Contract Number:
TECHNICAL EXHIBIT 5.5-002
CHLOROFLUOROCARBON (CFC) CONTROL
1. In accordance with EPA regulations, the Contractor shall fill out and maintain a Refrigerant Recovery and Refrigerant Usage Log for all uses and recovery of all refrigerants.
2. The Contractor shall complete and maintain an Accidental, Unintentional Venting log sheet any time a leak is discovered and when a system looses any refrigerant during repairs. The immediate notification to the KO is required upon a leak or accidental, unintentional venting. All leaks must be repaired within 30 calendar days in accordance with 40 CFR Part 82. The Contractor shall review all recorded leaks and leak repairs on an annual basis to highlight equipment and areas requiring corrective action.