BLDG NO. BUILDING NAME LOCATION PIPE SIZE (IN.)
BASIS OF DESIGN
METER MODEL
FLOW
DIRECTION
PEAK LOAD
(GPM)
OFF PEAK LOAD
(GPM)
NOTES
WING B 10" GE DF868 SUPPLY
WING B 10" GE DF868 RETURN
WING B 8" GE DF868 RETURN
WING E 12" ABB SWIRL RETURN
WING E 12" GE DF868 SUPPLY
1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2.
3.
4.
5. FLOW RATE LOAD IS SPLIT BETWEEN TWO OR MORE CHILLED WATER SERVICE TO BUILDING. SEE PLANS FOR LOCATIONS.
6. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.
7. DUE TO THE METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.
UNLESS NOTED OTHERWISE, HOT TAPPING WILL BE REQUIRED FOR CHILLED WATER SUPPLY AND RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE
SENSORS FOR TOTAL ENERGY DATA COLLECTION. REFER TO PLANS FOR LOCATIONS.
ABB SWIRL ARE FLANGED FITTING METERS AND GE DF868 ULTRASONICS ARE STRAP‐ON TYPE METERS.
CHILLED WATER METER TABLE
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURER'S RECOMMENDATION.
101 ADMINISTRATION 2,076 1,249 ALL
GENERAL NOTES:
BLDG NO. BUILDING NAME LOCATION
STEAM PIPE SIZE
(IN.)
BASIS OF DESIGN
STEAM METER
MODEL
PUMPED
CONDENSATE
RETURN SIZE (IN.)
BASIS OF DESIGN
CONDENSATE
METER TYPE
CONNECT
LOAD (PPH)
OFF PEAK
LOAD (PPH)
NOTES
WING C 8" ABB Swirl 4" GE DF868 7,383 4,430
WING E 6" ABB Vortex 4" GE DF868 5,987 3,590
1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2. DUE TO ALL HIGH PRESSURE STEAM METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.
3.
4.
5.
6. MULTIPLE FLOW METER INSTALLATION. SEE PLANS FOR ADDITIONAL INFORMATION.
7. FLOW RATE LOAD IS SPLIT BETWEEN TWO OR MORE HIGH PRESSURE STEAM SERVICE TO BUILDING. SEE PLANS FOR LOCATIONS.
HOT TAPPING WILL BE REQUIRED FOR ALL PUMPED CONDENSATE RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE SENSORS FOR TOTAL ENERGY DATA COLLECTION.
REFER TO PLANS FOR LOCATIONS.
ABB SWIRL AND VORTEX ARE FLANGED FITTING METERS AND GE DF868 ULTRASONICS ARE STRAP‐ON TYPE METERS.
STEAM AND CONDENSATE METER TABLE
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.
ALLADMINISTRATION 101
GENERAL NOTES:
PANEL PB-B-12K (E)
POLES 36 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION MECH. ROOM D01
AIC 10,000 MAIN 225 AMPS MLO FED FROM
NEUTRAL
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
LTS. MECH. EQUIP. RM. #2 0.90 20 1 1.80 2 20 0.90 LTS. MECH RM. #2
LTS. AIR PLENUM 0.60 20 3 1.20 4 20 0.60 LTS. AIR PLENUM
LTS. AIR PLENUM 0.60 20 5 1.08 6 20 0.48 CHILL WATER PBS4B6
LTS. DUGOUT OF MECH. RM. #2 0.60 20 7 1.14 8 20 0.54 RECPS. W. WALL EQUIP. RM. 2
FAN SHUT DOWN D01 0.18 20 9 0.72 10 20 0.54 RECPS. CENTER COL. EQUIP. RM. 2
HONEYWELL CABINET 0.12 20 11 0.66 12 20 0.54 RECPS. AIR PLENUM WALL OUT
MF-B-1A-MF-8-4 0.36 20 13 0.84 14 20 0.48 HOT WATER PUMP P-B9
MF-8-3 & MF-8-5 0.36 20 15 0.36 16 20 SPARE HOT WATER PUMP PB6
MF-B-6 & MF-B-2 0.36 20 17 0.96 18 20 0.60 FEED FOR AIR CONDITIONER (S)
MP-B-7 0.48 20 19 1.08 20 20 0.60 FEED FOR AIR CONDITIONER (S)
MP-B-8 0.48 20 21 1.08 22 20 0.60 OIL TEMP CONTROLLER/ C W PUMPS
FEED FOR AIRCONDITIONER (E) 0.60 20 23 1.20 24 20 0.60 FEED FOR AIR CONDITIONER (E)
FEED FOR AIRCONDITIONER (WEST) 0.60 20 25 1.20 26 20 0.60 FEED FOR AIR CONDTIONER (WEST)
27 0.36 28 20 0.36 CONDSATE PUMP CONTROL CIR. 1A
SPARE 40 29 0.36 30 20 0.36 RED AUDITORIUM- HANDICAP DOORS
31 32 20 SPACE
(N) FLOW METER CONTROLS 0.18 2 #12, #12 GD, 3/4" C. **20 33 0.18 34 SPACE
SPACE 35 36 SPACE
37 38
39 40
41 42
TOTAL CONNECTED KVA PER PHASE 6.1 3.9 4.3
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING 4.2 1.25 5.3 15 1.00 15
RECEPTACLES 2.0 NEC TABLE 220-13 2.0 6 1.00 6
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 8.0 1.00 8.0 22 1.00 22
DEMAND AMPS 42
NOTES **PROVIDE 20A CB IN EXISTING SPACE
SWITCHBOARD 101 B1 COM. 3
PANEL PB52PP (N)
POLES 30 VOLTS 120/208 VOLTS MOUNTING SURFACE
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION LAN ROOM
AIC 10,000 MAIN 100 AMPS MCB FED FROM PANEL H52PP2
NEUTRAL 100 %
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
LIGHTS MECH. EQUIPMT. 0.90 20 1 1.44 2 20 0.54 (E) LOAD
RECP'S FAN RM. #7 0.54 20 3 0.72 4 20 0.18 FAN SHUT-DOWN A-50
RECP'S MECH. EQUIP. RM. 1 0.54 20 5 1.44 6 20 0.90 LIGHTS IN AIR PLENUM
CHILLLED WATER PUMP 344 0.72 20 7 1.26 8 20 0.54 (E) LOAD
LTS. MECH. EQUIM. RM #1 0.90 20 9 1.44 10 20 0.54 (E) LOAD
FAN SHUT-DOWN E-04 0.18 20 11 1.08 12 20 0.90 LIGHTS FAN RM. #7
FILTER MOTORS 0.36 20 13 0.54 14 20 0.18 CONTROLS CABINET
FILTER MOTORS 0.36 20 15 0.90 16 20 0.54 M-E-8
LTS. IN AIR PLENUM 0.90 20 17 1.62 18 20 0.72 PE 5 & 7
COND. PUMP CPA5 0.36 20 19 0.90 20 20 0.54 (E) LOAD
FAN COIL UNITS (NORTH) 0.72 20 21 1.26 22 20 0.54 (E) LOAD
(E) LOAD 0.36 20 23 0.90 24 20 0.54 (E) LOAD
(N) FLOW METER 0.18 2 #12, #12 GD, 3/4"C. 20 25 0.18 26 20 SPARE
SPARE 20 27 28 20 SPARE
SPARE 20 29 30 20 SPARE
TOTAL CONNECTED KVA PER PHASE 4.3 4.3 5.0
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING 4.5 1.25 5.6 16 1.00 16
RECEPTACLES 3.2 NEC TABLE 220-13 3.2 9 1.00 9
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 5.9 1.00 5.9 17 1.00 17
DEMAND AMPS 41
NOTES
NOTES: REPLACE EXISTING PANEL W/ 30-POLE PANEL
| 101-955 |
| 101-956 |
| 101-957 |
| 101-958 |
| 101-959 |