER

2' MIN

2' MIN

PERMANENT VEGETATION TO

MATCH SURROUNDING AREA

FILL WITH SUITABLE MATERIAL

ACCORDING WITH SPECIFICATION

SECTION 32 92 23 - SODDING

EXISTING TOP

OF BANK

EXISTING BOTTOM

OF BANK

DRAWING NUMBER PLATE

SCALE: DATE: SHEET:

WASHINGTON AQUEDUCT

WASHINGTON, DC

MAINTENANCE AND IMPROVEMENTS

MARCH 2022

SECOND HIGH RESERVOIR

Nova Consulting

U.S. ARMY ENGINEER DISTRICT, BALTIMORE

CORPS OF ENGINEERS

BALTIMORE, MARYLAND

STEVEN S. EAGLE, PE

AS SHOWN

80.2-2.7-14 14

C-10

CIVIL

CIVIL DETAILS 1

SCALE: NTS

PERIMETER DRAINAGE SYSTEM

C-10

SCALE: NTS

TYPICAL ROOF DRAIN TRENCH DETAIL

C-10

SCALE: NTS

TYPICAL UNDERDRAIN CLEANOUT DETAIL

C-10

SCALE: NTS

TYPICAL WATERPROOFING @ JUNCTION OF

HORIZONTAL TO VERTICAL SURFACE DETAIL

C-10

SCALE: NTS

DOUBLE WYE DETAIL

C-03

SCALE: NTS

TYPICAL WATERPROOF

MEMBRANE TERMINATION DETAIL

C-10

SCALE: NTS

TYPICAL WATERPROOF MEMBRANE REPAIR DETAIL

C-10

SCALE: NTS

TYPICAL SEAL PIPE OPENING

C-10

SCALE: NTS

SLOPE REPAIR DETAIL

C-02

SCALE: NTS

SLOPE REPAIR DETAIL

C-10 A

1 SSE5/2022 AMENDMENT 00021

AutoCAD SHX Text

REV

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text US Army Corps

AutoCAD SHX Text of Engineers

AutoCAD SHX Text

A/E PRINCIPAL

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

APPROVED:

Sheets and Views
C-10
2022-05-03T16:46:29-0400
Steven S. Eagle P.E. 43684 State of Florida

File details come from the government source that posted it. Updated .