About this file

This document contains a federal contract opportunity solicitation for reservoir maintenance and improvements. The U.S. Army Corps of Engineers, Baltimore District is soliciting competitive, firm-fixed-price bids to implement upgrades and improvements to the Second High Reservoir in Washington D.C. as part of the Washington Aqueduct water treatment and distribution system. The project consists of replacing infrastructure such as a sample building, 24-inch drain line, and perimeter fence. Additional work includes installing mechanical mixers to seal interior joints and cracks, spreading spectrum radio communications equipment, and a roof sub-drainage system. The reservoir outage period for work is restricted. The solicitation number is W912DR22B0007 and the bid response deadline has not been specified.

View the file

Other files

File Type Posted
C.04.01 Abstract of Bids W912DR22B0007 2nd High Reservoir.pdf PDF
2nd High 04222022 Site Visit Sign In Sheet.pdf PDF
PL31_M-02.pdf PDF
B.08.03 Solicitation Amendment W912DR22B0007-0002.pdf PDF
PL40_E-06.pdf PDF
PL11_C-07.pdf PDF
PL33_M-04.pdf PDF
PL05_C-01.pdf PDF
PL20_S-05.pdf PDF
PL24_S-09.pdf PDF
B.08.03 RFI Responses W912DR22B0007.pdf PDF
PL10_C-06.pdf PDF
PL08_C-04.pdf PDF
PL07_C-03.pdf PDF
PL25_S-10.pdf PDF
PL03_G-03.pdf PDF
PL18_S-03.pdf PDF
PL14_C-10.pdf PDF
PL22_S-07.pdf PDF
PL06_C-02.pdf PDF
B.08.03 Solicitation Amendment W912DR22B0007.pdf PDF
B.08.02 Attachment C - DB Wage Determination DC20220002.pdf PDF
B.08.02 Attachment B - Drawings.pdf PDF
B.08.02 Solicitation W912DR22B0007.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BASIC DEVELOPMENT LENGTH AND SPLICE LENGTH

BASIC

1'-0"

1'-0"

1'-2"

1'-5"

2'-3"

2'-10"

3'-6"

4'-3"

5'-1"

TOP *

1'-0"

1'-2"

1'-6"

1'-9"

2'-11"

3'-8"

4'-6"

5'-6"

6'-7"

1'-0"

1'-6"

2'-2"

2'-11"

4'-7"

5'-8"

6'-4"

7'-2"

7'-11"

1'-3"

2'-0"

2'-10"

3'-9"

6'-0"

7'-4"

8'-3"

9'-3"

10'-3"

SIZE

# 3

# 4

# 5

# 6

# 7

# 8

# 9

# 10

# 11

BAR

1'-0"

1'-2"

1'-6"

1'-9"

2'-11"

3'-8"

4'-6"

5'-6"

6'-7"

1'-2"

1'-7"

1'-11"

2'-4"

3'-9"

4'-9"

5'-10"

7'-2"

8'-7"

1'-3"

2'-0"

2'-10"

3'-9"

6'-0"

7'-4"

8'-3"

9'-3"

10'-3"

1'-7"

2'-7"

3'-8"

4'-11"

7'-9"

9'-6"

10'-8"

12'-0"

13'-4"

BASIC DEVELOPMENT LENGTH CLASS B SPLICE LENGTH

d 1.3 x

* TOP REINFORCEMENT IS ANY HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN

12 INCHES OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE REINFORCEMENT.

FOR UNCOATED BARS IN TENSION

fy = 60,000 psi fc' = 4500 psi OR GREATER

FOR MATERIALS OR CONDITIONS DIFFERENT FROM THOSE STATED, LENGTHS SHOWN IN**

CHART SHALL BE MODIFIED TO CONFORM TO THE PROVISIONS OF ACI 318, SECTION 12.2.

CLEAR SPACING≥ 3" CLEAR SPACING <3"

BASIC TOP *

CLEAR SPACING <3"CLEAR SPACING≥ 3"

BASIC TOP * BASIC TOP *

NORMAL WEIGHT CONCRETE

** BASED ON MATERIALS AND CONDITIONS AS FOLLOWS:

CLEAR COVER≥ 1.5 INCHES

d

DEVELOPMENT LENGTH OF STANDARD HOOKS

HOOK AT LEAST 2".

END COVER BEYOND OUTSIDE END OF

AT LEAST 2 1/2"; AND FOR 90° HOOK,

SIDE COVER NORMAL TO PLANE OF HOOK*

FOR UNCOATED BARS IN TENSION

fc' = 4500 psi OR GREATERfy = 60,000 psi

DEVELOPMENT LENGTH, dh

#11

#10

#9

#8

#7

#6

#5

#4

#3 dh dh

W/ CONC COVER *

6"

7"

8"

10"

11"

1'-1"

1'-3"

1'-4"

1'-6"

BASIC

7"

9"

1'-0"

1'-2"

1'-4"

1'-6"

1'-9"

1'-11"

2'-2"

BAR SIZE

OPNG

NOTES:

1. THIS DETAIL APPLIES FOR OPENINGS 8"∅ AND LARGER. FOR SMALLER

OPENINGS, BEND BARS OR ADJUST SPACING OF REINFORCEMENT TO

AVOID OPENING.

2. PLACE EXTRA BARS OF THE SAME SIZE AS THE INTERRUPTED BARS AT

EACH SIDE OF OPENING. QUANTITY OF EXTRA BARS AT EACH SIDE

SHALL EQUAL HALF THE QUANTITY OF INTERRUPTED BARS EXCEPT

WHERE NOTED OTHERWISE.

3. PROVIDE ONE DIAGONAL BAR EACH SIDE OF OPENING WITH SIZE EQUAL

TO MAIN REINFORCEMENT, TYPICAL EACH FACE.

4. WHERE INVERT OF OPENING IN WALL IS LESS THAN 44 BAR DIAMETERS

FROM TOP OF SLAB, EXTRA REINFORCEMENT ON EACH SIDE SHALL

INCLUDE DOWELS EMBEDDED INTO SLAB WITH STANDARD 90 DEGREE

HOOKS TO SPLICE WITH EXTRA VERTICAL REINFORCEMENT. DOWELS

SHALL ALSO STILL BE PROVIDED BELOW OPENING.

5. WHERE INVERT OF OPENING IN WALL OR SLAB IS CLOSER THAN 44 BAR

DIAMETERS TO EDGE OF SLAB OR BOTTOM OF WALL, EXTRA DIAGONAL

BARS MAY BE TERMINATED TWO INCHES FROM EDGE OF SLAB OR

BOTTOM OF WALL. DOWELS DO NOT HAVE TO BE PROVIDED TO SPLICE

WITH DIAGONAL BARS.

TY

P44

D

2"

3"

TYP

44D

T

SPLICE +2"

CLASS "B"

FOR SLAB OR WALL THICKNESS AND

REINFORCING, SEE DESIGN DRAWINGS

FOR TYPICAL KEYWAY,

SEE DETAIL 1

WATERSTOP WHERE REQUIRED,

SEE SPECIFICATIONS AND

GENERAL CONCRETE NOTES

1/3" 1/3" 1/3" WATERSTOP

FOR EQUIPMENT

PLAN DIMENSION AS REQUIRED

EDGE DISTANCE SEE NOTE 3

0" OR 2" MIN

SEE NOTE 3

2" MIN EDGE DISTANCE

BOLT DESIGN

CONFIRM BY ANCHOR

REQUIRED COVER

+1" MAX

LEVELING CHANNEL,

SEE NOTES 2 AND 3

#5 DOWELS @12" ALL

AROUND, SEE NOTE 1

DOWEL ADHESIVE

LEVELING CHANNEL

ANCHORS, SEE NOTE 2

8" MIN, SEE NOTE 1

4" MIN, SEE NOTE 6

PUMP OR EQUIP BASE

CONC FLOOR

#4@12 EW

#5 DOWELS @12" ALL

AROUND, SEE NOTE 1

1" MIN GROUT,

SEE NOTES 2 & 3

CONC PAD

CL ANCHOR RODS

NOTES:

1. DOWELS MAY BE CAST IN WITH 90° HOOK OR ANCHORED WITH DOWEL ADHESIVE AT CONTRACTORS

OPTION. WHERE FLOOR IS 8" THICK OR LESS, USE #4 DOWELS EMBEDDED TO WITHIN 2" OF BOTTOM OF

FLOOR SLAB.

2. THE CONTRACTOR SHALL PROVIDE LEVELING CHANNELS AND LEVELING CHANNEL ANCHORS FOR

SWITCHGEAR, SWITCHBOARDS, MOTOR CONTROL CENTERS, AND SIMILAR EQUIPMENT WHEN

REQUIRED TO MEET EQUIPMENT MANUFACTURER'S LEVELING TOLERANCES. THE CONTRACTOR SHALL PROVIDE 1" MINIMUM NON-SHRINK GROUT FOR PUMPS AND SIMILAR EQUIPMENT WHEN REQUIRED TO

MEET EQUIPMENT MANUFACTURER'S UNIFORM BEARING AND LEVELING REQUIREMENTS.

3. PRIOR TO PLACING CONCRETE PAD, LEVELING CHANNEL SIZE AND MEANS OF INSTALLATION, ANCHORAGE, GROUT, CONCRETE EDGE DISTANCE, AND CONCRETE BLOCKOUTS REQUIREMENTS

SHALL BE COORDINATED WITH EQUIPMENT MANUFACTURER.

4. COAT DISSIMILAR MATERIALS PER THE CONTRACT DOCUMENTS.

5. STAGGER CHANNEL ANCHORS AND PAD DOWELS.

6. FOR PADS 24" OR GREATER IN DEPTH, PROVIDE #4@8" HORIZONTAL SKIN REINFORCING AROUND

PERIMETER OF PAD.

BASIC DEVELOPMENT LENGTH AND SPLICE LENGTH

BASIC

1'-0"

1'-0"

1'-3"

1'-6"

2'-5"

3'-0"

3'-8"

4'-6"

5'-5"

TOP *

1'-0"

1'-3"

1'-7"

1'-11"

3'-1"

3'-11"

4'-9"

5'-10"

7'-0"

1'-0"

1'-7"

2'-4"

3'-1"

4'-11"

6'-0"

6'-9"

7'-7"

8'-5"

1'-4"

2'-1"

3'-0"

4'-0"

6'-4"

7'-9"

8'-9"

9'-10"

10'-11"

SIZE

# 3

# 4

# 5

# 6

# 7

# 8

# 9

# 10

# 11

BAR

1'-0"

1'-3"

1'-7"

1'-11"

3'-1"

3'-11"

4'-9"

5'-10"

7'-0"

1'-3"

1'-8"

2'-0"

2'-5"

4'-0"

5'-1"

6'-3"

7'-7"

9'-1"

1'-4"

2'-1"

3'-0"

4'-0"

6'-4"

7'-9"

8'-9"

9'-10"

10'-11"

1'-8"

2'-9"

3'-11"

5'-2"

8'-3"

10'-1"

11'-4"

12'-9"

14'-2"

BASIC DEVELOPMENT LENGTH CLASS B SPLICE LENGTH

d 1.3 x

FOR UNCOATED BARS IN TENSION

fy = 60,000 psi fc' = 4000 psi OR GREATER

CLEAR SPACING≥ 3" CLEAR SPACING <3"

BASIC TOP *

CLEAR SPACING <3"CLEAR SPACING≥ 3"

BASIC TOP * BASIC TOP *

NORMAL WEIGHT CONCRETE

** BASED ON MATERIALS AND CONDITIONS AS FOLLOWS:

CLEAR COVER≥ 1.5 INCHES

TOP REINFORCEMENT IS ANY HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 12

INCHES OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE REINFORCEMENT.

FOR MATERIALS OR CONDITIONS DIFFERENT FROM THOSE STATED, LENGTHS SHOWN IN

CHART SHALL BE MODIFIED TO CONFORM TO THE PROVISIONS OF ACI 318-14, SECTION 25.3.

d

/4

C

L R

2" CLR 0.25L1

GREATER

0.3L1 OR L2

GREATER

0.3L1 OR L2

L1 L2

/4

C

L

R6" MIN 6" MIN

S E E P

L A N

S

SYM

ABOUT

CL

TOP BARS

TEMP STEEL

BOT BARS

SEE BEAM SCHEDULE

FOR TYP REINF AND

BEAM DEPTH

NOTE:

SEE PLAN FOR BAR SIZE AND SPACING.

Nova Consulting

REV DATE DESCRIPTION BY

U.S. ARMY ENGINEER DISTRICT, BALTIMORE

WASHINGTON AQUEDUCT

WASHINGTON, DC

SCALE: DATE:

DRAWING NUMBER PLATE

SHEET:

CORPS OF ENGINEERS

BALTIMORE, MARYLAND

SECOND HIGH RESERVOIR

MAINTENANCE AND IMPROVEMENTS

APPROVED:

A/E PRINCIPAL

SEAL:

MARCH 2022

80.2-2.7-.

US Army Corps of Engineers

S-06

STRUCTURAL DETAILS - SHEET 1

STRUCTURAL

AS SHOWN

MAY 22 AMENDMENT 0002 CTP

CHRISTOPHER T. PHILLIPS, PE

NTSS-06

5 DETAIL - TYPICAL REINFORCING AT OPENINGS

NTSS-06

2 DETAIL - CONSTRUCTION JOINT

NTSS-06

1 DETAIL - KEYWAY

NTSS-06

3 DETAIL - TYPICAL PUMP OR EQUIPMENT PAD

NTSS-06

4 DETAIL - TYPICAL SLAB SECTION

File details come from the government source that posted it. Updated .