BLDG NO. BUILDING NAME LOCATION
STEAM PIPE SIZE
(IN.)
BASIS OF DESIGN
STEAM METER
MODEL
PUMPED
CONDENSATE
RETURN SIZE (IN.)
BASIS OF DESIGN
CONDENSATE METER
MODEL
CONNECT
LOAD (PPH)
OFF PEAK
LOAD (PPH)
NOTES
SERVICE ENTRANCE 6" EXISTING
SERVICE ENTRANCE 4" ABB Swirl
1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2. DUE TO ALL HIGH PRESSURE STEAM METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.
3.
4.
5.
6. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL CONFIRM WITH GOVERNMENT EXISTING METERING WILL PROVIDE DATA COLLECTION POINTS REQUIRED IN THIS SCOPE OF WORK.
HOT TAPPING WILL BE REQUIRED FOR ALL PUMPED CONDENSATE RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE SENSORS FOR TOTAL ENERGY DATA COLLECTION.
REFER TO PLANS FOR LOCATIONS.
ABB SWIRL ARE FLANGED FITTING METERS.
STEAM AND CONDENSATE METER TABLE
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.
METROLOGY BUILDING 220 3" GE DF868 10,430 6,260 ALL
GENERAL NOTES:
BLDG NO. BUILDING NAME LOCATION PIPE SIZE (IN.)
BASIS OF DESIGN
METER MODEL
FLOW
DIRECTION
PEAK LOAD
(GPM)
OFF PEAK LOAD
(GPM) NOTES
14" EXISTING SUPPLY
14" GE DF868 RETURN
3" GE DF868 SUPPLY
3" GE DF868 RETURN
1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2.
3.
4.
5. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.
6. CONTRACTOR SHALL CONFIRM WITH GOVERNMENT EXISTING METERING WILL PROVIDE DATA COLLECTION POINTS REQUIRED IN THIS SCOPE OF WORK.
CHILLED WATER METER TABLE
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.
GENERAL NOTES:
1,531 954 ALL
TRANSFORMER VAULT C09
UNLESS NOTED OTHERWISE, HOT TAPPING WILL BE REQUIRED FOR CHILLED WATER SUPPLY AND RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE
SENSORS FOR TOTAL ENERGY DATA COLLECTION. REFER TO PLANS FOR LOCATIONS.
GE DF868 ULTRASONICS METERS ARE STRAP‐ON TYPE METERS.
METROLOGY BUILDING 220
SERVICE ENTRANCE
PANEL PB.B.4 (E)
POLES 42 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION ELECT. RM 272
AIC 10,000 MAIN 100 AMPS MCB FED FROM PANEL H2
NEUTRAL 100 %
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
(N) FLOW METER CONTROLS 0.18 2 #12, #12 GD, 3/4"C. 20 1 0.18 2 20 SPARE
SPACE 20 3 4
LIGHTS SUB-BSMT. 0.90 20 5 1.26 6 20 0.36 WATER COOLER
RECEPT. RMS. B50, B52 0.54 20 7 0.86 8 20 0.32 LIGHTS GEN. RM.
RECEPT. RMS. B50, B52 0.54 20 9 0.86 10 20 0.32 LIGHTS GEN. RM.
LIGHTS GEN. RM. 0.90 20 11 1.22 12 20 0.32 LIGHTS GEN. RM.
LIGHTS GEN. RM. 0.90 20 13 1.33 14 20 0.43 LIGHTS BATTERY RM.
LIGHTS GEN. RM. 0.90 20 15 1.33 16 20 0.43 LIGHTS BATTERY RM.
LIGHTS GEN. RM. 0.90 20 17 1.33 18 20 0.43 LIGHTS BATTERY RM.
LIGHTS GEN. RM. 0.90 20 19 1.98 20 20 1.08 L5-30R MECH. RM.
LIGHTS GEN. RM. 0.90 20 21 #REF! 22 20 1.08 L5-30R MECH. RM.
LIGHTS GEN. RM. 0.90 20 23 1.26 24 20 0.36 (E) LOAD
(E) LOAD 0.54 20 25 0.90 26 20 0.36 (E) LOAD
(E) LOAD 0.54 20 27 0.90 28 20 0.36 (E) LOAD
(E) LOAD 0.54 20 29 0.90 30 20 0.36 (E) LOAD
(E) LOAD 0.54 20 31 0.90 32 20 0.36 (E) LOAD
(E) LOAD 0.54 20 33 0.54 34 20 SPARE
(E) LOAD 0.54 20 35 0.54 36 20 SPARE
(E) LOAD 0.54 20 37 0.54 38 20 SPARE
SPACE 39 40 20 SPARE
SPACE 41 42 20 SPARE
TOTAL CONNECTED KVA PER PHASE 6.7 #REF! 6.5
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING 9.5 1.25 11.8 33 1.00 33
RECEPTACLES 9.2 NEC TABLE 220-13 9.2 26 1.00 26
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 0.2 1.00 0.2 0 1.00 0