ASP Addendum 0008 RFIs.doc

DOC document 28 KB Posted

Attached to
Construction of an Ammunitions Supply Point Facility Federal contract opportunity
Solicitation number
W911YP-09-B-0002
Issued by
Department of the Army Utah Army National Guard

About this file

Addendum 0008 RFIs.

View the file

Other files for this federal contract opportunity

Other files attached to Construction of an Ammunitions Supply Point Facility, newest first.
File Type Posted
ASP Addendum 0010.doc DOC document
ASP Davis Bacon UT080039.pdf PDF
ASP Davis Bacon UT080060.pdf PDF
ASP RFIs Addendum 0009.doc DOC document
ASP 08315 Sliding Blast Resistant Door Addendum 0009.doc DOC document
ASP Addendum 0009 Utah National Guard Seed Mix.doc DOC document
ASP 01360 —
ASP Addendum 0009.doc DOC document
ASP Addendum No 0009 - Notice to Bidders.doc DOC document
Davis Bacon UT080038 —
ASP Addendum 0008.doc DOC document
Davis Bacon UT080059 —
ASP Addendum 0007.doc DOC document
ASP Addendum 0007 Drawings Specifications.pdf PDF
ASP geotechnical report.pdf PDF
BID SCHEDULE ASP CW.Revised Add 0006.doc DOC document
ASP A-E's Addendum 3 Notice to Bidders.pdf PDF
ASP Addendum 0006.doc DOC document
ASP A-E's TOC-ADM3.pdf PDF
ASP Addendum 0006.doc DOC document
W911YP-09-B-0002-0005.doc DOC document
W911YP-09-B-0002-0004.doc DOC document
BID SCHEDULE ASP CW.Revised.doc DOC document
W911YP-09-B-0002-0002 ASP addendum.doc DOC document
ASP Site Visits Contractors.pdf PDF
UT Ammo Dwg 8-21-09 pgs 29-39.pdf PDF
UT Ammo Dwg 8-21-09 pgs 1-28.pdf PDF
UT Ammo Dwg 8-21-09 pgs 40-181.pdf PDF
J A Sole Source Telecommunications ASP.doc DOC document
W911YP-09-B-0002-0001 ASP Addendum 001.doc DOC document
Utah Ammo Specs 8-21-09.pdf PDF
Utah ARNG Camp Williams Ammo Storage Point - 95 Design Submittal PDF BINDER - 7-28-09.pdf PDF
W911YP-09-B-0002 Ammunitions Suppy Point —
20090729_UTAH_ASP_95 Plans.pdf PDF
Utah ARNG Camp Williams Ammo Storage Point - 95 Design Submittal PDF PKG - 7-28-09.pdf PDF
Show all 35

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum 0008 Ammunitions Supply Point (ASP) Facility

Camp Williams, Utah

RFIs

1. Could the A-E supply a foundation detail for the two tanks? Typically we build a grade beam at the perimeter of the tank 12” x 36”, fill under tank with engineered compacted fill covered with 6” to 8” of sand (oil added).

Answer: Because the tank foundations are specific to the tank supplier requirements, the specification 13213 requires the contractor to provide the foundation design.

2. The three Welded Storage Tank manufacturers were contacted to bid this project and none of them wanted to submit a bid. Are there other manufacturers that can bid:

Answer: These three manufacturers are suggested. The words “or equal” should have followed them. Any manufacturer capable of meeting the requirements of the specification is acceptable.

3. With regard to drawing 00E503, detail 3/00E503, it is noted that the wood poles are to be sized and classed as noted. I can determine size. But Class is not noted on drawing or in specifications.

Answer: Per a previous RFI response, the classification is:

Wood poles shall be Class 3, Grade C, Douglas Fir or Southern Yellow Pine

4. I need to know the design criteria for the blast doors in section 08315-2 of the specs for Camp Williams Ammo Storage Point. In section 2.1 paragraph B 3, 6, 8 the dynamic overpressure, duration, door edge rotation, fragment weight, and velocity are all blanked out on the specs. Please let me know when you find out the information on these doors.

Answer: Addendum 1 has a new edited version of this specification included.

5. After review of Amendment 7, I am still missing drawing 02E600. Is this part of Amendment 2? If so, I am unable to download off the FBO site. Do you have a tech support contact I can speak with?

Answer: This note actually says to refer to the 02E600 SERIES of drawings for the electrical schedules. There is no 02E600 drawing.

6. Do the contract documents call for special inspection testing? Are we asking the General Contractor to do this?

Answer: Yes we are. For the structural systems, we are requiring special inspection provided by the Contractor.