View the file

Other files

File Type Posted
Amendment 0007 Attachment 1 RFI Question Answer MATOC Solicitation.pdf PDF
Amendment 0007 Solicitation 36C26222R0044.pdf PDF
Amendment 0006 Solicitation 36C26222R0044.pdf PDF
Amendment 0005 Attachment 7 RFI Questions 28-51-119 B162 Geotechnical Evaluation Report.pdf PDF
Amendment 0005 Attachment 8 RFI Questions 28-51-119 Lab Pharmacy Soils Report.pdf PDF
Amendment 0005 Attachment 12 RFI 125 SF 24.pdf PDF
Amendment 0005 Attachment 5 RFI 24 Specification 32 12 16 Asphalt Paving.pdf PDF
Amendment 0005 Solicitation 36C26222R0044.pdf PDF
Amendment 0005 Attachment 15 Earthwork Fill Material Lab Rpt.pdf PDF
Amendment 0005 Attachment 10 RFI Questions 104-107 B162 Elevator Airflow.pdf PDF
Amendment 0005 Attachment 19 Testing_and_Inspection_Plans_Elevator_Pit_Footing_17.09.21_(28)_Day_Bre_14167911.pdf PDF
Amendment 0005 Attachment 2 RFI 11 Seed Project.pdf PDF
Amendment 0005 Attachment 17 GTI New Lab Pharmacy As Builts.pdf PDF
Amendment 0005 Attachment 1 RFI 2 Seed Project Physical_Access_Control__Data.pdf PDF
Amendment 0005 Attachment 9 RFI 34 EPDM Submittal.pdf PDF
Amendment 0005 Attachment 3 RFI Questions 20-104-107 B162 Elevator Drawings.pdf PDF
Amendment 0005 Attachment 6 RFI Questions 28-30-51-81-82 119 ED Soils Report.pdf PDF
Amendment 0005 Attachment 20 Testing_and_Inspection_Plans_Elevator_Pit_Walls_17.09.28_(7)_Day_Break_14167948.pdf PDF
Amendment 0005 Attachment 4 RFI Questions 20-104-107 B164 Elevator Drawings.pdf PDF
Amendment 0005 Attachment 13 RFI Questions 23-25-54-84 Additional Civil Specs.pdf PDF
Amendment 0005 FAR 52.216-22.pdf PDF
Amendment 0005 Seed Project RFI Questions and Answers.pdf PDF
Amendment 0005 Attachment 14 Earthwork Base Course Lab Rpt.pdf PDF
Amendment 0005 Attachment 11 RFI Questions 104 and 107 B162 Elevator Pit.pdf PDF
Amendment 0005 Attachment 16 ED Drainage Details.pdf PDF
Amendment 0005 Attachment 18 Proposed Lab_Pharmacy Bldg Plans_Hole locations.pdf PDF
Amendment 0004 Solicitation 36C26222R0044.pdf PDF
Amendment 0003 Solicitation 36C26222R0044.pdf PDF
Amendment 0002 Attachment 1 Site Visit Sign-In Sheet.pdf PDF
Amendment 0002 Solicitation 36C26222R0044.pdf PDF
Amendment 0001 Attachment 1 Site Visit Map - Bldg. 19.pdf PDF
Amendment 0001 Solicitation 36C26222R0044.pdf PDF
S02 Solicitation Attachment 2 Technical Proposal Data.docx DOCX document
Amendment 0001 Attachment 2 Seed Project Site Visit Information.pdf PDF
S02 Solicitation Attachment 3 Evaluation Ratings and Definitions.pdf PDF
S02 Solicitation Attachment 6 Contractor Surety Limitations.docx DOCX document
S02 Solicitation Attachment 4 Subcontractor Information And Consent.docx DOCX document
S02 Solicitation Attachment 1 Past Performance Questionnaire.docx DOCX document
S02 Solicitation Attachment 13 Seed Project Specifications.pdf PDF
S02 Solicitation Attachment 5 Bid Schedule - MATOC SEED Project.docx DOCX document
S02 Solicitation Attachment 12 Seed Project Drawings.pdf PDF
S02 Solicitation Attachment 9 Contractor Safety and EMR Info.docx DOCX document
S02 Solicitation Attachment 7 Financial Disclosure Questionnaire.docx DOCX document
S02 Solicitation Attachment 2 Technical Proposal Data.docx DOCX document
S02 Solicitation Attachment 10 Seed Project Wage Determination.pdf PDF
S02 Solicitation Attachment 8 Location Capabilities Questionnaire.docx DOCX document
S02 Solicitation Attachment 11 Prescott Facility Map.pdf PDF
S02 Solicitation Attachment 15 Seed Project Statement of Work.pdf PDF
S02 Solicitation 36C26222R0044.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1440 E Missouri Ave

Suite C195

Phoenix, AZ 85014 p.602.888.0336 www.pangolinstr.com

NORTERN ARIZONA VA HEALTH CARE SYSTEM

500 AZ-89, PRESCOTT, AZ 86301

21-065

6/3/2022

STRUCTURAL CALCULATIONS

INSTALL ELEVATORS AND COMPLETE SPACE BUILT-OUT

FOR B162 AND B164

of 19

6/01/2022

Sheet No. _________________

Project No. _________________

Project Name______________________________________________ Date __________________

Subject __________________________________________________ Computed By __________________

21-065

10/04

SP

Pangolin Structural has been consulted to provide structural services for Northern Arizona VA Health Care System at 500 AZ-89, Prescott, AZ 86301.

Scope of services includes openings in existing concrete walls, and coordination between existing structure and new elevators, including new guide rail support columns.

Hand calculations and Enercalc have been used to design lintels at openings.

1. Project Description

Phoenix, AZ 85014

2. Lintel at Double Door

Project Name______________________________________________ Date __________________

21-065

SP

W12X22 (10)

W

X2

(1 5)

W12X22 (10)

W12X22 (10)

EL. 13'-7"

SF202

C3

EP1

EP1

6'-4" 7'-0"

'-3

Load from floor above

Dead load (CFS Exterior wall) = 12 psf * (35-14)ft

Dead load (Floor self wt + superimposed dead)

= 12.25/2 ft * 18/2 ft * (150pcf * 4.5"/12 + 20 psf floor dead)

= 252 plf

= 4.2 kips

Floor load (Floor live) = 12.25/2 ft * 18/2 ft * 100psf = 5.51 kips

Point load at 2ft (conservative) from beam end

Load from wall directly above lintel

Dead load (Wall self wt.) = (14-7) ft * (0.150pcf * 12"/12) = 1050 plf

Lintel beam provided - MC 12x31 See Enercalc report on next page.

2. Lintel at Double door opening Grid G.3 b/w Grid 5 and 6

PLAN

Steel Beam LIC# : KW-06012239, Build:20.21.10.4 Pangolin Structural LLC (c) ENERCALC INC 1983-2021

DESCRIPTION: Channel lintel

Project File: 21-065_va_prescott_elevator_install_012239.EC6

Project Title:

Engineer:

Project ID:

Project Descr:

CODE REFERENCES

Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16

Load Combination Set : IBC 2018

Material Properties Analysis Method :

ksi Bending Axis : Major Axis Bending

Completely Unbraced

Allowable Strength Design Fy : Steel Yield : 36.0 ksi

Beam Bracing : E: Modulus : 29,000.0

.Service loads entered. Load Factors will be applied for calculations.Applied Loads

Beam self weight NOT internally calculated and added Uniform Load : D = 0.2520 k/ft, Tributary Width = 1.0 ft, (CFS wall)

Point Load : D = 4.20, L = 5.510 k @ 2.0 ft, (Beam Point load)

Uniform Load : D = 1.050 k/ft, Tributary Width = 1.0 ft, (Wall above lintel)

.Design OKDESIGN SUMMARY

Maximum Bending Stress Ratio = 0.271 : 1

Load Combination +D+L

Span # where maximum occurs Span # 1

Location of maximum on span 2.006ft

10.954 k Mn / Omega : Allowable 71.317 k-ft Vn/Omega : Allowable

MC12x31Section used for this span

Span # where maximum occurs

Location of maximum on span

Span # 1

Load Combination +D+L

57.428 k

Section used for this span MC12x31 Ma : Applied

Maximum Shear Stress Ratio = 0.191 : 1

0.000 ft

19.296 k-ft Va : Applied

0 <360

Ratio = 0 <180

Maximum Deflection Max Downward Transient Deflection 0.008 in 10,225Ratio = >=360

Max Upward Transient Deflection 0.000 in Ratio =

Max Downward Total Deflection 0.022 in Ratio = >=180 Max Upward Total Deflection 0.000 in

Span: 1 : L Only

Span: 1 : +D+L

Maximum Forces & Stresses for Load Combinations

Span #

Summary of Moment ValuesLoad Combination Summary of Shear ValuesMax Stress Ratios

M V Mmax -Mmax + Rm VnxMa Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length

D Only

Dsgn. L = 6.50 ft 1 0.164 0.124 11.72 11.72 119.10 71.32 1.17 1.00 7.14 95.90 57.43

+D+L

Dsgn. L = 6.50 ft 1 0.271 0.191 19.30 19.30 119.10 71.32 1.25 1.00 10.95 95.90 57.43

+D+0.750L

Dsgn. L = 6.50 ft 1 0.244 0.174 17.39 17.39 119.10 71.32 1.24 1.00 10.00 95.90 57.43

+0.60D

Dsgn. L = 6.50 ft 1 0.099 0.075 7.03 7.03 119.10 71.32 1.17 1.00 4.28 95.90 57.43

Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl

Overall Maximum Deflections

+D+L 1 0.0223 3.064 0.0000 0.000

Load Combination Support 1 Support 2

Vertical Reactions Support notation : Far left is #1 Values in KIPS

Overall MAXimum 10.954 7.219

Overall MINimum -3.815 -1.695

Steel Beam

DESCRIPTION: Channel lintel

Project File: 21-065_va_prescott_elevator_install_012239.EC6

Project Title:

Engineer:

Project ID:

Project Descr:

Load Combination Support 1 Support 2

Vertical Reactions Support notation : Far left is #1 Values in KIPS

D Only 7.139 5.524

+D+L 10.954 7.219

+D+0.750L 10.000 6.795

+0.60D 4.284 3.314

L Only 3.815 1.695

Max Reaction (Factored) = 1.2*7.2+1.6*3.8k = 14.72k www.hilti.com

Hilti PROFIS Engineering 3.0.73

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

Specifier's comments: Anchor to Concrete Column

1 Input data

Anchor type and diameter: HIT-RE 500 V3 + HAS-V-36 (ASTM F1554 Gr.36) 3/4

Item number: 2198030 HAS-V-36 3/4"x10" (element) / 2123401 HIT-RE 500 V3 (adhesive)

Effective embedment depth: hef,act = 8.000 in. (hef,limit = - in.)

Material: ASTM F1554 Grade 36

Evaluation Service Report: ESR-3814

Issued I Valid: 3/1/2021 | 1/1/2023

Proof: Design Method ACI 318-14 / Chem

Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in.

Anchor plateR : lx x ly x t = 24.000 in. x 12.000 in. x 0.500 in.; (Recommended plate thickness: not calculated)

Profile: no profile

Base material: cracked concrete, 4000, fc' = 4,000 psi; h = 12.000 in., Temp. short/long: 32/32 °F

Installation: hammer drilled hole, Installation condition: Dry

Reinforcement: tension: condition A, shear: condition A; no supplemental splitting reinforcement present edge reinforcement: > No. 4 bar Seismic loads (cat. C, D, E, or F) Tension load: yes (17.2.3.4.3 (d))

Shear load: yes (17.2.3.5.3 (c))

R - The anchor calculation is based on a rigid anchor plate assumption.

Geometry [in.] & Loading [lb, in.lb]

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

1.1 Design results

Case Description Forces [lb] / Moments [in.lb] Seismic Max. Util. Anchor [%]

1 Combination 1 N = 0; Vx = 0; Vy = -14,720;

Mx = 0; My = 0; Mz = 0;

Nsus = 0; Mx,sus = 0; My,sus = 0;

yes 84

1 2 3

4 5 6 x y

2 Load case/Resulting anchor forces

Anchor reactions [lb] Tension force: (+Tension, -Compression)

Anchor Tension force Shear force Shear force x Shear force y 1 0 2,453 0 -2,453 2 0 2,453 0 -2,453 3 0 2,453 0 -2,453 4 0 2,453 0 -2,453 5 0 2,453 0 -2,453 6 0 2,453 0 -2,453 max. concrete compressive strain: - [‰] max. concrete compressive stress: - [psi] resulting tension force in (x/y)=(0.000/0.000): 0 [lb] resulting compression force in (x/y)=(0.000/0.000): 0 [lb]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load

Load Nua [lb] Capacity f Nn [lb] Utilization bN = Nua/f Nn Status Steel Strength* N/A N/A N/A N/A

Bond Strength** N/A N/A N/A N/A

Sustained Tension Load Bond Strength* N/A N/A N/A N/A

Concrete Breakout Failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

4 Shear load

Load Vua [lb] Capacity f Vn [lb] Utilization bV = Vua/f Vn Status Steel Strength* 2,453 4,540 55 OK

Steel failure (with lever arm)* N/A N/A N/A N/A

Pryout Strength (Concrete Breakout Strength controls)**

14,720 60,669 25 OK

Concrete edge failure in direction y-** 14,720 17,710 84 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength

Vsa,eq = ESR value refer to ICC-ES ESR-3814 f Vsteel ³ Vua ACI 318-14 Table 17.3.1.1

Variables

Ase,V [in.2] futa [psi] aV,seis

0.33 58,000 0.600

Calculations

Vsa,eq [lb] 6,984

Results

Vsa,eq [lb] f steel f Vsa,eq [lb] Vua [lb] 6,984 0.650 4,540 2,453

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

4.2 Pryout Strength (Concrete Breakout Strength controls)

Vcpg = kcp [(ANc ANc0

) y ec,N y ed,N y c,N y cp,N Nb ] ACI 318-14 Eq. (17.5.3.1b) f Vcpg ³ Vua ACI 318-14 Table 17.3.1.1 ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) ANc0 = 9 h2 ef ACI 318-14 Eq. (17.4.2.1c) y ec,N = ( 1

1 + 2 e'

N 3 hef

) £ 1.0 ACI 318-14 Eq. (17.4.2.4) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef

) £ 1.0 ACI 318-14 Eq. (17.4.2.5b) y cp,N = MAX(ca,min cac

1.5hef cac ) £ 1.0 ACI 318-14 Eq. (17.4.2.7b)

Nb = kc l a √f'c h 1.5 ef ACI 318-14 Eq. (17.4.2.2a)

Variables kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] 2 8.000 0.000 0.000 8.000 y c,N cac [in.] kc l a f'c [psi]

1.000 19.647 17 1.000 4,000

Calculations

ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 1,140.00 576.00 1.000 1.000 0.900 1.000 24,328

Results

Vcpg [lb] f concrete f seismic f nonductile f Vcpg [lb] Vua [lb] 86,670 0.700 1.000 1.000 60,669 14,720

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

4.3 Concrete edge failure in direction y-

Vcbg = (AVc AVc0

) y ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1b) f Vcbg ³ Vua ACI 318-14 Table 17.3.1.1 AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b) AVc0 = 4.5 c2 a1 ACI 318-14 Eq. (17.5.2.1c) y ec,V = ( 1

1 + 2e' v 3ca1

) £ 1.0 ACI 318-14 Eq. (17.5.2.5) y ed,V = 0.7 + 0.3( ca2 1.5ca1

) £ 1.0 ACI 318-14 Eq. (17.5.2.6b) y h,V = √1.5ca1 ha

³ 1.0 ACI 318-14 Eq. (17.5.2.8)

Vb = 9 l a √f'c c 1.5 a1 ACI 318-14 Eq. (17.5.2.2b)

Variables ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]

12.000 8.000 0.000 1.200 12.000 le [in.] l a da [in.] f'c [psi] y parallel,V

6.000 1.000 0.750 4,000 1.000

Calculations

AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [lb]

528.00 648.00 1.000 0.833 1.225 23,662

Results

Vcbg [lb] f concrete f seismic f nonductile f Vcbg [lb] Vua [lb] 23,613 0.750 1.000 1.000 17,710 14,720

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

5 Warnings

• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility!

• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs.

• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the Evaluation Service Report for cleaning and installation instructions.

• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/

• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section

17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).

• Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3

(b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non-yielding attachment. Section 17.2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by w0.

• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14, Section 17.8.1.

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

Coordinates Anchor [in.]

Anchor x y c-x c+x c-y c+y

1 -9.000 -2.000 8.000 42.000 12.000 26.000 2 0.000 -2.000 17.000 33.000 12.000 26.000 3 9.000 -2.000 26.000 24.000 12.000 26.000

Anchor x y c-x c+x c-y c+y

4 -9.000 4.000 8.000 42.000 18.000 20.000 5 0.000 4.000 17.000 33.000 18.000 20.000 6 9.000 4.000 26.000 24.000 18.000 20.000

6 Installation data Anchor type and diameter: HIT-RE 500 V3 + HAS-V-36 (ASTM F1554 Gr.36) 3/4

Profile: no profile Item number: 2198030 HAS-V-36 3/4"x10" (element) / 2123401 HIT-RE 500 V3 (adhesive)

Hole diameter in the fixture: df = 0.812 in. Maximum installation torque: 1,200 in.lb Plate thickness (input): 0.500 in. Hole diameter in the base material: 0.875 in.

Recommended plate thickness: not calculated Hole depth in the base material: 8.000 in.

Drilling method: Hammer drilled Minimum thickness of the base material: 9.750 in.

Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

3/4 Hilti HAS Carbon steel threaded rod with Hilti HIT-RE 500 V3

6.1 Recommended accessories

Drilling Cleaning Setting

• Suitable Rotary Hammer

• Properly sized drill bit

• Compressed air with required accessories to blow from the bottom of the hole

• Proper diameter wire brush

• Dispenser including cassette and mixer

• Torque wrench

1 2 3

4 5 6 x y -0.000

0.

12.000 12.000

3.000 9.000 9.000 3.000

4.

6.

2.

6.

6.

Input data and results must be checked for conformity with the existing conditions and for plausibility!

PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Company:

Address:

Phone I Fax:

Design:

Fastening point:

Lintel on Wall Calc 3

Page:

Specifier:

E-Mail:

Date:

10/26/2021

7 Remarks; Your Cooperation Duties

• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.

Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.

Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application.

• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you.

Phoenix, AZ 85014

2. Lintel at Window Openings

Project Name______________________________________________ Date __________________

21-067

SP

Load from floor above

Dead load (CFS Exterior wall) = 12 psf * (35-14)ft

Dead load (Floor self wt + superimposed dead)

= 9/2 ft * (150 pcf * 4.5"/12 + 20 psf floor dead)

= 252 plf

= 344 plf

Floor load (Floor live) = 9/2 ft * 100 psf = 0.45 kips

Load from wall directly above lintel

Dead load (Wall self wt.) = (14-7) ft * (150 pcf * 12"/12) = 1050 plf

Existing wall is 12" thick with #5 @ 12" o.c. horizontal and #6 @ 12" o.c. vertical reinforcement.

Available beam depth = 7'-0" deep x 12" wide

Assumed lintel-beam section = 24" deep x 12" wide with 2-#5 rebars, conservative design.

See Enercalc report on next page.

'-0

7' -0

3' -0

4'-0"

3. Lintel at Window opening Grid 3 b/w Grid E and G

Window Elevation

Concrete Beam

DESCRIPTION: Concrete lintel at Window openings

Project File: 21-065_va_prescott_elevator_install_012239.EC6

Project Title:

Engineer:

Project ID:

Project Descr:

CODE REFERENCES

Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16

Load Combination Set : IBC 2018

Material Properties

4.0 7.50

145.0

Elastic Modulus 3,122.0 ksi

60.0 29,000.0

40.0

29,000.0

= 0.90

0.750 f'c ksi fy - Main Rebar ksi

Density

1/2 fr = f'c * 474.342 pcf

E - Main Rebar ksi psi

= 1.0λ LtWt Factor

Fy - Stirrups ksi

E - Stirrups ksi β 0.850

Shear :

Stirrup Bar Size #

Number of Resisting Legs Per Stirrup

Phi Values Flexure :

ψ φ

Cross Section & Reinforcing Details

Rectangular Section, Width = 12.0 in, Height = 24.0 in

Span #1 Reinforcing

2-#5 at 3.0 in from Bottom, from 0.0 to 6.0 ft in this span

Beam self weight calculated and added to loads Load for Span Number 1

Uniform Load : D = 1.050 k/ft, Tributary Width = 1.0 ft, (Wall above lintel)

Uniform Load : D = 0.3440, L = 0.450 k/ft, Tributary Width = 1.0 ft, (Floor above loads)

Uniform Load : D = 0.2520 k/ft, Tributary Width = 1.0 ft, (CFS Exterior Wall)

Design OKDESIGN SUMMARY

Maximum Bending Stress Ratio = 0.239 : 1

Span # where maximum occurs Span # 1

Location of maximum on span 2.995 ft

Mn * Phi : Allowable 57.318 k-ft

Typical SectionSection used for this span

Mu : Applied 13.694 k-ft

Maximum Deflection

0 <360.0

44676 Ratio = 0 <180.0

Max Downward Transient Deflection 0.000 in 0Ratio = <360.0

Max Upward Transient Deflection 0.000 in Ratio =

Max Downward Total Deflection 0.002 in Ratio = >=180.0

Max Upward Total Deflection 0.000 in

Span: 1 : L Only

Span: 1 : L Only

Span: 1 : +D+L

Span: 1 : +D+L

Load Combination Support 1 Support 2

Vertical Reactions Support notation : Far left is #1

Overall MAXimum 7.158 7.158

Overall MINimum 1.350 1.350

D Only 5.808 5.808

+D+L 7.158 7.158

+D+0.750L 6.821 6.821

DESCRIPTION: Concrete lintel at Window openings

Project File: 21-065_va_prescott_elevator_install_012239.EC6

Project Title:

Engineer:

Project ID:

Project Descr:

Load Combination Support 1 Support 2

Vertical Reactions Support notation : Far left is #1

+0.60D 3.485 3.485

L Only 1.350 1.350

Detailed Shear Information

Load Combination

Vu (k)Span Distance 'd' Comment Phi*Vs

Req'd

Phi*Vnd*Vu/MuMu

(ft) (k)(in) (k)Actual Suggest(k-ft)Number (k)

Spacing (in)

Design

Phi*Vc

+1.20D+1.60L 1 0.00 21.00 9.13 9.13 0.00 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.07 21.00 8.93 8.93 0.59 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.13 21.00 8.73 8.73 1.17 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.20 21.00 8.53 8.53 1.74 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.26 21.00 8.33 8.33 2.29 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.33 21.00 8.13 8.13 2.83 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.39 21.00 7.93 7.93 3.36 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.46 21.00 7.73 7.73 3.87 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.52 21.00 7.53 7.53 4.37 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.59 21.00 7.33 7.33 4.86 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.66 21.00 7.13 7.13 5.33 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.72 21.00 6.93 6.93 5.79 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.79 21.00 6.73 6.73 6.24 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.85 21.00 6.54 6.54 6.68 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.92 21.00 6.34 6.34 7.10 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 0.98 21.00 6.14 6.14 7.51 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 1.05 21.00 5.94 5.94 7.90 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 1.11 21.00 5.74 5.74 8.29 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 1.18 21.00 5.54 5.54 8.66 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 1.25 21.00 5.34 5.34 9.01 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 1.31 21.00 5.14 5.14 9.36 0.96 23.83 Vu < PhiVc/2Not Reqd 9.6.3 23.8 0.0 0.0

+1.20D+1.60L 1 1.38 21.00 4.94 4.94 9.69 0.89 23.75 Vu < PhiVc/2Not Reqd 9.6.3 23.7 0.0 0.0

+1.20D+1.60L 1 1.44 21.00 4.74 4.74 10.00 0.83 23.68 Vu < PhiVc/2Not Reqd 9.6.3 23.7 0.0 0.0

+1.20D+1.60L 1 1.51 21.00 4.54 4.54 10.31 0.77 23.61 Vu < PhiVc/2Not Reqd 9.6.3 23.6 0.0 0.0

+1.20D+1.60L 1 1.57 21.00 4.34 4.34 10.60 0.72 23.54 Vu < PhiVc/2Not Reqd 9.6.3 23.5 0.0 0.0

+1.20D+1.60L 1 1.64 21.00 4.14 4.14 10.88 0.67 23.49 Vu < PhiVc/2Not Reqd 9.6.3 23.5 0.0 0.0

+1.20D+1.60L 1 1.70 21.00 3.94 3.94 11.14 0.62 23.43 Vu < PhiVc/2Not Reqd 9.6.3 23.4 0.0 0.0

+1.20D+1.60L 1 1.77 21.00 3.74 3.74 11.39 0.57 23.38 Vu < PhiVc/2Not Reqd 9.6.3 23.4 0.0 0.0

+1.20D+1.60L 1 1.84 21.00 3.54 3.54 11.63 0.53 23.33 Vu < PhiVc/2Not Reqd 9.6.3 23.3 0.0 0.0

+1.20D+1.60L 1 1.90 21.00 3.34 3.34 11.86 0.49 23.28 Vu < PhiVc/2Not Reqd 9.6.3 23.3 0.0 0.0

+1.20D+1.60L 1 1.97 21.00 3.14 3.14 12.07 0.46 23.24 Vu < PhiVc/2Not Reqd 9.6.3 23.2 0.0 0.0

+1.20D+1.60L 1 2.03 21.00 2.94 2.94 12.27 0.42 23.20 Vu < PhiVc/2Not Reqd 9.6.3 23.2 0.0 0.0

+1.20D+1.60L 1 2.10 21.00 2.74 2.74 12.46 0.39 23.16 Vu < PhiVc/2Not Reqd 9.6.3 23.2 0.0 0.0

+1.20D+1.60L 1 2.16 21.00 2.54 2.54 12.63 0.35 23.12 Vu < PhiVc/2Not Reqd 9.6.3 23.1 0.0 0.0

+1.20D+1.60L 1 2.23 21.00 2.34 2.34 12.79 0.32 23.08 Vu < PhiVc/2Not Reqd 9.6.3 23.1 0.0 0.0

+1.20D+1.60L 1 2.30 21.00 2.15 2.15 12.94 0.29 23.05 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 2.36 21.00 1.95 1.95 13.07 0.26 23.01 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 2.43 21.00 1.75 1.75 13.19 0.23 22.98 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 2.49 21.00 1.55 1.55 13.30 0.20 22.95 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 2.56 21.00 1.35 1.35 13.40 0.18 22.92 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 2.62 21.00 1.15 1.15 13.48 0.15 22.88 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 2.69 21.00 0.95 0.95 13.55 0.12 22.85 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 2.75 21.00 0.75 0.75 13.60 0.10 22.82 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 2.82 21.00 0.55 0.55 13.64 0.07 22.79 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 2.89 21.00 0.35 0.35 13.67 0.04 22.76 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 2.95 21.00 0.15 0.15 13.69 0.02 22.73 Vu < PhiVc/2Not Reqd 9.6.3 22.7 0.0 0.0

+1.20D+1.60L 1 3.02 21.00 -0.05 0.05 13.69 0.01 22.72 Vu < PhiVc/2Not Reqd 9.6.3 22.7 0.0 0.0

+1.20D+1.60L 1 3.08 21.00 -0.25 0.25 13.68 0.03 22.75 Vu < PhiVc/2Not Reqd 9.6.3 22.7 0.0 0.0

+1.20D+1.60L 1 3.15 21.00 -0.45 0.45 13.66 0.06 22.78 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 3.21 21.00 -0.65 0.65 13.63 0.08 22.81 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 3.28 21.00 -0.85 0.85 13.58 0.11 22.84 Vu < PhiVc/2Not Reqd 9.6.3 22.8 0.0 0.0

+1.20D+1.60L 1 3.34 21.00 -1.05 1.05 13.51 0.14 22.87 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 3.41 21.00 -1.25 1.25 13.44 0.16 22.90 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

DESCRIPTION: Concrete lintel at Window openings

Project File: 21-065_va_prescott_elevator_install_012239.EC6

Project Title:

Engineer:

Project ID:

Project Descr:

Detailed Shear Information

Load Combination

Vu (k)Span Distance 'd' Comment Phi*Vs

Req'd

Phi*Vnd*Vu/MuMu

(ft) (k)(in) (k)Actual Suggest(k-ft)Number (k)

Spacing (in)

Design

Phi*Vc

+1.20D+1.60L 1 3.48 21.00 -1.45 1.45 13.35 0.19 22.93 Vu < PhiVc/2Not Reqd 9.6.3 22.9 0.0 0.0

+1.20D+1.60L 1 3.54 21.00 -1.65 1.65 13.25 0.22 22.96 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 3.61 21.00 -1.85 1.85 13.13 0.25 23.00 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 3.67 21.00 -2.05 2.05 13.01 0.28 23.03 Vu < PhiVc/2Not Reqd 9.6.3 23.0 0.0 0.0

+1.20D+1.60L 1 3.74 21.00 -2.24 2.24 12.87 0.31 23.07 Vu < PhiVc/2Not Reqd 9.6.3 23.1 0.0 0.0

+1.20D+1.60L 1 3.80 21.00 -2.44 2.44 12.71 0.34 23.10 Vu < PhiVc/2Not Reqd 9.6.3 23.1 0.0 0.0

+1.20D+1.60L 1 3.87 21.00 -2.64 2.64 12.55 0.37 23.14 Vu < PhiVc/2Not Reqd 9.6.3 23.1 0.0 0.0

+1.20D+1.60L 1 3.93 21.00 -2.84 2.84 12.37 0.40 23.18 Vu < PhiVc/2Not Reqd 9.6.3 23.2 0.0 0.0

+1.20D+1.60L 1 4.00 21.00 -3.04 3.04 12.17 0.44 23.22 Vu < PhiVc/2Not Reqd 9.6.3 23.2 0.0 0.0

+1.20D+1.60L 1 4.07 21.00 -3.24 3.24 11.97 0.47 23.26 Vu < PhiVc/2Not Reqd 9.6.3 23.3 0.0 0.0

+1.20D+1.60L 1 4.13 21.00 -3.44 3.44 11.75 0.51 23.31 Vu < PhiVc/2Not Reqd 9.6.3 23.3 0.0 0.0

+1.20D+1.60L 1 4.20 21.00 -3.64 3.64 11.52 0.55 23.35 Vu < PhiVc/2Not Reqd 9.6.3 23.4 0.0 0.0

+1.20D+1.60L 1 4.26 21.00 -3.84 3.84 11.27 0.60 23.40 Vu < PhiVc/2Not Reqd 9.6.3 23.4 0.0 0.0

+1.20D+1.60L 1 4.33 21.00 -4.04 4.04 11.01 0.64 23.46 Vu < PhiVc/2Not Reqd 9.6.3 23.5 0.0 0.0

+1.20D+1.60L 1 4.39 21.00 -4.24 4.24 10.74 0.69 23.51 Vu < PhiVc/2Not Reqd 9.6.3 23.5 0.0 0.0

+1.20D+1.60L 1 4.46 21.00 -4.44 4.44 10.46 0.74 23.58 Vu < PhiVc/2Not Reqd 9.6.3 23.6 0.0 0.0

+1.20D+1.60L 1 4.52 21.00 -4.64 4.64 10.16 0.80 23.64 Vu < PhiVc/2Not Reqd 9.6.3 23.6 0.0 0.0

+1.20D+1.60L 1 4.59 21.00 -4.84 4.84 9.85 0.86 23.71 Vu < PhiVc/2Not Reqd 9.6.3 23.7 0.0 0.0

+1.20D+1.60L 1 4.66 21.00 -5.04 5.04 9.52 0.93 23.79 Vu < PhiVc/2Not Reqd 9.6.3 23.8 0.0 0.0

+1.20D+1.60L 1 4.72 21.00 -5.24 5.24 9.19 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 4.79 21.00 -5.44 5.44 8.84 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 4.85 21.00 -5.64 5.64 8.47 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 4.92 21.00 -5.84 5.84 8.10 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 4.98 21.00 -6.04 6.04 7.71 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.05 21.00 -6.24 6.24 7.30 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.11 21.00 -6.44 6.44 6.89 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.18 21.00 -6.64 6.64 6.46 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.25 21.00 -6.83 6.83 6.02 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.31 21.00 -7.03 7.03 5.56 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.38 21.00 -7.23 7.23 5.10 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.44 21.00 -7.43 7.43 4.62 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.51 21.00 -7.63 7.63 4.12 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.57 21.00 -7.83 7.83 3.61 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.64 21.00 -8.03 8.03 3.09 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.70 21.00 -8.23 8.23 2.56 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.77 21.00 -8.43 8.43 2.02 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.84 21.00 -8.63 8.63 1.46 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.90 21.00 -8.83 8.83 0.88 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

+1.20D+1.60L 1 5.97 21.00 -9.03 9.03 0.30 1.00 23.87 Vu < PhiVc/2Not Reqd 9.6.3 23.9 0.0 0.0

Maximum Forces & Stresses for Load Combinations

Span #

Bending Stress Results ( k-ft )Location (ft)Load Combination

Mu : Max Stress RatioSegment Phi*Mnxalong Beam

MAXimum BENDING Envelope Span # 1 1 6.000 13.69 57.32 0.24

+1.40D Span # 1 1 6.000 12.20 57.32 0.21

+1.20D+1.60L Span # 1 1 6.000 13.69 57.32 0.24

+1.20D+0.50L Span # 1 1 6.000 11.47 57.32 0.20

+1.20D Span # 1 1 6.000 10.45 57.32 0.18

+0.90D Span # 1 1 6.000 7.84 57.32 0.14

Location in Span (ft)Load CombinationMax. "-" Defl (in)Location in Span (ft)Load Combination Span Max. "+" Defl (in)

Overall Maximum Deflections

+D+L 1 0.0016 3.000 0.0000 0.000