Water Testing and Evaluation Report, Lake Isabella Dam
January 2017
Prepared by
SOIL DESIGN SECTION
GEOTECHNICAL ENGINEERING BRANCH
Water Testing and Evaluation Report, Lake Isabella Dam
Table of Contents
1. GENERAL INFORMATION
2. MATERIAL REQUIREMENTS
3. MATERIAL SOURCES
4. MATERIAL EVALUATION
5. RECOMMENDATION
6. CONCLUSION
APPENDICES
APPENDIX 1: FY12 Water Testing Laboratory Results, Kern River water testing.
APPENDIX 2: FY14 -15 Water Testing Laboratory Results, Lake Isabella Reservoir and Auxiliary Dam well water testing.
1. General Information Water will be required for aggregate production and processing, moisture conditioning aggregates for handling and compaction, concrete surface preparation and joint cleaning, rock foundation surface preparation, cleaning drill holes, mixing and curing concrete and grout mixtures, and other miscellaneous applications. The objective of this report is to provide information on water quality for the on-site water sources to support the Lake Isabella project.
2. Material Requirements Water must be clean, free of organic material, sediments, and contaminants that interfere with cement hydration. Water from on-site water sources must conform to CRD-C 400 and ASTM C1602.
3. Material Sources Three on site sources were identified for this effort; (1) Kern River immediately downstream of the Main Dam outlet works, (2) Lake Isabella Reservoir immediately upstream of the Main Dam, (3) Well at the toe of the Auxiliary Dam, (reference Figure No.1).
Branch file data includes Design Memorandum No. 6 Isabella Lake Spillway and Dam Modifications, dated September 1983 Chapter VIII. Design Memorandum No. 6 reports water from Isabella Lake and local wells is available for construction purposes including concrete mixing and curing. No problems are anticipated in developing an adequate supply of water for concrete construction uses.”
4. Material Evaluation Water Sampling and Testing: Samples of materials obtained from the prospective material sources were sent to a commercial laboratory for testing.
Water samples were collected from the Kern River downstream of the Main Dam outlet structure quarterly during FY12 and tested in accordance with CRD-C 400, (reference Appendix 1). Water from the Kern River immediately downstream of the Main Dam outlet structure at the time of sampling was determined to be suitable for use in mixing and curing concrete mixtures.
Water samples from the well at the toe of the Auxiliary Dam and from the Lake Isabella Dam Reservoir were collected quarterly during FY14 and FY15 and tested in accordance with CRD- C 400 and for time of set in accordance with ASTM C403, (reference Appendix 2). Water from the well was determined to be suitable for use in mixing and curing concrete mixtures.
Water from the Lake Isabella Dam reservoir was determined to be unsuitable for use in mixing and curing concrete mixtures.
The Kern River water quality downstream of the main dam will be influenced by the water quality in the reservoir and may be inconsistent. Therefore, water from the Lake Isabella reservoir and Kern River is unsuitable for use in aggregate production and processing, aggregate moisture conditioning, concrete surface preparation and joint cleaning, rock foundation surface preparation, cleaning drill holes, and for mixing and curing concrete and grout mixtures.
5. Recommendation The Lake Isabella Dam reservoir is relatively shallow and warmer water which encourage the growth of algae and other organic material. Algae typically remains near the surface in the littoral (light) zone. Water sampling was performed at 20 - 30 foot depth to in an attempt to avoid algae and suspended material. However, wind and wave action on shallow reservoirs result in mixing action in the reservoir. Therefore, algae, organic material, and suspended sediments, in the reservoir water is not confined to the littoral zone.
6. Conclusion Water shall be obtained from wells downstream of the Auxiliary Dam and/or public water supply. Depending on water demand a group of wells may be required. Water obtained from on-site sources must be tested in accordance with ASTM C1602 prior to use and at least quarterly to verify water quality. Water from Lake Isabella reservoir and Kern River shall not be used for aggregate production and processing, moisture conditioning aggregates, concrete surface preparation and joint cleaning, rock foundation surface preparation, cleaning drill holes, and for mixing and curing concrete and grout mixtures.
Figure No. 1 Lake Isabella Dam, map of approximate water sampling locations.
APPENDIX 1
FY12 Water Testing Laboratory Results
Kern River Water Testing
DATE:
TO: Bill Halczak JOB NO:
US Army Corps of Engineers, Sacramento District LAB LOG:
CESPK-ED-GS
1325 J Street
Sacramento, CA 95814-2922
RE: Lab Report: Lake Isabella DSAP Water Analysis
Enclosed are results for: Samples Received -
Code Item Quantity
24005 1
24006 1
24000 1
24001 1
24002 1
24003 1
Sincerely, at 1-530-272-2448. This testing is based up on accepted industry practice as well as the for the test to working with you again. If you have any questions or require any additional information, please call us
Staining Properties of Water, CRC #401-75
Thank you for consulting Geo-Logic Associates for your material testing requirements. We look forward method listed. These results apply only to the samples supplied and tested for the above referenced job.
Ph of Water EPA 150.1
Iron Content, SM3120B
Sulfate, SM4500SO4
Effect of mix Water on Mortar Strength, CRC# 405-79
Chloride, SM 4500CL-B
Technical DirectorLaboratory Project Manager
Reviewed By: Kenneth R. CrileyPrepared By: Jodi Laferte
January 6, 2012
3305.0
2011.A154
November 17, 2011
Geo-Logic Associates 143E Spring Hill Drive Grass Valley, CA 95945
USA
T+1 530 272 2448 F+1 530 272 8533 www.geo-logic.com
LT-1-AF (rev.2-10-04)
Client : Project No: Lab Log:
USACOE, Sacramento District Project Name: Report Date:
Lake Isabella DSAP Water Analysis
Staining Properties of Mix Water
CRD-C-401-75
7-day = 100+ Slight Stain
28-day = 97
7-day = 197 No Visible staining
28-day = 97
Notes:
Entered By: Rev. By: Lab Log:
Soil Summary Report (rev. 7/28/00 ncl) JL krc
3027B
Mix Water Sample
FL-S-2
3305A
This testing is based up on accepted industry practice as well as the test method listed. These results apply only to the samples supplied and tested for the above referenced job.
SUMMARY REPORT
January 3, 2012
Water Sample
Water Sample
2011.A154
L:\labexcel\projects\1920\2011.A\3055-soil-rp
LSN Sample ID Sample Description
Compressive Strength
CRD-C-406-79
Percent of Standard, %
Client : Project No: Lab Log:
US Army Corps of Engineers Project Name: Report Date:
Lake Isabella DSAP Water Analysis
Staining Properties of Mix Water
CRD-C-401-75
7-day = 127 Slight staining
28-day = 107
Notes:
Entered By: Rev. By: Lab Log:
Soil Summary Report (rev. 7/28/00 ncl)
KRC
Compressive Strength
CRD-C-406-79
Percent of Standard, %
2011.A154
L:\labexcel\projects\1920\2011.A\3341-soil-rp
LSN Sample ID Sample Description
SUMMARY REPORT
April 20 2012
Water Sample
This testing is based up on accepted industry practice as well as the test method listed. These results apply only to the samples supplied and tested for the above referenced job.
Mix Water 3341A
LAKE ISABELLA WATER TESTING Project No. E12017.002 LABORATORY TEST RESULTS 25 July 2012
Laboratory Test Results
Staining properties of water (CRC-C 401)
The condition of the test mortar after testing does not appear to have any stain or discoloration.
Effect of mixing water on compressive strength (CRD-C 406)
Table 1
Sample Number & Water Type
Age (Days) Area (sq in) Ultimate Load
(lbs)
PSI
A Distilled 7 4.0 20995 5250
B Distilled 28 4.0 21254 5310
C Distilled 28 4.0 20663 5170
A Lake DSAP 7 4.0 21225 5310
B Lake DSAP 28 4.0 21970 5490
C Lake DSAP 28 4.0 22552 5640
APPENDIX 2
FY14 -15 Water Testing Laboratory Results
Lake Isabella Reservoir and Auxiliary Dam Well Water Testing
Project No. E12017.009 16 July 2014
US Army Corps of Engineers
Sacramento District
1325 J Street
Sacramento, CA 95814-2922
Attention: Ms. Fiorella Fuentes
Subject: Final Laboratory Test Results Lake Isabella Auxiliary Dam, Water Testing W91238-12-A-0004-0009-02
Dear Ms. Fuentes:
In accordance with your request, selected physical property tests of cementitious mortars made with various different waters have been performed. The waters used in the physical property tests were Lake Water and Well Water, each of which was supplied by the US Army Corps of Engineers (USACE) in plastic 1-gallon containers.
We also used distilled water purchased from a local retail store in the fabrication of control specimens. In addition, samples of the Lake Water and Well Water were submitted to Sunland Analytical Lab for chemical analysis.
The purpose of the tests was to provide data to the USACE to aid in the comparison of the different waters (Lake Water, Well Water, and distilled water) to produce concrete that meets applicable USACE and ASTM International (ASTM) standards. The tests performed were:
� Compressive Strength, CRD-C 406-79 � Setting Time of Concrete, ASTM C403 � Staining Properties of Water, CRD-C 401-75 � pH of Water � Sulfate Content of Water � Chloride Content of Water � Iron Content of Water
The physical property tests are discussed below, and the results of the chemical tests are presented in the attached letter of results from Sunland Analytical Lab.
Lake Isabella Water Testing Project No. 12017.009 Page 2 16 July 2014
Compressive Strength Testing
Cubes of cement mortar were made using each of the different waters following the criteria in CRD-C 406-79. This standard provides the quantities of materials used to make the cement mortar, which are:
� 600 grams of cement � 360 grams of water (this results in a water:cement ratio of 0.60) � 2,100 grams of graded standard Ottawa sand
Three sets of six cubes were fabricated for each water type, with three cubes from each set being tested at 7-days age, and three cubes from each set being tested at 28-days age. Results of these tests are presented below.
Water Type
Specimen Age, days
Individual Specimen
Unconfined Compressive Strength, psi
Average Unconfined
Compressive Strength, psi
Percent of Distilled Water
2,640
2,620 7
2,780
2,680 105
3,660
3,390
Lake
3,640
3,560 98
2,700
2,470 7
2,660
2,610 102
3,400 3,710
Well
3,830
3,650 100
2,440
2,520 7
2,690
2,550 100
3,670 3,630
Distilled
3,610
3,640 100
Specimen Size: 2 x 2 x 2 inches Cement Used: Basalite, Type II/V, Manufactured May 28, 2014
Page 3 16 July 2014
Setting Time of Concrete
Setting time of concrete was tested following the criteria in ASTM C1602-12. This standard is a specification for water used in making concrete, and it directs setting time tests to be performed in accordance with ASTM C403. ASTM C1602 specifies the mortar batches be made with the following quantities of materials:
� Portland cement, 1 part by mass � ASTM C33 concrete sand, 2.25 parts by mass � Water, to produce a water:cement ratio of 0.50
Results of the tests are as follows:
Set
Individual Trial Setting
Time, minutes
Average Setting Time, minutes
Deviation from Control, minutes
207 Initial
213 +20
Lake
Final
278 +2
186 Initial
193 0
Well
Final
276 0
186 Initial
193 NA
Distilled
Final
276 NA
Detailed test data for each test is attached.
Page 4 16 July 2014
Staining Properties of Water
The staining properties of the Lake Water and Well Water were tested in accordance with CRD-C 401-75. Results of the tests were visually determined by comparison to a control specimen, and are as follows:
Water Type Staining Property Lake Water Slight Stain Well Water No Stain
Photograph of staining test specimens, after completion of the tests.
Well Water Lake Water
Control Specimen
Page 5 16 July 2014
Limitations
Our work was performed in a manner consistent with that level of care and skill ordinarily exercised by other members of Youngdahl Consulting Group Inc.’s profession practicing in the same locality, under similar conditions and at the date the services were provided. Our conclusions, opinions and recommendations are based on a limited number of observations and data. It is possible that conditions could vary between or beyond the data evaluated. Youngdahl Consulting Group, Inc. makes no guarantee or warranty, express or implied, regarding the services, communication (oral or written), report, opinion, or instrument of service provided.
Closure
If you have any questions regarding this letter report, or need additional information, please call us at (916) 933-0633.
Sincerely, Jeffry Cannon
Laboratory Department Head
Attachments:
� Time of Setting of Concrete Mixtures, 3 Pages � Chemical Analysis of Water, by Sunland Analytical Lab, Dated 06/11/2014, 4 Pages
Project Name: Lake Isabella Water Testing
Project No.: E12017.009
Date Tested: June 19, 2014
Sample: Lake Water
Cement: Basalite, Type II/V, Manufactured May 28, 2014
Material Proportions:
Sand: Standard Graded Ottawa Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Lake Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 213 207 218 213
276 277 282 278
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: June 25, 2014 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Date Tested: June 19, 2014
Sample: Well Water
Cement: Basalite, Type II/V, Manufactured May 28, 2014
Material Proportions:
Sand: Standard Graded Ottawa Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Well Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 207 186 187 193
277 273 279 276
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: June 25, 2014 Reviewed By: JLC
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: June 19, 2014
Sample: Distilled Water (Control Sample)
Cement: Basalite, Type II/V, Manufactured May 28, 2014
Material Proportions:
Sand: Standard Graded Ottawa Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Distilled Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 205 186 187 193
277 273 279 276
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: June 25, 2014 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
20 November 2014
US Army Corps of Engineers
Sacramento District
Subject: Final Laboratory Test Results September 2014 Water Sampling mortars made with various different waters have been performed. The waters used in the physical property tests were Lake Water and Well Water, each of which was supplied by the US Army Corps of Engineers (USACE) in plastic 1-gallon containers.
We also used distilled water purchased from a local retail store in the fabrication of control specimens. In addition, samples of the Lake Water and Well Water were submitted to Sunland Analytical Lab for chemical analysis.
The purpose of the tests was to provide data to the USACE to aid in the comparison of the different waters (Lake Water, Well Water, and distilled water) to produce concrete
� Staining Properties of Water, CRD-C 401-75 � pH of Water � Sulfate Content of Water
Page 2 20 November 2014
Specimen Age, days
Individual Specimen
Unconfined Compressive Strength, psi
Average Unconfined
Compressive Strength, psi
Percent of Distilled Water
2,260
2,590 7
2,480
2,440 89
3,410
3,260
Lake
3,450
3,370 84
2,990
3,010 7
3,040
3,010 110
4,220 4,110
Well
4,270
4,200 105
2,880
2,660 7
2,690
2,740 100
3,980 3,980
Distilled
4,040
4,000 100
Cement Used: Basalite, Type II/V, Manufactured September 19, 2014
Page 3 20 November 2014 standard is a specification for water used in making concrete, and it directs setting time
Set
Individual Trial Setting
Time, minutes
Average Setting Time, minutes
Deviation from Control, minutes
183 Initial
193 -40
Lake
Final
281 -3
205 Initial
204 -29
Well
Final
282 -2
235 Initial
233 NA
Distilled
Final
284 NA
Page 4 20 November 2014
Lake Water Moderately Stain Well Water Light Stain
Page 5 20 November 2014 ordinarily exercised by other members of Youngdahl Consulting Group Inc.’s profession practicing in the same locality, under similar conditions and at the date the services were provided. Our conclusions, opinions and recommendations are based on a limited number of observations and data. It is possible that conditions could vary between or beyond the data evaluated. Youngdahl Consulting Group, Inc. makes no guarantee or
� Chemical Analysis of Water, by Sunland Analytical Lab, Dated 11/12/2014, 2 Pages
Date Tested: October 2, 2014
Sample: Distilled Water (Control Sample)
Cement: Basalite, Type II/V, Manufactured 9/19/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Distilled Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 227 235 236 233
282 285 284 284
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: November 20, 2014 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: October 2, 2014
Sample: Lake Water
Cement: Basalite, Type II/V, Manufactured 9/19/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Lake Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 213 183 183 193
282 281 280 281
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: November 20, 2014 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: October 2, 2014
Sample: Well Water
Cement: Basalite, Type II/V, Manufactured 9/19/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Well Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 203 205 205 204
279 282 284 282
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: November 20, 2014 Reviewed By: JLC
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
7 January 2015
US Army Corps of Engineers
Sacramento District
Subject: Laboratory Test Results December 2014 Water Sampling mortars made with various different waters have been performed. The waters used in the physical property tests were Lake Water and Well Water, each of which was supplied by the US Army Corps of Engineers (USACE) in plastic 1-gallon containers.
We also used distilled water purchased from a local retail store in the fabrication of control specimens. In addition, samples of the Lake Water and Well Water were submitted to Sunland Analytical Lab for chemical analysis.
The purpose of the tests was to provide data to the USACE to aid in the comparison of the different waters (Lake Water, Well Water, and distilled water) to produce concrete
� Staining Properties of Water, CRD-C 401-75 � pH of Water � Sulfate Content of Water
Page 2 7 January 2015
Specimen Age, days
Individual Specimen
Unconfined Compressive Strength, psi
Average Unconfined
Compressive Strength, psi
Percent of Distilled Water
1,970
2,190 7
2,220
2,130 92
3,920
3,750
Lake
3,840
3,840 104
1,800
1,890 7
2,330
2,010 87
3,410 3,540
Well
3,630
3,530 96
2,050
2,480 7
2,400
2,310 100
3,840 3,630
Distilled
3,610
3,690 100
Cement Used: Basalite, Type II/V, Manufactured November 18, 2014
Page 3 7 January 2015 standard is a specification for water used in making concrete, and it directs setting time
Set
Individual Trial Setting
Time, minutes
Average Setting Time, minutes
Deviation from Control, minutes
243 Initial
233 +8
Lake
Final
343 +15
220 Initial
218 -7
Well
Final
326 -2
225 Initial
225 NA
Distilled
Final
328 NA
Page 4 7 January 2015
Lake Water Moderate Well Water Slight
Page 5 7 January 2015 ordinarily exercised by other members of Youngdahl Consulting Group Inc.’s profession practicing in the same locality, under similar conditions and at the date the services were provided. Our conclusions, opinions and recommendations are based on a limited number of observations and data. It is possible that conditions could vary between or beyond the data evaluated. Youngdahl Consulting Group, Inc. makes no guarantee or
� Chemical Analysis of Water, by Sunland Analytical Lab, Dated 12/10/2014, 2 Pages
Date Tested: December 9, 2014
Sample: Lake Water
Cement: Basalite, Type II/V, Manufactured 11/18/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Lake Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 230 243 226 233
345 342 342 343
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: December 10, 2014 Reviewed By: JLC
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Trial 1
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: December 9, 2014
Sample: Well Water
Cement: Basalite, Type II/V, Manufactured 11/18/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Well Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 217 220 217 218
323 327 327 326
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: December 10, 2014 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: December 9, 2014
Sample: Distilled Water (Control Sample)
Cement: Basalite, Type II/V, Manufactured 11/18/14
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Distilled Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 223 225 226 225
322 335 327 328
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: December 10, 2014 Reviewed By: JLC
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Trial 1
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350 400
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
14 April 2015
US Army Corps of Engineers
Sacramento District
Subject: Laboratory Test Results March 2015 Water Sampling mortars made with various different waters have been performed. The waters used in the physical property tests were Lake Water and Well Water, each of which was supplied by the US Army Corps of Engineers (USACE) in plastic 1-gallon containers.
We also used distilled water purchased from a local retail store in the fabrication of control specimens. In addition, samples of the Lake Water and Well Water were submitted to Sunland Analytical Lab for chemical analysis.
The purpose of the tests was to provide data to the USACE to aid in the comparison of the different waters (Lake Water, Well Water, and distilled water) to produce concrete
� Staining Properties of Water, CRD-C 401-75 � pH of Water � Sulfate Content of Water
Page 2 14 April 2015
Specimen Age, days
Individual Specimen
Unconfined Compressive Strength, psi
Average Unconfined
Compressive Strength, psi
Percent of Distilled Water
2,540
2,430 7
2,400
2,460 92
3,520
3,460
Lake
3,460
3,480 92
2,500
2,560 7
2,450
2,500 94
3,430 3,420
Well
3,570
3,470 92
2,710
2,660 7
2,650
2,670 100
3,760 3,860
Distilled
3,720
3,780 100
Cement Used: Basalite, Type II/V, Manufactured February 4, 2015
Page 3 14 April 2015 standard is a specification for water used in making concrete, and it directs setting time
Set
Individual Trial Setting
Time, minutes
Average Setting Time, minutes
Deviation from Control, minutes
230 Initial
231 17
Lake
Final
327 29
224 Initial
224 10
Well
Final
307 9
214 Initial
214 NA
Distilled
Final
298 NA
Page 4 14 April 2015
Lake Water Slight Well Water Very Slight
Well Water Lake Water
Page 5 14 April 2015 ordinarily exercised by other members of Youngdahl Consulting Group Inc.’s profession practicing in the same locality, under similar conditions and at the date the services were provided. Our conclusions, opinions and recommendations are based on a limited number of observations and data. It is possible that conditions could vary between or beyond the data evaluated. Youngdahl Consulting Group, Inc. makes no guarantee or
� Chemical Analysis of Water, by Sunland Analytical Lab, Dated 03/25/15, 2 Pages
Date Tested: March 18, 2015
Sample: Distilled Water (Control Sample)
Cement: Basalite, Type II/V, Manufactured 2/4/15
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Distilled Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 214 214 214 214
298 296 300 298
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: April 13, 2015 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: March 18, 2015
Sample: Lake Water
Cement: Basalite, Type II/V, Manufactured 2/4/15
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Lake Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 230 230 234 231
326 325 330 327
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: April 13, 2015 Reviewed By: JLC
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
Date Tested: March 18, 2015
Sample: Well Water
Cement: Basalite, Type II/V, Manufactured 2/4/15
Material Proportions:
Sand: ASTM C33 Concrete Sand, 2.25 parts by mass
Cement: Basalite, Type II/V, 1 part by mass
Water: Well Water, water:cement ratio = 0.50
Test Results:
Trial 1 Trial 2 Trial 3 Average 224 224 225 224
303 312 307 307
Initial Set: Penetration Resistance at 500 psi
Final Set: Penetration Resistance at 4,000 psi
Report Date: April 13, 2015 Reviewed By: JLC
Test specimens were fabricated in accordance with ASTM C1602-12, Mixing Water Used in the Production of Hydraulic Cement Concrete;
Section 5.3.3, Testing Using Laboratory Mortar Batches
Duration, minutes
Initial Set
Final Set
ASTM C403-08, Time of Setting of Concrete Mixtures by Penetration Resistance
Trial 1
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 2
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p s i
Trial 3
0 50 100 150 200 250 300 350
Elapsed Time, min.
P e n e tr a ti o n
R e s is ta n c e p
| Water Testing and Evaluation Report_26 JAN 2017 |
| 1. General Information |
| 2. Material Requirements |
| 3. Material Sources |
| 4. Material Evaluation |
| 5. Recommendation |
| 6. Conclusion |
| APPENDIX 1 FY12 WATER TESTING LAB DATA |
| APPENDIX 1 |
| FY12 Water Testing Laboratory Results |
| FY12_November 2011 Sample |
| 3305-tran |
| 3305-Summary |
| ORDER-61259-fuentes-isabella |
| FY12_February 2012 Sample |
| CRD C 406 |
| ORDER-61728-fuentes-lakeisabella |
| FY12_May 2012 Sample |
| E12017 002 Mixing water |
| SKMBT_C65212060111290 |
FY12_August 2012 Sample
| APPENDIX 2 FY14-15 WATER TESTING LAB DATA |
| APPENDIX 2 |
| FY14-15 Water Testing Laboratory Results |
| FY14_Water Testing Laboratory Results |
| FY14_December 2013 |
| Dec 2013 |
| ORDER-66088 youngdahl |
| FY14_March 2014 |
| FY14_June 2014 |
| FY14_Sept 2014 |
| FY15_Water Testing Laboratory Results |
| FY15_December 2014 |
| FY15_March 2015 |
File details come from the government source that posted it. Updated .