33_52_43.12.pdf

PDF 27 KB Posted

Attached to
DESC1802 Replace POL Facilities Hill AFB, UT
Solicitation number
W91238-18-R-0020
Issued by

About this file

Revised Spec - 33 52 43.12

View the file

Other files

File Type Posted
Appendix_1-Revised-Drawings-Am-0009.PDF PDF
W912838-18-R-0020-Am_0009_Narrative.pdf PDF
W91238-18-R-0020-0009.pdf PDF
Appendix_2-Revised-Specifications-Am-0009.pdf PDF
W91238-18-R-0020-0008.pdf PDF
Attachment_26_-_Price_Breakout_Schedule.xlsx XLSX spreadsheet
Amendment_0007_Narrative.pdf PDF
W91238-18-R-0020-0007.pdf PDF
Revised_Specifications_2.pdf PDF
Revised_Drawings_5.PDF PDF
Appendix_1b_-_Drawings-Am-6-2.docx DOCX document
W91238-18-R-0020-0006.pdf PDF
Appendix_1c_-_Drawings-Am-6-3.docx DOCX document
Appendix_1a_-_Drawings-Am-6-1rev.docx DOCX document
Appendix_2-Specifications-Am-6.pdf PDF
W912838-18-R-0020-Am_0006_Narrative.pdf PDF
Attachment_2_-_Revised_Supplemental_Contract_Requirements.pdf PDF
Appendix_1d_-_Drawings-Am-6-4.docx DOCX document
W91238-18-R-0020-0005.pdf PDF
POL_Pumphouse_Site_Walk_Photos_28_Aug.pdf PDF
Pre-Proposals_Site_Visit_Sign-In.pdf PDF
W912838-18-R-0020-Am-0002-Drawings.pdf PDF
33_52_43.11.pdf PDF
33_52_43.23.pdf PDF
33_52_43.28.pdf PDF
33_52_43.14.pdf PDF
33_52_43.13.pdf PDF
33_56_10.pdf PDF
W91238-18-R-0020-0004_-_SF30.pdf PDF
W912838-18-R-0020-Am_00001_Narrative.docx DOCX document
W91238-18-R-0020-0003_-_Change_Project_Title.pdf PDF
W91238-18-R-0020-0001_-_Correct_Proposals_Due_Date.pdf PDF
Appendix_1e_-_Drawings_5.pdf PDF
Attachment_5_-_Cover_Letter.DOCX DOCX document
Appendix_1b_-_Drawings_2.pdf PDF
Attachment_7_-_Truck_Offload_FONSI.pdf PDF
Appendix_2_-_Specifications_for_Construction.pdf PDF
Attachment_1_-_SOW_Replace_POL_Facilities.DOCX DOCX document
Attachment_3_-_Wage_Determinations.docx DOCX document
Attachment_2_-_Supplemental_Contract_Requirements.docx DOCX document
Attachment_6_-_Truck_Offload_Environmental_Assessment.pdf PDF
Attachment_4_-_Acknowledgement_Statement.DOCX DOCX document
Appendix_1a_-_Drawings_1.pdf PDF
W91238-18-R-0020_-_SF1442.pdf PDF
Attachment_8_-_Site_Walk_Instructions.docx DOCX document
Appendix_1d_-_Drawings_4.pdf PDF
Appendix_1c_-_Drawings_3.pdf PDF
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Replace POL Facilities, Hill AFB, Utah HU05

SECTION TABLE OF CONTENTS

DIVISION 33 - UTILITIES

SECTION 33 52 43.12

AVIATION FUEL PANTOGRAPHS

02/10

PART 1 GENERAL

1.1 REFERENCES

1.2 ADMINISTRATIVE REQUIREMENTS

1.3 SUBMITTALS

1.4 QUALITY ASSURANCE

1.4.1 Design Conditions

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Piping

2.1.2 Fitting and Bends

2.1.3 Components

2.1.4 Structural Steel

2.2 EQUIPMENT AND MATERIAL

2.2.1 Truck Fill Stand Pantograph Fabrication - (Non-Recessable)

2.2.2 Flanged Swivel Joints

2.2.3 Not Used

2.2.4 Sampling Connection

2.2.5 Pressure gage assembly

2.2.6 Drain and Vent Assemblies

2.2.7 Shut-Off Valve

2.2.8 Dry Break Quick Disconnect

2.2.9 Pressure Fueling Nozzle

2.2.10 Aviation Fuel Hose

2.2.11 Pantograph Control Valve

PART 3 EXECUTION

3.1 ASSEMBLY

3.2 TESTING

-- End of Section Table of Contents --

SECTION 33 52 43.12 Page 1 Revised in Accordance with Am #0002

SECTION 33 52 43.12

AVIATION FUEL PANTOGRAPHS

02/10

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

ASME INTERNATIONAL (ASME)

ASME B16.5 (2013) Pipe Flanges and Flanged Fittings:

NPS 1/2 Through NPS 24 Metric/Inch Standard

ASME B40.100 (2013) Pressure Gauges and Gauge Attachments

ASTM INTERNATIONAL (ASTM)

ASTM A312/A312M (2014b) Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes

ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel

ENERGY INSTITUTE (EI)

EI 1529 (2005; 6th Ed) Aviation Fueling Hose and Hose Assemblies

SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)

SAE AS5877 (2007; Rev A) Aircraft Pressure Refueling Nozzle

U.S. AIR FORCE (USAF)

AFI 91-202 (1998; Change 2010) US Air Force Mishap Prevention Program

1.2 ADMINISTRATIVE REQUIREMENTS

Provide aircraft pantograph approved by the Air Force System Safety Engineer Analysis (AFSSEA) Team in accordance with AFI 91-202. Submit scaled assembly drawings identifying components and showing dimensions and tolerances. Complete technical literature shall be submitted on specific function equipment. OMSI information shall be submitted for the equipment items or systems specified. Refer to Section 01 78 23.33 OPERATION AND MAINTENANCE MANUALS FOR AVIATION FUEL SYSTEMS for the information to be submitted for various types of equipment and systems. Emergency dry breakaway coupler (EDBC) is required for USN/USMC projects.

SECTION 33 52 43.12 Page 2

1.3 SUBMITTALS

[*Am-2] Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Scaled assembly drawings; G-OMA

SD-03 Product Data

Shut-off valve; G-OMA

Pressure fueling nozzle; G-OMA

Flanged Swivel joints; G-OMA Pressure gage assembly; G-OMA

SD-07 Certificates

Materials; G-RO

SD-10 Operation and Maintenance Data

Shut-off valve; G-OMA

Pressure fueling nozzle; G-OMA

Flanged Swivel joints; G-OMA Pressure gage assembly; G-OMA

1.4 QUALITY ASSURANCE

1.4.1 Design Conditions

[*Am-2] Design shall be as specified in Section 33 52 43.11 AVIATION FUEL MECHANICAL EQUIPMENT. Components shall be ASME B16.5 Class 150 ( 275 psig at 100 degrees F, except that swivel joints and pressure fueling nozzles shall be 125 psig at 100 degrees F). Nominal diameters shall be as follows:

Hydrant coupler 4 inch Piping sections 3 and 4 inch Flanged connection ASME B16.5 125 LB

[Text Deleted] Shut-off valve/40 mesh strainer 2-1/2 or 3 inch Dry break quick disconnects 2-1/2 or 3 inch Flanged pantograph swivel joints 3 and 4 inch Pressure fueling nozzle 2-1/2 inch outlet

SECTION 33 52 43.12 Page 3

PART 2 PRODUCTS

2.1 MATERIALS

The type of materials which come in contact with the fuel shall be noncorrosive. No zinc coated metals, brass, bronze or other copper bearing alloys shall be used in contact with the fuel. Additional requirements are as follows:

2.1.1 Piping

Construct all pipe and piping components of Schedule 10S, Grade TP304L, stainless steel conforming to ASTM A312/A312M. Only seamless pipe will be used.

2.1.2 Fitting and Bends

Same thickness as adjoining pipe.

2.1.3 Components

Stainless steel.

2.1.4 Structural Steel

Structural steel shall conform to ASTM A36/A36M, hot dipped galvanized after fabrication and painted a factory standard color.

2.2 EQUIPMENT AND MATERIAL

2.2.1 Truck Fill Stand Pantograph Fabrication - (Non-Recessable)

a. Truck fill stand pantographs shall consist of three main sections, plus one connecting section and one dispensing end. Total length of the three main sections shall be 10 feet.

b. The dispensing end shall be designed to be coupled to the refueling truck at heights of 12 to 55 inches above the road.

c. The dispensing end shall be supported by an adjustable spring, weight device or hydraulically actuated cylinder to counter balance the weight of the pressure fueling nozzle, shut-off valve, flanged swivel joints and connecting pipes to ensure that only minimum force occurs when connecting pantograph to tank trucks. One person shall be able to operate the dispensing end. Pantograph shall be provided with a nozzle hanging support.

d. Hoses shall not be permitted as a part of the truck fill stand pantograph.

e. The three main sections of the pantograph shall be locked together when stored.

f. The overall electrical resistance between the flanged end and the pressure fueling nozzle shall not exceed 1 kilo Ohm. Grounding straps across the swivel joints are not permitted.

g. The pantograph shall be equipped with a permanent sampling, pressure gage, drain and vent assemblies.

SECTION 33 52 43.12 Page 4

h. The connecting section and the dispensing end shall be locked to the main sections of the pantograph when in the stored mode.

2.2.2 Flanged Swivel Joints

a. Anchor end, intermediate, and hose end pantograph swivel joints shall be stainless steel, single plane, flanged capable of rotating 360 degrees. Welded swivel joints and welding of swivel joints to the pipe and/or elbow is not permitted. Welding of swivel joints to flange joints is permitted. Swivel joints shall be of the non-lubricated, maintenance free type with non-lubricated bearings and no lubricating fittings.

b. No leakage shall be permitted under positive or negative pressure conditions. No leakage shall be permitted under high or low temperature conditions. The swivel joints shall be warranted for three years against leakage due to both positive and negative pressure conditions.

c. There must be electrical continuity from one flange to the other without the use of ground straps. The electrical continuity from one flange to another (without the use of ground straps) shall be less than 1000 ohms. Each swivel joint shall have at least two ball bearings and one roller bearing and two seals.

[*Am-2]

2.2.3 Not Used

2.2.4 Sampling Connection

Sampling connection shall be provided. Materials shall be Type 316 stainless steel. Material for ball valve, quick disconnect coupling shall be Type 316 stainless steel. Each sampling connection shall consist of a 1/4-inch sampling probe where the probe faces upstream, ball valve, a quick disconnect coupling and aluminum dust cap. The sampling connections shall be capable of accepting a sampling kit for drawing the samples required to assure fuel quality. Provide a 3-foot, fuel resistant sampling hose with mating quick disconnect fitting.

2.2.5 Pressure gage assembly

Assembly shall consist of 4-inch ASME B40.100 pressure gage and pressure gage stop cock. Pressure gage shall be liquid filled type with an indicating range 0-275 psig. Material shall be Type 316 stainless steel.

2.2.6 Drain and Vent Assemblies

Assemblies shall consist of a 1/2 inch ball valve and shall terminate with a 180 degree pipe gooseneck and screwed cap for the vent, and the drain shall have a 1/2 inch ball valve and shall terminate with a cam type quick disconnect.

2.2.7 Shut-Off Valve

A 3-inch shutoff valve shall be mounted upstream of the pressure fueling nozzle and shall provide safe shutoff of the pantograph for inspection of the dry break quick disconnect strainer.

SECTION 33 52 43.12 Page 5

2.2.8 Dry Break Quick Disconnect

A 3-inch semi-dry break quick disconnect (MIL-DTL-24788, Class 1 or equivalent) shall be mounted between the shut-off valve hose end and the pressure fueling nozzle. The semi-dry break quick disconnect shall be capable of swiveling through 360 degrees and shall incorporate a 60 mesh strainer in the portion attached to the pressure refueling nozzle (also known as the male half).

[*Am-2]

2.2.9 Pressure Fueling Nozzle

SAE AS5877, 2-1/2-inch nozzle D-3 [Text Deleted] shall be provided for the connection between pantograph and aircraft. Design shall be for single point fueling of truck at a flow rate of 600 gpm with maximum pressure drop of 30 psig. Nozzle shall be provided with a permanently installed quick disconnect sampling coupler. (Gammon GTP-235-3/8 Jet Test QD meets this requirement.) Provide pressure gage with 0-100 psig indicating range mounted on actuator for use with quick disconnect sampling coupler.

2.2.10 Aviation Fuel Hose

Fueling hose shall conform to EI 1529, Grade 2, Type C, semi-hardwall, 3 -inch nominal hose designed for use with specified fuel for a working pressure of 300 PSIG over a working temperature range of -22 to 131 degrees F. Hose shall be constructed of braided synthetic cord surrounded by an interior rubber tube and an exterior rubber cover. Provide permanent brass, threaded, male NPT, both ends.

2.2.11 Pantograph Control Valve

Refer to Section 33 52 43.14 AVIATION FUEL CONTROL VALVES.

PART 3 EXECUTION

3.1 ASSEMBLY

The pantograph shall be delivered completely assembled.

3.2 TESTING

The pantograph shall be tested as described in Section 33 08 53 AVIATION

FUEL DISTRIBUTION SYSTEM START-UP.

-- End of Section --

SECTION 33 52 43.12 Page 6