This document includes a solicitation for construction services for reservoir maintenance and improvements at the Second High Reservoir in Washington, DC, as well as a description of the related federal contract opportunity. The solicitation seeks competitive, firm-fixed-price bids to replace the brick Sample Building, replace the 24-inch drain line, install mechanical mixers, seal all interior joints and cracks, install a spread spectrum radio communications antenna, install a roof sub-drainage system, and replace the perimeter fence at the Second High Reservoir. The U.S. Army Corps of Engineers, Baltimore District will award the construction contract in accordance with FAR 14 using an Invitation for Bid. The reservoir is a critical part of the water distribution system for over one million people, so the outage period for work is restricted. The opportunity aims to address previously identified operational and water quality issues through the upgrades in order to improve system operations.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FF: 342.97
SECOND HIGH
RESERVOIR
WARREN ST NW
VAN NESS ST NW
th
S T
N W
VERPLANCK PL NW
th
S T
N W
NEW 8' PICKET FENCE,
SEE SHEET C-11 FOR
DETAILS
APPROXIMATE
RESERVOIR LIMIT
APPROXIMATE
RESERVOIR LIMIT
APPROXIMATE
RESERVOIR LIMIT
APPROXIMATE
RESERVOIR LIMIT
NEW 8'' PVC ROOF
DRAIN LINE
EXISTING 24'' CI
DRAIN PIPE
NEW 24" HDPE
OVERFLOW
NEW 24" DIP
DRAIN PIPE
SAMPLE BUILDING R-2
NEW 4' CONCRETE SIDEWALK
SEE DETAIL 1/C-11 AND
GENERAL SHEET NOTE 4,
SHEET C-04
NEW 4'' PVC
DRAIN PIPE
EXISTING STAIRS
TO REMAIN
NEW 20' MOTORIZED
SLIDING GATE, SEE
DETAIL 4, SHEET C-11TRENCH RESTORATION (TYP)
PAVEMENT
RESTORATION
CURB AND GUTTER
RESTORATION
GRASS RESTORATION
EXCAVATION
RESTORATION
SIDEWALK - STOOP
INTERFACE, SEE
DETAIL 2/C-11
NEW SWING GATE, SEE
DETAIL 5, SHEET C-11
DRAWING NUMBER PLATE
SCALE: DATE: SHEET:
WASHINGTON AQUEDUCT
WASHINGTON, DC
MAINTENANCE AND IMPROVEMENTS
MARCH 2022
SECOND HIGH RESERVOIR
Nova Consulting
U.S. ARMY ENGINEER DISTRICT, BALTIMORE
CORPS OF ENGINEERS
BALTIMORE, MARYLAND
STEVEN S. EAGLE, PE
SCALE: 1"=30'-0"
0 30 60
GENERAL SHEET NOTES
KEY PLAN
2. CONTRACT SHALL PERFORM ALL THE WORK IN STRICT ADHERENCE TO THE
RESERVOIR LOADING LIMITATION NOTES PER SHEET C-02.
3. CONTRACTOR SHALL REPAIR, OR REPLACE IN KIND, ANY EXISTING FENCING
REMOVED AND STORED FOR REPLACEMENT OR DAMAGED BY CONSTRUCTION
ACTIVITIES.
4. MATCH NEW SIDEWALK TO EXISTING STAIR ELEVATION.
5. STOCKPILING OF SOIL OR EARTH ON TOP OF THE RESERVOIR IS NOT ALLOWED.
RESTORATION PLAN
AS SHOWN
80.2-2.7.08 08
C-04
CIVIL
RESTORATION PLAN
XXXXXXXX
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X X X X X
X X
X X
X X
X X
X X
X X
X X
X
XX
VAN NESS ST NW
th
S T
N W th
S T
N W
WARREN ST NW
1. CONTACT: NOTIFY THE FOLLOWING DC WATER DEPARTMENTS PRIOR TO THE
COMMENCEMENT OF UTILITY CONSTRUCTION:
A. CONSTRUCTION INSPECTION SECTION AT 202-787-4024 AT LEAST TWO
WEEKS PRIOR TO THE COMMENCEMENT OF UTILITY CONSTRUCTION TO
SCHEDULE PRE-CONSTRUCTION MEETING.
B. DEPARTMENT OF WATER SERVICES AT 202-612-3400 AT LEAST ONE WEEK
PRIOR TO THE COMMENCEMENT OF WATER UTILITY CONSTRUCTION.
C. DEPARTMENT OF SEWER SERVICES AT 202-264-3862 OR 3873 AT LEAST
ONE WEEK PRIOR TO THE COMMENCEMENT OF SEWER UTILITY
CONSTRUCTION.
2. STANDARDS: ALL CONSTRUCTION, MATERIALS, AND APPURTENANCES SHALL
COMPLY WITH THE LATEST EDITIONS OF THE DC WATER PROJECT DESIGN
MANUAL, STANDARD DETAILS & DESIGN GUIDELINES, AND SPECIFICATIONS.
3. LEAD SERVICE REPLACEMENT: IF THIS PROJECT INCLUDES THE REPLACEMENT
OF A WATER MAIN THAT HAS EXISTING LEAD WATER SERVICE LATERALS, THE
CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE DC WATER
CONSTRUCTION INSPECTION SECTION AT 202-787-4024 AT LEAST NINETY (90)
CALENDAR DAYS PRIOR TO CONSTRUCTION TO ALLOW ADEQUATE TIME TO
INITIATE STANDARD LEAD SERVICE REPLACEMENT PROTOCOL. LATERAL
REPLACEMENT INCLUDES THE FULL LENGTH OF PIPE IN PUBLIC SPACE.
4. PAINT ON EXISTING VALVES IS SUSPECTED TO CONTAIN LEAD, THEREFORE,
SHALL BE HANDLED AND DISPOSED OFF IN ACCORDANCE WITH SPECIFICATION
SECTION 02 83 13.00 20 - LEAD IN CONSTRUCTION.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ANY NECESSARY
PUBLIC SPACE PERMITS AND THEN CONTACT DC WATER PRIOR TO
PERFORMING THE EXCAVATION TO INSTALL/INSPECT THE UTILITY WORK. THE
CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGES TO EXISTING
STRUCTURES AND UTILITIES CAUSED BY CONSTRUCTION ACTIVITY.
6. MISS UTILITY: CONTACT MISS UTILITY AT 800-257-7777 48 HOURS BEFORE ANY
DIGGING.
7. PLAN SET: A SET OF SIGNED & SEALED AND DC WATER STAMPED PLANS SHALL
BE KEPT AT ALL TIMES AT THE JOB SITE ON WHICH ALL CHANGES OR
VARIATIONS IN THE WORK, INCLUDING ALL EXISTING UTILITIES, ARE TO BE
RECORDED AND/OR CORRECTED DAILY.
8. ABANDONMENT: THE OWNER MUST PHYSICALLY DISCONNECT EXISTING
WATER, SEWER, AND STORM LATERALS THAT ARE TO BE ABANDONED AT
THEIR CONNECTION TO THE PUBLIC MAIN.
9. UNMETERED WATER: THERE SHALL BE NO UNMETERED CONNECTIONS TO THE
CITY'S WATER SYSTEM, INCLUDING CONNECTIONS BYPASSING METERS FOR
TESTING ON-SITE PLUMBING OR FOR OBTAINING CONSTRUCTION WATER.
10. PRESSURE TESTING AGAINST VALVES: PRESSURE TESTING AGAINST VALVES
WILL NOT BE ALLOWED.
11. WATER METER INSTALLATION: TO SCHEDULE THE INSTALLATION OF A
DOMESTIC WATER METER CONTACT PERMIT OPERATIONS AT 202-646-8600. DC
WATER WILL FURNISH AND INSTALL THE METER AFTER THE CONNECTION TO
THE MAIN HAS BEEN MADE AND THE METER PIT/VAULT HAS BEEN INSTALLED.
12. CROSS CONTAMINATION CONTROL: ASSE 1048 CERTIFIED BACKFLOW
PREVENTION ASSEMBLIES ARE REQUIRED ON ALL FIRE SERVICES AND ARE TO
BE LOCATED INSIDE THE BUILDING (UNLESS AN EXTERNAL LOCATION IS
NECESSARY OR REQUIRED BY DC WATER) WHERE IT IS SUPPLIED, OWNED,
OPERATED, AND MAINTAINED BY THE OWNER. DC WATER DOES NOT FURNISH
NOR INSTALL FIRE DOUBLE CHECK DETECTOR FIRE PROTECTION BACKFLOW
PREVENTION ASSEMBLIES.
13. UTILITY SERVICE DISRUPTIONS: PHASE ALL UTILITY WORK TO MAINTAIN
UTILITY SERVICES TO THE SURROUNDING AREA DURING ALL PHASES OF
CONSTRUCTION. LIMIT REQUIRED UTILITY SHUT-DOWNS IN NUMBER AND
DURATION. COORDINATE THESE SHUTDOWNS WITH DC WATER
CONSTRUCTION INSPECTION STAFF.
14. WATER VALVE OPERATION: THE CONTRACTOR IS REQUIRED TO COORDINATE
WITH DC WATER FOR ALL NECESSARY WATER MAIN SHUTDOWNS WITH
ADEQUATE ADVANCED NOTICE. ONLY DC WATER EMPLOYEES MAY SHUT DOWN
A PUBLIC WATER MAIN. A CERTIFIED PLUMBER IS ONLY AUTHORIZED TO TURN
OFF VALVES INSIDE METER PITS.
15. WATER GATE VALVE LOCATION: LOCATE GATE VALVES FOR DOMESTIC AND
FIRE SERVICES AS CLOSE TO THE PUBLIC WATER MAIN TEE AS POSSIBLE.
HOWEVER, IF NECESSARY ADJUSTMENTS ARE REQUIRED DUE TO CONFLICTS,
COORDINATE WITH A DC WATER INSPECTOR.
16. MATERIAL: THE CONTRACTOR IS RESPONSIBLE FOR SUBMITTING SHOP CUTS
TO THE APPROPRIATE DC WATER OFFICE FOR APPROVAL OR OBTAINING A DC
WATER APPROVAL STAMP FOR ALL WORK IN PUBLIC SPACE IN ADVANCE OF
INSTALLATION. ONLY APPROVED MATERIALS MAY BE USED.
17. TEMPORARY CONDITIONS MINIMUM COVER: A NOMINAL FOUR FEET OF COVER
IS REQUIRED FOR ALL WATER MAINS AT FINAL GRADE. COVER OF LESS THAN
FOUR FEET REQUIRES DC WATER APPROVAL.
18. AS-BUILT: DEVELOPERS, CONTRACTORS AND/OR PLUMBERS MUST SUBMIT
FINAL CONSTRUCTION AS-BUILT INFORMATION TO THE APPROPRIATE DC
WATER INSPECTOR(S) FOR REVIEW AND APPROVAL, UPON COMPLETION OF
INSTALLATION OF NEW SERVICES OR ABANDONMENT OF EXISTING SERVICES.
WHEN THE FINAL AS-BUILT IS APPROVED ALL DEPOSITS WILL BE RETURNED TO
THE APPLICANT. SEE DC WATER AS-BUILT REQUIREMENTS FOR ADDITIONAL
INFORMATION.
19. CONFLICTS: THE CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF
EXISTING UNDERGROUND UTILITIES PRIOR TO INSTALLATION OF PROPOSED
UTILITIES. A MINIMUM OF ONE FOOT VERTICAL AND FIVE FEET HORIZONTAL
CLEARANCE SHALL BE MAINTAINED FROM ANY UTILITIES AND PUBLIC WATER
AND SEWER MAINS.
20. FIRE HYDRANT USE: THE USE OF A FIRE HYDRANT AS A WATER SOURCE IS
PROHIBITED UNLESS A PERMIT HAS BEEN OBTAINED FROM DC WATER FOR
USE OF A SPECIFIC HYDRANT(S). DAILY OR EXTENDED USE PERMITS CAN BE
OBTAINED FROM THE DC WATER PERMIT OPERATIONS DEPARTMENT
202-646-8600.
21. FIRE HYDRANT STATUS: THE CONTRACTOR SHALL NOTIFY FEMS AT
202-277-1889, PRIOR TO TAKING ANY FIRE HYDRANT OUT OF SERVICE OR
RENDERING ANY HYDRANT INACCESSIBLE FOR ANY REASON. FEMS IS ALSO TO
BE PROVIDED WITH THE LOCATION OF ANY NEW INSTALLATION OF PRIVATE
FIRE HYDRANTS.
22. DC WATER SAFETY OFFICE: THE DC WATER SAFETY OFFICE CAN BE
CONTACTED AT 202-787-4350.
23. SEWER BACKWATER PREVENTION: THE PLUMBING SYSTEM MUST BE IN
COMPLIANCE WITH SECTION 715 OF THE 2006 INTERNATIONAL PLUMBING CODE
WHICH STATES A BACKWATER IS VALVE IS REQUIRED FOR ALL PLUMBING
FIXTURES BELOW THE ELEVATION OF THE MANHOLE COVER OF THE NEXT
UPSTREAM MANHOLE IN THE PUBLIC
GENERAL NOTES
GENERAL FENCING NOTES
1. THE ARCHITECT'S SELECTION OF FENCE MATERIALS AND DETAILS DOES NOT
RELIEVE THE CONTRACTOR FROM VERIFYING WITH THE FENCE MATERIAL
SUPPLIERS THAT THE PROPOSED NEW FENCE MATERIALS ARE CORRECT AND
PROPER FOR THE INTENDED APPLICATION AND USE.
2. CONTRACTOR SHALL PROVIDE PERIMETER SITE SECURITY THROUGHOUT
CONSTRUCTION. AT A MINIMUM, CONTRACTOR SHALL INSTALL TEMPORARY
FENCING AND SIGNS ALONG LIMITS OF DISTURBANCE WHERE EXISTING FENCE
HAS BEEN REMOVED FOR CONSTRUCTION ACTIVITIES OR AS DIRECTED BY THE
GOVERNMENT. TEMPORARY FENCING SHALL BE A SPECIFIC COMPONENT OF THE
CONTRACTOR'S WORK PLAN SUBMITTAL.
3. PRIOR TO THE DEMOLITION OF THE EXISTING FENCE, THE CONTRACTOR SHALL
COORDINATE WITH THE GOVERNMENT (WASHINGTON AQUEDUCT) TO DETERMINE
IF THE FENCE IS TO BE SALVAGED OR REMOVED. IF IT IS TO BE SALVAGED, THE
GOVERNMENT WILL PROVIDE THE STORAGE LOCATION FOR THE FENCE. IF THE
FENCE IS TO BE REMOVED, THE CONTRACTOR SHALL DISPOSE OF THE FENCE IN
COMPLIANCE WITH THE APPLICABLE REGULATORY AGENCY.
4. ALL EQUIPMENT ASSOCIATED WITH THE EXISTING FENCE AND GATE INCLUDING
BUT NOT LIMITED TO THE GATE MOTOR, CAMERAS, SMART CARD READER AND
KEYPAD EXTRA SHALL BE TESTED IN THE PRESENCE OF THE GOVERNMENT
REPRESENTATIVE IMMEDIATELY PRIOR TO REMOVAL, THEN, THE CONTRACTOR
SHALL REMOVE WITHOUT ANY DEGRADATION IN CONDITION, SALVAGE AND TURN
THE EQUIPMENT OVER TO THE GOVERNMENT FOR STORAGE AND FUTURE
REINSTALLATION/REUSE ON THE NEW PICKET FENCE BY THE GOVERNMENT'S
APPROVED SECURITY CONTRACTOR. THE CONTRACTOR SHALL COORDINATE THE
REQUIRED REINSTALLATION AND RETESTING WITH A MINIMUM OF 30 CALENDAR
DAYS NOTICE AND PRIOR TO COMPLETION OF THE WORK IN THIS CONTRACT.
5. THE CONTRACTOR SHALL COORDINATE AND EXECUTE THE DEMOLITION OF THE
EXISTING CHAIN LINK FENCE AND GATES AND INSTALLATION OF THE NEW 8-FOOT
HIGH PICKET FENCE & GATES IN A MANNER SO THAT SECOND HIGH RESERVOIR IS
NEVER WITHOUT A SECURE FENCE, AND THAT THE SECURITY CAMERA SYSTEM
(LOCATED ON INDEPENDENT POLES JUST INSIDE THE EXISTING FENCE LINE) ARE
NOT DISTURBED, IMPACTED OR DAMAGED. NO GAP IN FENCING SHALL BE LEFT
UNATTENDED AT ANY TIME AND THE CONTRACTOR SHALL VERIFY AT THE END OF
EACH WORK DAY THAT NO GAP EXISTS THAT COMPROMISES THE SECURITY OF
THE RESERVOIR. TEMPORARY FENCING SHALL BE INSTALLED, REPAIRED AND
UTILIZED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
6. CONTRACTOR SHALL PROVIDE LATCH ON THE PICKET FENCE THAT PERMITS
OPERATION FROM EITHER SIDE OF THE GATE, WITH A PADLOCK EYE PROVIDED AS
AN INTEGRAL PART OF THE LATCH. PEDESTRIAN GATE LATCH SHALL HAVE
INTERCHANGEABLE 1.25" MORTISE CYLINDER LOCK SO A CYBERLOCK CAN BE
INSTALLED.
7. CONTRACTOR SHALL REPAIR, OR REPLACE IN KIND, ANY EXISTING FENCING
REMOVED AND STORED OR DAMAGED BY CONSTRUCTION ACTIVITIES.
8. CONTRACTOR SHALL SCHEDULE AND FULLY COORDINATE WORK WITH THE
GOVERNMENT CONTRACTING OFFICER AND COGNIZANT SECURITY OFFICER
SUFFICIENTLY IN ADVANCE IN ORDER FOR THE GOVERNMENT TO ARRANGE FOR
THEIR APPROVED SECURITY CONTRACTOR TO RE-INSTALL AND TEST SALVAGED
SECURITY EQUIPMENT WITH NO LAPSE IN SITE SECURITY COVERAGE.
GENERAL SHEET NOTES
1. REFER TO SPECIFICATION 31 00 00 FOR EARTHWORK SPECIFICATIONS, INCLUDING
PLACEMENT AND COMPACTION REQUIREMENTS FOR SOIL OVER ROOF. REFER TO
SAME SPECIFICATION FOR ALL TRENCHING REQUIREMENTS.
LEGEND:
SOD RESTORATION
PAVEMENT RESTORATION
CURB AND SIDEWALK RESTORATION
1 SSE
5/2022 AMENDMENT 0002
AutoCAD SHX Text
EOI
AutoCAD SHX Text
EOI
AutoCAD SHX Text
EOI
AutoCAD SHX Text
EOI
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text W
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
EOI
AutoCAD SHX Text
SD1
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
REV
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BY
AutoCAD SHX Text US Army Corps
AutoCAD SHX Text of Engineers
AutoCAD SHX Text
A/E PRINCIPAL
AutoCAD SHX Text