Am_0010_Specs.pdf
PDF 262 KB Posted
- Solicitation number
- W9128F25R0014
About this file
This document is a detailed technical specification (Section 28 10 05) for the Electronic Security Systems (ESS) for the New Dairy Forage Research Center in Prairie du Sac, Wisconsin. The specification provides comprehensive requirements for an integrated security system including an Access Control System (ACS), Intrusion Detection System (IDS), Closed-Circuit Television (CCTV) System, and associated communications infrastructure.
Key technical requirements include providing a USDA-compatible security system with contactless card readers, high security switches, video surveillance cameras (interior and exterior, including 180 and 360-degree multi-sensor types), network equipment, servers, workstations, and printers. The system must support Personal Identity Verification (PIV) credentials, have embedded video analytics, encryption capabilities, and be designed for redundancy and expansion. The specification mandates specific technical parameters for components like camera resolution, low-light performance, data transmission, power supply, and environmental durability. Additionally, the document outlines extensive training requirements for system administrators, operators, and maintenance personnel, including multiple on-site training sessions covering system configuration, operation, and troubleshooting.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
New Dai r y For age Resear ch Cent er , Pr ai r i e du Sac, WI ARS01
SECTI ON TABLE OF CONTENTS
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
SECTI ON 28 10 05
ELECTRONI C SECURI TY SYSTEMS ( ESS)
05/ 16
PART 1 GENERAL
1. 1 REFERENCES
1. 2 Wor k I ncl udes
1. 3 DESI GN REQUI REMENTS
1. 3. 1 Cabl es
1. 3. 2 Condui t Requi r ement s
1. 3. 3 Backbox / Junct i on Box
1. 3. 4 Door Har dwar e and Door Har dwar e Power Suppl i es
1. 3. 5 I nt egr at ed Door Har dwar e Request t o Exi t Swi t ch I nt er f ace
1. 3. 6 Li f e Saf et y Coor di nat i on
1. 3. 7 Ar chi t ect ur al Bar r i er s Act ( ABA) Ent r ances
1. 4 PERFORMANCE REQUI REMENTS
1. 4. 1 Car d Reader Locat i ons
1. 4. 2 Hi gh Secur i t y Swi t ch ( HSS) Locat i ons
1. 4. 3 Aut omat i c Door Ent r ances
1. 5 COORDI NATI ON
1. 6 SUBMI TTALS
1. 7 QUALI TY ASSURANCE
1. 7. 1 Regul at or y Requi r ement s
1. 7. 2 St andar d Pr oduct s
1. 7. 2. 1 Al t er nat i ve Qual i f i cat i ons
1. 7. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
1. 7. 2. 3 Pr oduct Saf et y
1. 7. 3 Shop Dr awi ngs
1. 7. 3. 1 ESS Component s
1. 7. 3. 2 Over al l Syst em Schemat i c
1. 7. 4 Evi dence of Exper i ence and Qual i f i cat i ons
1. 7. 4. 1 Cont r act or Qual i f i cat i ons
1. 7. 4. 2 I nst r uct or Qual i f i cat i ons
1. 8 Envi r onment al Condi t i ons
1. 8. 1 I nt er i or Condi t i ons
1. 8. 1. 1 Temper at ur e
1. 8. 1. 2 Pr essur e
1. 8. 1. 3 Rel at i ve Humi di t y
1. 8. 1. 4 Fungus
1. 8. 1. 5 Acoust i cal Noi se
1. 8. 2 Ext er i or Condi t i ons
1. 8. 2. 1 Temper at ur e
1. 8. 2. 2 Pr essur e
1. 8. 2. 3 Sol ar Radi at i on
1. 8. 2. 4 Sand and Dust
1. 8. 2. 5 Rai n
1. 8. 2. 6 Humi di t y
1. 8. 2. 7 Fungus
1. 8. 2. 8 Snow
SECTI ON 28 10 05 Page 1
1. 8. 2. 9 I ce Accr et i on
1. 8. 2. 10 Wi nd
1. 8. 2. 11 Acoust i cal Noi se
1. 9 SYSTEM CALCULATI ONS AND ANALYSI S
1. 9. 1 Backup Bat t er y Capaci t y Cal cul at i ons
1. 9. 2 CCTV St or age Cal cul at i ons
1. 10 AS- BUI LT DRAWI NGS
PART 2 PRODUCTS
2. 1 SYSTEM DESCRI PTI ON
2. 2 PERFORMANCE REQUI REMENTS
2. 2. 1 Gr owt h Capabi l i t y
2. 2. 2 Hazar dous Locat i ons
2. 2. 3 Net wor k Cer t i f i cat i on
2. 2. 4 Mai nt ai nabi l i t y
2. 2. 5 Avai l abi l i t y
2. 2. 6 Fai l - Saf e Capabi l i t y
2. 2. 7 Li ne Super vi s i on
2. 2. 8 Power Loss Det ect i on
2. 2. 9 Cont r ol s and Desi gnat i ons
2. 2. 10 Speci al Test Equi pment
2. 2. 11 El ect r omagnet i c I nt er f er ence ( EMI )
2. 2. 12 El ect r omagnet i c Radi at i on ( EMR)
2. 2. 13 I nt er changeabi l i t y
2. 3 I NTRUSI ON DETECTI ON SYSTEM ( I DS)
2. 3. 1 I DS Component s
2. 3. 2 Det ect i on Sensi t i v i t y
2. 3. 3 Det ect i on Al ar m and Repor t i ng Capaci t y
2. 3. 4 Fal se Al ar m Rat e
2. 3. 5 Nui sance Al ar m Rat e
2. 3. 6 Pr emi se Cont r ol Uni t ( PCU)
2. 3. 6. 1 PCU Capabi l i t i es
2. 3. 6. 2 Over cur r ent Pr ot ect i on and I ndi cat i on
2. 3. 6. 3 Manual and Sel f - Test
2. 3. 7 Det ect i on Sensor s
2. 3. 7. 1 I nt er i or Sensor s
2. 3. 7. 1. 1 Hi gh Secur i t y Swi t ch ( HSS)
2. 3. 7. 1. 2 Gl ass Br eak Det ect i on
2. 3. 7. 1. 2. 1 Cei l i ng Mount ed Recessed Gl ass Br eak Sensor
2. 3. 7. 2 Tamper Swi t ches
2. 3. 7. 2. 1 Tamper Swi t ch Per f or mance Requi r ement s
2. 4 ACCESS CONTROL SYSTEM ( ACS)
2. 4. 1 ACS Badgi ng Requi r ement s
2. 4. 2 Er r or and Thr oughput Rat es
2. 4. 3 Access Cont r ol Syst em Cent r al Pr ocessi ng
2. 4. 4 Access Cont r ol Uni t ( ACU)
2. 4. 5 Access Cont r ol Devi ces
2. 4. 5. 1 Car d Reader s
2. 4. 5. 1. 1 Cont act l ess Car d Reader s
2. 4. 5. 1. 2 Car d Reader Di spl ay
2. 4. 5. 1. 3 Car d Reader Response Ti me
2. 4. 5. 1. 4 Car d Reader Power
2. 4. 5. 1. 5 Car d Reader Mount i ng Met hod
2. 4. 5. 2 Access Cont r ol Car ds
2. 4. 5. 2. 1 Cr edent i al Car d Modi f i cat i on
2. 4. 5. 2. 2 Car d Si ze and Di mensi onal St abi l i t y
2. 4. 5. 2. 3 Car d Mat er i al s and Physi cal Char act er i st i cs
2. 4. 5. 2. 4 Car d Const r uct i on
SECTI ON 28 10 05 Page 2
2. 4. 5. 2. 5 Car d Dur abi l i t y and Mai nt ai nabi l i t y
2. 4. 5. 2. 6 War r ant y
2. 4. 5. 3 Por t al Cont r ol Devi ces
2. 5 CLOSED- CI RCUI T TELEVI SI ON ( CCTV) SYSTEM
2. 5. 1 Camer as
2. 5. 1. 1 CCTV Camer a
2. 5. 1. 1. 1 Sensi t i v i t y
2. 5. 1. 1. 2 Si gnal - To- Noi se Rat i o
2. 5. 1. 1. 3 Resol ut i on
2. 5. 1. 1. 4 Low Li ght Level
2. 5. 1. 2 Camer a Lenses
2. 5. 1. 3 I nt er i or Camer a
2. 5. 1. 4 Ext er i or Fi xed Posi t i on Camer a
2. 5. 1. 5 180 Degr ee Camer a
2. 5. 1. 6 360 Degr ee Camer a
2. 5. 1. 7 Camer a Housi ng and Mount s
2. 5. 1. 7. 1 I ndoor Camer a Housi ng
2. 5. 1. 7. 2 I nt er i or Mount
2. 5. 1. 7. 3 Low Pr of i l e Cei l i ng Mount
2. 5. 1. 7. 4 I nt er i or Dome Housi ng
2. 5. 1. 7. 5 Ext er i or Dome Housi ng
2. 5. 1. 7. 6 Ext er i or Wal l Mount
2. 5. 1. 7. 7 Expl osi on Pr oof Housi ng
2. 5. 2 Vi deo Anal yt i cs ( VA)
2. 5. 2. 1 Sof t war e
2. 5. 2. 1. 1 Basi c Mot i on Det ect i on
2. 5. 2. 2 Embedded VA
2. 5. 2. 2. 1 I nt el l i gent Vi deo Anal ysi s
2. 5. 3 Col or Vi deo Moni t or s
2. 5. 3. 1 Mount i ng and I dent i f i cat i on
2. 5. 4 Anci l l ar y Equi pment
2. 5. 4. 1 Vi deo Dat e and Ti me Gener at or
2. 5. 4. 2 Camer a I dent i f i er s
2. 5. 4. 3 Vi deo Recor di ng
2. 5. 4. 3. 1 I P Based Vi deo Recor di ng Devi ce/ Syst em
2. 5. 4. 3. 2 Vi deo Recor di ng Per f or mance
2. 5. 4. 4 Camer a Cont r ol
2. 5. 5 Camer a Mount i ng St r uct ur es
2. 6 Net wor k Equi pment
2. 7 Dat a Out l et s
2. 8 Ser ver Har dwar e
2. 9 Wor kst at i on Har dwar e
2. 10 Col or Vi deo Moni t or s
2. 10. 1 Rack Mount Moni t or - 17 i nch LED
2. 10. 2 Mount i ng and I dent i f i cat i on
2. 11 Pr i nt er s
2. 11. 1 Repor t Pr i nt er
2. 11. 2 Al ar m Pr i nt er
2. 11. 3 Badge Pr i nt er
2. 12 Enr ol l ment Cent er
2. 12. 1 Enr ol l ment Cent er Equi pment
2. 12. 1. 1 Enr ol l ment Cent er I . D. Pr oduct i on
2. 12. 1. 2 Enr ol l ment Cent er Sof t war e
2. 13 COMMUNI CATI ONS
2. 13. 1 Li nk Super vi s i on
2. 13. 1. 1 Har dwi r e Di r ect Cur r ent Li ne Super vi s i on
2. 13. 1. 2 Har dwi r e Di gi t al Super vi s i on
2. 13. 2 Har dwi r e
2. 13. 2. 1 El ect r i cal Conduct or Li nes
SECTI ON 28 10 05 Page 3
2. 13. 2. 2 Communi cat i on Li nk
2. 13. 3 Dat a Encr ypt i on
2. 13. 4 Net wor k Swi t ch
2. 13. 4. 1 I nsi de Pl ant
2. 13. 5 Vi deo and ESS Tr ansmi ssi on
2. 13. 6 Fi ber Opt i c Tr anscei ver
2. 13. 6. 1 Ext er i or POE Mi dspan
2. 13. 7 Wi r e and Cabl e
2. 13. 8 Di gi t al Dat a I nt er connect i on Wi r i ng
2. 13. 9 Abovegr ound Sensor Wi r i ng
2. 13. 10 Di r ect Bur i al Sensor Wi r i ng
2. 13. 11 Local Ar ea Net wor k ( LAN) Cabl i ng
2. 13. 12 Fi ber Opt i c Cabl e
2. 13. 13 Cabl e Const r uct i on
2. 14 BACKUP POWER
2. 14. 1 Uni nt er r upt i bl e Power Suppl y ( UPS)
2. 14. 2 Power Suppl i es
2. 14. 3 Bat t er i es
2. 15 SURGE SUPPRESSI ON DEVI CES
2. 16 COMPONENT ENCLOSURE
2. 16. 1 I nt er i or Sensor
2. 16. 2 Ext er i or Sensor
2. 16. 3 I nt er i or Encl osur es
2. 16. 4 Exposed- t o- Weat her Encl osur es
2. 16. 5 Cor r osi on- Resi st ant Encl osur es
2. 16. 6 Hazar dous Envi r onment Equi pment
2. 16. 7 Met al Thi ckness
2. 16. 8 Door s and Cover s
2. 16. 9 Vent i l at i on
2. 16. 10 Mount i ng
2. 16. 11 Label s
2. 16. 12 Test Poi nt s
2. 17 EQUI PMENT RACK
2. 17. 1 Label s
2. 18 LOCKS AND KEY LOCK
2. 18. 1 Lock
2. 18. 2 Key- Lock Oper at ed Swi t ches
2. 18. 3 Const r uct i on Locks
2. 19 FI ELD FABRI CATED NAMEPLATES
2. 19. 1 Manuf act ur er ' s Namepl at e
2. 20 FACTORY APPLI ED FI NI SH
PART 3 EXECUTI ON
3. 1 I NSTALLATI ON
3. 1. 1 Penet r at i ons and Fi r est oppi ng
3. 1. 1. 1 Concr et e Bases
3. 1. 1. 2 Cut t i ng and Pat chi ng
3. 1. 2 Sof t war e I nst al l at i on
3. 1. 3 Encl osur e Penet r at i ons
3. 1. 4 Cabl e and Wi r e Runs
3. 1. 5 Sol der i ng
3. 1. 6 Gal vani z i ng
3. 1. 7 Condui t s
3. 1. 8 Under gr ound Cabl e I nst al l at i on
3. 1. 9 Fi el d Appl i ed Pai nt i ng
3. 2 ADJUSTMENT, ALI GNMENT, SYNCHRONI ZATI ON, AND CLEANI NG
3. 3 SYSTEM STARTUP
3. 4 SUPPLEMENTAL CONTRACTOR QUALI TY CONTROL
SECTI ON 28 10 05 Page 4
3. 5 ESS SYSTEM TESTI NG
3. 6 ESS TRAI NI NG
3. 6. 1 ESS Tr ai ni ng Out l i ne
3. 6. 2 Typi cal Tr ai ni ng Day
3. 6. 3 ESS Admi ni st r at or Tr ai ni ng
3. 6. 4 ESS Oper at or Tr ai ni ng
3. 6. 5 Mai nt enance Per sonnel Tr ai ni ng
3. 6. 6 Fol l ow- up Tr ai ni ng
3. 7 NAMEPLATE MOUNTI NG
- - End of Sect i on Tabl e of Cont ent s - -
SECTI ON 28 10 05 Page 5
SECTI ON 28 10 05
ELECTRONI C SECURI TY SYSTEMS ( ESS)
05/ 16
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ASC/ X9 X9. 52 ( 1998) Tr i pl e Dat a Encr ypt i on Al gor i t hm Modes of Oper at i on
ASTM I NTERNATI ONAL ( ASTM)
ASTM A123/ A123M ( 2017) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s
ASTM B32 ( 2020) St andar d Speci f i cat i on f or Sol der Met al
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 802. 3 ( 2018) Et her net
I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code
I NTERNATI ONAL ORGANI ZATI ON FOR STANDARDI ZATI ON ( I SO)
ANSI I SO/ I EC 7816 ( R 2009) I dent i f i cat i on Car ds - I nt egr at ed Ci r cui t Car ds
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA 250 ( 2020) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NEMA I CS 1 ( 2000; R 2015) St andar d f or I ndust r i al Cont r ol and Syst ems: Gener al Requi r ement s
NEMA I CS 2 ( 2000; R 2020) I ndust r i al Cont r ol and Syst ems Cont r ol l er s, Cont act or s, and Over l oad Rel ays Rat ed 600 V
NEMA I CS 6 ( 1993; R 2016) I ndust r i al Cont r ol and Syst ems: Encl osur es
SECTI ON 28 10 05 Page 6
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2020; TI A 22- 1; ERTA 1 2022) Nat i onal El ect r i cal Code
NATI ONAL I NSTI TUTE OF STANDARDS AND TECHNOLOGY ( NI ST)
NI ST FI PS 140- 2 ( 2001) Secur i t y Requi r ement s f or Cr ypt ogr aphi c Modul es
NI ST FI PS 197 ( 2001) Advance Encr ypt i on St andar d
NI ST FI PS 201- 2 ( 2013) Per sonal I dent i t y Ver i f i cat i on ( PI V) of Feder al Empl oyees and Cont r act or s
OPEN NETWORK VI DEO I NTERFACE FORUM ( ONVI F)
ONVI F ( 2017) Cor e Speci f i cat i on Ver si on 17. 06
TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)
TI A- 222 ( 2018H; Add 1 2019) St r uct ur al St andar d f or Ant enna Suppor t i ng St r uct ur es and Ant ennas and Smal l Wi nd Tur bi ne Suppor t St r uct ur es
TI A- 568. 2 ( 2018d) Bal anced Twi st ed- Pai r Tel ecommuni cat i ons Cabl i ng and Component s St andar ds
TI A- 606 ( 2021d) Admi ni st r at i on St andar d f or Tel ecommuni cat i ons I nf r ast r uct ur e
U. S. DEPARTMENT OF DEFENSE ( DOD)
DODI 8500. 01 ( 2014) Cyber secur i t y
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
47 CFR 15 Radi o Fr equency Devi ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 50 ( 2015) UL St andar d f or Saf et y Encl osur es f or El ect r i cal Equi pment , Non- Envi r onment al Consi der at i ons
UL 294 ( 2018; Repr i nt Oct 2018) UL St andar d f or Saf et y Access Cont r ol Syst em Uni t s
UL 437 ( 2013; Repr i nt Oct 2017) UL St andar d f or Saf et y Key Locks
UL 497B ( 2004; Repr i nt Feb 2022) UL St andar d f or Saf et y Pr ot ect or s f or Dat a Communi cat i ons and Fi r e Al ar m Ci r cui t s
UL 634 ( 2007; Repr i nt Mar 2015) Connect or s and
SECTI ON 28 10 05 Page 7
Swi t ches f or Use wi t h Bur gl ar - Al ar m Syst ems
UL 639 ( 2007; Repr i nt Nov 2019) St andar d f or I nt r usi on Det ect i on Uni t s
UL 681 ( 2014; Repr i nt Jan 2021) UL St andar d f or Saf et y I nst al l at i on and Cl assi f i cat i on of Bur gl ar and Hol dup Al ar m Syst ems
UL 796 ( 2020; Repr i nt Aug 2021) UL St andar d f or Saf et y Pr i nt ed- Wi r i ng Boar ds
UL 969 ( 2017; Repr i nt Mar 2018) UL St andar d f or Saf et y Mar ki ng and Label i ng Syst ems
UL 1037 ( 2016; Repr i nt Sep 2017) UL St andar d f or Saf et y Ant i t hef t Al ar ms and Devi ces
UL 1076 ( 2018; Repr i nt Feb 2021) UL St andar d f or Saf et y Pr opr i et ar y Bur gl ar Al ar m Uni t s and Syst ems
UL 1449 ( 2021) UL St andar d f or Saf et y Sur ge Pr ot ect i ve Devi ces
UL 1610 ( 2016; Repr i nt Apr 2021) UL St andar d f or Saf et y Cent r al - St at i on Bur gl ar - Al ar m Uni t s
[ * Am- 7]
U. S. DEPARTMENT OF AGRI CULTURE ( USDA)
4620- 002 ( 2021) Common I dent i f i cat i on St andar d f or U. S. Depar t ment of Agr i cul t ur e ( USDA)
[ * * Am- 7]
1. 2 Wor k I ncl udes
a. Pr ovi de an Access Cont r ol Syst em ( ACS) wher e i ndi cat ed on t he dr awi ngs. The ACS must be [ * Am- 7] f ul l y compat i bl e wi t h t he USDA Depar t ment al Manual " 4620- 002 Common I dent i f i cat i on St andar d" ( see At t achment 28 10 05A) [ * * Am- 7] . The ACS must be host ed at USDA Dat a Cent er , handl ed by EPACS EMO st af f , and moni t or ed l ocal l y at c l i ent wor kst at i ons i ndi cat ed on t he dr awi ngs t hr ough a dedi cat ed secur i t y et her net net wor k. Pr ovi de a badgi ng st at i on wi t h camer a and badgi ng pr i nt er per i pher al s wher e i ndi cat ed on t he dr awi ngs.
b. I nt r usi on Det ect i on Syst em ( I DS) : Pr ovi de a separ at e I DS f or t he Admi ni st r at i on Bui l di ng. I nt er f ace t he I DS Pr emi se Cont r ol Uni t ( PCU) t o t he ACS syst em f or l ocal moni t or i ng, and pr ovi de i nt er f ace f or r emot e moni t or i ng at t he t hi r d par t y moni t or i ng st at i on.
1. I nt er f ace Hi gh Secur i t y Swi t ches ( HSS) and gl ass br eak det ect or s t o bot h t he ACS and I DS syst ems.
c. Vi deo Sur vei l l ance
1. Pr ovi de a compl et e Vi deo Sur vei l l ance Syst em ( VSS) i n t he
SECTI ON 28 10 05 Page 8
Admi ni st r at i on and Lab Bui l di ng, moni t or ed and r ecor ded on- si t e, communi cat i ng t hr ough a dedi cat ed secur i t y et her net net wor k.
2. Pr ovi de a VSS i n al l ani mal r el at ed bui l di ngs. Vi deo camer as wi l l be i nt er f aced t o t he USDA net wor k, moni t or ed f r om wor kst at i ons i n t he Admi ni st r at i on bui l di ng, l ocat i ons i ndi cat ed on t he dr awi ngs, Pr ovi de a head end f or cent r al i zed moni t or i ng. Whi l e i t i s accept abl e t o pr ovi de an NVR sol ut i on t o moni t or v i deo i n ani mal bui l di ngs, v i deo i s not r equi r ed t o be r ecor ded and must be di sabl ed.
1. 3 DESI GN REQUI REMENTS
Pr ovi de al l r el at ed devi ces, equi pment , associ at ed har dwar e, sof t war e, appur t enances, connect i ons, devi ces, power suppl i es, t r ansf or mer s, panel boar ds, c i r cui t br eaker s, wi r i ng/ cabl i ng, condui t , backboxes, f i t t i ngs and pr ogr ammi ng necessar y t o compl et e t he wor k as a compl et e and f ul l y oper at i onal syst em. Fur ni sh and i nst al l al l of t he above mat er i al i n accor dance wi t h t he manuf act ur er s wr i t t en r ecommendat i ons and i n compl i ance wi t h Di v i s i on 26 and t he NEC.
Mount equi pment pl umb, l evel , squar e and secur e.
Ref er t o t hi s Sect i on, and Sect i on 25 05 11. 03 f or Cyber secur i t y r equi r ement s.
Cover s must be secur ed wi t h t amper r esi st ant har dwar e such as one way scr ews or t or x wi t h peg f ast ener s at l ocat i ons wher e j unct i on boxes or f i t t i ngs woul d pr ovi de access. Ti ght en har dwar e t o manuf act ur er ' s speci f i cat i ons.
Al l equi pment , devi ces, cabl e, connect or s, t er mi nal st r i ps, or ot her i t ems i ncl uded i n t he Di v i s i on 28 Ser i es Speci f i cat i ons shal l be secur ed t o t he mount i ng sur f ace, and f ast ened wi t h har dwar e appr oved by t he manuf act ur er and capabl e of suppor t i ng 4 t i mes t he r at ed l oad. Mount i ng by use of gl ue, Vel cr o, t ape or ot her adhesi ves i s unaccept abl e. Al l cabl es wi t hi n encl osur es shal l be neat l y r out ed and t i e wr apped at 6 I N on cent er .
1. 3. 1 Cabl es
a. I nst al l cabl e usi ng met hods t hat wi l l ensur e t hat t he el ect r i cal and physi cal pr oper t i es wi l l not be compr omi sed and physi cal and el ect r i cal i nt er f er ence wi t h not be i nduced f r om ot her cabl es or equi pment .
b. Secur i t y conduct or s shal l be mi ni mum 22 AWG unl ess ot her wi se not ed.
Si ze conduct or s i n accor dance wi t h t he equi pment manuf act ur er ' s r ecommendat i ons and wi t h NEC and t o ensur e pr oper oper at i on and al ar m not i f i cat i ons.
c. Mi ni mum 18- gauge wi r e, shal l be ut i l i zed f or cont r ol of el ect r i cal and mot or i zed door s and gat es. Si ze cabl e f or pr oper oper at i on based on el ect r i cal l oad and di st ance.
d. Al l cabl i ng shal l be UL l i s t ed. The UL l i s t i ng shal l be l abel ed on t he j acket .
e. Al l wi r e or cabl es t hat ar e t o be i nst al l ed i n duct s, pl enum, or ot her ai r handl i ng spaces shal l be appr oved pl enum t ype cabl e. Pl enum cabl e
SECTI ON 28 10 05 Page 9 shal l be an appr oved t ype under NEC 725 2( b) and by UL as a Cl ass 2 power l i mi t ed c i r cui t cabl e.
f . Net wor k cabl e r uns shal l not exceed 295 FT, and t he sum of al l pat ch cor ds and cr oss connect i on wi r i ng shal l not exceed 32 FT.
g. Al l spl i ces shal l be j oi ned wi t h sol der heat shr i nk s l eeve connect or s.
Each i ndi v i dual sol der j oi nt shal l be encased usi ng heat shr i nk t ubi ng wi t h i nsul at i on pr oper t i es equi val ent t o t he conduct or i nsul at i on.
Cabl e shal l be secur ed by t wi st i ng t he copper conduct or s pr i or t o sol der i ng t he connect i on. Use of wi r e nut s or ot her cr i mp t ype connect or s ar e unaccept abl e.
h. Pat ch Cor ds shal l be UL 3992- A l i s t ed.
i . Spl i ces i n hand hol es ar e unaccept abl e.
1. 3. 2 Condui t Requi r ement s
a. Ri gi d met al condui t ( RMC) or I nt er medi at e Met al Condui t ( I MC) shal l be used i n exposed ext er i or appl i cat i ons.
b. EMT condui t wi t h compr essi on f i t t i ngs may be ut i l i zed i n al l i nt er i or i naccessi bl e ar eas i n Admi ni st r at i on and Lab bui l di ng unl ess ot her wi se r equi r ed by code.
c. Ri gi d PVC Schedul e 40 condui t encased i n concr et e shal l be ut i l i zed i n al l under gr ound appl i cat i ons. The condui t shal l be bur i ed at a mi ni mum 3 FT bel ow gr ade. War ni ng f l aggi ng t ape shal l be bur i ed 1 FT bel ow gr ade t o i ndi cat e t he condui t r out i ng l ocat i on. Ri gi d St eel condui t ( RGS) shal l be ut i l i zed on al l st ub- ups. The Secur i t y Cont r act or shal l have t he opt i on t o ut i l i ze t he same t r ench/ r out i ng l ocat i on as ot her ut i l i t i es. I n no case shal l t he secur i t y condui t or duct bank be combi ned wi t h ot her el ect r i cal ut i l i t i es. The Secur i t y Cont r act or shal l pr ovi de handhol es as r equi r ed, dedi cat ed f or secur i t y cabl e. Pr ovi de dr ai nage t o al l under gr ound handhol es as speci f i ed i n Di v i s i on 26 and 33. Spl i ces i n hand hol es ar e unaccept abl e.
d. Ri gi d met al condui t ( RMC) or I nt er medi at e Met al Condui t ( I MC) shal l be used i n al l i nt er i or accessi bl e ar eas wher e conceal ed condui t r equi r ement s cannot be met , as wel l as ut i l i t y and communi cat i ons r ooms. Submi t dr awi ngs, di agr ams and i nf or mat i on t o Gover nment ' s Repr esent at i ve and Ar chi t ect f or r evi ew pr i or t o wor k.
e. Cor r osi on r esi st ant condui t shal l be pr ovi ded i n cor r osi ve envi r onment s. Condui t shal l meet ETL PVC- 001, NEMA RN- 1 and UL 1203 r equi r ement s.
f . Pr ovi de si ngl e or t wo hol e condui t st r aps t o f ast en condui t agai nst wal l . Use of condui t hanger s on ver t i cal sur f aces i s unaccept abl e.
1. 3. 3 Backbox / Junct i on Box
a. Al l backboxes shal l be f l ush mount ed unl ess not ed ot her wi se.
b. Met al ' FS' t ype backboxes and j unct i on boxes shal l be used i n al l accessi bl e ar eas wher e conceal ed box r equi r ement s cannot be met .
St amped met al boxes ar e not accept abl e. Mount i ng hol es wi t hi n t he box shal l be ut i l i zed t o accommodat e mount i ng har dwar e. Mount i ng t he box
SECTI ON 28 10 05 Page 10 usi ng ext er nal mount i ng t abs i s not accept abl e. Submi t dr awi ngs, di agr ams and i nf or mat i on t o Gover nment ' s Repr esent at i ve and Ar chi t ect f or r evi ew pr i or t o wor k.
c. Pr ovi de weat her pr oof backboxes and j unct i on boxes i n ext er i or , uncondi t i oned spaces, or l ocat i ons exposed t o t he el ement s.
d. Pr ovi de secur i t y dat a out l et s at wor kst at i on l ocat i ons. Out l et s shal l compl y wi t h r equi r ement s of Sect i on 27 10 00.
1. 3. 4 Door Har dwar e and Door Har dwar e Power Suppl i es
a. Revi ew t he Di vi s i on 08 Door Har dwar e Sect i on t o i ncl ude t he Door Har dwar e Schedul e and not e al l el ect r oni c door har dwar e devi ces per door l ocat i on. Have a f ul l under st andi ng of t he i nt er f ace r equi r ement s of each t ype devi ce, and shal l pr ovi de t he cor r ect number of conduct or s t o each door har dwar e devi ce t o pr ovi de oper at i ons and f unct i onal i t y as speci f i ed i n t he Di v i s i on 28 Sect i ons.
b. I nst al l and t er mi nat e al l secur i t y c i r cui t s t o t he door har dwar e suppl i ed and i nst al l ed by Di v i s i on 08. Coor di nat e wi t h t he Di v i s i on 08 cont r act or t he i nst al l at i on and t er mi nat i on of al l cabl i ng and secur i t y devi ces.
c. Cabl i ng f or door har dwar e shal l be s i zed t o ensur e t hat t he devi ce i s oper abl e when power ed by power suppl i es i n t he secur i t y equi pment r oom.
d. Pr ovi de power suppl i es suf f i c i ent t o power al l l ow vol t age har dwar e.
I t i s accept abl e t o power door s f r om one power suppl y, pr ovi ded t hat t he cur r ent r at i ngs ar e not exceeded.
e. Pr ovi de pr ot ect i on devi ces wi t h bui l t - i n sur ge pr ot ect i on and vol t age r egul at i on at each el ect r i c har dwar e devi ce t o pr ot ect t he r el ays and sensi t i ve el ect r oni cs of t he syst em f r om t he el ect r i cal spi ke t hat occur s when el ect r i c har dwar e l ocks or unl ocks.
1. 3. 5 I nt egr at ed Door Har dwar e Request t o Exi t Swi t ch I nt er f ace
a. I nt er f ace t o t he r equest t o exi t swi t ches t hat ar e i nt egr al t o t he door har dwar e. Oper at i ng t he handl e/ l ever on t he egr ess s i de of t he door , or pushi ng t he pani c bar shal l aut omat i cal l y shunt t he door posi t i on swi t ch f or a per i od of t i me as coor di nat ed wi t h t he Gover nment
b. Pr ovi de r equest t o exi t mot i on det ect or s at door l ocat i ons wher e i nt egr al r equest t o exi t swi t ches ar e not pr ovi ded t o per f or m t he same shunt f unct i on as descr i bed above.
1. 3. 6 Li f e Saf et y Coor di nat i on
a. Coor di nat e t he i nt er f ace t o l i f e saf et y wi t h t he appr opr i at e t r ade.
El ect r oni c l ocks or ot her bar r i er s shal l not i nhi bi t egr ess i n t he event of an emer gency. I nt er f ace el ect r i cal l y l ocked equi pment i n t he emer gency pat h of egr ess t o t he f i r e al ar m syst em f or aut omat i c r el ease upon act i vat i on of f i r e al ar m. Pr ovi de auxi l i ar y exi t but t on as r equi r ed by code t o r el ease t he door i n t he event of equi pment f ai l ur e by t he pr i mar y means of door r el ease. The but t on shal l pr ovi de a t i me del ay t o r el ease t he door f or a t i me per i od as det er mi ned t he Aut hor i t y Havi ng Jur i sdi ct i on ( AHJ) and appl i cabl e l i f e saf et y codes.
The pushbut t on shal l al so be conf i gur ed t o al l ow di r ect r el ease of t he
SECTI ON 28 10 05 Page 11 door l ock whi l e t he but t on i s pr essed t o ensur e r el ease i n t he event of f ai l ur e of t he pushbut t on el ect r oni cs. The Secur i t y Cont r act or i s r esponsi bl e f or al l condui t , cabl e and connect i ons t o f i r e al ar m equi pment l ocat i on f or door r el ease.
b. Pr ovi de t he i nt er f ace t o t he bui l di ng f i r e al ar m syst em as r equi r ed i n accor dance wi t h al l appl i cabl e l i f e saf et y codes and coor di nat e wi t h t he f i r e al ar m syst em pr ovi der f or al l r equi r ed syst em i nt egr at i on r equi r ement s. I nt er f ace t he f i r e al ar m connect i ons di r ect l y t o t he l ock or power suppl y power i ng t he door . I nt er f ace t hr ough t he secur i t y syst em i s not accept abl e.
1. 3. 7 Ar chi t ect ur al Bar r i er s Act ( ABA) Ent r ances
a. I nt er f ace t o el ect r i c l ocks and aut omat i c door openi ng equi pment at handi capped access l ocat i ons. Pr esent at i on of a val i d car d shal l unl ock t he door , and enabl e t he door open but t on. The car d hol der shal l t hen have t he opt i on t o pr ess t he door open but t on, or manual l y open t he door . The car d access syst em shal l not di sabl e t he egr ess door - open but t on.
1. 4 PERFORMANCE REQUI REMENTS
1. 4. 1 Car d Reader Locat i ons
Pr esent i ng a val i d car d on t he secur e s i de of a car d r eader l ocat i on wi l l moment ar i l y unl ock t he door , as wel l as moment ar i l y shunt t he Hi gh Secur i t y Swi t ch ( HSS) . Act i vat i ng t he i nt egr al Request t o Exi t ( REX) devi ce on t he door har dwar e at t he egr ess s i de wi l l al so moment ar i l y shunt t he HSS.
1. 4. 2 Hi gh Secur i t y Swi t ch ( HSS) Locat i ons
HSS wi l l r emai n secur e at al l t i mes. Openi ng t he door wi l l cause an al ar m at t he secur i t y moni t or i ng st at i on
1. 4. 3 Aut omat i c Door Ent r ances
I nt er f ace t o el ect r i c l ocks and aut omat i c door openi ng equi pment at mot or i zed access l ocat i ons. Pr esent at i on of a val i d car d shal l unl ock t he door , and enabl e t he door open but t on. The car d hol der shal l t hen have t he opt i on t o pr ess t he door open but t on, or manual l y open t he door . The car d access syst em shal l not di sabl e t he egr ess door - open but t on.
1. 5 COORDI NATI ON
a. Coor di nat e ar r angement , mount i ng, and suppor t of el ect r oni c saf et y and secur i t y equi pment :
1. To al l ow maxi mum possi bl e headr oom unl ess speci f i c mount i ng hei ght s t hat r educe headr oom ar e i ndi cat ed.
2. To pr ovi de f or ease of di sconnect i ng t he equi pment wi t h mi ni mum i nt er f er ence t o ot her i nst al l at i ons.
3. To al l ow r i ght of way f or pi pi ng and condui t i nst al l ed at r equi r ed sl ope.
4. So connect i ng r aceways, cabl es, wi r eways, cabl e t r ays, and busways
SECTI ON 28 10 05 Page 12 wi l l be c l ear of obst r uct i ons and of t he wor ki ng and access space of ot her equi pment .
b. I f i nst al l at i on of equi pment , r aceways, cabl e t r ays and/ or condui t i s per f or med pr i or t o coor di nat i on wi t h ot her t r ades, whi ch i nt er f er es wi t h wor k of ot her t r ades, make necessar y changes t o cor r ect t he condi t i on at no addi t i onal cost t o t he Gover nment .
c. Coor di nat e any condui t r out i ng, t he i nst al l at i on of el ect r i cal boxes, pul l boxes, r ough- i ns of equi pment , ser vi ces and/ or cont r ol s t o i t ems by ot her s.
d. Coor di nat e r equi r ement s wi t h Di v i s i on 31 f or Excavat i on, Tr enchi ng and Backf i l l i ng.
e. Coor di nat e chases, s l ot s, i nser t s, s l eeves, condui t r out i ng, and openi ngs wi t h gener al const r uct i on wor k and ar r ange i n bui l di ng st r uct ur e dur i ng pr ogr ess of const r uct i on t o f aci l i t at e t he secur i t y el ect r oni cs i nst al l at i ons t hat f ol l ow.
f . Set i nser t s and sl eeves i n pour ed- i n- pl ace concr et e, masonr y wor k, and ot her st r uct ur al component s as t hey ar e const r uct ed.
g. Sequence, coor di nat e, and i nt egr at e i nst al l i ng secur i t y el ect r oni cs mat er i al s and equi pment f or ef f i c i ent f l ow of t he Wor k and a compl et el y oper at i onal syst em.
h. Coor di nat e el ect r oni c secur i t y wor k wi t h t hat of ot her sect i ons as r equi r ed ensur i ng t hat t he ent i r e el ect r oni c secur i t y wor k wi l l be car r i ed out i n an or der l y, compl et e and coor di nat ed f ashi on.
i . Coor di nat e el ect r i cal connect i ons t o secur i t y equi pment wi t h Di v i s i on 26.
j . Coor di nat e wi t h Di v i s i on 26, al l condui t r equi r ement s f or t he ESS as out l i ned i n t hi s Sect i on. Coor di nat e s i zes of condui t and r out i ng f or secur i t y equi pment wi t h Di v i s i on 26.
k. Coor di nat e l ocat i on of access panel s and door s f or secur i t y el ect r oni cs i t ems t hat ar e conceal ed by f i ni shed sur f aces. Access door s and panel s ar e speci f i ed i n Sect i on 08 31 00 " Access Door s and Panel s" .
l . Compl y wi t h r equi r ement s Di v i s i on 03 f or equi pment concr et e bases and pads.
m. For equi pment mount i ng r equi r i ng coor di nat i on wi t h ot her t r ades, obt ai n t empl at es and equi pment anchor bol t s f or mount i ng pr epar at i on,
e. g. pedest al s or ot her devi ces r equi r i ng mount i ng on concr et e pads, wal l s or ot her sur f aces. Coor di nat e del i ver y of t empl at es and equi pment anchor bol t s t o af f ect ed t r ade( s) t o pr ecl ude any del ay i n t he const r uct i on schedul e or t he wor k of t he af f ect ed t r ade.
n. Coor di nat e del i ver y of encl osur es wi t h ot her Sect i ons of t hi s Pr oj ect Manual t o f aci l i t at e mount i ng, t er mi nat i ons of condui t s, and pul l i ng of cabl es/ conduct or s t o t he encl osur e, and t o pr ecl ude any del ay i n t he const r uct i on schedul e or t he Wor k of af f ect ed t r ades.
o. Because of t he dr awi ng scal e, symbol s ar e shown as c l ose as possi bl e
SECTI ON 28 10 05 Page 13 t o t he mount i ng l ocat i on. Ver i f y exact l ocat i ons wi t h t he Gover nment ' s Repr esent at i ve, Ar chi t ect , and wor k of ot her t r ades t o ensur e t hat t he devi ce i s not obst r uct ed, or l ocat ed i n pr oxi mi t y t o equi pment t hat may i nt er f er e or degr ade t he oper at i on or per f or mance.
Not i f y t he Gover nment ' s Repr esent at i ve and Ar chi t ect of pot ent i al i nt er f er ence pr i or t o i nst al l at i on.
p. Coor di nat e wi t h t he Gover nment ' s Repr esent at i ve t he exact pl acement of camer as and l ens t ype, and demonst r at e v i deo at each l ocat i on t o ensur e pr oper v i deo cover age as accept abl e t o t he Gover nment pr i or t o i nst al l at i on of camer a. Tempor ar i l y power and i nt er f ace each camer a t o a t empor ar y, por t abl e CCTV moni t or . Demonst r at e v i ew t o t he Gover nment ' s Repr esent at i ve at each camer a l ocat i on. Rel ocat e camer a and ut i l i ze pr oper l ens i f necessar y t o obt ai n desi r ed vi ew t hat i s accept abl e t o t he Gover nment pr i or t o f i nal i nst al l at i on.
q. Cooper at e wi t h ot her t r ades t o i ncl ude, but not l i mi t ed t o el ect r i cal , mechani cal , concr et e, masonr y, cabi net r y door s, f r ames, har dwar e, f i r e al ar m, l i f e saf et y, pai nt i ng and si t e ut i l i t i es f or a pr oper l y coor di nat ed i nst al l at i on. For esee conf l i c t s wi t h wor k of ot her t r ades and adj ust wor k as necessar y t o accommodat e equi pment of ot her t r ades and pr eser ve opt i mal oper at i on and aest het i cs. Not i f y t he Gover nment and Ar chi t ect i n wr i t i ng of any conf l i c t s t hat wi l l af f ect t he accessi bi l i t y , ef f ect i veness or per f or mance of t he equi pment .
Coor di nat e al l wor k, schedul i ng and access t o t he pr oj ect s i t e wi t h t he Gener al Cont r act or .
r . Ver i f y and coor di nat e wi t h t he appr opr i at e door har dwar e t r ade t o ensur e t hat t he cont r ol / moni t or i ng equi pment i s compat i bl e t o oper at e t he door har dwar e equi pment as out l i ned i n t he Di v i s i on 28 ser i es sect i ons. Repor t i n wr i t i ng t o t he Gover nment and Ar chi t ect al l di scr epanci es t hat wi l l af f ect t he oper at i on of t he equi pment .
1. 6 SUBMI TTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . When used, a code f ol l owi ng t he " G" c l assi f i cat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " AE" ar e f or Ar chi t ect / Engi neer r evi ew. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00
SUBMI TTAL PROCEDURES:
The AE wi l l r evi ew and t he Gover nment wi l l appr ove submi t t al s r equi r i ng speci al r evi ew i n t hi s sect i on.
SD- 02 Shop Dr awi ngs
ESS Component s; G, AE
Over al l Syst em Schemat i c; G, AE
SD- 03 Pr oduct Dat a
Pr emi se Cont r ol Uni t ; G, AE
Det ect i on Sensor s; G, AE
Access Cont r ol Uni t ; G, AE
SECTI ON 28 10 05 Page 14
Access Cont r ol Devi ces; G, AE
Camer as; G, AE
Camer a Lenses; G, AE
Camer a Housi ng and Mount s; G, AE
Vi deo Recor di ng; G, AE
Pr i nt er s; G, AE
Communi cat i ons I nt er f ace Devi ces; G, AE
Net wor k Swi t ch; G, AE
Vi deo and ESS Tr ansmi ssi on; G, AE
Uni nt er r upt i bl e Power Suppl y ( UPS) ; G, AE
Bat t er i es; G, AE
Component Encl osur e; G, AE
Equi pment Rack; G, AE
Fi ber Opt i c Tr anscei ver ; G, AE
Ext er i or POE Mi dspan; G, AE
SD- 05 Desi gn Dat a
Backup Bat t er y Capaci t y Cal cul at i ons; G, AE
Access Cont r ol Thr oughput Rat es; G, AE
CCTV St or age Cal cul at i ons; G, AE
SD- 07 Cer t i f i cat es
Cont r act or Qual i f i cat i ons; G, AE
I nst r uct or Qual i f i cat i ons; G, AE
Dat a Encr ypt i on; G, AE
SD- 10 Oper at i on and Mai nt enance Dat a
Tr ai ni ng Pl an; G, RO
Tr ai ni ng Cont ent ; G, RO
ESS Component s: Dat a Package 4; G, RO
Submi t dat a package i n accor dance wi t h Sect i on 01 78 23
OPERATI ON AND MAI NTENANCE DATA
SD- 11 Cl oseout Submi t t al s
SECTI ON 28 10 05 Page 15
As- Bui l t Dr awi ngs; G, AE
1. 7 QUALI TY ASSURANCE
1. 7. 1 Regul at or y Requi r ement s
The advi sor y pr ovi s i ons i n each of t he publ i cat i ons r ef er r ed t o i n t hi s speci f i cat i on ar e mandat or y. I nt er pr et t hese publ i cat i ons as t hough t he wor d " must " has been subst i t ut ed f or " shoul d" wher ever i t appear s.
I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer .
Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p must be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
Mount i ng hei ght s and accessi bi l i t y t o equi pment r equi r i ng access by i ndi v i dual s wi t h di sabi l i t i es shal l compl y wi t h Ar chi t ect ur al Bar r i er s Act ( ABA) accessi bi l i t y st andar ds.
1. 7. 2 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p and:
a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng, and have been ut i l i zed i n appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.
b. Have been avai l abl e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.
c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er .
d. Pr ovi de commer ci al of f - t he- shel f ( COTS) pr oduct s i n whi ch t he manuf act ur er al l ows a net wor k of qual i f i ed di st r i but or s t o sel l , i nst al l , i nt egr at e, mai nt ai n, and r epai r t he har dwar e and sof t war e pr oduct s t hat make up t he syst em.
1. 7. 2. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2 year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s f ur ni shed.
1. 7. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han one year pr i or t o dat e of del i ver y t o t he s i t e ar e not accept abl e.
1. 7. 2. 3 Pr oduct Saf et y
Syst em component s ar e t o conf or m t o appl i cabl e r ul es and r equi r ement s of
SECTI ON 28 10 05 Page 16
NFPA 70. Equi p syst em component s wi t h i nst r uct i on st i cker s i ncl udi ng war ni ngs and caut i ons descr i bi ng physi cal saf et y, and speci al or i mpor t ant pr ocedur es t o be f ol l owed i n oper at i ng and ser vi c i ng syst em equi pment .
1. 7. 3 Shop Dr awi ngs
1. 7. 3. 1 ESS Component s
Submi t t he ESS Component s, Dat a Package 4 wi t h t he ESS Sof t war e submi t t al package i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA. Submi t dr awi ngs t hat c l ear l y and compl et el y i ndi cat e each ESS component f unct i on t hat i ncl udes:
a. Ter mi nat i on devi ce poi nt s
b. I nt er connect i ons r equi r ed f or syst em oper at i on
c. I nt er connect i ons bet ween modul es and devi ces
d. Pr oposed wi r eway or condui t syst ems t o be used i ncl udi ng:
( 1) Locat i ons
( 2) Si zes
( 3) Types
e. Dr awi ngs showi ng:
( 1) Devi ce l ocat i ons and spaci ng
( 2) Mount i ng and posi t i oni ng det ai l s
( 3) Ri ser Di agr ams wi t h cabl e s i zes and t ypes
( 4) Bi l l of Mat er i al s ( Devi ce make, model and quant i t i es)
( 5) Al ar m and access cont r ol zones
( 6) CCTV and sensor cover age ar eas
( 7) Spar e capaci t y
1. 7. 3. 2 Over al l Syst em Schemat i c
I ndi cat e t he r el at i onshi p of i nt egr at ed component s on one- l i ne di agr am and show:
a. Power sour ce
b. Syst em cont r ol s
c. I mpedance mat ches
d. I nt er connect i ng wi r e dat a i ncl udi ng:
( 1) Number
( 2) Si ze
SECTI ON 28 10 05 Page 17
( 3) I dent i f i cat i on
( 4) Maxi mum l engt hs
1. 7. 4 Evi dence of Exper i ence and Qual i f i cat i ons
1. 7. 4. 1 Cont r act or Qual i f i cat i ons
Submi t exper i ence and cer t i f i ed qual i f i cat i ons dat a pr i or t o i nst al l at i on. Show t hat speci f i c i nst al l er s who wi l l per f or m t he wor k have a mi ni mum of 2 year s of exper i ence successf ul l y i nst al l i ng ESS of t he same t ype and si mi l ar desi gn as speci f i ed. I ncl ude t he names, l ocat i ons, and poi nt s of cont act of at l east t wo i nst al l at i ons of s i mi l ar t ype and desi gn as speci f i ed i n t hi s document wher e t he i nst al l er has i nst al l ed such syst ems. I ndi cat e t he t ype of each syst em i nst al l ed. Cer t i f y t hat each syst em has per f or med sat i sf act or i l y i n t he manner i nt ended f or a per i od of at l east 12 mont hs.
1. 7. 4. 2 I nst r uct or Qual i f i cat i ons
Submi t t he i nst r uct or ' s exper i ence and cer t i f i ed qual i f i cat i ons dat a pr i or t o i nst al l at i on. Show t hat t he i nst r uct or has r ecei ved a mi ni mum of 24 hour s of ESS t r ai ni ng f r om a t echni cal or gani zat i on such as t he Nat i onal Bur gl ar and Fi r e Al ar m Associ at i on, and 2 year s exper i ence i n i nst al l i ng t he speci f i ed ESS t ype.
1. 8 Envi r onment al Condi t i ons
1. 8. 1 I nt er i or Condi t i ons
Equi pment i nst al l ed i n envi r onment al l y pr ot ect ed i nt er i or ar eas must meet per f or mance r equi r ement s speci f i ed f or t he f ol l owi ng ambi ent condi t i ons:
1. 8. 1. 1 Temper at ur e
32 t o 120 degr ees F. Component s i nst al l ed i n unheat ed secur i t y pr ot ect ed ar eas must meet per f or mance r equi r ement s f or t emper at ur es as l ow as 0 degr ees F
1. 8. 1. 2 Pr essur e
Sea l evel t o 15, 000 f eet above sea l evel
1. 8. 1. 3 Rel at i ve Humi di t y
5 t o 95 per cent
1. 8. 1. 4 Fungus
Component s must be const r uct ed of non f ungus nut r i ent mat er i al s or be t r eat ed t o i nhi bi t f ungus gr owt h
1. 8. 1. 5 Acoust i cal Noi se
Component s must be sui t abl e f or use i n hi gh noi se ar eas above 100 dB, wi t hout adver sel y af f ect i ng t hei r per f or mance
SECTI ON 28 10 05 Page 18
1. 8. 2 Ext er i or Condi t i ons
Component s i n encl osur es must meet per f or mance r equi r ement s when exposed t o t he f ol l owi ng ambi ent condi t i ons:
1. 8. 2. 1 Temper at ur e
Mi nus 40 t o 140 degr ees F
1. 8. 2. 2 Pr essur e
Sea l evel t o 15, 000 f eet above sea l evel
1. 8. 2. 3 Sol ar Radi at i on
Si x hour s of sol ar r adi at i on per day at dr y bul b t emper at ur e of 120 degr ees F i ncl udi ng 4 hour s of sol ar r adi at i on at 104 wat t s per squar e f oot
1. 8. 2. 4 Sand and Dust
Wi nd dr i ven f or up t o 6 mi l es per hour ( mph)
1. 8. 2. 5 Rai n
2 i nches per hour and 5 i nches per hour cycl i c wi t h wi nd pl us one per i od of 12 i nches per hour
1. 8. 2. 6 Humi di t y
5 t o 95 per cent
1. 8. 2. 7 Fungus
War m, humi d at mospher e conduci ve t o t he gr owt h of het er ot r ophi c pl ant s
1. 8. 2. 8 Snow
Snow l oadi ng of 48 ( psf ) per hour ; bl owi ng snow of 4. 6 psf per hour
1. 8. 2. 9 I ce Accr et i on
Up t o 1/ 2 i nches of r adi al i ce
1. 8. 2. 10 Wi nd
Cont i nual vel oci t y up t o 50 mph wi t h gust s t o 66 mph, except t hat f ence sensor s must det ect i nt r usi ons up t o 35 mph
1. 8. 2. 11 Acoust i cal Noi se
Component s must be sui t abl e f or use i n hi gh noi se ar eas above 110 dB wi t hout adver sel y af f ect i ng t hei r per f or mance. Exampl es ar eas i ncl ude f l i ght l i nes, r un- up pads, and gener at or s i t es.
1. 9 SYSTEM CALCULATI ONS AND ANALYSI S
1. 9. 1 Backup Bat t er y Capaci t y Cal cul at i ons
Submi t cal cul at i ons showi ng t hat backup bat t er y capaci t y exceeds sensor
SECTI ON 28 10 05 Page 19 oper at i on, communi cat i ons super vi s i on, and al ar m annunci at i on power r equi r ement s f or pr oposed equi pment pl us 25 per cent spar e capaci t y.
1. 9. 2 CCTV St or age Cal cul at i ons
Submi t cal cul at i ons showi ng t he r equi r ed st or age capaci t y f or each vi deo st or age devi ce.
1. 10 AS- BUI LT DRAWI NGS
Mai nt ai n a separ at e set of dr awi ngs, el ement ar y di agr ams, and wi r i ng di agr ams of t he syst em t o be used f or as- bui l t dr awi ngs. Keep t hi s set accur at el y and neat l y up- t o- dat e wi t h al l changes and addi t i ons. Thi s set i s not t o be used f or i nst al l at i on pur poses.
Fi ni sh t he f i nal dr awi ngs submi t t ed wi t h t he endur ance t est r epor t i n accor dance wi t h Sect i on 01 78 00 CLOSEOUT SUBMI TTALS f or as- bui l t r equi r ement s.
PART 2 PRODUCTS
2. 1 SYSTEM DESCRI PTI ON
[ * Am- 7] ePACS syst em component s shal l be f ul l y compat i bl e wi t h t he USDA Depar t ment al Manual " 4620- 002 Common I dent i f i cat i on St andar d" ( see At t achment 28 10 05A) . ESS consi st i ng of t he f ol l owi ng subsyst ems and f eat ur es: [ * * Am- 7]
a. I nt r usi on Det ect i on Syst em ( I DS)
b. Access Cont r ol Syst em ( ACS)
c. Cl osed- ci r cui t Tel evi s i on Syst em ( CCTV)
d. Communi cat i ons Syst em
I ncl ude mat er i al s not nor mal l y f ur ni shed by t he manuf act ur er wi t h t he ESS equi pment as speci f i ed i n:
a. Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
b. Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
2. 2 PERFORMANCE REQUI REMENTS
Pr ovi de el ect r oni c equi pment t hat compl i es wi t h 47 CFR 15 and ar e sui t abl e f or t he envi r onment wher e t hey wi l l be i nst al l ed.
2. 2. 1 Gr owt h Capabi l i t y
Pr ovi de capabi l i t y f or modul ar ESS expansi on of i nput s, out put s, car d r eader s, and r emot e cont r ol st at i ons wi t h mi ni mal equi pment modi f i cat i on.
Sof t war e must be abl e t o handl e desi gn r equi r ement s pl us 25 per cent spar e capaci t y. Gr owt h capabi l i t y i s not t o be l i mi t ed by t he pr ovi ded pr oduct s.
2. 2. 2 Hazar dous Locat i ons
When l ocat ed i n ar eas wher e f i r e or expl osi on hazar ds exi st , pr ovi de syst em component s r at ed and i nst al l ed accor di ng t o Chapt er 5 of NFPA 70.
SECTI ON 28 10 05 Page 20
2. 2. 3 Net wor k Cer t i f i cat i on
Cer t i f y al l Pl at f or m I nf or mat i on Technol ogy ( PI T) i n accor dance wi t h DODI 8500. 01 and t he i ndi v i dual ser vi ce i mpl ement at i on pol i cy.
2. 2. 4 Mai nt ai nabi l i t y
Pr ovi de component s t hat can be mai nt ai ned usi ng commer ci al l y avai l abl e t ool s and equi pment . Ar r ange and assembl e component s t o be r eadi l y accessi bl e t o mai nt enance per sonnel wi t hout compr omi si ng syst em def eat r esi st ance and wi t h no degr adat i on i n t amper pr ot ect i on, st r uct ur al i nt egr i t y, EMI or RFI at t enuat i on, or l i ne super vi s i on af t er mai nt enance when i t i s per f or med i n accor dance wi t h manuf act ur er ' s i nst r uct i ons.
2. 2. 5 Avai l abi l i t y
Pr ovi de component s r at ed f or cont i nuous oper at i on. Pr ovi de sol i d- st at e el ect r oni c component s mount ed on pr i nt ed ci r cui t boar ds, conf or mi ng t o UL 796. Pr ovi de boar ds t hat ar e pl ug- i n, qui ck- di sconnect t ype. Do not i mpede mai nt enance wi t h densel y packed ci r cui t r y. Pr ovi de power - di ssi pat i ng component s wi t h saf et y mar gi ns of not l ess t han 25 per cent wi t h r espect t o di ssi pat i on r at i ngs, maxi mum vol t ages, and cur r ent - car r y i ng capaci t y. Pr ovi de sol i d- st at e t ype or her met i cal l y seal ed el ect r omechani cal t ype l i ght dut y r el ays and si mi l ar swi t chi ng devi ces.
2. 2. 6 Fai l - Saf e Capabi l i t y
Pr ovi de f ai l - saf e capabi l i t y i n cr i t i cal el ement s of t he ESS i ncl udi ng, but not be l i mi t ed t o, t he capabi l i t y t o moni t or communi cat i on l i nk i nt egr i t y and t o pr ovi de sel f - t est . Pr ovi de f aul t annunci at i on when di mi ni shed f unct i onal capabi l i t i es ar e det ect ed. Annunci at e f ai l - saf e al ar ms t o c l ear l y di st i ngui sh f r om ot her t ypes of al ar ms.
2. 2. 7 Li ne Super vi s i on
Pr ovi de t he same geogr aphi c r esol ut i on f or f aul t i sol at i on at t he syst ems l evel as pr ovi ded f or i nt r usi on det ect i on. Pr ovi de ei t her a st at i c or dynami c syst em wi t h act i ve mode f or l i ne super vi s i on of communi cat i on l i nks of t he ESS.
a. The st at i c syst em must r epr esent " no- al ar m" al ways by t he same si gnal , whi ch i s di f f er ent t han t he or i gi nal l y t r ansmi t t ed s i gnal .
b. The dynami c syst em must r epr esent " no- al ar m" wi t h a s i gnal whi ch cont i nual l y changes wi t h t i me.
2. 2. 8 Power Loss Det ect i on
Det ect AC and DC power l oss and gener at e an al ar m when a cr i t i cal component of t he syst em exper i ences t empor ar y or per manent l oss of power .
Annunci at e t he al ar m i n t he Secur ed Ar ea and t he Secur i t y Command Cent er t o c l ear l y i dent i f y t he component exper i enci ng power l oss.
2. 2. 9 Cont r ol s and Desi gnat i ons
Pr ovi de cont r ol s and desi gnat i ons as speci f i ed i n NEMA I CS 1.
SECTI ON 28 10 05 Page 21
2. 2. 10 Speci al Test Equi pment
Pr ovi de al l speci al t est equi pment , speci al har dwar e, sof t war e, t ool s, and pr ogr ammi ng or i ni t i al i zat i on equi pment r equi r ed t o st ar t or mai nt ai n any par t of t he syst em and i t s component s. Speci al t est equi pment i s def i ned as any t est equi pment not nor mal l y used i n an el ect r oni cs mai nt enance f aci l i t y .
2. 2. 11 El ect r omagnet i c I nt er f er ence ( EMI )
Conf i gur e and pr ovi de ESS component s empl oyi ng el ect r omagnet i c r adi at i on const r uct ed t o pr ovi de mi ni mal vul ner abi l i t y t o el ect r oni c count er measur es.
2. 2. 12 El ect r omagnet i c Radi at i on ( EMR)
Pr ovi de onl y ESS communi cat i on component s whi ch ar e Feder al Communi cat i ons Commi ssi on ( FCC) l i censed and appr oved. Pr ovi de syst em component s whi ch ar e el ect r omagnet i cal l y compat i bl e.
2. 2. 13 I nt er changeabi l i t y
Use of f - t he- shel f component s whi ch ar e physi cal l y, el ect r i cal l y, and f unct i onal l y i nt er changeabl e wi t h equi val ent component s as compl et e i t ems. Equi val ent , r epl acement component s must not r equi r e new or ot her component modi f i cat i on. Do not use cust om desi gned or one- of - a- ki nd i t ems. I nt er changeabl e component s or modul es must not r equi r e t r i al and er r or mat chi ng i n or der t o meet i nt egr at ed syst em r equi r ement s, syst em accur acy, or r est or e compl et e syst em f unct i onal i t y.
2. 3 I NTRUSI ON DETECTI ON SYSTEM ( I DS)
The I DS pr i mar y f unct i on i s t o det ect i nt r usi on i nt o secur ed ar eas. The I DS event s must be vi ewabl e as separ at e or as a combi ned l i s t of al l ESS event s.
a. Pr ovi de bot h super vi sed and non- super vi sed al ar m poi nt moni t or i ng.
b. Secur e or access al ar m poi nt s bot h manual l y and aut omat i cal l y by t i me of day, day of week or by oper at or command.
2. 3. 1 I DS Component s
Pr ovi de component s:
a. Pr emi se Cont r ol Uni t s ( PCU)
b. Det ect i on Sensor s
c. Tamper Swi t ches
2. 3. 2 Det ect i on Sensi t i v i t y
The sensi t i v i t y of t he I DS must al l ow f or t he f ol l owi ng:
a. Locat i ng i nt r usi ons at i ndi v i dual l y pr ot ect ed asset s or at an i ndi v i dual por t al
b. Locat i ng i nt r usi ons wi t hi n t he cover age on a s i ngl e gl ass br eak sensor
SECTI ON 28 10 05 Page 22
c. Locat i ng f ai l ur es or t amper i ng at i ndi v i dual sensor s
2. 3. 3 Det ect i on Al ar m and Repor t i ng Capaci t y
Col l ect , communi cat e, and di…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .