BUILDING101-PLOTFILE.pdf

PDF 922 KB Posted

Attached to
SITE CHILLED WATER, STEAM & NATURAL GAS METERING at NIST GAITHERSBURG
Solicitation number
SB1341-14-RP-0017
Issued by

About this file

BUILDING101-PLOTFILE.pdf

View the file

Other files

File Type Posted
Amendment_003_Metering_Project.pdf PDF
1352.215-70_Proposal_Preparation_(updated_30_May_2014).pdf PDF
Sign-In_Sheet-Site_Visit.pdf PDF
Section_J_(updated_30_May_2014).docx DOCX document
Amendment_002_Metering_Project.pdf PDF
Attachment_5_Questions_ _Answers_(Final_Round).doc DOC document
Attachment_4_Questions_ _Answers_(Initial_Round).pdf PDF
Amendment_001_Metering_Project.pdf PDF
Revised_Drawings.zip ZIP file
Specifications-Revised_15_May_2014.pdf PDF
BUILDING235-PLOTFILE.pdf PDF
BUILDING302-PLOTFILE.pdf PDF
BUILDING202-PLOTFILE.pdf PDF
BUILDING226-PLOTFILE.pdf PDF
BUILDING224-PLOTFILE.pdf PDF
BUILDING225-PLOTFILE.pdf PDF
BUILDING236-PLOTFILE.pdf PDF
BUILDING203-PLOTFILE.pdf PDF
BUILDING245-PLOTFILE.pdf PDF
BUILDING237-PLOTFILE.pdf PDF
Attachment_2_GUIDELINES_FOR_OFPM_CONTRACTORS.doc DOC document
BUILDING320-PLOTFILE.pdf PDF
BUILDING312-PLOTFILE.pdf PDF
BUILDING301-PLOTFILE.pdf PDF
BUILDING222-PLOTFILE.pdf PDF
BUILDING223-PLOTFILE.pdf PDF
Attachment_1_SAFETY_PROCEDURES_5-13-09.doc DOC document
BUILDING303-PLOTFILE.pdf PDF
Specifications.pdf PDF
BUILDING231-PLOTFILE.pdf PDF
BUILDING233-PLOTFILE.pdf PDF
BUILDING206-PLOTFILE.pdf PDF
BUILDING221-PLOTFILE.pdf PDF
BUILDING220-PLOTFILE.pdf PDF
BUILDING304-PLOTFILE.pdf PDF
BUILDING227-PLOTFILE.pdf PDF
SB1341-14-RP-0017_Metering_Project.pdf PDF
BUILDING230-PLOTFILE.pdf PDF
BUILDING215-PLOTFILE.pdf PDF
Attachment_3_Pricing_Worksheet_for_SB1341-14-RP-0017.xlsx XLSX spreadsheet
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG NO. BUILDING NAME LOCATION PIPE SIZE (IN.)

BASIS OF DESIGN

METER MODEL

FLOW

DIRECTION

PEAK LOAD

(GPM)

OFF PEAK LOAD

(GPM)

NOTES

WING B 10" GE DF868 SUPPLY

WING B 10" GE DF868 RETURN

WING B 8" GE DF868 RETURN

WING E 12" ABB SWIRL RETURN

WING E 12" GE DF868 SUPPLY

1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.

2.

3.

4.

5. FLOW RATE LOAD IS SPLIT BETWEEN TWO OR MORE CHILLED WATER SERVICE TO BUILDING. SEE PLANS FOR LOCATIONS.

6. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.

7. DUE TO THE METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.

UNLESS NOTED OTHERWISE, HOT TAPPING WILL BE REQUIRED FOR CHILLED WATER SUPPLY AND RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE

SENSORS FOR TOTAL ENERGY DATA COLLECTION. REFER TO PLANS FOR LOCATIONS.

ABB SWIRL ARE FLANGED FITTING METERS AND GE DF868 ULTRASONICS ARE STRAP‐ON TYPE METERS.

CHILLED WATER METER TABLE

TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURER'S RECOMMENDATION.

101 ADMINISTRATION 2,076 1,249 ALL

GENERAL NOTES:

BLDG NO. BUILDING NAME LOCATION

STEAM PIPE SIZE

(IN.)

BASIS OF DESIGN

STEAM METER

MODEL

PUMPED

CONDENSATE

RETURN SIZE (IN.)

BASIS OF DESIGN

CONDENSATE

METER TYPE

CONNECT

LOAD (PPH)

OFF PEAK

LOAD (PPH)

NOTES

WING C 8" ABB Swirl 4" GE DF868 7,383 4,430

WING E 6" ABB Vortex 4" GE DF868 5,987 3,590

1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.

2. DUE TO ALL HIGH PRESSURE STEAM METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.

3.

4.

5.

6. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.

7. FLOW RATE LOAD IS SPLIT BETWEEN TWO OR MORE HIGH PRESSURE STEAM SERVICE TO BUILDING. SEE PLANS FOR LOCATIONS.

HOT TAPPING WILL BE REQUIRED FOR ALL PUMPED CONDENSATE RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE SENSORS FOR TOTAL ENERGY DATA COLLECTION.

REFER TO PLANS FOR LOCATIONS.

ABB SWIRL AND VORTEX ARE FLANGED FITTING METERS AND GE DF868 ULTRASONICS ARE STRAP‐ON TYPE METERS.

STEAM AND CONDENSATE METER TABLE

TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.

ALLADMINISTRATION 101

GENERAL NOTES:

PANEL PB-B-12K (E)

POLES 36 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:

SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION MECH. ROOM D01

AIC 10,000 MAIN 225 AMPS MLO FED FROM

NEUTRAL

LOAD CKT PHASE KVA CKT LOAD

LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION

LTS. MECH. EQUIP. RM. #2 0.90 20 1 1.80 2 20 0.90 LTS. MECH RM. #2

LTS. AIR PLENUM 0.60 20 3 1.20 4 20 0.60 LTS. AIR PLENUM

LTS. AIR PLENUM 0.60 20 5 1.08 6 20 0.48 CHILL WATER PBS4B6

LTS. DUGOUT OF MECH. RM. #2 0.60 20 7 1.14 8 20 0.54 RECPS. W. WALL EQUIP. RM. 2

FAN SHUT DOWN D01 0.18 20 9 0.72 10 20 0.54 RECPS. CENTER COL. EQUIP. RM. 2

HONEYWELL CABINET 0.12 20 11 0.66 12 20 0.54 RECPS. AIR PLENUM WALL OUT

MF-B-1A-MF-8-4 0.36 20 13 0.84 14 20 0.48 HOT WATER PUMP P-B9

MF-8-3 & MF-8-5 0.36 20 15 0.36 16 20 SPARE HOT WATER PUMP PB6

MF-B-6 & MF-B-2 0.36 20 17 0.96 18 20 0.60 FEED FOR AIR CONDITIONER (S)

MP-B-7 0.48 20 19 1.08 20 20 0.60 FEED FOR AIR CONDITIONER (S)

MP-B-8 0.48 20 21 1.08 22 20 0.60 OIL TEMP CONTROLLER/ C W PUMPS

FEED FOR AIRCONDITIONER (E) 0.60 20 23 1.20 24 20 0.60 FEED FOR AIR CONDITIONER (E)

FEED FOR AIRCONDITIONER (WEST) 0.60 20 25 1.20 26 20 0.60 FEED FOR AIR CONDTIONER (WEST)

27 0.36 28 20 0.36 CONDSATE PUMP CONTROL CIR. 1A

SPARE 40 29 0.36 30 20 0.36 RED AUDITORIUM- HANDICAP DOORS

31 32 20 SPACE

(N) FLOW METER CONTROLS 0.18 2 #12, #12 GD, 3/4" C. **20 33 0.18 34 SPACE

SPACE 35 36 SPACE

37 38

39 40

41 42

TOTAL CONNECTED KVA PER PHASE 6.1 3.9 4.3

LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY

CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY

LIGHTING 4.2 1.25 5.3 15 1.00 15

RECEPTACLES 2.0 NEC TABLE 220-13 2.0 6 1.00 6

KITCHEN EQUIPMENT - 0.65 - - 1.00 -

LARGEST MOTOR 1.25 - - 1.00 -

OTHER LOADS 8.0 1.00 8.0 22 1.00 22

DEMAND AMPS 42

NOTES **PROVIDE 20A CB IN EXISTING SPACE

SWITCHBOARD 101 B1 COM. 3

PANEL PB52PP (N)

POLES 30 VOLTS 120/208 VOLTS MOUNTING SURFACE

SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION LAN ROOM

AIC 10,000 MAIN 100 AMPS MCB FED FROM PANEL H52PP2

NEUTRAL 100 %

LOAD CKT PHASE KVA CKT LOAD

LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION

LIGHTS MECH. EQUIPMT. 0.90 20 1 1.44 2 20 0.54 (E) LOAD

RECP'S FAN RM. #7 0.54 20 3 0.72 4 20 0.18 FAN SHUT-DOWN A-50

RECP'S MECH. EQUIP. RM. 1 0.54 20 5 1.44 6 20 0.90 LIGHTS IN AIR PLENUM

CHILLLED WATER PUMP 344 0.72 20 7 1.26 8 20 0.54 (E) LOAD

LTS. MECH. EQUIM. RM #1 0.90 20 9 1.44 10 20 0.54 (E) LOAD

FAN SHUT-DOWN E-04 0.18 20 11 1.08 12 20 0.90 LIGHTS FAN RM. #7

FILTER MOTORS 0.36 20 13 0.54 14 20 0.18 CONTROLS CABINET

FILTER MOTORS 0.36 20 15 0.90 16 20 0.54 M-E-8

LTS. IN AIR PLENUM 0.90 20 17 1.62 18 20 0.72 PE 5 & 7

COND. PUMP CPA5 0.36 20 19 0.90 20 20 0.54 (E) LOAD

FAN COIL UNITS (NORTH) 0.72 20 21 1.26 22 20 0.54 (E) LOAD

(E) LOAD 0.36 20 23 0.90 24 20 0.54 (E) LOAD

(N) FLOW METER 0.18 2 #12, #12 GD, 3/4"C. 20 25 0.18 26 20 SPARE

SPARE 20 27 28 20 SPARE

SPARE 20 29 30 20 SPARE

TOTAL CONNECTED KVA PER PHASE 4.3 4.3 5.0

LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY

CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY

LIGHTING 4.5 1.25 5.6 16 1.00 16

RECEPTACLES 3.2 NEC TABLE 220-13 3.2 9 1.00 9

KITCHEN EQUIPMENT - 0.65 - - 1.00 -

LARGEST MOTOR 1.25 - - 1.00 -

OTHER LOADS 5.9 1.00 5.9 17 1.00 17

DEMAND AMPS 41

NOTES

NOTES: REPLACE EXISTING PANEL W/ 30-POLE PANEL

101-955
101-956
101-957
101-958
101-959