B615_Final_Design_Plans_Aug_12_2019_Sheet_-145_-159__of_191.pdf

PDF 849 KB Posted

Attached to
JBSA FSH ARNORTH Bldg 615 Renovation Project for Army Band
Solicitation number
W9126G-19-B-3286
Issued by

About this file

B615 Final Design Plans Sheets 145 - 159 of 191

View the file

Other files

File Type Posted
C1_Rev_2_SF_1409_Abstract_of_Offers-Page2of3_PRINT1.pdf PDF
C1_Rev_SF_1409_Abstract_of_Offers-Page_3of3.pdf PDF
C1_Rev_2_SF_1409_Abstract_of_Offers-Page1of3_Signed_29Sep_19.pdf PDF
am_0007.pdf PDF
am_0006.pdf PDF
am_0005_12_Sep_19.pdf PDF
Revise_Site_Visit_Form_11_Sep_19.pdf PDF
B3_Amendment_03_30_Aug_19.pdf PDF
Amendment_02_Change_of_Solicitation_closing_date_and_Bidder_Key_28_Aug_19.pdf PDF
B3_Unescorted_Access_Request_Form_pg_1-4-26_Aug_19-5.pdf PDF
JBSA_FSH_ARNORTH_Building_615-Amend_01.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-165__of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-136_-144__of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_1-7_of_191.pdf PDF
W9126G19B3286_DIV_02_Specifications_Appendix_A_Abatement_Guidelines_Part_2_of_2.pdf PDF
B3_W9126G19B3286_DIV_27_28_31_and_32_Specifications_23_Aug_19.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_20-22_of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-166_-170__of_191.pdf PDF
B3_W9126G19B3286_DIV_08_to_DIV_10_Specifications_23_Aug_19.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_1A_of_5_Sampling_Methodology.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_1C.2_of_5_All_Other_areas__Lead_Based_Paint_Findings.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-113_-_115__of_191.pdf PDF
B3_W9126G19B3286_DIV_03_to_DIV_06_Specifications_23_Aug_19.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-127_-130__of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-123_-126__of_191.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_3_of_5.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-162__of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-160_-161__of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_-61-67_of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_-46-50_of_191.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_4_of_5_page_13_to_21_of_21.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_-51-55_of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_23-27_of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-186__of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-179_-183__of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_-75-77_of_191.pdf PDF
B3_W9126G19B3286_DIV_02_Specifications_Appendix_A_Abatement_Guidelines_ACM_Map.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_28-30_of_191.pdf PDF
B3_W9126G19B3286_DIV_26_Specifications_23_Aug_19.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_1C.3_of_5_Lead_Based_Paint_Findings.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_4_of_5_page_17_to_21_of_21.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_1E_of_5_Conclusions_and_recommendations.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_-78-81_of_191.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-187__of_191.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_36_-40_of_191.pdf PDF
W9126G19B3286_Attachment_A_HAZMAT_SURVEY_Section_4_of_5_page_10-_11_of_21.pdf PDF
B3_B615_Final_Design_Plans_Aug_12_2019_Sheet_31-35_of_191.pdf PDF
B3_W9126G19B3286_DIV_01_Specifications_23_Aug_19.pdf PDF
B615_Final_Design_Plans_Aug_12_2019_Sheet_-184__of_191.pdf PDF
B3_W9126G19B3286_DIV_02_Specifications_Asbestos_Abatement_23_Aug_19.pdf PDF
Show 40 more

Latest 50 of 92 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I 'D

F

IL

E

N A

M E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

U M

B E

R

1 2 3 4 5

D

C

B

A

M-602

H V

A C

S C

H E

D U

L E

S I

I

R E

N O

V A

T

IO

N O

F B

U

IL

D

IN

G

J O

IN

T

B A

S E

S A

N A

N T

O N

IO

F

O R

T S

A M

H O

U S

T O

N T

X

K E

N A

L L

F N

I S

A V

O Y

D R

IV

E

S

U

IT

E

H O

U S

T O

N T

E X

A S

P H

O N

E (8

-8

D e s ig n e r

A u th o r

C h e c k e r

A U

G U

S T

K F

B

L D

G H

V A

C

FINAL SUBMITTAL

M -6

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

R E

E

NI

GNELANOI

SS

E F

O R

S

TATE O

SAXETF

P

RYAN EDWARDS

131050

NECI

L

SED

2. MINIMUN CFM FOR FREEZE PROTECTION IS USED TO REPLACE THE VENTILATION CFM TO MAINTAIN ROOM TEMPERATURE AT 40 0F IN WINTER.

1. BASED ON TABLE 403.3.1.1 MINIMUM VENTILATION RATES INTERNATIONAL MECHANICAL CODE 2015.

NOTES:

TOTAL CFM 5425

C206 Corridor 688 0 0 0.06 50

C204 & 205 Corridor 604 0 0 0.06 40

C203 Corridor 87 0 0 0.06 20

C201 & 202 Corridor 399 0 0 0.06 40

218 Rock Rehersal 1290 46 10 0.06 540

216 Open Office 2007 11 5 0.06 180

213 Performance/Rehersal Hall 3135 314 7.5 0.06 2565

210 Admin. 155 1 5 0.06 20

209 Operations 176 1 5 0.06 20

208 Commander 232 2 5 0.06 25

207 1SG 190 1 5 0.06 20

203 Break/Conference 1356 68 5 0.12 520

C109 & 110 Corridor - - 0 0.06 40

C108 Corridor - - 0 0.06 30

C107 Corridor - - 0 0.06 40

C106 Corridor 622 - 0 0.06 40

127 Ind. Practice Rooms 1643 0 0 0.06 155

124 Supply Office 137 1 5 0.06 20

123 Group Rehersal 4 334 12 10 0.06 140

116 Instrument Maintenance 952 0 0 0.00 75

115 STG 42 0 0 0 30

114 Group Rehersal 1 334 12 10 0.06 140

113 Group Rehersal 2 340 12 10 0.06 140

112 Group Rehersal 3 346 13 10 0.06 150

C105 Corridor 238 0 0 0.06 25

C103 & 104 Corridor 539 0 0 0.06 40

102 Recept 69 3 5 0.06 20

101 Library 1444 15 5 0.12 250

C101 & 102 Corridor 508 0 0 0.06 50

ROOM NO. ROOM NAME AREA (S.F.) OCCUPANTS

OUTDOOR AIR RATE

(CFM/PERSON)

OUTDOOR AIR

RATE (CFM/S.F.)

MIN. VENTILATION

PER IMC (CFM)

VENTILATION CALCULATION

TEMPERATURE AT 40°F IN WINTER.

2. MINIMUN CFM FOR FREEZE PROTECTION IS USED TO REPLACE THE VENTILATION CFM TO MAINTAIN ROOM

1.CALCULATION IS BASED ON TABLE 6-1 MINIMUM VENTILATION RATES IN BREATHING ZONE OF ASHRAE 62.1-2016

NOTES:

TOTAL: 2185

206 Men 222 4.0 FIXTURE 75.0 300

205 Jan. 25 25.0 SQ FT 1.0 45

204 Women 233 4.0 FIXTURE 75.0 300

645 EF-3

122 Mens Locker 690 690.0 SQ FT 0.5 350

121 Mens Shower 235 235.0 SQ FT 0.5 120

120 Mens 288 6.0 FIXTURE 75.0 450

920 EF-2

106 Showers 136 136.0 SQ FT 0.5 70

105 Women Locker 350 350.0 SQ FT 0.5 180

104 Women 321 4.0 FIXTURE 75.0 300

103 Jan. 69 69.0 SQ FT 1.0 70

620 EF-1

ROOM NO. ROOM NAME

AREA

(SQ FT) # OF UNITS UNIT

CFM/

UNIT EXHAUST CFM

CFM/FAN

EXHAUST

FAN

EXHAUST CALCULATION

B-1 15.4 3 1 1/4 HW 2-WAY MODULATING

CH-1 78.5 4 3 CHW 2-WAY MODULATING

DOAS-3 2.6 1 1/2 HW 2-WAY MODULATING

DOAS-2 6.3 2 3/4 HW 2-WAY MODULATING

DOAS-1 5.2 2 3/4 HW 2-WAY MODULATING

DOAS-3 28.1 3 2 CHW 2-WAY MODULATING

DOAS-2 18.0 3 1 1/2 CHW 2-WAY MODULATING

DOAS-1 12.6 2 1 1/4 CHW 2-WAY MODULATING

END OF LOOP 15.8 3 1 1/4 HW 2-WAY MODULATING

FCU 2-14 1.3 1 1/2 HW 2-WAY MODULATING

FCU 2-13 2.1 1 1/2 HW 2-WAY MODULATING

FCU 2-12 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-11 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-10 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-9 3.1 1 1/2 HW 2-WAY MODULATING

END OF LOOP 42.7 4 2 1/2 HW 2-WAY MODULATING

FCU 2-8 2.1 1 1/2 HW 2-WAY MODULATING

FCU 2-7 4.9 2 3/4 HW 2-WAY MODULATING

FCU 2-6 4.9 2 3/4 HW 2-WAY MODULATING

FCU 2-5 4.9 2 3/4 HW 2-WAY MODULATING

FCU 2-4 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-3 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-2 3.1 1 1/2 HW 2-WAY MODULATING

FCU 2-1 16.6 3 1 1/4 HW 2-WAY MODULATING

END OF LOOP 8.3 2 1 HW 2-WAY MODULATING

FCU 1-9 1.8 1 1/2 HW 2-WAY MODULATING

FCU 1-8 1.8 1 1/2 HW 2-WAY MODULATING

FCU 1-7 1.3 1 1/2 HW 2-WAY MODULATING

FCU 1-6 1.3 1 1/2 HW 2-WAY MODULATING

FCU 1-5 2.1 1 1/2 HW 2-WAY MODULATING

END OF LOOP 9.8 2 1 HW 2-WAY MODULATING

FCU 1-4 1.8 1 1/2 HW 2-WAY MODULATING

FCU 1-3 1.8 1 1/2 HW 2-WAY MODULATING

FCU 1-2 3.1 1 1/2 HW 2-WAY MODULATING

FCU 1-1 3.1 1 1/2 HW 2-WAY MODULATING

END OF LOOP 27.8 3 1 1/2 CHW 2-WAY MODULATING

FCU 2-14 3.2 1 1/2 CHW 2-WAY MODULATING

FCU 2-13 5.0 2 3/4 CHW 2-WAY MODULATING

FCU 2-12 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-11 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-10 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-9 4.9 1 1/2 CHW 2-WAY MODULATING

END OF LOOP 66.1 4 2 1/2 CHW 2-WAY MODULATING

FCU 2-8 5.0 2 3/4 CHW 2-WAY MODULATING

FCU 2-7 6.1 1 1/2 CHW 2-WAY MODULATING

FCU 2-6 6.1 1 1/2 CHW 2-WAY MODULATING

FCU 2-5 6.1 1 1/2 CHW 2-WAY MODULATING

FCU 2-4 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-3 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-2 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 2-1 28.1 3 2 CHW 2-WAY MODULATING

END OF LOOP 20.4 3 1 1/2 CHW 2-WAY MODULATING

FCU 1-9 4.5 1 1/2 CHW 2-WAY MODULATING

FCU 1-8 4.5 2 3/4 CHW 2-WAY MODULATING

FCU 1-7 3.2 1 1/2 CHW 2-WAY MODULATING

FCU 1-6 3.2 1 1/2 CHW 2-WAY MODULATING

FCU 1-5 5.0 2 3/4 CHW 2-WAY MODULATING

END OF LOOP 18.4 3 1 1/4 CHW 2-WAY MODULATING

FCU 1-4 4.3 1 1/2 CHW 2-WAY MODULATING

FCU 1-3 4.3 1 1/2 CHW 2-WAY MODULATING

FCU 1-2 4.9 1 1/2 CHW 2-WAY MODULATING

FCU 1-1 4.9 1 1/2 CHW 2-WAY MODULATING

MARK

MAX. FLOW

(GPM)

PRESSURE

DROP (PSI)

VALVE SIZE

(IN)

SERVICE CONFIGURATION ACTION

VALVE SCHEDULE

Notes:

1. Refer to technical specification 23 05 48 Vibration and Seismic Controls for HVAC for more detail.

2. Use Vibration Isolation with types and deflections per manufacturer recommendation.

Air Cooled Condensing Unit Spring Isolators 0.75 1,2

Chillers Rubber-in-shear (RIS) Isolators 0.5 1,2

All other isolators: Spring Hangers 0.75 1,2

Piping Serving Motorized Equipment

First two isolators adjacent to equpiment: Spring hangers with vertical stops

Same as connected equpiment

1,2

In-line Exhaust fans Neoprene Base 0.2 1,2

Centrifugal Pumps Spring Isolators 1 1,2

FCU Spring Isolators 1 1,2

Ductwork Spring Isolators 0.75 1,2

Equipment Isolator Type Minimum Deflection (in) NOTES

VIBRATION ISOLATION SCHEDULE

1.TEST IN ACCORDANCE WITH UFGS 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC AND THE PROCEDURES IN SMACNA HVAC

AIR DUCT LEAKAGE TEST MANUAL.

Notes:

DOAS-3 3.5 - - - A 3 A 6 - - 3.5 1

DOAS-3 - 3.5 - - - - - - A 3 3.5 1

DOAS-3 - - -1 - - - - - A 24 1 1

DOAS-3 - - - 1.5 - - - - A 12 1.5 1

DOAS-2 3.5 - - - A 3 A 6 - - 3.5 1

DOAS-2 - 3.5 - - - - - - A 3 3.5 1

DOAS-2 - - -1 - - - - - A 24 1 1

DOAS-2 - - - 1.5 - - - - A 12 1.5 1

DOAS-1 3.5 - - - A 3 A 6 - - 3.5 1

DOAS-1 - 3.5 - - - - - - A 3 3.5 1

DOAS-1 - - -1 - - - - - A 24 1 1

DOAS-1 - - - 1.5 - - - - A 12 1.5 1

EF-3 - - -1 - - - - - A 24 1 1

EF-2 - - -1 - - - - - A 24 1 1

EF-1 - - -1 - - - - - A 24 1 1

FCU 2-15 3.5 - - - A 3 A 6 - - 3.5 1

FCU 2-14 - 3.5 - - - - - - A 3 3.5 1

FCU 2-14 3.5 - - - A 3 A 6 - - 3.5 1

FCU 2-13 - 3.5 - - - - - - A 3 3.5 1

FCU 2-9 3.5 - - - A 3 A 6 - - 3.5 1

FCU 2-8 - 3.5 - - - - - - A 3 3.5 1

FCU 2-2 3.5 - - - A 3 A 6 - - 3.5 1

FCU 2-1 - 3.5 - - - - - - A 3 3.5 1

FCU 1-9 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-9 - 3.5 - - - - - - A 3 3.5 1

FCU 1-8 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-8 - 3.5 - - - - - - A 3 3.5 1

FCU 1-7 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-7 - 3.5 - - - - - - A 3 3.5 1

FCU 1-6 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-6 - 3.5 - - - - - - A 3 3.5 1

FCU 1-5 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-5 - 3.5 - - - - - - A 3 3.5 1

FCU 1-4 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-4 - 3.5 - - - - - - A 3 3.5 1

FCU 1-3 3.5 - - - A 3 A 6 - - 3.5 1

FCU 1-3 - 3.5 - - - - - - A 3 3.5 1

Supply Duct

Return Duct

Exhaust/ Relief Duct

Outside Air Duct

Duct Seal Class

Duct Leak Class

Duct Seal Class

Duct Leak Class

Duct Seal Class

Duct Leak Class

Inches of Water Column Round/Oval Rectangular

System

Duct Pressure Class Supply Return/Outside Air

Duct Test Pressure: Inches of Water Column

Notes

DUCT LEAKAGE SCHEDULE

NOTES:

1. REFER TO CHILLED WATER P&ID CONTROL SEQUENCE SHEET M-506

AND HEATING WATER P&ID CONTROL SEQUENCE M-507 FOR DETAILS.

CI-1,2 2 200 200 6.3 1

TAGS QTY

MAX. PRESSURE

(PSI)

MAX. TEMP. (F) GALLONS NOTES

CHEMICAL INJECTOR SCHEDULE

1. REFER TO CHILLED WATER P&ID CONTROL SEQUENCE SHEET M-507 AND

HEATING WATER P&ID CONTROL SEQUENCE M-508 FOR DETAILS.

NOTES:

ET-2 B-1 14 11.3 100 240 1

ET-1 CH-1 14 11.3 100 240 1

TAGS SERVES

TANK

VOLUME

(GALLONS)

MAX. ACCEPTED

VOLUME

(GALLONS)

MAX DESIGN

PRESSURE

(PSI)

MAX DESIGN

TEMPERATURE

(°F)

NOTES

EXPANSION TANK SCHEDULE

1. REFER TO CHILLED WATER P&ID CONTROL SEQUENCE SHEET M-507 AND HEATING

WATER P&ID CONTROL SEQUENCE M-508 FOR DETAILS.

NOTES:

AS-2 B-1 175 300 125 3" 21.5 1

AS-1 CH-1 175 300 25 1 1/4" 3.5 1

TAGS SERVES

MAX.

WORKING

PRESSURE

(PSI)

MAX.

WORKING

TEMP. (°F)

MAX FLOW

(GPM)

SIZE (NPT)

WEIGHT

(LBS)

NOTES

AIR SEPARATOR SCHEDULE

5. MAINTAIN MIN. 18" OVERHEAD AND SIDE CLEARANCE AND 48" FRONT CLEARANCE.

4. PROVIDE WITH FACTORY-FURNISHED CONDENSATE PUMP.

3. MOUNT BOTTOM AT MIN. 24" AFF.

2. PROVIDE WITH CONDENSATE PUMP. REFER TO SHEET M103 FOR CONDENSATE DRAIN LINE ROUTING.

1. PROVIDE WITH FACTORY-FURNISHED HUMIDISTAT.

NOTES:

DH-1

INSTRUMENT

STORAGE 119

SELF CONTAINED WALL MOUNT 8,369 FT3 62 360 115/1 8A EBAC INDUSTRIAL / WM80 1,2,3,4,5

VOLUME EXTRACTION (PPD) (CFM)

MARK SERVES TYPE

EFFECTIVE TYPICAL AIRFLOW

VOLT/PH MCA MANUFACTURER / MODEL NOTES

DEHUMIDIFIER & HUMIDIFIER SCHEDULE

4. MAINTAIN MIN. 18" OVERHEAD AND SIDE CLEARANCE AND 48" FRONT CLEARANCE.

3. MOUNT BOTTOM AT MIN. 24" AFF.

2. PROVIDE WITH CONDENSATE PUMP. REFER TO SHEET M103 FOR CONDENSATE DRAIN LINE AND POTABLE WATER LINE ROUTING.

1. PROVIDE WITH FACTORY-FURNISHED ON/OFF WALL HUMIDISTAT.

NOTES:

HM-1

INSTRUMENT

STORAGE 119

WALL-MOUNTED 0.1 1.6 2-8 110-240/1 20A 12.7A CONDAIR/RH2+ SPACE QDV 1,2,3,4

MARK SERVES TYPE

FILL RATE

(GPM)

DRAIN RATE

(GPM)

OUTPUT RANGE

MIN - MAX (lbs/h)

VOLT/PH MOP MCA MANUFACTURER / MODEL NOTES

HUMIDIFIER SCHEDULE

1. UNIT SHALL CONTAIN ECM MOTOR.

NOTES:

HWP-2 B-1 CIRCULATOR 16 10 1 120/1/60 1

HWP-1 B-1 CIRCULATOR 16 10 1 120/1/60 1

BCP-2 B-1 IN-LINE CIRCULATOR 16 10 1 120/1/60 1

BCP-1 B-1 IN-LINE CIRCULATOR 16 10 1 120/1/60 1

CHP-2 CH-1 CLOSE COUPLED INLINE 120 65 2 240/1/60 1

CHP-1 CH-1 CLOSE COUPLED INLINE 120 65 2 240/1/60 1

MARK SERVES TYPE

MAX. FLOW

(GPM)

ESP (FT.

W.G)

HP VOLTS/PH/HZ NOTES

PUMP SCHEDULE

W

G

B

08/09/2019

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I 'D

F

IL

E

N A

M E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

U M

B E

R

1 2 3 4 5

D

C

B

A

M-603

H V

A C

S C

H E

D U

L E

S I

II

R E

N O

V A

T

IO

N O

F B

U

IL

D

IN

G

J O

IN

T

B A

S E

S A

N A

N T

O N

IO

F

O R

T S

A M

H O

U S

T O

N T

X

K E

N A

L L

F N

I S

A V

O Y

D R

IV

E

S

U

IT

E

H O

U S

T O

N T

E X

A S

P H

O N

E (8

-8

D e s ig n e r

A u th o r

C h e c k e r

A U

G U

S T

K F

B

L D

G H

V A

C

FINAL SUBMITTAL

M -6

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

R E

E

NI

GNELANOI

SS

E F

O R

S

TATE O

SAXETF

P

RYAN EDWARDS

131050

NECI

L

SED

IN ACCORDANCE WITH ASHRAE FUNDAMENTALS HANDBOOK.

1. OUTDOOR DESIGN CONDITION IS BASED ON 0.4 OUTDOOR PEAK DEWPOINT DESIGN VALUE AND ITS MCDB FOR THE OUTSIDE AIR CONDITIONS

NOTES:

219 Mechanical/Electrical 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

218 Rock Rehersal 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

217 Comm. Room 99.3/73.9 75.3/80.8 33.8 80/50 85 40 55

216 Open Office 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

215 Mechanical 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

214 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

213 Performance/Rehersal Hall 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

211 Elec 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

210 Admin. 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

209 Operations 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

208 Commander 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

207 1SG 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

206 Men 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

205 Jan. 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

204 Women 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

203 Break/Conference 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

202 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

201 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C206 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C204 & 205 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C203 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C201 & 202 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

128 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

127 Ind. Practice Rooms 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

126 Comm. Room 99.3/73.9 75.3/80.8 33.8 80/50 85 40 55

125 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

124 Supply Office 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

123 Group Rehersal 4 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

122 Mens Locker 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

121 Mens Shower 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

120 Mens 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

119 Instrument Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

118 Sprinkler 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

117 Mech/Elec 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

116 Instrument Maintenance 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

114 Group Rehersal 1 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

113 Group Rehersal 2 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

112 Group Rehersal 3 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

111 Mechanical/Electrical 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

110 Machine 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

E1 Elev 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

108 Mechanical 99.3/73.9 75.3/80.8 33.8 80/50 85 40 55

107 Storage 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

106 Showers 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

105 Women Locker 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

104 Women 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

103 Jan. 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

102 Recept 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

101 Library 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C106 - C110 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C105 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C103 & 104 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

C101 & 102 Corridor 99.3/73.9 75.3/80.8 33.8 78/50 85 68 55

COOLING TOTAL

DB/MCWB °F

COOLING

DEHUMIDIFICATION

DB/MCDB °F

HEATING

DB °F

COOLING

DB °F / %RH

COOLING

SETBACK °F

HEATING

DB °F

HEATING

SETBACK °F

ROOM NO. ROOM NAME

OUTDOOR DESIGN CONDITION INDOOR DESIGN CONDITION

DESIGN CONDITION SCHEDULE

6. MAINTAIN MIN. 13/16" CLEARANCE ON TOP SIDE.

5. UNIT IS COOLING ONLY AND CONTROLLED BY FACTORY-FURNISHED THERMOSTAT, SETPOINT 80 0F (ADJ.).

4. PROVIDE WITH INTEGRAL DISCONNECT, WIRING, AND CONDUIT FROM OUTDOOR UNIT.

3. PROVIDE WITH MERV-4 WASHABLE FILTER.

2. POWERED BY AIR-COOLED CONDENSING UNIT.

1. PROVIDE WITH FIELD-INSTALLED CONDENSATE LIFT PUMP AND UL-APPROVED FLOAT SWITCH IN DRAIN PAN.

NOTES:

AHU 2-1 MACHINE 110 CU-2 WALL MOUNTED 80.0/67.0 55.0 101.5 23.8 DAIKIN/FAQ24PVJU 1,2,3,4,5,6

AHU 1-2 COMM 217 CU-1 WALL MOUNTED 80.0/67.0 55.0 101.5 23.8 DAIKIN/FAQ24PVJU 1,2,3,4,5,6

AHU 1-1 COMM 126 CU-1 WALL MOUNTED 80.0/67.0 55.0 101.5 23.8 DAIKIN/FAQ24PVJU 1,2,3,4,5,6

EAT (°F)

DB/WB

LAT (°F)

DB

AMBIENT

(°F) DB

RATED TOTAL

CAPACITY (MBH)

MAKR

AREA

SERVED

ACCU

ASSIGNMENT

TYPE

COOLING

MANUFACTURER

/MODEL

NOTES

MINI-SPLIT AIR HANDLING UNIT SCHEDULE

5. MAINTAIN MIN. 13/16" CLEARANCE ON TOP SIDE.

4. PROVIDE WITH LOW-AMBIENT COOLING CONTROLS DOWN TO 20°F.

3. COOLING-ONLY.

2. PROVIDE WITH 12" ROOF CURB.

1. PROVIDE WITH THIRD PARTY HAIL GUARD TO PROTECT CONDENSING COIL EQUAL TO PERMATRON HAILSTOP HAIL GUARD NETTING.

NOTES:

CU-2 18.0 101.5 24.0 1/4 208/1 18.3 20.0 DAIKIN/RK24NMVJU 1,2,3,4,5

CU-1 19.2 101.5 48.0 1/4 208/1 18.5 32.0 DAIKIN/RZR 1,2,3,4,5

EFFICIENCY

(SEER)

AMBIENT (°F)

DB

NOM. TOTAL

CAPACITY

(KBTU/H)

MCA MOP

MARK

COOLING

REFRIG PIPE

SIZE O.D. (IN)

VOLT / PH

ELECTRICAL

MANUFACTURER

/MODEL

NOTES

MINI-SPLIT AIR-COOLED CONDENSING UNIT SCHEDULE

2. FINISH/PAINT COLOR SHALL BE WHITE UNLESS OTHERWISE NOTED.

1. UNITS SHALL BE FURNISHED WITH APPROPRIATE FRAMES FOR DUCT, CEILING OR WALL MOUNTING.

NOTES:

I SUPPLY DIFFUSER 24X24 14"Ø TITUS/TMS 1,2

H RETURN GRILLE 24x24 22x22 TITUS/50F 1,2

G WALL-MOUNTED SUPPLY GRILLE 14X14 12X12 TITUS/301FS 1,2

F RETURN GRILLE 14X14 12X12 TITUS/50F 1,2

E EXHAUST GRILLE 14X14 12X12 TITUS/50F 1,2

D SUPPLY DIFFUSER 24X24 12"Ø TITUS/TMS 1,2

C SUPPLY DIFFUSER 12X12 8"Ø TITUS/TMS 1,2

B SUPPLY DIFFUSER 12X12 6"Ø TITUS/TMS 1,2

A SUPPLY DIFFUSER 12X12 4"Ø TITUS/TMS 1,2

MARK TYPE

FACE SIZE

INCHES

NECK SIZE

INCHES

MANUFACTURE

/MODEL

NOTES

DIFFUSER AND GRILLE SCHEDULE

3. CONNECT TO DUAL TECHNOLOGY OCCUPANCY SENSOR.

2. PROVIDE WITH 120V/24V CONTROL TRANSFORMERS FOR DDC CONTROL.

1. PROVIDE NECESSARY DUCT ACCESSORIES TO CONNECT TO INCOMING AND OUTGOING DUCTWORK.

NOTES:

VAV 2-3 900 770 8 120/1 31 TITUS/DESV08 1,2,3

VAV 2-2 900 770 8 120/1 31 TITUS/DESV08 1,2,3

VAV 2-1 900 770 8 120/1 31 TITUS/DESV08 1,2,3

MARK MAX CFM MIN CFM

UNIT

SIZE

VOLT/PH MAX NC

MANUFACTURE

/MODEL

NOTES

VARIABLE AIR VOLUME BOX SCHEDULE

W

G

B

GENERAL NOTES:

1. THIS PROJECT IS DESIGNED BASED ON THE FOLLOWING CODES AND STANDARDS: INTERNATIONAL PLUMBING CODE, INTERNATIONAL FUEL GAS CODE, INTERNATIONAL ENERGY CONSERVATION CODE 2015, ASHRAE STANDARD 90.1, AS

ADOPTED BY THE LATEST EDITION, UFC-3-420-01 PLUMBING SYSTEMS, UFC 1-200-02 HIGH PERFORMANCE AND

SUSTAINABLE BUILDING REQUIREMENTS, UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, UFC 4-010-01 DOD

MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, UFC-4-024-01 PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL

PROTECTION FOR BUILDINGS.

2. REFER TO ARCHITECTURAL INTERIOR ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR

THE LOCATIONS OF ALL WALL MOUNTED DEVICES. OTHERWISE INSTALL PER INDUSTRY STANDARDS, CODES AND/OR

ORDINANCES OF THE AUTHORITY HAVING JURISDICTION. NO ATTACHMENT OR PENETRATION SHALL BE MADE TO THE

EXTERIOR MASONRY WALL WITHOUT APPROVAL BY OWNER AND ARCHITECT.

3. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES PRIOR TO EACH CONCRETE POUR. VERIFY EXACT LOCATION OF

CONCRETE FLOOR "LEAVE-OUTS" FOR PLUMBING FIXTURE ROUGH-INS.

4. PROVIDE ACCESS DOORS FOR INSTALLATION IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED

PLUMBING EQUIPMENT, VALVES, CONTROLS AND OTHER DEVICES.

5. INSTALL PIPING TO PROVIDE THE MAXIMUM POSSIBLE CLEAR HEIGHT UNDERNEATH. MAINTAIN A MINIMUM OF 10 INCHES

ABOVE FINISHED CEILING TO PROVIDE CLEARANCE FOR LIGHTING FIXTURES.

6. COORDINATE THE EXACT LOCATION OF FLOOR DRAINS WITH THE ARCHITECTURAL DRAWINGS AND MECHANICAL

EQUIPMENT LOCATIONS PRIOR TO INSTALLATION OF DRAINS.

7. COORDINATE WORK WITH ARCHITECTURAL FEATURES, PIPING, EQUIPMENT, MECHANICAL WORK, ELECTRICAL WORK, AND

BUILDING STRUCTURE TO AVOID INTERFERENCES.

8. PROVIDE RATED INTUMESCENT CAULK OR PUTTY AT ALL FIRE RATED PENETRATION LOCATIONS, INCLUDING BUT NOT

LIMITED TO STAIRWELLS, CORRIDORS, AND MECHANICAL OR ELECTRICAL EQUIPMENT ROOMS. ESCUTCHEONS ARE NOT

REQUIRED, EXCEPT IN EXPOSED LOCATIONS. HOWEVER THE CAULK OR PUTTY SHALL BE INSTALLED SMOOTH AND FLUSH TO

THE SURROUNDING SURFACE.

9. MINIMUM SLOPE FOR DRAINAGE PIPE WITHIN 5'-0" OF BUILDING IS 1/4" PER FOOT FOR 2-1/2" DIAMETER AND LESS AND

1/8" PER FOOT FOR 3" DIAMETER AND GREATER. MINIMUM SLOPE FOR DRAINAGE PIPE BEYOND 5'-0" OF BUILDING IS 1%.

10. COORDINATE ALL TRADES TO CONSOLIDATE EXTERIOR WALL PENETRATIONS. ARCHITECT AND OWNER TO APPROVE

COMPREHENSIVE PENETRATION LOCATION(S) AND SIZE(S) ON COORDINATION DRAWING PRIOR TO WORK.

11. VERIFY LOCATION OF EXISTING UTILITIES ON SITE PRIOR TO BEGINNING UTILITY WORK. COORDINATE INSTALLATION WITH

ALL UTILITIES ON SITE AND OFFSET AS NECESSARY TO PROVIDE SERVICES INDICATED.

12. TAKE PHOTOGRAPHS OF ALL EXISTING UTILITIES AND SERVICES BEING DEMOLISHED AND CAPPED AND CLEARLY INDICATE

ON AS-BUILT DRAWINGS. PROVIDE PHOTOS IN THE O & M MANUALS AND THE AS-BUILT DOCUMENTS.

13. PROVIDE TRAP SEAL DEVICES IN ALL FLOOR DRAINS.

14. PROVIDE VACUUM BREAKER DEVICE ON ALL HOSE BIBBS AND JANITOR SINKS/SERVICE SINKS.

15. THIS IS A HISTORICAL BUILDING. CONTRACTOR SHALL NOT DEMOLISH ANY PART OF THE EXTERIOR WITHOUT WRITTEN

CONSENT FROM THE OWNER. COORDINATE EXACT LOCATIONS WITH MASON PRIOR TO WORK. MORTAR SHALL BE

RESTORATION MORTAR APPROVED BY THE OWNER.

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION, ACCEPTABLE MANUFACTURER AND MODEL NUMBER ON PLUMBING

FIXTURES.

ROUGH-IN (INCHES)

1/2"

1/2"

ELECTRIC WATER COOLER

NOTE:

EWC1

SSK1 SERVICE SINK

2" 2"

3" 2"

DESCRIPTION

URINALUR1

L1 LAVATORY

MARK

2"2"

2" 2"

W V

WALL MOUNTED, DUAL, HI-LO TYPE W/APRON ON HIGH UNIT AND WITH BOTTLE FILLER, ADA/TAS ACCESSIBLE

30"x30" FLOOR MOUNTED, TERRAZO OR MOLDED STONE

1/2"

1/2"

COUNTER-TOP MOUNTED, OVAL, 0.25 FLOW RESTRICTOR

WALL MOUNTED, MANUAL FLUSH VALVE TYPE, ADA/TAS ACCESSIBLE3/4"

1/2"

HW CW

REMARKS

WC1 WATER CLOSET 2"4" -

WC2 WATER CLOSET 4" 2"

FLOOR MOUNTED, REAR OUTLET, MANUAL FLUSH VALVE TYPE

FLOOR MOUNTED, REAR OUTLET, MANUAL FLUSH VALVE TYPE, ADA/TAS ACCESSIBLE

1"

- 1"

1/2"S1 KITCHEN SINK 2" 2" COUNTER-TOP MOUNTED, STAINLESS STEEL WITH HAND SPRAYER, DOUBLE COMPARTMENT, GOOSENECK FAUCET1/2"

PLUMBING FIXTURE ROUGH-IN SCHEDULE

PLAN/DETAIL

SHEET WHERE RISER

DIAGRAM IS SHOWN

NOTE: ALL SYMBOLS AND ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS.

NUMBER

RE: X/PX

PLUMBING RISER LOCATOR

DRAWING/DETAIL REFERENCE

RISER

NUMBER

X

TEE OUT OF TOP OF PIPE

CAP ON END OF PIPE

BELOW FINISHED GRADE

BELOW FINISHED FLOOR

1/8" PER FOOT SLOPE

1/4" PER FOOT SLOPE

ABOVE FINISHED GRADE

ABOVE FINISHED FLOOR

TEE OUT OF BOTTOM OF PIPE

AMERICANS WITH DISABILITIES ACT

GALLONS PER HOUR

GALLONS PER MINUTE

VENT THROUGH ROOF

TEXAS ACCESSIBILITIES STANDARD

DOUBLE CHECK BACKFLOW PREVENTER

TEXAS COMMISSION ON ENVIRONMENTAL QUALITY

POINT OF NEW TO EXISTING CONNECTION

DRAINAGE WASTE AND VENT

RECOVERY

HORSE POWER

TEMPERATURE

REFER TO:

TYPICAL

WITH

RD

1/4"/FT

1/8"/FT

OFD OVERFLOW DRAIN

ROOF DRAIN

FLOOR SINK

FLOOR DRAIN

BFG

DCBFP

TAS

TEMP

TCEQ

RE:

REC

GPH

HP

GPM

TYP

VTR

W/

DWV

BFF

FS

RD

ADA

AFG

AFF

OFD

FD

HW(140°)

SS

ABBREVIATION

NFWH or HB

PUMPED SANITARY WASTE

PUMPED CONDENSATE DRAIN

DOUBLE GRADE CLEANOUT

DIRECTION OF FLOW

DIRECTION OF PITCH DOWN (SLOPE)

VALVE IN RISER (TYPE AS SPECIFIED OR NOTED)

SHUT-OFF VALVE (SEE SPECIFICATIONS FOR TYPE)

NON-FREEZE WALL HYDRANT or HOSE BIBB

EXISTING PIPING TO BE REMOVED (DEMO PLAN ONLY) (INDICATE SERVICE TYPE)

PIPE TURNING AND RISING UP

PIPE TURNING AND DROPPING DOWN

PCO

WCO

GCO

DGCO

FCO

NFWH or HB

PLUG CLEANOUT

WALL CLEANOUT

GRADE CLEANOUT

RELIEF VALVE

FLOOR CLEANOUT

UNION

FOS

A

TP

G

FOR

PS

D

GW

PC

AW

AV

CD

TRAP PRIMER

NATURAL GAS

COMPRESSED AIR

FUEL OIL SUPPLY

DRAIN

FUEL OIL RETURN

GREASE LADEN WASTE

ACID WASTE

ACID WASTE VENT

EXISTING PIPING (INDICATE SERVICE TYPE)

CONDENSATE DRAIN

PCO

WCO

GCO

FCO

DGCO

A G

D

FOS

TP

PS

FOR

GW

PC

AW

AV

CD

PLUMBING LEGEND

SYMBOL

OFD

RD

COLD WATER

ROOF DRAIN

VENT

SANITARY SEWER

OVERFLOW DRAIN

HOT WATER (140°)

DESCRIPTION

V

CW

RD

OFD

COLD WATER FIXTURE UNITS CWFU'S

SWFU'SSANITARY WASTE FIXTURE UNITS

NOT TO SCALE NTS

INVERT ELEVATION OR FLOW LINE I.E.

HWHOT WATER

140HW

HOT WATER RETURN HWR

UNDERFLOOR U/F

REDUCER OR INCREASER FITTING

FIXTURE UNIT F.U.

REDUCED PRESSURE BACKFLOW PREVENTER RPBFP

140HW

RD

OFD

G A

TP

FOS

FOR

D

PS

CD

PC

GW

AW

AV

X

X

WATER HAMMER ARRESTOR WHA

XX

XX XX

XX

WH-1 MECH 108 & 111 DOMESTIC HW 55 70 10 50 RHEEM MODEL NO. XG55T12EC50U0

STORAGE

CAP GAL

GAS WATER HEATER SCHEDULE

LOCATION

TEMP RISE °F FLOW GPM

RECOVERY

MANUFACTURER AND MODEL NO.SERVES

GAS DATA

MBH INPUT

MARK

NOTES:

1.PROVIDE HEAT TRAP IN PIPING IF REQUIRED BY CODE.

2. PROVIDE AN AUTOMATIC OR MANUAL SWITCH FOR TURNING

THE WATER HEATING SYSTEM AND ACCESSORIES OFF WHEN

NOT IN USE OR WHEN BUILDING IS NOT IN USE.

3.PROVIDE APPROVED PIPE INSULATION ON ALL HW & CW PIPING.

1/2"S2 SHOP SINK 2" 2" DOUBLE COMPARTMENT, STAINLESS STEEL, 4 - LEGS, WITH BACKSPLASH & DRAIN BOARD ON EACH SIDE1/2"

1/2"SH1 SHOWER 2" 2" BUILT-UP TYPE ENCLOSURE, WITH MIXING VALVE AND SHOWER HEAD1/2"

1/2"SH2 ACCESSIBLE SHOWER 2" 2" 1/2" WIDE BUILT-UP TYPE ENCLOSURE, WITH MIXING VALVE, HAND HELD SPRAYER, SHOWER ARM, 5'-0" FLEXIBLE HOSE, IN-LINE VACUUM BREAKER, SLIDE BAR, ADA/TAS ACCESSIBLE

TMVS BY-PASS

SHUT-OFF VALVE

(NORMALLY CLOSED)

THERMOSTATIC

MIXING VALVE

STATION (TMVS)

REDUCER (TYP)

UNION (TYP)

FINISHED

FLOOR

6" FLUE

FULL SIZE FLUE

DUCT THRU ROOF

HW-140

TH

TH

HOSE

BIBB

DRAIN

FLOOR DRAIN

GAS COCK

UNION

DIRT LEG

HW SUPPLY FROM

MIXING VALVE TO

FIXTURES

EXPANSION TANK. SIZED PER

MANUFACTURER'S RECOMMENDATION

CW SUPPLY TO

WATER HEATER

AND MIXING VALVE

CHECK VALVE

WITH 1/8" HOLE

DRILLED THRU

CLAPPER

TEMPERATURE &

PRESSURE RELIEF

VALVE PIPED TO

FLOOR DRAIN

DOMESTIC WATER

HEATER

DRAIN PAN

4" THICK REINFORCED CONCRETE

HOUSEKEEPING PAD (WITH 1.4 X

1.4 WELDED WIRE FACRIC - 6" X 6"

AT THE CENTERLINE OF PAD)

G

WH

H W

-1

R E

E

NI

GNELANOI

SS

E F

O R

S

TATE O

SAXETF

P

RYAN EDWARDS

131050

NECI

L

SED

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I 'D

F

IL

E

N A

M E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

U M

B E

R

1 2 3 4 5

D

C

B

A

P-001

P L U

M B

IN

G

L E

G E

N D

G

E N

E R

A L N

O T

E S

D

E T

A

IL

A N

D S

C H

E D

U L E

S

R E

N O

V A

T

IO

N O

F B

U

IL

D

IN

G

F O

R T

W O

R T

H D

IS

T

R

IC

T

K E

N A

L L

F N

I S

A V

O Y

D R

IV

E

S U

IT

E

P H

O N

E (8

)2

-8

M R

B

M R

B

R J K

A U

G U

S T

W G

B

K F

B

L D

-P

L B

G

FINAL SUBMITTAL

12" = 1'-0"1

GAS WATER HEATER DETAIL

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

DN

CW

SS SS

HW

CW

HW

H W

C W

H W

C W

HW

CW

SS

VV

1 (TYP)

1 (TYP)

R E

E

NI

GNELANOI

SS

E F

O R

S

TATE O

SAXETF

P

RYAN EDWARDS

131050

NECI

L

SED

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I 'D

F

IL

E

N A

M E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

U M

B E

R

1 2 3 4 5

D

C

B

A

PD-101

D E

M O

L

IT

IO

N

P L A

N

F

IR

S T

F L O

O R

R E

N O

V A

T

IO

N O

F B

U

IL

D

IN

G

F O

R T

W O

R T

H D

IS

T

R

IC

T

K E

N A

L L

F N

I S

A V

O Y

D R

IV

E

S U

IT

E

P H

O N

E (8

)2

-8

A T

A T

S T

V

A U

G U

S T

W G

B

K F

B

L D

-P

L B

G

FINAL SUBMITTAL

1/8" = 1'-0"PD-101

1 DEMOLITION PLAN - FIRST FLOOR

1. DEMOLISH ALL FIXTURES AND ASSOCIATED PIPING BACK

TO EXISTING PIPING LOCATION OUTSIDE OF BUILDING.

PATCH FLOOR TO MATCH EXISTING.

2. DEMOLISH EXISTING TANK TYPE WATER HEATER AND

ASSOCIATED PIPING IN MECHANICAL ROOM. EXHAUST FLUE

IS TO REMAIN FOR RE-USE.

3. DEMOLISH EXISTING DOMESTIC SUPPLY RISER AND SHUT-

OFF VALVE. EXISTING PIPE PENETRATING WALL/GRADE IS

TO REMAIN FOR NEW CONNECTION.

4. DEMOLISH EXISTING DOMESTIC WATER SUPPLY ABOVE

CEILING.

5. EXISTING GAS METER AND REGULATOR (750 CFH).

REPLACE GAS METER AND REGULATOR ASSEMBLY WITH

NEW, ACCORDING TO THE REQUIREMENTS OF THE LOCAL

GAS SERVICE PROVIDER. DEMOLISH ALL EXISTING GAS

PIPING IN BUILDING BACK TO METER AND REGULATOR

ASSEMBLY.

6.DEMOLISH EXISTING SANITARY PIPING ON EXTERIOR WALL

TO BELOW GRADE. REMAINING PIPE BELOW GRADE TO

REMAIN FOR USE IN NEW LAYOUT.

7.DEMOLISH EXISTING LAUNDRY EQUIPMENT AND

ASSOCIATED PIPING IN THIS AREA.

NOTES BY SYMBOL " "

1. REFER TO P-001 FOR PLUMBING LEGEND, GENERAL

NOTES, DETAIL AND SCHEDULES.

GENERAL NOTES:

NORTH

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

M A

R K

D E

S C

R

IP

T

IO

N D

A T

S S

V

S S

CW

V

1 (TYP)

1 (TYP)

V V

CW

CW

HW

R E

E

NI

GNELANOI

SS

E F

O R

S

TATE O

SAXETF

P

RYAN EDWARDS

131050

NECI

L

SED

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I 'D

F

IL

E

N A

M E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

F

IL

E N

U M

B E

R

1 2 3 4 5

D

C

B

A

PD-102

D E

M O

L

IT

IO

N

P L A

N

S E

C O

N D

F L O

O R

R E

N O

V A

T

IO

N O

F B

U

IL

D

IN

G

F O

R T

W O

R T

H D

IS

T

R

IC

T

K E

N A

L L

F N

I S

A V

O Y

D R

IV

E

S U

IT

E

P H

O N

E (8

)2

-8

A T

A T

S T

V

A U

G U

S T

W G

B

K F

B

L D

-P

L B

G

FINAL SUBMITTAL

1/8" = 1'-0"PD-102

1 DEMOLITION PLAN - SECOND FLOOR

1. DEMOLISH ALL FIXTURES AND ASSOCIATED PIPING BACK

TO EXISTING PIPING LOCATION OUTSIDE OF BUILDING.

PATCH FLOOR TO MATCH EXISTING.

2. DEMOLISH EXISTING ELECTRIC WATER COOLER AND

ASSOCIATED PIPING.

3. DEMOLISH EXPOSED SANITARY PIPING ON EXTERIOR WALL

TO BELOW GROUND. PLUG REMAINING PIPE BELOW

GRADE.

NOTES BY SYMBOL " "

GENERAL NOTES:

NORTH

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1. REFER TO P-001 FOR PLUMBING LEGEND, GENERAL

NOTES, DETAIL AND SCHEDULES.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

General Sheets
Cover Sheet
G-002.1
G-002.2
G-002
G-003
G-004
G-102
Civil Sheets
C-001
C-002
C-101
CS-101
CS-102
CS-103
CS-104
CS-105
CS-106
CU-101
CU-102
C-301
C-302
CS-401
CS-402
CS-403
CS-404
CS-405
C-501
C-502
C-503
C-504
C-505
C-506
C-507
C-508
C-509
C-510
Structural Sheets
S-001
S-002
S-101
S-102
S-103
S-301
S-302
S-303
S-304
Architectural Sheets
AD101
AD102
AD111
AD112
AD201
AD202
AD203
A-100
A-101
A-102
A-103
A-104
A-111
A-112
A-120
A-201
A-202
A-203
A-301
A-302
A-303
A-304
A-305
A-306
A-307
A-308
A-309
A-310
A-321
A-322
A-401
A-402
A-403
A-404
A-405
A-406
A-501
A-502
A-503
A-504
A-505
A-511
A-512
A-513
A-514
A-520
A-521
A-601
A-602
A-621
A-622
A-801
A-901
A-902
I-101
I-102
I-531
I-611
I-901
IF101
IF102
Mechanical Sheets
M-001
MD-101
MD-102
MH-101
MH-102
M-103
M-104
M-105
M-106
M-501
M-502
M-503
M-504
M-505
M-506
M-507
M-508
M-509
M-510
M-511
M-512
M-601
M-602
M-603
Plumbing Sheets
P-001
PD-101
PD-102
PP-103
PP-104
PP-401
PP-402
PP-501
PP-502
PP-503
E-001
E-002
ED-101
ED-102
E-101
E-102
E-111
E-112
E-113
E-201
E-202
E-401
E-501
E-601
E-602
E-603
E-604
E-605
E-606
E-607
E-608
Telecomm Sheets
TN-000
TN-001
TND-101
TND-102
TN-011
TN-101
TN-102
TN-201
TN-202
TN-401
TN-402
TN-501
TN-601
TN-602
TN-603
Fire Protection Sheets
LS101
LS102
FD101
FP-001
FP-101
FP-102
FP-103
FP-501
FP-502
FP-801
FP-802
FA-001
FA-101
FA-102
FA-501
FA-601

File details come from the government source that posted it.