Contract No: TECHNICAL EXHIBIT 5.1-020
GROUND FAULT PROTECTION SUBSYSTEM CHECKLIST FOR EXISTING FACILITIES
For use of this form, see TM 5-690; the proponent agency is COE.
1. F ACILITY 2. DATE (YYYYMMDD)
3 . L O C A T I O N 4. INSPECTOR
5. CHECK THE GROUNDED (Neutral) AND GROUNDING CIRCUITS FOR PROPER NSTALLATION, CONNECTION, AND BONDING FROM THE SERVICE ENTRANCE PANELS T O THE DISTRIBUTION PANELS. VERIFY THAT T HE GROUNDED AND GROUNDING CONDUCTORS ARE LOCATED IN THE SAME CONDUIT AS THE LINE (Hot) CONDUCTORS. RECORD THE DATA AND ALL DEFICIENCIES.
LOCATION
MAIN BREAKER
GROUNDED CIRCUIT
GROUNDING CIRCUIT
PROPER INSTALLATION
PROPER BONDING
LOCATED IN SAME CONDUIT
RATING
SIZE MATERIAL SIZE MATERIAL YES NO YES NO YES NO
6. MEASURE THE LINE-TO-NEUTRAL VOLTAGES, LINE -TO-GROUND VOLTAGES, AND NEUTRAL -TO-GROUND VOLTAGES AT ALL PANELS AND DISCONNECTED SWITCHES
LINE-TO-NEUTRAL VOLTAGES LINE-TO-GROUND VOLTAGES NEUTRAL-TO-GROUND VOLTAGES
V (A - N) V (B - N) V(C-N) V ( A - G ) V (B - G ) V(C-G) V(N-G)
7. MEASURE THE LINE (Hot) CURRENTS, NEUTRAL CURRENTS, AND GROUND CURRENTS
LINE CURRENTS NEUTRAL CURRENT NEUTRAL CURRENT
I (A) I (B) I (C) I (N) I (N-G)
8. RECORD ALL NATIONAL ELECTRIC CODE (NEC) AND NATIONAL ELECTRIC SAFETY CODE (NESC) VIOLATIONS
LOCATION VIOLATIONS
DA FORM 7452-7-R, FEB 2002 USAPA V1.00