DEVICE SYMBOL
TECHNOLOGY SYMBOL LEGEND
DEVICE DESCRIPTION
"X" = QUANTITY OF CAT6 TPDATA OUTLET
CEILING MOUNTED
WALL MOUNTED
120 VOLT 20 AMP
QUADPLEX ELEC.
RECEPTACLE
CABLE TRAY
4" CONDUIT SLEEVES
NEW WALL PHONE
WORK AREA OUTLET
PRINTER WAO WALL
MOUNTED
"X" = QUANTITY OF CAT6 TP
"1" = (1) CAT6 TP
(NIPR WALL PHONE)
DATA OUTLET
FLOOR BOX
XD
XV
VOICE/DATA
WALL MOUNTED
"X" = QUANTITY OF CAT6 TP
DATA = CABLE
VOICE = CABLE
NEW AV WAO WALL
MOUNTED
"X" = QUANTITY OF CAT6 TP
"X" = QUANTITY OF RG6
"1" = QUANTITY OF CAT6 TP
DATA = CABLE
VOICE = CABLE
= 4" DOWN
= 4" UP
5-20R ELEC.
RECEPTACLE
L5-30R ELEC.
RECEPTACLE
LADDER RACK MOUNTED
120 VOLT 20 AMP
LADDER RACK MOUNTED
120 VOLT 20 AMP
WAP CEILING MOUNTED
NEW WIRELESS
ACCESS POINT
SECURE WORK AREA
OUTLET
"X" = QUANTITY OF STR OF SC -
SIPRNET
AACS CALL-OUT LEGEND
OPERATIONAL DOOR
(EXISTING)
PORTAL CATEGORY
DOOR IDENTIFIER
LESS SECURE SIDE
MORE SECURE SIDE
D1
161A
ACS
W
S X
X
X
XD
XV
X
PDS
WALL MOUNTED
PROTECTED
DISTRIBUTION BOX
OPERATIONAL DOOR
PORTAL CATEGORY
DOOR IDENTIFIER
LESS SECURE SIDE
MORE SECURE SIDE
D1
161A
ACS
WALL MOUNTEDALERT STROBES
WALL MOUNTEDMOTION SENSORM
MOYE IT CONSULTING, LLC
1255 CORPORATE DRIVE , SUITE 100
IRVING, TX 75038
972 887 5555
WWW.MOYECONSULTING.COM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F O
R T
S A
M H
O U
S T
O N
T
E X
A S
TN-000
T E
C H
N O
L O
G Y
A B
B R
E V
IA
T
IO
N
S A
N D
L E
G E
N D
R E
N O
V A
T
IO
N O
F B
U
IL
D
IN
G
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F
O R
T S
A M
H O
U S
T O
N T
X
K E
N A
L L
F N
I S
A V
O Y
D R
IV
E
S
U
IT
E
H O
U S
T O
N T
E X
A S
P H
O N
E (8
-8
M O
Y E
M O
Y E
M O
Y E
A U
G U
S T
W G
B
FINAL SUBMITTAL
AUGUST 12, 2019
N
N/A NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRIC
MANUFACTURERS ASSOCIATION
NIC NOT IN CONTRACT
NIPR NON-SECURE INTERNET
PROTOCOL ROUTER NETWORK
NTS NOT TO SCALE
O
OAR OWNER AUTHORIZED
REPRESENTATIVE
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER
INSTALLED
P
PDS PREMISE DISTRIBUTION SYSTEM
PVC POLYVINYL CHLORIDE
PWR POWER
Q
QTY QUANTITY
R
RCP REFLECTED CEILING PLAN
REF REFER, REFERENCE
REQD REQUIRED
REST RESTROOM
REV REVISE, REVISED, REVISION
RGS RIGID GALVANIZED STEEL
RM ROOM
RMC RIGID METALLIC CONDUIT
RU RACK UNIT
S
SCS STRUCTURED CABLING SYSTEM
SECT SECTION
SF SQUARE FEET
SIPR SECRET INTERNET PROTOCOL
ROUTER NETWORK
SMF SINGLE MODE FIBER
ST STAIR
STD STANDARD
STOR STORAGE
STP SHIELDED TWISTED PAIR
SUSP SUSPEND
SVC SERVICE
T
TBD TO BE DETERMINED
TEF TELECOM ENTRANCE FACILITY
TEMF TRANSPORTATION EQUIPMENT
MAINTENANCE FACILITY
TER TELECOM EQUIPMENT ROOM
TGB TELECOMMUNICATIONS
GROUND BUSBAR
THRU THROUGH
TMD TEXAS MILITARY DEPARTMENT
TR TELECOMMUNICATIONS ROOM
TYP TYPICAL
U
UL UNDERWRITERS
LABORATORIES, INC.
UNO UNLESS NOTED OTHERWISE
UTP UNSHIELDED TWISTED PAIR
V
VERT VERTICAL
VEST VESTIBULE
VIP VERY IMPORTANT PERSON
VTC VIDEO TELECONFERENCE
W
W/ WITH
W/O WITHOUT
WAO WORK AREA OUTLET
WAP WIRELESS ACCESS POINT
WP WEATHERPROOF
A
ABV ABOVE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
AP ACCESS POINT
ARCH ARCHITECT, ARCHITECTURAL
AWG AMERICAN WIRE GAUGE
B
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
C
C CONDUIT
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CL CENTER LINE
CLG CEILING
COMM COMMUNICATIONS
CONF CONFERENCE
CORR CORRIDOR
CR COMMUNICATIONS ROOM
D
DEMO DEMOLISH
DIA DIAMETER
DN DOWN
E
EA EACH
EF ENTRANCE FACILITY
ELEC ELECTRICAL
ELEV ELEVATOR
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EXIST EXISTING
F
FA FIRE ALARM
FACP FACP
FMS FACILITIES MAINTENANCE SHOP
FOC FIBER OPTIC CABLE
G
G,GND GROUND
GA GAUGE
GALV GALVANIZED
GUI GRAPHIC USER INTERFACE
H
HH HANDHOLE
I
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION
FRAME
IEEE INSTITUTE OF ELECTRICAL AND
ELECTRONICS ENGINEERS
J
J-BOX JUNCTION BOX
K
KVA KILOVOLT AMPERE
KW KILOWATT
L
LB POUND
LCD LIQUID CRYSTAL DISPLAY
LF LINEAR FEET
LTG LIGHTING
M
MATV MASTER ANTENNA TELEVISION
MAX MAXIMUM
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MT MOUNTED
(ALL ABBREVIATIONS SHOWN ARE NOT
NECESSARILY USED ON DRAWINGS)ABBREVIATIONS:
Sheet List
Sheet Number Sheet Name
TN-000 TECHNOLOGY ABBREVIATIONS AND LEGEND
TN-001 TECHNOLOGY GENERAL NOTES
TN-011 TECHNOLOGY SITE PLAN
TN-101 TECHNOLOGY LEVEL 1 FLOOR PLAN
TN-102 TECHNOLOGY LEVEL 2 FLOOR PLAN
TN-201 TECHNOLOGY LEVEL 1 REFLECTED CEILING PLAN
TN-202 TECHNOLOGY LEVEL 2 REFLECTED CEILING PLAN
TN-401 TECHNOLOGY ENLARGED COMM ROOM
TN-402 TECHNOLOGY ENLARGED COMM ROOM
TN-501 TECHNOLOGY RISER DIAGRAM
TN-601 TECHNOLOGY DETAILS
TN-602 TECHNOLOGY DETAILS
TN-603 TECHNOLOGY DETAILS
TND-101 TECHNOLOGY LEVEL 1 DEMO PLAN
TND-102 TECHNOLOGY LEVEL 2 DEMO PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
GENERAL NOTES:
1. DRAWINGS ARE DRAWN TO SCALE UNLESS OTHERWISE NOTED.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF
ALL SERVICES WITH EXISTING CONDITIONS AND WITH ALL OTHER TRADES.
2. IN THE INSTALLATION OF THIS WORK, THE CONTRACTOR SHALL COMPLY
IN EVERY WAY WITH THE REQUIREMENTS OF LOCAL LAWS AND
ORDINANCES, THE LAWS OF THE STATE OF TEXAS, AND THE NATIONAL
ELECTRICAL CODE.
3. CAREFULLY EXAMINE THE PREMISES TO DETERMINE THE EXTENT OF
WORK AND THE CONDITIONS UNDER WHICH IT MUST BE DONE. IF THERE
ARE ANY QUESTIONS REGARDING THE PROJECT, THE CONTRACTOR IS
RESPONSIBLE FOR OBTAINING CLARIFICATIONS FROM THE DESIGN
CONSULTANT OR THEIR DESIGNATED REPRESENTATIVE BEFORE
PROCEEDING WITH WORK OR RELATED WORK IN QUESTION.
4. ANY DISCREPANCIES BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
OAR FOR CLARIFICATION.
5. ALL WORK SHALL BE DONE IN A THOROUGH AND CONSCIENTIOUS
MANNER ACCORDING TO INDUSTRY STANDARDS AND SHALL BE SUBJECT
TO INSPECTION AND ACCEPTANCE. WORK THAT IS DEEMED
SUBSTANDARD OR NOT TO INDUSTRY STANDARD WILL BE SUBJECT TO
REPLACEMENT OR REPAIR AT NO ADDITIONAL COST TO THE OWNER OR
GENERAL CONTRACTOR.
6. CONTRACTOR TO COORDINATE ALL DEMOLITION ACTIVITIES WITH
GENERAL CONTRACTOR, OWNER AND SERVICE PROVIDERS PRIOR TO
PERFORMANCE OF ALL ACTIVITIES.
7. PRIOR TO DEMOLITION OF ANY COMMUNICATIONS COPPER OR FIBER
CABLES, CONTRACTOR SHALL VERIFY WITH DESIGN CONSULTANT AND
OWNER THAT ALL ACTIVE CIRCUITS HAVE BEEN CUT OVER OR
DEACTIVATED. DO NOT DEMO WITHOUT AUTHORIZATION FROM OWNER OR
TENANTS.
8. THE CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE, PATCH, CROSS-
CONNECT, LABEL, AND DOCUMENT COMMUNICATIONS CABLING SYSTEMS
BASED ON THE PROJECT SPECIFICATIONS AND ACCOMPANYING
DRAWINGS.
9. CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE, AND LABEL RACKS,
PATCH PANELS, WIRE MANAGEMENT AND CABLING AS DESCRIBED IN THE
DRAWINGS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER BONDING AND
GROUNDING OF THE SYSTEMS IN ACCORDANCE WITH APPLICABLE
ELECTRICAL CODES AND ANSI-J-STD-607-A.
11. ALL CONDUITS SHALL BE ROUTED TO ACCESSIBLE CEILING SPACE OR AN
ACCESS PANEL SHALL BE PROVIDED. ACCESS PANELS SHALL COMPLY
WITH FIRE CODE.
12. DIVISION 26 ELECTRICAL CONTRACTOR TO PROVIDE (1) - 4-11/16" X 4-11/16"
X 2-1/8"D BACKBOX AND SINGLE GANG DEVICE RING WITH (1) ONE-INCH
CONDUIT TO EITHER THE CABLE TRAY OR ABOVE ACCESSIBLE CEILING AS
REQUIRED FOR STANDARD, CEILING AND WALL MOUNTED
TELEPHONE/DATA COMMUNICATION WORK-AREA-OUTLETS (WAO), UNLESS
NOTED OTHERWISE.
13. COORDINATE WORK AREA OUTLET PLACEMENT WITH THE PLACEMENT OF
ELECTRICAL OUTLETS WHEREVER POSSIBLE. IN ALL CASES THERE SHALL
BE A ELECTRICAL OUTLET NO FURTHER THAN ONE STUD BAY DISTANCE
FROM A LOW VOLTAGE WAO.
14. VERIFY THAT THE INSTALLATION IS IN LINE WITH THE REQUIREMENTS OF
UFC 3-580-01/TELECOMMUNICATIONS INTERIOR INFRASTRUCTURE
PLANNING AND DESIGN WHICH STATES THAT NO OTHER SYSTEMS
UNRELATED TO THE TELECOM/COMMUNICATIONS SYSTEM SHALL PASS
THRU OR BE LOCATED IN THE COMMUNICATIONS ROOM; IT SHALL BE
DEDICATED SPACE AND NOT SHARED WITH OTHER NON-
TELECOMMUNICATIONS FUNCTIONS, EXCEPT FOR THE/A SECURITY
SYSTEM. VERIFY THAT NO FOREIGN SYSTEMS WILL OCCUPY OR PASS
THROUGH THE COMMUNICATIONS ROOMS.
GENERAL:
CONDUIT:
TELECOMM PATHWAY NOTES:
1. CONDUITS SHALL HAVE A MAXIMUM 40% FILL RATIO. CABLE TRAY SHALL
HAVE A MAXIMUM 50% FILL RATIO.
2. NON-CONTINUOUS CABLE SUPPORT SYSTEMS (J-HOOKS) INSTALLATION
AND CONFIGURATION SHALL CONFORM TO THE REQUIREMENTS OF THE
CURRENT REVISION LEVELS OF ANSI/EIA/TIA STANDARDS 568 & 569, NFPA
70 (NATIONAL ELECTRICAL CODE), APPLICABLE LOCAL CODES, AND TO
THE MANUFACTURERS INSTALLATION INSTRUCTIONS AND THE NEMA VE-2
GUIDELINES.
3. REGARDLESS OF PATHWAY TYPE, ALL CABLING SHALL BE SUPPORTED AT
A 5'-0" MAXIMUM INTERVAL.
4. UNLESS OTHERWISE NOTED, CABLE PATHWAY WITHIN ROOMS WILL RUN
PARALLEL TO WALLS.
5. UNLESS OTHERWISE NOTED ALL CONDUITS ARE ONE-INCH IN DIAMETER.
1. CONDUIT RUNS SHALL NOT CONTAIN 90° CONDUIT BODIES (OR LB'S).
2. MAINTAIN PROPER CONDUIT BEND RADIUS IN ACCORDANCE WITH
ANSI/EIA/TIA-569-B. FOR CONDUIT WITH AN INTERNAL DIAMETER OF 2" OR
LESS, MAINTAIN A BEND RADIUS OF AT LEAST 6 TIMES THE INTERNAL
CONDUIT DIAMETER. FOR CONDUIT WITH AN INTERNAL DIAMETER
GREATER THAN 2", MAINTAIN A BEND RADIUS OF AT LEAST 10 TIMES THE
INTERNAL CONDUIT DIAMETER.
3. DO NOT CONSIDER A PULL BOX AS A BEND. ALL CONDUITS MUST RUN
STRAIGHT THROUGH A PULL BOX WITH THE BEND EITHER BEFORE OR
AFTER THE PULL BOX.
4. REAM ALL CONDUIT ENDS. FIT STUBBED CONDUITS WITH AN INSULATED
BUSHING TO ELIMINATE SHARP EDGES THAT MAY DAMAGE CABLE DURING
INSTALLATION OR SERVICE. EQUIP ALL CONDUIT WITH PULL CORD WITH A
MINIMUM TEST RATING OF 200LBS.
5. ALL OUTLET BOX CONDUITS SHALL BE ROUTED TO NEAREST ACCESSIBLE
CEILING SPACE WHETHER OR NOT SHOWN AS SUCH ON DRAWINGS.
DEMOLITION GENERAL NOTES:
CONTRACTOR TO COORDINATE ALL DEMOLITION ACTIVITIES WITH
GENERAL CONTRACTOR, OWNER AND SERVICE PROVIDERS PRIOR
TO PERFORMANCE OF ALL ACTIVITIES.
CONTRACTOR SHALL COORDINATE REMOVAL OF ALL DEVICES
AND THEIR REQUIREMENT TO BE DEMOLISHED, SALVAGED,
REUSED OR RELOCATED WITH THE GENERAL CONTRACTOR AND
OWNER PRIOR TO DEMOLITION.
EXISTING HORIZONTAL OUTLET CONDUITS INSIDE WALLS ARE TO
REMAIN. INCLUDING THE BACKBOX AND CONDUIT UP TO
ACCESSIBLE CEILING. THE EXISTING DATA CABLING IS TO BE
DEMOLISHED AS PART OF THIS WORK. THE PATHWAY SHALL
REMAIN AVAILABLE FOR FUTURE USE DURING CONSTRUCTION
WHERE APPROPRIATE AND APPROVED.
CONTRACTOR MUST RETURN ALL ACTIVE EQUIPMENT AND
ELECTRONICS REMOVED AS PART OF THE DEMOLITION SCOPE TO
OWNER. ALL EQUIPMENT MUST BE REMOVED, STORED, LOGGED
AND LABELED CAREFULLY.
PRIOR TO DEMOLITION OF ANY COMMUNICATIONS COPPER OR
FIBER CABLES, CONTRACTOR SHALL VERIFY WITH DESIGN
CONSULTANT AND OWNER THAT ALL ACTIVE CIRCUITS HAVE BEEN
CUT OVER OR DEACTIVATED. DO NOT DEMO WITHOUT
AUTHORIZATION FROM OWNER OR TENANTS.
CONTRACTOR SHALL PROTECT ANY EQUIPMENT IN THE
DESIGNATED DEMOLITION AND/OR CONSTRUCTION AREA FROM
DAMAGE PRIOR TO COMMENCING WORK.
REMOVAL OF EQUIPMENT AND DEVICES SHALL INCLUDE
BRACKETS, CABLING, CONDUIT, JUNCTION BOXES, MOUNTING
HARDWARE, TRIM PIECES AND RELATED EQUIPMENT HARDWARE.
ITEMS SHOWN ON DRAWINGS MAY NOT BE DRAWN TO EXACT
SCALE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING
EXACT ROUTING OF ALL SERVICES WITH EXISTING CONDITIONS
AND WITH OTHER TRADES.
IN THE EXECUTION OF THIS WORK, THE CONTRACTOR SHALL
COMPLY IN EVERY WAY WITH THE REQUIREMENTS OF LOCAL
LAWS AND ORDINANCES, THE LAWS OF THE STATE OF TEXAS,
THE NATIONAL BOARD OF FIRE UNDERWRITERS, AND THE
NATIONAL ELECTRICAL CODE.
CAREFULLY EXAMINE THE PREMISES TO DETERMINE THE EXTENT
OF WORK AND CONDITION UNDER WHICH IT MUST BE DONE. IF
THERE ARE ANY QUESTIONS REGARDING THE PROJECT, THE
CONTRACTOR IS RESPONSIBLE FOR OBTAINING CLARIFICATIONS
FROM THE DESIGN CONSULTANT, OR THEIR DESIGNATED
REPRESENTATIVE BEFORE PROCEEDING WITH WORK OR RELATED
WORK IN QUESTION.
ANY DISCREPANCIES BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION
OF THE OWNER AUTHORIZED REPRESENTATIVE OR THEIR
DESIGNATED REPRESENTATIVE FOR CLARIFICATION.
ALL WORK SHALL BE DONE IN A THOROUGH AND CONSCIENTIOUS
MANNER ACCORDING TO INDUSTRY STANDARDS AND SHALL BE
SUBJECT TO INSPECTION AND ACCEPTANCE. WORK THAT IS
DEEMED SUB-STANDARD OR NOT TO INDUSTRY STANDARD WILL
BE SUBJECT TO REPLACEMENT OR REPAIR AT NO ADDITIONAL
COST TO THE OWNER OR GENERAL CONTRACTOR.
PRIOR TO STARTING THE INSTALLATION, THE ASSIGNED
INSTALLATION SUPERVISOR OR LEAD TECHNICIAN SHALL
PARTICIPATE IN A WALK-THROUGH OF THE PROJECT LOCATION
WITH THE DESIGN CONSULTANT, OR THEIR DESIGNATED
REPRESENTATIVE, TO REVIEW THE INSTALLATION
DOCUMENTATION.
THE CONTRACTOR IS REQUIRED TO PROPERLY FIRESTOP ANY
CORES, UTILIZED FOR THE PLACEMENT OF COMMUNICATIONS
CABLING, WITH APPROVED FIRESTOPPING COMPOUND AND
ACCORDING TO LOCAL AND NATIONAL CODES.
COMPLETION OF THIS WORK MUST BE COORDINATED WITH WORK
BEING PERFORMED UNDER CONCURRENT, ADJACENT PROJECTS.
CONTRACTOR SHALL COORDINATE WITH OWNER AND OTHER
CONTRACTORS AS REQUIRED REGARDING SCHEDULE, PATHWAYS,
LABELING, TESTING, ET AL.
COORDINATE TELECOM PATHWAYS WITH OTHER CONDUIT.
CONTRACTOR TO PERFORM DEMOLITION OF CABLING BEGINNING
AT ENDS OF THE CABLING RUN TO VERIFY CONNECTIVITY STATUS.
REGARDLESS OF ANY CABLING LABELS ATTACHED TO SUBJECT
RUN.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
IT SYSTEMS OVERVIEW:
TECHNOLOGY SYSTEMS OVERVIEW
THIS DRAWING PACKAGE CONSISTS OF TECHNOLOGY SYSTEMS INFRASTRUCTURE
REQUIRED IN THE DEMOLITION, CONSTRUCTION AND RENOVATION OF THE EXISTING
FACILITY. THIS PACKAGE PROVIDES LOCATIONS OF DEVICE AND CABLING
TERMINATIONS, MAJOR CABLING PATHWAY ACCOMMODATIONS AND
COMMUNICATIONS ROOMS REQUIREMENTS. THE TECHNOLOGY SYSTEMS INCLUDED
IN THIS PACKAGE ARE IDENTIFIED BELOW.
DEMOLITION
CONTRACTOR IS RESPONSIBLE FOR DEMOLITION OF ALL VOICE/DATA SYSTEMS
CABLING WITHIN THE SCOPE OF WORK BOUNDARIES. CONTRACTOR MUST PROTECT
AND LABEL ALL INFRASTRUCTURE SHOWN ON DRAWINGS TO REMAIN THROUGHOUT
CONSTRUCTION. ALL PHONE, NETWORK SWITCHGEAR AND AUDIO-VISUAL END
DEVICES SHALL BE REMOVED AND RETURNED TO THE OWNER FOR FUTURE USE.
CONTRACTOR SHALL RETURN ANY ADDITIONAL NETWORK EQUIPMENT FOUND IN
DEMOLITION AREA TO OWNER FOR RE-USE OR DISPOSAL.
BUSINESS CONTINUITY AND SELECTIVE DEMOLITION
THE CURRENT COPPER AND FIBER BACKBONE INFRASTRUCTURE WILL BE REQUIRED
TO BE DISCONNECTED,COILED, TAGED AND PROTECTED. CONTRACTOR SHALL LABEL
AND PROTECT THE BACKBONE CABLING AT THE ENTRACE CONDUIT THROUGH OUT
CONSTRUCTION. ONCE THE NEW COMMUNICATION ROOM ARE BUILT, THE
CONTRACTOR SHALL ROUTE THE PROTECTED CABLES, TERMINATE AND TEST THE
CABLES IN THE NEW RACK AND WALL MOUNTED TERMINAL BLOCK. THOROUGH
COORDINATION BETWEEN THE OWNER AND CONTRACTOR IS REQUIRED.
COMMUNICATIONS ROOMS
HORIZONTAL CABLING
CONTRACTOR SHALL INSTALL ALL NEW COMMUNICATIONS ROOM INFRASTRUCTURE
AS INDICATED ON DRAWINGS. THIS INCLUDES WALL/FLOOR PENETRATIONS, WORK
AREA OUTLETS, EQUIPMENT CABINETS/RACKS, ETC. INDICATED ON PLANS UNLESS
NOTED OTHERWISE.
CONTRACTOR SHALL INSTALL ALL HORIZONTAL CABLING INFRASTRUCTURE,
INCLUDING CONDUIT AND CABLE TRAY, AS REQUIRED ON THE DRAWINGS AND
SPECIFICATIONS. INSTALL PHONE AND DATA OUTLETS AND CABLE FROM THE
NEAREST COMMUNICATIONS ROOM, UNLESS NOTED OTHERWISE. PROVIDE COPPER
PATCH CABLES FOR ALL INSTALLED OUTLETS AS REQUIRED IN SPECIFICATIONS.
INTRUSION DETECTION SYSTEM
CONTRACTOR SHALL PROVIDE AND INSTALL NEW INTRUSION DETECTION PANELS,
KEYPADS, MOTION SENSORS,ALERT STROBES, ALL ASSOCIATED PATHWAYS AND
CABLING.
MOYE IT CONSULTING, LLC
1255 CORPORATE DRIVE , SUITE 100
IRVING, TX 75038
972 887 5555
WWW.MOYECONSULTING.COM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F O
R T
S A
M H
O U
S T
O N
T
E X
A S
TN-001
T E
C H
N O
L O
G Y
G E
N E
R A
L N
O T
E S
R E
N O
V A
T
IO
N O
F B
U
IL
D
IN
G
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F
O R
T S
A M
H O
U S
T O
N T
X
K E
N A
L L
F N
I S
A V
O Y
D R
IV
E
S
U
IT
E
H O
U S
T O
N T
E X
A S
P H
O N
E (8
-8
D e s ig n e r
A u th o r
C h e c k e r
A U
G U
S T
W G
B
FINAL SUBMITTAL
AUGUST 12, 2019
SECURITY GENERAL NOTES
A. THE TEXAS DEPARTMENT OF PUBLIC SAFETY REQUIRES THAT PORTIONS OF
THIS WORK, DEFINED AS REGULATED UNDER THE PROVISIONS OF SB 1252,
78TH LEGISLATIVE SESSION OF THE STATE OF TEXAS, BE PERFORMED BY A
CONTRACTOR HOLDING A VALID AND CURRENT CLASS B SECURITY
CONTRACTOR COMPANY LICENSE.
B. ALL WORK ON THE ACCESS CONTROL SYSTEM AND VIDEO SURVEILLANCE
SYSTEM SHALL BE PERFORMED BY THE OWNER'S APPROVED SECURITY
CONTRACTOR.
C. ALL WORK SHALL BE DONE IN A THOROUGH AND CONSCIENTIOUS MANNER
ACCORDING TO INDUSTRY STANDARDS AND SHALL BE SUBJECT TO
INSPECTION AND ACCEPTANCE. WORK THAT IS DEEMED SUB-STANDARD OR
NOT TO INDUSTRY STANDARD WILL BE SUBJECT TO REPLACEMENT OR REPAIR
AT NO ADDITIONAL COST TO THE OWNER OR GENERAL CONTRACTOR.
D. IN THE EXECUTION OF THIS WORK, THE CONTRACTOR SHALL COMPLY IN EVERY
WAY WITH THE REQUIREMENTS OF LOCAL LAWS AND ORDINANCES, THE LAWS
OF THE STATE OF TEXAS, AND THE NATIONAL ELECTRICAL CODE.
E. DRAWINGS ARE DRAWN TO SCALE UNLESS OTHERWISE NOTED. CONTRACTOR
IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL SERVICES WITH
EXISTING CONDITIONS AND WITH ALL OTHER TRADES.
F. CAREFULLY EXAMINE THE PREMISES TO DETERMINE THE EXTENT OF WORK
AND THE CONDITIONS UNDER WHICH IT MUST BE DONE. IF THERE ARE ANY
QUESTIONS REGARDING THE PROJECT, THE CONTRACTOR IS RESPONSIBLE
FOR OBTAINING CLARIFICATIONS FROM THE DESIGN CONSULTANT OR THEIR
DESIGNATED REPRESENTATIVE BEFORE PROCEEDING WITH WORK OR
RELATED WORK IN QUESTION.
G. ANY DISCREPANCIES BETWEEN THESE PLANS AND ACTUAL FIELD CONDITIONS
MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT/DESIGN
CONSULTANT OR THEIR DESIGNATED REPRESENTATIVE FOR CLARIFICATION.
H. PRIOR TO STARTING THE INSTALLATION, THE ASSIGNED INSTALLATION
SUPERVISOR OR LEAD TECHNICIAN SHALL PARTICIPATE IN A WALK THROUGH
OF THE PROJECT LOCATION WITH THE DESIGN CONSULTANT, OR THE
DESIGNATED OWNERS AUTHORIZED REPRESENTATIVE, TO REVIEW THE
INSTALLATION.
I. COMPLETION OF THIS WORK MAY RELY ON PRIOR COMPLETION OF WORK
BEING PERFORMED UNDER CONCURRENT, ADJACENT PROJECTS.
CONTRACTOR SHALL COORDINATE WITH OTHER CONTRACTORS AND
SUBCONTRACTORS REGARDING SCHEDULE, PATHWAYS, EQUIPMENT
ADDRESSING, TESTING, ET AL.
J. CONTRACTORS AND SUBCONTRACTORS SHALL COOPERATE AND BEAR ALL
COSTS TO REPRESENT INSTALLED COMPONENTS WITHIN THIS SCOPE OF
WORK, AS NECESSARY AND TO TEST AND TROUBLESHOOT INSTALLATION,
CONFIGURATION, AND ROUTING FOR THE DEPENDENT LOW VOLTAGE
SYSTEMS.
K. REFERENCE ALL OTHER LOW VOLTAGE SHEETS THAT CORRESPOND TO THIS
WORK, SUCH AS PREMISE DISTRIBUTION AND PUBLIC ADDRESS, AS THERE MAY
BE PARALLEL WORK ACROSS SYSTEMS.
L. NO IP CAMERA CABLE SHALL BE ANY LONGER THAN (90) METERS. IF THE
CONTRACTOR BELIEVES ANY IP CAMERA CABLE WILL BE LONGER THAN (90)
METERS, WRITTEN APPROVAL FROM THE DESIGN CONSULTANT WILL BE
REQUIRED PRIOR TO INSTALLATION.
M. THE CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE, PATCH,
CROSS-CONNECT, LABEL, AND DOCUMENT SECURITY CABLING SYSTEMS
BASED ON THE PROJECT SPECIFICATIONS AND ACCOMPANYING DRAWINGS.
N. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER BONDING AND
GROUNDING OF THE SYSTEMS IN ACCORDANCE WITH APPLICABLE ELECTRICAL
CODES AND ANSI-J-ST0-607-C.
O. CONTRACTOR SHALL LABEL RACKS, FIELD PANELS, FIELD DEVICES, PATCH
PANELS, AND CABLING AS DESCRIBED IN THE SPECIFICATIONS AND DRAWINGS.
P. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE OWNER BEFORE
PLACING ANY DOOR OR CAMERA INTO SERVICE.
M A
R K
D E
S C
R
IP
T
IO
N D
A
DN
C
SSS
S SSSS
S
S
S
S
S
S S
T303
T303T303
T303
T303
T303
T303
EE
EF
E7.2 E7.8
E
D
C
W1 W2 W3 W4 W5 W6 W7 W8 W9 W10W11 W12 W13 W14 W15 W16 W17 W18
WA
WB
WC
WD
EA
EB
EC
ED
E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 E12
T301T301
T308T308
T307
T304
MOYE IT CONSULTING, LLC
1255 CORPORATE DRIVE , SUITE 100
IRVING, TX 75038
972 887 5555
WWW.MOYECONSULTING.COM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F O
R T
S A
M H
O U
S T
O N
T
E X
A S
TND-101
T E
C H
N O
L O
G Y
L E
V E
L
D E
M O
P L
A N
R E
N O
V A
T
IO
N O
F B
U
IL
D
IN
G
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F
O R
T S
A M
H O
U S
T O
N T
X
K E
N A
L L
F N
I S
A V
O Y
D R
IV
E
S
U
IT
E
H O
U S
T O
N T
E X
A S
P H
O N
E (8
-8
M O
Y E
M O
Y E
M O
Y E
A U
G U
S T
W G
B
FINAL SUBMITTAL
AUGUST 12, 20191/8" = 1'-0"TND-101
A1 DEMOLITION PLAN - FIRST FLOOR
0' 8' 16'
GRAPHIC SCALE 1/8" = 1'-0"
4'NORTH
Sheet Keynote Summary
Key Value Keynote Text
T301 EXISTING ENTRANCE
CONDUITS. COIL AND
PROTECT EXISTING COPPER
AND FIBER OPTIC ENTRANCE
CABLES THROUGH OUT
CONSTRUCTION. SALVAGE
EXISTING PROTECTOR
BLOCKS. ENTRANCE CABLES
MAY NEED TO PULL BACK TO
NEAREST MAINTENANCE
HOLE. CONTRACTOR TO
CONFIRM LOCATION OF
NEAREST MAINTENANCE
HOLE.
T303 GENERAL LOW VOLTAGE
DEMOLITION BOUNDARY
AREA. CONTRACTOR TO
DEMO ALL LOW VOLTAGE
CABLING AND PATHWAY WITH
IN BOUNDARY BACK TO
POINT OF ORIGIN, UNLESS
NOTED OTHERWISE. RETURN
TO OWNER ANY AND ALL
SECURITY PANELS, RACKS,
AND NETWORK EQUIPMENT,
T304 EXISTING SURVEILLANCE
CAMERA REMOVE AND
SALVAGE FOR
REINSTALLATION.(TYPICAL)
T307 EXISTING COMMUNICATION
RACK. REMOVE AND RETURN
RACK AND ANY EQUIPMENT
TO OWNER.
T308 EXISTING 12" LADDER TRAY.
SALVAGE AND REUSE 12"
LADDER TRAY.
M A
R K
D E
S C
R
IP
T
IO
N D
A
C
S
S
S
S
S
S
P
C
C
S
S
C
P
T303
T303
T303
T303 T303
T303
EE
EF
E7.2 E7.8
E
D
C
W1 W2 W3 W4 W5 W6 W7 W8 W9 W10W11 W12 W13 W14 W15 W16 W17 W18
WA
WB
WC
WD
EA
EB
EC
ED
E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 E12
T304
T304
T306
T304
T302
T304
T305 T305
T305
T305
MOYE IT CONSULTING, LLC
1255 CORPORATE DRIVE , SUITE 100
IRVING, TX 75038
972 887 5555
WWW.MOYECONSULTING.COM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F O
R T
S A
M H
O U
S T
O N
T
E X
A S
TND-102
T E
C H
N O
L O
G Y
L E
V E
L
D E
M O
P L
A N
R E
N O
V A
T
IO
N O
F B
U
IL
D
IN
G
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F
O R
T S
A M
H O
U S
T O
N T
X
K E
N A
L L
F N
I S
A V
O Y
D R
IV
E
S
U
IT
E
H O
U S
T O
N T
E X
A S
P H
O N
E (8
-8
M O
Y E
M O
Y E
M O
Y E
A U
G U
S T
W G
B
FINAL SUBMITTAL
AUGUST 12, 20191/8" = 1'-0"TND-102
A1 DEMOLITION PLAN - SECOND FLOOR
Sheet Keynote Summary
Key Value Keynote Text
T302 EXISTING ACCESS CONTROL
PANEL. REMOVE AND
RETURN TO OWNER.
(TYPICAL)
T303 GENERAL LOW VOLTAGE
DEMOLITION BOUNDARY
AREA. CONTRACTOR TO
DEMO ALL LOW VOLTAGE
CABLING AND PATHWAY WITH
IN BOUNDARY BACK TO
POINT OF ORIGIN, UNLESS
NOTED OTHERWISE. RETURN
TO OWNER ANY AND ALL
SECURITY PANELS, RACKS,
AND NETWORK EQUIPMENT,
T304 EXISTING SURVEILLANCE
CAMERA REMOVE AND
SALVAGE FOR
REINSTALLATION.(TYPICAL)
T305 EXISTING AV EQUIPMENT.
RETURN ALL AV EQUIPMENT
TO OWNER.
T306 EXISTING ALERT STROBES
REMOVE AND SALVAGE FOR
REINSTALLATION.(TYPICAL)
M A
R K
D E
S C
R
IP
T
IO
N D
A
F R
A N
K S
T
IN
F
A N
T R
Y P
O S
T R
D
13'-0"
MINIMUM STAND OFF
EXIT
MAIN
ENTRANCE
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
BOLLARDS
GATE
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
P A
R K
IN
G
FSH
PERIMETER
FENCE
FSH
PERIMETER
FENCE
B615
80' - 0"
CONVENTIONAL
CONSTRUCTION
STAND OFF
P A
R K
IN
G
P A
R K
IN
G
B606
B607
B617
B609
B616
MOYE IT CONSULTING, LLC
1255 CORPORATE DRIVE , SUITE 100
IRVING, TX 75038
972 887 5555
WWW.MOYECONSULTING.COM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F O
R T
S A
M H
O U
S T
O N
T
E X
A S
TN-011
T E
C H
N O
L O
G Y
S
IT
E P
L A
N
R E
N O
V A
T
IO
N O
F B
U
IL
D
IN
G
J O
IN
T
B A
S E
S A
N A
N T
O N
IO
F
O R
T S
A M
H O
U S
T O
N T
X
K E
N A
L L
F N
I S
A V
O Y
D R
IV
E
S
U
IT
E
H O
U S
T O
N T
E X
A S
P H
O N
E (8
-8
M O
Y E
M O
Y E
M O
Y E
A U
G U
S T
W G
B
FINAL SUBMITTAL
AUGUST 12, 2019
1" = 20'-0"TN-011
A1 SITE PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A
| General Sheets |
| Telecomm Sheets |
| TN-000 |
| TN-001 |
| TND-101 |
| TND-102 |
| TN-011 |