BLDG NO. BUILDING NAME LOCATION
STEAM PIPE SIZE
(IN.)
BASIS OF DESIGN
STEAM METER
MODLE
PUMPED
CONDENSATE
RETURN SIZE (IN.)
BASIS OF DESIGN
CONDENSATE
METER MODEL
CONNECT
LOAD (PPH)
OFF PEAK
LOAD (PPH)
NOTES
202 ENGINEERING MECHANICS SERVICE ENTRANCE 5" ABB Vortex 3" GE DF868 4,830 2,900 ALL
1. REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2. DUE TO ALL HIGH PRESSURE STEAM METER INSTALLATION REQUIREMENTS, CONTRACTOR SHALL SCHEDULE WITH COTR BUILDING SHUTDOWN/OUTAGE UPON AWARD OF CONSTRUCTION CONTRACT.
3.
4.
5.
HOT TAPPING WILL BE REQUIRED FOR ALL PUMPED CONDENSATE RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE SENSORS FOR TOTAL ENERGY DATA COLLECTION.
REFER TO PLANS FOR LOCATIONS.
ABB VORTEX ARE FLANGED FITTING METERS AND ULTRASONICS ARE STRAP‐ON TYPE METERS.
STEAM AND CONDENSATE METER TABLE
GENERAL NOTES:
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.
BLDG NO. BUILDING NAME LOCATION PIPE SIZE (IN.)
BASIS OF DESIGN
METER MODEL
FLOW
DIRECTION
PEAK LOAD
(GPM)
OFF PEAK LOAD
(GPM) NOTES
8" GE DF868 SUPPLY
8" GE DF868 RETURN
1 REFER TO DETAIL SHEET AND SPECIFICATION FOR INSTALLATION REQUIREMENTS.
2.
3.
4. GE DF868 ULTRASONICS ARE STRAP‐ON TYPE METERS.
UNLESS NOTED OTHERWISE, HOT TAPPING WILL BE REQUIRED FOR CHILLED WATER SUPPLY AND RETURN LINES FOR INSTALLATION OF DRY WELL TYPE INSERTION TEMPERATURE
SENSORS FOR TOTAL ENERGY DATA COLLECTION. REFER TO PLANS FOR LOCATIONS.
CHILLED WATER METER TABLE
TABLE IS FOR INFORMATION PURPOSES ONLY. FLOW METER SIZE AND INSTALLATION SHALL BE ACCORDING TO MANUFACTURERS RECOMMENDATION.
202 ENGINEERING MECHANICS SERVICE ENTRANCE 696 441 ALL
GENERAL NOTES:
PANEL PB-2-L5 (E)
POLES 42 VOLTS 120/208 VOLTS MOUNTING SURFACE NOTES:
SECT 1 PH/WIRE 3 PHASE/4 WIRE (A, B, C, N, EG) LOCATION MECH ROOM 200
AIC 10,000 MAIN 100 AMPS MLO FED FROM FUSED DISCONNECT
NEUTRAL 100 %
LOAD CKT PHASE KVA CKT LOAD
LOAD DESCRIPTION KVA FEEDER TRIP # A B C # TRIP FEEDER KVA LOAD DESCRIPTION
(E) V.H #9 0.60 20 1 0.96 2 20 0.36 EXH. FAN #21 (E)
(E) LIGHTS FAN CASING 0.90 20 3 1.26 4 20 0.36 EXH. FAN #20 (E)
(E) LIGHTS FAN CASING 0.90 20 5 1.26 6 20 0.36 EXH. FAN #17 (E)
(E) RECEPT. M.E. EQUPMT. RM #2 0.54 20 7 0.90 8 20 0.36 EXH. FAN #12 (E)
(E) RECEPT. VBENDING MACH. 0.54 20 9 0.90 10 20 0.36 FILTERS MOTOR (E)
(E) RECEPT. VBENDING MACH. 0.54 20 11 0.90 12 20 0.36 FAN SHUT-DOWN (E)
(E) TIMER AHU-2 0.18 20 13 0.54 14 20 0.36 CONCENTRATOR CONTROLS (E)
(E) SPACE 20 15 0.18 16 20 2 #12, #12GD, 3/4" C. 0.18 FLOW METER CONTROLS (N)
(E) SPACE 20 17 18 20 SPACE
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
TOTAL CONNECTED KVA PER PHASE 2.4 2.3 2.2
LOAD COMPUTATIONS AND MINIMUM FEEDER AMPACITY
CATEGORY CONNECTED KVA DMD FACTOR DMD KVA DEMAND AMPS MULTIPLIER MIN AMPACITY
LIGHTING 1.8 1.25 2.3 6 1.00 6
RECEPTACLES 1.6 NEC TABLE 220-13 1.6 5 1.00 5
KITCHEN EQUIPMENT - 0.65 - - 1.00 -
LARGEST MOTOR 1.25 - - 1.00 -
OTHER LOADS 3.5 1.00 3.5 10 1.00 10
DEMAND AMPS 20
NOTES
| 202-345 |
| 202-346 |
| 202-347 |
| 202-348 |