This document package includes construction drawings and specifications for concrete and joint repairs to the Second High Reservoir in Washington, DC. The U.S. Army Corps of Engineers, Baltimore District is soliciting fixed-price bids to implement upgrades and improvements including replacement of the brick Sample Building, replacement of the 24-inch drain line, installation of mechanical mixers and communication antennas, addition of a roof drainage system, and replacement of the perimeter fence. The work must be completed during a restricted outage period to minimize disruption to the water supply system serving over one million people. Drawings S-09 provide repair details for concrete spalls, expansion joints, and construction joints between walls and slabs. Replacement of deteriorated materials, sawcutting, doweling, and application of waterproof membranes, epoxy, and injection grout are specified.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B C D E F G H I J K L M N O P Q
A S-09
B S-09
A B C D E F G H I J K L M N O P Q
EXISTING
REMOVE UNSOUND MATERIALS BY APPROVED
MEANS AND CLEAN SUBSTRATE. REBAR EXPOSED
DURING REMOVAL OPERATIONS SHALL BE CLEANED
AND PROTECTED WITH ANTI-CORROSION COATING
EXISTING CONCRETE
NEW
REPAIR MATERIAL, SEE
SPECIFICATION SECTION 03 01 35
EPOXY BONDING AGENT
EXISTING CONCRETE
D
S E
E N
O T
E
SAWCUT AROUND PERIMETER TO
PROVIDE 1/2" MIN MATERIAL DEPTH
/2
M
IN
D
E P
T H
EXISTING
REMOVE UNSOUND MATERIALS BY APPROVED
MEANS AND CLEAN SUBSTRATE. REBAR EXPOSED
DURING REMOVAL OPERATIONS SHALL BE CLEANED
AND PROTECTED WITH ANTI-CORROSION COATING
EXISTING CONCRETE
NEW
WWF 6x6- W12xW12 OR #3@12"
MIN EDGE DISTANCE = 3"
#3 BAR @12"
DOWEL ADHESIVE
D
S E
E N
O T
E
REPAIR MORTAR, SEE SPECIFICATION 03 01 35
M
IN
/2
M
IN
D
E P
T H
M
IN
C O
V E
R
EPOXY BONDING AGENT, TYP
EXISTING CONCRETE
SAWCUT AROUND PERIMETER TO
PROVIDE 1/2" MIN MATERIAL DEPTH
EXISTING
REMOVE EXISTING WATERSTOP
EXISTING CONCRETE
REMOVE BATTEN BARS AND EXPANSION
ANCHORS IN THEIR ENTIRETY
THOROUGHLY CLEAN JOINT, REMOVE ALL
UNSOUND MATERIALS AND DETERIORATED
JOINT REPAIR
BASE OF EXISTING CONCRETE
PATCH ANY RESULTING VOIDS FROM
EXPANSION ANCHOR REMOVAL WITH
APPROVED EPOXY RESIN BINDER
SEAL JOINT SURFACE WITH APPROVED 12"
WIDE WATERPROOF MEMBRANE PATCH
BASE OF EXISTING CONCRETE
TYPE I - NON-LEAKING CRACKS
PATCH ANY RESULTING VOIDS FROM EXPANSION
ANCHOR REMOVAL WITH APPROVED EPOXY RESIN
BINDER PER MANUFACTURE RECOMMENDATIONS
APPLY WATERPROOFING INJECTION GROUT
PER TYPICAL CRACK REPAIR
BASE OF EXISTING CONCRETE
TYPE II - LEAKING CRACKS
(WATERPROOF INJECTION GROUT)
SEAL JOINT SURFACE WITH APPROVED 12"
WIDE MINIMUM WATERPROOF MEMBRANE
PATCH
EXISTING CONCRETE
EXISTING
REMOVE GROUT SEALANT
BETWEEN ANGLE AND
CONC WALL
EXISTING CONCRETE WALL
EXISTING CONSTRUCTION JOINT
BETWEEN BASE SLAB AND WALL
NEW
REMOVE STEEL ANGLE
AND ANCHORAGE
SEAL JOINT SURFACE WITH
APPROVED 12" WIDE MINIMUM
WATERPROOF MEMBRANE PATCH
EXISTING CONCRETE WALL
EXISTING CONSTRUCTION JOINT
BETWEEN BASE SLAB AND WALL
APPLY WATERPROOF INJECTION
GROUT PER TYPICAL CRACK
REPAIR DETAIL TYPE II
GENERAL SHEET NOTES
1. CONCRETE REPAIR WORK SHALL BE PERFORMED PER
SPECIFICATION 03 01 35 - CONCRETE REPAIRS AND THE
DETAILS ON THIS SHEET AND SHEET S-10.
2. SPALLED AND/OR DETERIORATED AREAS WHERE DEPTH "D"
TO BE REPAIRED IS LESS THAN OR EQUAL TO 6" SHALL BE
REPAIRED PER DETAIL 2/S-09, AREAS WHERE DEPTH "D" IS
GREATER THAN 6" SHALL BE REPAIRED PER DETAIL 3/S-09.
3. THE ACTUAL PLACES TO BE REPAIRED WILL BE DETERMINED
DURING JOINT ASSESSMENT WITH THE GOVERNMENT. ANY
AND ALL COPPER REMOVED FROM THE EXPANSION JOINT
WATERSTOP SHALL BE RETURNED TO THE OWNER.
4. HOLES DRILLED FOR INJECTION PORTS SHALL NOT CUT
REBAR. THE CONTRACTOR SHALL CONSIDER GPR OR
EQUIVALENT SCANNING METHODS TO LOCATE REBAR PRIOR
TO UNDERTAKING REPAIRS.
5. THE WATER USED FOR MIXING CONCRETE REPAIR PRODUCTS
SHALL BE CLEAR, POTABLE, AND FREE OF DELETERIOUS
SUBSTANCES.
6. ALL REPAIR PRODUCTS SHALL BE CURED IN STRICT
ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS.
Nova Consulting
N
REV DATE DESCRIPTION BY
U.S. ARMY ENGINEER DISTRICT, BALTIMORE
WASHINGTON AQUEDUCT
WASHINGTON, DC
SCALE: DATE:
DRAWING NUMBER PLATE
SHEET:
CORPS OF ENGINEERS
BALTIMORE, MARYLAND
SECOND HIGH RESERVOIR
MAINTENANCE AND IMPROVEMENTS
APPROVED:
A/E PRINCIPAL
SEAL:
MARCH 2022
80.2-2.7-.
US Army Corps of Engineers
STEVEN S. EAGLE, PE
S-09
CONCRETE AND JOINTS REPAIR
DETAILS I
STRUCTURAL
AS SHOWN
5/2022 AMENDMENT 0002 SSE
3/64" = 1'-0"1
SHR OVERALL PLAN
3/64" = 1'-0"S-09
A CROSS SECTION
/6
S -0
B L
O N
G
IT
U D
IN
A
L S
E C
T
IO
N
NTSS-09
2 SPALL REPAIR DETAIL
NTSS-09
3 FORMED SPALL REPAIR DETAIL
NTSS-09
5 EXPANSION JOINT REPAIR AT WATERSTOP DETAIL
NTSS-09
4 CONSTRUCTION JOINT REPAIR AT WALL & SLAB JOINT DETAIL
OrlandoAlfonso Polygon
| Sheets |
| S-09 - CONCRETE AND JOINTS REPAIR DETAILS I |
| 2022-05-05T13:41:05-0400 | |
| Steven S. Eagle P.E. 43684 State of Florida |