(CONT.)ELECTRICAL GENERAL NOTES:
T
ELECTRICAL SYMBOL LIST:
MC
D
T
ELECTRICAL SYMBOL LIST:
EPM ELECTRICAL POWER MODULE
EXIT SIGN
2 X 2 EMERG. LED LIGHT FIXTURE WITH DRIVER
PP
DATA OUTLET-3 DATA PORTS
MOUNTING TO BE +18" A.F.F. UNLESS OTHERWISE NOTED
TELEPHONE- SINGLE GANG TELEPHONE OUTLET, 18" A.F.F.
(W= 48" A.F.F.), STUB CONDUIT 6" INTO
ACCESSIBLE CEILING SPACE UNLESS NOTED OTHERWISE
ELECTRICAL SYMBOL NOTES:
2 X 4 EMERG. LED LIGHT FIXTURE WITH DRIVER
2 X 4 LED LIGHT FIXTURE WITH DRIVER
2 X 2 LED LIGHT FIXTURE WITH DRIVER
LED DOWNLIGHT WITH DRIVER
DATA OUTLET-2 DATA PORTS
MOUNTING TO BE +18" A.F.F. UNLESS OTHERWISE NOTED
POWER POLES FOR POWER AND COMMUNICATIONS FOR LAB &
PHARMACY - SINGLE POLE W/ DIVIDER FOR COMMUNICATIONS:
(PROVIDED BY FURNITURE VENDOR.) E.C. TO PROVIDE ALL
WIRING AND RECEPTACLES.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH, SIZE AND RATING AS
NOTED ON DRAWINGS. REFER TO MECHANICAL EQUIPMENT SCHEDULE FOR
ADDITIONAL INFORMATION
THERMOSTAT JUNCTION BOX MOUNTED 54" A.F.F. UNLESS OTHERWISE NOTED.
FUSED DISCONNECT SWITCH, SIZE AND RATING AS NOTED ON DRAWING
NON-FUSED DISCONNECT SWITCH, SIZE AND RATING AS NOTED ON DRAWINGS
ELECTRICAL PANEL
MOTOR CONNECTION
PUSH PLATE FOR AUTOMATIC DOORS
JUNCTION BOX WITH FLEXIBLE CONDUIT CONNECTION
JUNCTION BOX WALL MOUNTED
JUNCTION BOX CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE, VOLTAGE, RATING AND MOUNTING AS NOTED ON PLANS
CEILING MOUNTED DUPLEX RECEPTACLE, 120V, 20 AMPERE
DUPLEX RECEPTACLE, 120V, 20 AMPERE RATED 6" ABOVE FINISHED COUNTER TOP OR
BACK SPLASH MOUNTED HORIZONTALLY. AT LOCATIONS WHERE THERE IS NO COUNTER
TOP, RECEPTACLE SHALL BE MOUNTED 42" A.F.F.
SINGLE RECEPTACLE, 120V, 20 AMP RATED, SPECIFICATION GRADE, MOUNTED
HORIZONTALLY 6" TO CENTERLINE, OF RECEPTACLE ABOVE
COUNTER/BACK/SPLASH/DESK.
DOUBLE DUPLEX RECEPTACLE, 120V, 20 AMP RATED 18" A.F.F. UNLESS OTHERWISE
NOTED. MOUNTED IN COMMON JUNCTION BOX.
DESCRIPTIONSYMBOLDESCRIPTIONSYMBOL
ABOVE FINISHED FLOOR
ELECTRICAL CONTRACTOR
INDICATES FIXTURE CONNECTED TO EMERGENCY SERVICE
ELECTRIC WATER COOLER
GROUND FAULT INTERRUPTER
GROUND INDICATES GREEN GROUND CONDUCTOR CONNECTED TO EQUIPMENT AND
PANEL
NIGHT LIGHT, 24 HOUR OPERATION
UNLESS NOTED OTHERWISE
WEATHERPROOF
SINGLE POLE TOGGLE SWITCH, 20 AMPERE RATED, MOUNTED 48" A.F.F. UNLESS NOTED
OTHERWISE.
SUBSCRIPT: "a" - LOWER CASE LETTER INDICATES SWITCH CONTROL
THERMAL OVERLOAD TOGGLE SWITCH WITH PROPERLY SIZED HEATER ELEMENTS, 48"
A.F.F. UNLESS EQUIPMENT MOUNTED
SINGLE POLE SLIDE TYPE ARCHITECTURAL INCANDESCENT DIMMER SWITCH WITH FINS,
1200 WATT CAPACITY (LUTRON NOVA SERIES OR LEVITON). ALL NON-DIMMING SWITCHED
ADJACENT TO OR IN SAME ROOM SHALL BE THE SLIDE TYPE TO MATCH DIMMERS.
"LV" - DENOTES LOW VOLTAGE DIMMER TO MATCH ABOVE
SUBSCRIPT: "FD" - DENOTES FLUORESCENT DIMMER TO MATCH ABOVE
"IG" - DENOTES ISOLATED GROUND TYPE RECEPTACLE HUBBELL OR
LEVITON #IG-5362
SUBSCRIPT: "GFI" - DENOTES GROUND FAULT INTERRUPTER TYPE
RECEPTACLE
DUPLEX RECEPTACLE, 120 VOLT, 20 AMPERE RATED, 18" A.F.F. UNLESS NOTED
OTHERWISE. HUBBELL OR LEVITON #5362-I, MTD HORIZONTALLY IN JUNCTION BOX.
TOGGLE MOMENTARY CONTACT SWITCH WITH CENTER OFF POSITION
"3W" - DENOTES THREE WAY TOGGLE SWITCH
"2P" - DENOTES TWO POLE TOGGLE SWITCH
"P" - DENOTES LIGHTED HANDLE TOGGLE SWITCH, LIGHT IN
SWITCH SHALL LIGHT WHEN EQUIPMENT IS OPERATING
"4W" - DENOTES FOUR WAY TOGGLE SWITCH
A.F.F.
E.C.
EM
EWC
GFI
GND
NL
U.N.O.
WP
WIREMOLD 4000 W/ DIVIDER FOR LOW VOLTAGE
DATA OUTLET-1 DATA PORT
MOUNTING TO BE +18" A.F.F. UNLESS OTHERWISE NOTED
1. ELECTRICAL CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT DOCUMENTS: INCLUDING BUT NOT NECESSARILY LIMITED TO ALL ARCHITECTURAL, ALL STRUCTURAL, ALL MECHANICAL, ALL ELECTRICAL, ALL
PLUMBING, AND ENTIRE PROJECT MANUAL. ELECTRICAL CONTRACTOR SHALL ACKNOWLEDGE AND
INCLUDE IN THE SCOPE OF WORK (CONTRACT) ALL CONDITIONS PERTINENT TO THE COMPLETION OF THE ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL FULLY COORDINATE ELECTRICAL WORK WITH THE INSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE ABOVE SHALL BE INCLUDED IN THE SCOPE
OF WORK AT NO ADDITIONAL COST TO THE OWNER.
2. ELECTRICAL CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND SPECIFICATIONS, VISIT THE SITE OF THE WORK, AND FULLY INFORM HIMSELF AS TO ALL CONDITIONS AND MATTERS THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST THEREOF, SHOULD THIS CONTRACTOR FIND DISCREPANCIES IN, OR OMISSIONS FROM, THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS OR BE IN DOUBT AS TO THEIR MEANING, NOTIFY THE OWNER AND ARCHITECT AT ONCE, IN WRITING, OF ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND NEW WORK, OR BETWEEN ELECTRICAL WORK AND THE WORK OF OTHER TRADES PRIOR AND OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. LACK OF SUCH NOTIFICATION
SHALL BE CONSTRUED TO INDICATE NO DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL
COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF CONTRACT FOR ANY WORK REQUIRED TO
COMPLY WITH THESE REQUIREMENTS.
3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL A COMPLETE ELECTRICAL SYSTEM. WHERE THERE IS NO MENTION OF THE RESPONSIBLE PARTY FOR A SPECIFIC ITEM TO BE FURNISHED, INSTALLED OR WIRED ON THE ELECTRICAL DRAWINGS, THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE COMPLETELY FOR ALL PURCHASES AND LABOR FOR A COMPLETE OPERATING SYSTEM
FOR THIS ITEM.
4. ANY MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO PURCHASING OR
ROUGH-IN WORK.
5. ELECTRICAL CONTRACTOR SHALL VERIFY ALL OUTLET MOUNTING ARRANGEMENTS, HEIGHTS AND LOCATIONS WITH THE ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. ANY MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT OR LOCATION SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH THE EQUIPMENT FURNISHED OR THE OTHER TRADES WORKING IN THE SAME AREA. NO ADDITIONS TO THE CONTRACT SUM WILL BE PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH OTHER WORK ETC. THE OWNER RESERVES THE RIGHT TO RELOCATE ANY DEVICE 10'-0" PRIOR TO ROUGH-IN WITHOUT ANY ADDITIONAL CHARGES BY THE
ELECTRICAL CONTRACTOR.
6. ALL INSTRUMENTS, APPARATUS AND EQUIPMENT SHALL BE TESTED AND PROVED TO BE ELECTRICALLY AND MECHANICALLY WITHOUT DEFECTS. THE ELECTRICAL SYSTEM SHALL BE TESTED FOR GROUNDS OR SHORTS AND IF SHORTED OR GROUNDED, ALL SUCH WIRES SHALL BE REMOVED AND REPLACED. IF TROUBLE IS WITHIN CIRCUIT, ALL METERS, CABLES, EQUIPMENT OR APPARATUS NECESSARY FOR MAKING
ALL TESTS SHALL BE FURNISHED AND PROVIDED BY ELECTRICAL CONTRACTOR.
7. ELECTRICAL CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL CITY, STATE, AND FEDERAL SAFETY LAWS (OSHA), AND AS RECOMMENDED IN THE "MANUAL OF ACCIDENT PREVENTION IN CONSTRUCTION" AS ISSUED BY THE ASSOCIATION OF GENERAL CONTRACTORS OF AMERICA, INC., 20TH
AND E. STREETS, N.W. WASHINGTON, D.C.
8. THE CONSULTING ENGINEER MAY MAKE PERIODIC VISITS TO THE JOB SITE TO OBSERVE THE PROGRESS OF THE WORK AND TO OBSERVE WHETHER OR NOT IT IS BEING PERFORMED IN ACCORDANCE WITH THE ELECTRICAL PLANS AND SPECIFICATIONS. THIS DOES NOT IN ANY WAY MEAN THAT THE ENGINEER IS A GUARANTOR OF THE CONTRACTOR'S WORK, OR RESPONSIBLE FOR SAFETY IN, ON, OR ABOUT THE JOB SITE, IN CONTROL OF THE SAFETY OR ADEQUACY SAFETY OR ADEQUACY OF ANY SHIPMENT, BUILDING, SCAFFOLDING, FORMS OR OTHER WORK AIDS, OR FOR SUPERINTENDING, DIRECTING OR HAVING CHARGE
AT THE ERECTION AND/OR CONSTRUCTION OF THE WORK.
9. UPON COMPLETION OF THE WORK, THE ELECTRICAL CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE OWNER'S PROPERTY, LEAVING THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE WORKING CONDITION. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL OF ANY CARTON, DEBRIS, ETC. FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR INCLUDING EQUIPMENT FURNISHED BY THE OWNER. THE ABOVE SHALL ALSO APPLY TO ALL EQUIPMENT FURNISHED BY OTHERS AND UNPACKED
OR REMOVED FROM CARTON, BY THE ELECTRICAL CONTRACTOR.
10. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, RECEIVING, UNLOADING, UNCRATING, STORING SETTING IN PLACE, AND PROTECTING FROM DAMAGE, VANDALISM, THEFT OR
WEATHER DURING CONSTRUCTION FOR ALL NEW EQUIPMENT FURNISHED BY THE ELECTRICAL
CONTRACTOR.
11. THE ELECTRICAL CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN REVIEW FEES, LICENSE FEES, INSPECTIONS AND TAXES APPLICABLE TO THIS DIVISION AND SHALL BE INCLUDED IN THE BASE BID AS PART
OF THIS CONTRACT.
12. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL TEMPORARY WIRING FOR HAND TOOLS AND CONSTRUCTION LIGHTING PER LATEST OSHA STANDARDS AND INCLUDE ALL COSTS IN THE BASE BID.
13. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD TO BE
COORDINATED WITH VA REQUIREMENTS. AFTER THE FINAL ACCEPTANCE BY THE OWNER/COR.
14. ELECTRICAL CONTRACTOR SHALL FURNISH CONTRACT RECORD DOCUMENTS TO THE
ARCHITECT/ENGINEER BEFORE FINAL PAYMENT WILL BE ISSUED. THE CONTRACT RECORD DOCUMENTS SHALL DIAGRAMMATICALLY INDICATE THE INSTALLED CONDITION AND BE IN REPRODUCIBLE DRAWING
FORM.
15. THE ELECTRICAL INSTALLATION IS TO BE IN ACCORDANCE WITH ALL NATIONAL, STATE, LOCAL ELECTRICAL CODES AND LOCAL UTILITY COMPANY'S REQUIREMENTS. ANY MODIFICATION'S AND/OR ADDITIONS TO
THESE PLANS, REQUIRED FOR PROPER COMPLIANCE TO ANY APPLICABLE CODES SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR AND SHALL BE INCLUDED IN HIS/HER BASE BID.
16. ALL EQUIPMENT/DEVICES SHALL BE NEW AND/OR FIRST QUALITY AND IS TO BEAR THE APPROPRIATE UL OR
CSA APPROVED LABELS FOR SPECIFIC PURPOSE.
17. ALL WIRE AND CABLE SHALL BE COPPER ONLY, TYPE "THWN" OR "XHHW". MINIMUM WIRE SIZE TO BE #12 EXCEPT FOR CONTROL WIRE. ALL WIRE SIZE #10 AWG AND SMALLER SHALL BE SOLID. ALL CABLE #8 AWG AND LARGER SHALL BE STRANDED. FOR ALL UNDERGROUND SERVICE CONDUCTORS FROM THE UTILITY COMPANY TRANSFORMER TO THE SERVICE EQUIPMENT SHALL BE TYPE "RHH-RHW-USE" (CROSS-LINKED
POLYETHYLENE INSULATION).
18. ALL 20 AMPERE BRANCH CIRCUIT HOMERUNS 100' OR LONGER SHALL BE MINIMUM #10 AWG OR LARGER
SIZED TO LIMIT VOLTAGE DROP TO CODE REQUIREMENTS.
19. NO ROMEX OR BX WILL BE PERMITTED.
20. ALL WIRE SHALL BE INSTALLED IN THIN WALL (E.M.T.) CONDUIT UNLESS OTHERWISE NOTED. MINIMUM SIZE SHALL BE 3/4" EXCEPT FOR DROPS FOR DEVICES, SWITCH LEGS, TEMPERATURE CONTROL CONDUITS, WHERE INDICATED OR AS CALLED FOR ON DRAWINGS. ALL THINWALL FITTINGS SHALL BE OF THE STEEL
COMPRESSION GLAND TYPE.
21. ALL UNDERFLOOR, UNDERGROUND OR EXPOSED-TO-WEATHER CONDUIT SHALL BE HEAVYWALL
GALVANIZED RIGID STEEL. (G.R.S.), MINIMUM 3/4".
22. ALL CONDUITS 2" OR LARGER SHALL BE GALVANIZED RIGID STEEL OR INTERMEDIATE METAL CONDUIT (I.M.C.).
23. ELECTRICAL CONTRACTOR SHALL INSTALL SIZE OF CONDUIT SHOWN AND AS SCHEDULED ABOVE AND
SHALL NOT REDUCE SIZING OF CONDUITS TO SUIT WIRE FILL CAPACITY.
24. ALL CONDUIT FASTENERS, STRAPS, SUPPORTS ETC. MUST BE "BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION AND IN WET AREAS. SNAP-ON BLACK METAL "CADDY" CLIPS IN METAL PARTITION WALLS AND ABOVE SUSPENDED CEILINGS WILL BE PERMITTED. ALL FASTENERS, STRAPS, CLIPS, ETC. SHALL BE UL
LISTED FOR THEIR USE.
25. NO CONDUITS SHALL BE ROUTED THROUGH HVAC AIR DUCTS.
26. ALL CONDUIT RACEWAYS SHALL BE CONCEALED IN OR WITHIN: WALLS, CEILING CAVITY, ROOF CONSTRUCTION (WHERE APPROVED), SLAB, GRADE, ETC. UNLESS OTHERWISE NOTED. ANY RACEWAY
THAT IS TO BE ROUTED EXPOSED SHALL BE APPROVED BY THE OWNER/COR AND SUCCESSFULLY
REVIEWED BY THE ARCHITECT. PRIOR TO INSTALLATION. ALL CONDUIT SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALLS AND STRUCTURAL MEMBERS WITH 90° BENDS WHERE REQUIRED AND SHALL BE
RACKED. PULL AND JUNCTION BOXES SHALL BE HELD TO A MINIMUM.
27. NO WIREWAY, THROUGH OR JUNCTION SHALL BE UTILIZED WHERE MORE THAN 8 CONDUITS ARE ENTERING OR LEAVING. MULTIPLE WIREWAYS, TROUGHS OR JUNCTIONS SHALL BE UTILIZED. IN NO CASE SHALL
FEEDER OR CONDUIT OR CABLING BE MIXED WITH BRANCH CONDUIT.
28. NO CONDUITS SHALL BE ROUTED ON ROOF. ELECTRICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH MECHANICAL PIPE CURBS. WHERE CONDUIT MUST BE RUN ON ROOF, IT SHALL BE RACKED WITH OTHER TRADES WHERE POSSIBLE OR PROVIDED WITH ITS OWN ROOF RACK SUPPORT
SYSTEM WITH PROPER ROOF PLATE SO AS NOT TO CAUSE DAMAGE TO ROOF COVERING.
29. ELECTRICAL CONTRACTOR SHALL FIREPROOF ALL CONDUIT OPENINGS BETWEEN FLOORS AND ANY INTERSPACE FIRE SEPARATION BLOCK WALLS WITH AN OWNER APPROVED UL LISTED FIRE RETARDANT
MATERIAL. AS SUCCESSFULLY REVIEWED BY THE ARCHITECT.
30. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL SLEEVES THRU WALLS AND CORING THRU FLOORS. ELECTRICAL CONTRACTOR SHALL WEATHERPROOF ALL PENETRATIONS THRU FOUNDATION AND
EXTERIOR WALLS.
31. FINAL EQUIPMENT CONNECTION TO PILOT CONTROL DEVICES SHALL BE MADE WITH 1'-0" MINIMUM LENGTH
OF FLEXIBLE CONDUIT CONNECTION (IE. SOLENOID VALVES, MOTORIZED DAMPERS, ETC.).
32. ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUITS AND FINAL POWER CONNECTIONS FOR FIRE
PROTECTION FLOW SWITCHES, TAMPER SWITCHES AND ALARM BELLS AS REQUIRED.
33. RECEPTACLES INDICATED FOR G.F.I. PROTECTION SHALL PROTECT RECEPTACLE INDICATED ONLY. AT LOCATIONS WHERE G.F.I. RECEPTACLES ARE INDICATED WITHIN 5' OFA PLUMBING FIXTURE AND IN SIGHT OF EACH OTHER, ELECTRICAL CONTRACTOR MAY ELECT TO USE ONE "FEED THRU" G.F.I. RECEPTACLE TO FEED "SLAVE" G.F.I. RECEPTACLE (S). G.F.I. CIRCUIT BREAKERS WILL NOT BE PERMITTED TO PROTECT
RECEPTACLES INDICATED FOR G.F.I. PROTECTION.
34. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIRE ALARM SYSTEM; REFER TO "FA" DRAWINGS.
OS
VS
CR
DB
PB
OSD
WAP
PC
NCL
OCCUPANCY SENSOR, DUAL TECHNOLOGY (PIR/ULTRASONIC)
VACANCY SENSOR
OCCUPANCY SENSOR WITH DIMMER
LUTRON OR EQUAL #MAESTRO MSCL-OP153M
PROXIMITY CARD READER
DOOR BELL
PUSH BUTTON
WIRELESS ACCESS POINT, PROVIDE CAT6 CABLE FROM WAP
TO IT CLOSET
CCTV CAMERA, ZOOM/PAN/TILT
PULL CORD, CONNECT TO NURSE CALL SYSTEM
NURSE CALL LIGHT
SURFACE MOUNTED (1) TELEPHONE AND (1) DATA OUTLET, 18" A.F.F.
W=WALL MOUNTED, 48" A.F.F.
SURFACE MOUNTED DUPLEX, EXPOSED CONDUIT.
OPEN CABLE LADDER TRAY
CRITICAL POWER (CP PANEL)
SAFETY POWER (SP PANEL)
REGULAR POWER (LP PANEL)
NOTE:
1. ALL "NORMAL" SWITCHES SHALL BE IVORY IN COLOR. "EMERGENCY" SWITCHES IN LAB & PHARMACY
SHALL BE RED.
2. ALL "NORMAL" RECEPTACLES SHALL BE IVORY IN COLOR AND "EMERGENCY" RECEPTACLES IN LAB &
PHARMACY SHALL BE RED.
3. ALL "NORMAL" COVER PLATES (SWITCHES, RECEPTACLES AND TELEPHONES) IN FINISHED AREAS SHALL
BE IVORY. IN "EMERGENCY AREAS", ALL SHALL BE RED.
SPEAKERS
CAT 6 DATA CABLE WITH WHITE
KEYSTONE.
(DATA=RJ45)
(TELEPHONE=RJ11)
CAT 6 DATA CABLE TO NEAREST IT ROOM
3/4" EMT CONDUIT STUBBED TO THE
NEAREST ACCESSIBLE CEILING
ORPLAN SYMBOL
CAT 6 DATA CABLE WITH BLACK
KEYSTONE. RJ45
CAT 6 DATA CABLE WITH
IVORY KEYSTONE. RJ45
CAT 6 DATA CABLE TO NEAREST IT ROOM
CAT 6 DATA CABLE TO NEAREST IT ROOM
3/4" EMT CONDUIT STUBBED TO THE NEAREST
ACCESSIBLE CEILING
PLAN SYMBOL
(2
CAT 6 DATA CABLE WITH BLACK
KEYSTONE. RJ45
BLANK FACEPLATE
CAT 6 DATA CABLE WITH IVORY
KEYSTONE. RJ45
CAT 6 DATA CABLE TO NEAREST IT ROOM
CAT 6 DATA CABLE TO NEAREST IT ROOM
1" EMT CONDUIT STUBBED TO THE NEAREST
ACCESSIBLE CEILING
PLAN SYMBOL
CAT 6 DATA CABLE TO NEAREST IT ROOM
CAT 6 DATA CABLE WITH WHITE
KEYSTONE. RJ45
(3
CAT 6 DATA CABLE WITH BLACK
KEYSTONE. RJ45
CAT 6 DATA CABLE WITH IVORY
KEYSTONE. RJ11
CAT 6 DATA CABLE TO NEAREST IT ROOM
CAT 6 DATA CABLE TO NEAREST IT ROOM
3/4" EMT CONDUIT STUBBED TO THE NEAREST
ACCESSIBLE CEILING
PLAN SYMBOL ( SURFACE, EXPOSED CONDUIT)
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
100% BID DOCUMENT
/1
5/
2:
:1
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
ELECTRICAL GENERAL NOTES & SYMBOLS LIST
E001
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
3/32" = 1'-0"E001 1 Telephone or Data Port Face Plate
3/32" = 1'-0"E001 2 Two Data Port Face Plate
3/32" = 1'-0"E001 3 Three Data Port Face Plate
3/32" = 1'-0"E001 4 One Telephone and One Data Port Face Plate
Bidding Document Revision 1 Nov. 02, 2015 BID SUBMISSION Dec. 03, 2015
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B10825 C7895
29190
10470
MOUNTING
SEMI-RECESS
LOCATION
LOAD TYPE
EM-UL1
NAME
LOAD (VA)
A B C
120/208V
LOAD (VA)
A
3PH, 4W
B
VOLTAGE
AMPS
VA
VA
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
3REC+L5
L1+L3+L4+1REC
3REC+L24
3REC
L19
L62+L85
4REC
L64
SPARE
SPARE
SPARE
3REC
3REC+L23
4REC
3REC
L10 (SERVER)
L83+3REC
L84+3REC
L12
UPS L14, FEED L9
4REC
4REC
4REC
500720
3REC
L65+3REC
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B15060
C12925
39165
11180
MOUNTINGLOCATION
LOAD TYPE
EM-UL2
NAME
LOAD (VA)
A B C
120/208V
LOAD (VA)
A
3PH, 4W
B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
L70
L50,L54
L55
L73+L48+L46
5REC
L40
3REC
6REC
L44
L45
L87
L88
6REC
5REC
6REC
5REC
20A
20A
20A
20A
5REC+L72
L43
L56
6REC
6REC
1200 1200
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B16840
C16540
48220
14840
MOUNTING
SURFACE
LOCATION
LOAD TYPE
PP-PENT-1
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
400A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
PENTHOUSE
ACCU-1 2000
1450ACCU-2
GMU-1 (1/2HP)
SPARE
SPARE
EF-3 (1/4HP)
EF-4 (1/2HP)
HWP-1 (5HP)
EF-5 (1/2HP)
UH-3, UH-4
SPARE
SPARE
SF-5 (5HP)
HWP-2
(STANDBY 5HP)
STRF-1
(3HP)
STRF-2
(10HP)
STRF-3*
(10HP)
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B8500
C10600
27600
MOUNTING
SURFACE
LOCATION
LOAD TYPE
PP-PENT-2
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
30A
PENTHOUSE
HWP-3 (5HP)
SPARE
REC-PENTHOUSE
REC-ROOF
20A
20A
20A
20A
CP-1 (2)@ 1/3HP*
ROS-A & PUMP
HWCP-1 (1/2HP)
SPARE
SPARE
120/208V
3PH, 4W
HWP-4
(STANDBY 5HP)
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B10300
C9200
28300
MOUNTING
SURFACE
LOCATION
LOAD TYPE
PP-LL
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
LOWER LEVEL
SF-2 & RF-2
SPARE
SPARE
SPARE
SPACE
20A
EF-1
EF-2
CUH1,UH1,UH2
GMU-2 (1/2HP)
SPARE
SINK-ELEC EYE
120/208V
3PH, 4W
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
HUM-3
SPACE
SPACE
SPACE
SPACE
SPACE
SPARE
SPARE
RECEP. CRAWL AHU-2
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPARE
SPARE
SPARE
SPARE
SPARE
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B12680
C9800
34700
12220
MOUNTINGLOCATION
LOAD TYPE
RP-UL
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
4REC 116,119 720
GFI 109
20A
20A
20A
20A
TEF1,TEF2,CUH2
SINK/TOLT SENSR
120/208V
3PH, 4W
4REC 117,118
SPARE
SPARE
SPARE
6REC 109,104 SINK/TOLT SENSR
L25+L26+L27+1R
2REC
UPS L11,FEED L13
SPARE
SPARE
SPARE
SPARE
5REC
L52
L53
SPARE
SPACE
SPACE
SPACE
SPACE
IT 164
IT 164
L31
L36,L37
L33,L34,L38
L29,L30,2REC
L32,L74
L42
2REC 109
GFI 113
GFI 107,108
GFI 105,106
1REC
SPARE
IT ROOM 128
SPARE
2REC 128
6REC 129,130
GFI 131
GFI 127
GFI 127
2REC 127
4REC 133,132
1REC EXT 132
SPARE
DOORBELL
AMPS
VA
VA
AMPS
VA
VA
AMPS
VA
VA
AMPS
VA
VA
AMPS
VA
VA
HUM-1
HUM-4
1REC 134,135
2REC 136,137
6REC 137,138
3REC 130,132
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B11800
C10820
33520
10900
MOUNTINGLOCATION
LOAD TYPE
RP-LL
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
LOWER LEVEL
5REC 01,06,02
GFI 003,005
GFI 004
SPARE
3REC 12,17,13
6REC 09,10
5REC 13,14
1REC 14
20A
20A
20A
20A
IT CLOSET 3REC
SPARE
AMPS
VA
VA
120/208V
3PH, 4W
REC 008
IT 011
IT 011
IT 011
IT 011
IT 011
EXTERIOR/CRAWL GFI
WATER PURIFIER
SINKS/TOILET-003/004
EWC
SUB FEED
RP-UL2
SEMI-RECESSSEMI-RECESS
SURFACE
EWC
EWC
EWC
EWC
EWC
EWC
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B7061
C4306
17167
MOUNTING
SURFACE
LOCATION
LOAD TYPE
EM-LTG-LL
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
100A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
LOWER LEVEL
EXIT-PENTHOUSE,LL
EXIT, UL
SPARE
SP-1
EM LTG PENT, LL
EM LTG LAB
EM LTG PHARM
EM L 125,126,121
EM L 104,102,127
AMPS
VA
VA
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B5500
C4745
13675
MOUNTING
SURFACE
LOCATION
LOAD TYPE
LP-LL
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
100A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
LOWER LEVEL
SPARE
OPEN ENTR. LIGHTS
CORRID 1,6,17,12
SPARE
LTG-104, BATH
SPARE
L-9,10,8,2,3,4
L-8,11,13,14
CRAWL SPACE
LTG-LL
SPACE
SPARE
AMPS
VA
VA
SP-1
ELEV. LTG/RECEPT.
IT-011
IT-011
FIRE/VOICE EVAC PNL
PIT LIGHT
SPARE
SPARE
SPARE
CCTV PANEL
SECURITY PANEL
LTG-EXT.REAR
SPARE
SPARE
SPARE
SPARE
TIMECLOCK
SPARE
20A
20A
20A
20A
20A
SPARE
PENTHOUSE LTG
SPARE
SPARE
SPARE
OPN ENTR. ROOF
EXT. SOFFIT (S3)
SPACE
SPACE
120/208V
3PH, 4W
SPARE
BOLLARD LIGHTS
120/208V
3PH, 4W
120/208V
3PH, 4W
- SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20A
20A
20A
20A
20A
20A
20A
20A
20A
DSS-2
DSS-1
ALL `EM' CB SHALL BE LOCK-OUT TYPE.
(BLDG EM. PANEL)
(SERVES LAB) (SERVES LAB)
20A
20A
20A
30A
30A
*ELECTRICAL CONTRACTOR SHALL PROVIDE ASCO 918 TIMECLOCK OR EQUAL AND PHOTOCELL ON ROOF, 4-POLE. PANEL 'LP-LL', CCT. 1,3 & 17.
2000 30A
30A
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B3500
C1740
MOUNTING
SEMI-RECESS
LOCATION
LOAD TYPE
RP-UL2
NAME
LOAD (VA)
A B C
120/208V
LOAD (VA)
A B
VOLTAGE
AMPS
VA
VA
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
100A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
SINKS & TOILETS EYE
MONITORS 104
REFRIGERATOR 127
4R-110, 10
5R. 111, 114
3R. 111, 110, 114
1R. 109
3 GFI. 110, 113
SPACE
3R. 104
3R-112
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20A
20A
20A
20A
20A
20A
IT ROOM 128
IT ROOM 128
IT ROOM 128
IT ROOM 128
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
SPACE
SPARE
SPARE
EF-6
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
*TO CONTROL PANEL
20A
20A
20A
20A
20A
AHU-2
AHU-5*
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B8480 C10140
24640
MOUNTINGLOCATION
LOAD TYPE
EM-UL5
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
PNEUMATIC TUBE
5R
20A
20A
20A
20A
P57
P54,P53+2R
P56+P55+2R
P49+P48+P47
P42+P41
3R
120/208V
3PH, 4W
AMPS
VA
VA
SEMI-RECESS
SPARE
2R-122,124
P81
(SERVES PHARMACY)
20A
20A
20A
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B10530 C8690
29017
MOUNTING
SEMI-RECESS
LOCATION
LOAD TYPE
EM-UL3
NAME
LOAD (VA)
A B C
120/208V
LOAD (VA)
A
3PH, 4W
B
VOLTAGE
AMPS
VA
VA
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
L39
L35
L16
L15
L17
L8
L71
L28
1900 L41
L60
L61
(SERVES LAB)
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20A
20A
20A
20ASPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
BUS AMP
CONN. LOADISOLATED GND BUS
100% NEUTRAL
200% NEUTRAL
PHASE
TOTAL CONN. LOAD
A B11410 C11860
34080
10810
MOUNTINGLOCATION
LOAD TYPE
EM-UL4
NAME
LOAD (VA)
A B C
LOAD (VA)
A B
VOLTAGE
MAIN O.C.
DEVICE
MLO
LOAD TYPE
C
200A
SIZE
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
UPPER LEVEL
P1+P2+P3
6REC
6REC
6REC
6REC
P-29
P-30
P58,P59
P60,P61
P26,P27
P13,P12,P8
3R+P25
P11+P10+3R
P9+2R
3R
20A
20A
20A
20A
P23,P22,P21
P20,P18,P19
P45,P46,P44
P31
4R+P28
P36+3R
P37+P38
P40+3R
P35
P39+P52+2R
P32+P33+4R
P50+P51+2R
P67,P34
P15,P17,P16+2R
120/208V
3PH, 4W
P82
AMPS
VA
VA
SEMI-RECESS
SPARE
(SERVES PHARMACY)
20A
20A
20ASPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
P69,P71
DOOR OPERATOR
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
81 81
L20
L47,L49,L59
L75
L86
L22
L63
L57,L58,L66
L67,L68,L69
L89,L90
L91
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
P4
P24
P64,P65
P76,P77
P82
P5,P6,P7
P62,P63
P68
P70,P72
P79,P80
SPARE SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
AUTOMATIC DOOR
DOOR OPERATOR
DOOR OPERATOR
DOOR OPERATOR
*ADD ALTERNATE
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
1 2
ABC
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
41 42
1 2
ABC
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
100% BID DOCUMENT
/1
5/
2:
:1
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
ELECTRICAL PANEL SCHEDULES
E002
13-127
FPNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
ELECTRICAL NOTES
A. REFER TO DRAWING 164-E003 FOR ELECTRICAL/MECHANICAL SCHEDULE FOR FEEDER
SIZING AND CIRCUITS.
B. REFER TO DRAWING 164-Q601 & 164-Q602 FOR LAB AND PHARMACY EQUIPMENT LIST.
ELECTRICAL/MECHANICAL SCHEDULE
LIGHTING FIXTURE SCHEDULE
EQUIPMENT
AHU-1
AHU-2
AHU-5
STRF-1
EF-1
TEF-1
TEF-2
HUM-1
UH-1
CUH-1
SYSTEM
PACKAGED
SUPPLY FAN
STROBIC FAN
EXHAUST FAN
HUMIDIFIER
UNIT HEATER
CABINET UNIT HEATER
LOCATION
ROOF
PENTHOUSE
ROOF
LL
LL
PENT ROOF
ROOF
UL
UL
ROOF
LL
PENTHOUSE
LL
LL
LL
7.5 & 10 HP
3 & 15 HP
5 HP
3 HP
10 HP
1/2 HP
1/4 HP
150 WATTS
150 WATTS
3.4 KW
32.4 KW
1/60 HP
1/60 HP
1/8 HP
1/8 HP
0.03 HP
80/62
90/65
30/22
MCA
MDCP/
TOGGLE
DISCONNECT SWITCH
PROVIDE
EM-DP-LL
PP-PENT-1
PP-LL
PP-LL
PP-PENT-1
RP-UL
PP-PENT-2
PP-LL
PP-PENT-1
PP-LL
PANEL
ELECTRICAL
2/4/6
8/10/12
20/22/24
32/34/36
32/34
36/38
40/42
CCT.
3#4,#8GRD, 1-1/4"C
3#10, #10GRD, 3/4"C
3#12, #12GRD, 3/4"C
3#8, #10GRD, 1"C
3#8, #10GRD, 1"C
2#12, #12GRD, 3/4"C
3#3/0 #6GRD, 2"C
2#12, #12GRD, 3/4"C
FEEDER
208/3
208/3
120/1
120/1
VOLT/PAHSE NOTES
AHU-3
AHU-4
208/3
208/3
208/3
120/1
120/1
120/1
120/1
120/1
120/1
208/1
208/3
208/1
208/1
208/3
120/1
120/1
120/1
120/1
10 HP
1/2 HP
1/2 HP
1/2 HP
24.3 KW
1.6 KW
2 KW
150A/3P
200A/3P
ROOF
ROOF
PENT ROOF
ROOF
ROOF
PENTHOUSE
PENTHOUSE
STROBIC FAN
STROBIC FAN
EXHAUST FAN
EXHAUST FAN
EXHAUST FAN
EXHAUST FAN
EXHAUST FAN
EXHAUST FAN
HUMIDIFIER
HUMIDIFIER
HUMIDIFIER
HUMIDIFIER
UNIT HEATER
UNIT HEATER
UNIT HEATER
STRF-2
STRF-3
EF-2
EF-3
EF-4
EF-5
HUM-2
HUM-3
HUM-4
HUM-5
UH-2
UH-3
UH-4
PP-PENT-1
PP-PENT-1
PP-PENT-1
RP-UL
MSB-1
PP-PENT-2
PP-PENT-2
DP-PENTHOUSE
PP-LL
PP-PENT-1
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
ACCU-1
DSS-1
ACCU-2
DSS-2
HWP-1
HWP-2 STANBY
HWP-3
CP-1
GMU-2
GMU-1
ROS-1
HWCP-1
DUCTLESS SPLIT SYSTEM
CONDENSING UNIT
HOT WATER PUMP
CONDENSATE PUMP
GLYCOL MAKE-UP UNIT
REVERSE OSMOSIS SYSTEM
DOMESTIC HW CIRC PUMP
LL
UL
ROOF
ROOF
PENTHOUSE
LL
PENTHOUSE
PENTHOUSE
1A
1A
18A
13A
5 HP
2 @ 1/3 HP
1/2 HP
3/4 HP & 1HP
1/6 HP
PP-PENT-1
PP-PENT-2
PP-PENT-2
PP-PENT-2
PP-LL
PP-PENT-1
PP-PENT-2
PP-PENT-2
1/3
5/7
1/3
5/7
19/21/23
25/27/29
1/3/5
7/9/11
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
3#10, #12GRD, 3/4"C
208/1
208/3
120/1
PP-PENT-1
PP-PENT-1
CONDENSING UNIT
HOT WATER PUMP
HOT WATER PUMP
HOT WATER PUMP
GLYCOL MAKE-UP UNIT
PENTHOUSE
PENTHOUSE
PENTHOUSE
PENTHOUSE
PENTHOUSE
5 HP
5 HP
5 HP
1/2 HP
PP-PENT-1
PP-PENT-1
PP-PENT-1
PP-PENT-1
PP-PENT-1
2#10, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
3#10, #12GRD, 3/4"C
3#10, #12GRD, 3/4"C
3#10, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
2#10, #12GRD, 3/4"C
2#12, #12GRD, 3/4"C
208/1
208/1
208/1
208/3
208/3
208/3
120/1
120/1
120/1
SP-1 LL TOOGLE EM-LTG-LL 11 2#12, #12GRD, 3/4"C 120/1
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
TOGGLE
30A DISC
TOGGLE
TOGGLE
TOOGLE
TOOGLE
TOOGLE
TOOGLE
1/2 HP
POWER TO CONTROL PANEL
120/1
DUCTLESS SPLIT SYSTEM
2#12, #12GRD, 3/4"C
2#10, #12GRD, 3/4"C
FIXTURE TAG DESCRIPTION MANUFACTURER LAMP TYPE WATTS GENERAL LOCATIONSYMBOL
F1 2'X4' RECESSED LED TROFFER W/DRIVER, 3500K, 6400 LUMENS METALUX OR EQUAL: 24SR-LD1-64-C-UNV-L830-CD1-U LED 71 OFFICES, LAB, PHARM
F1A METALUX OR EQUAL: 24SR-LD1-45-C-UNV-L835-CD1-U 46 CORRIDORS
F2 METALUX OR EQUAL: 22SR-LD1-29-S-UNV-L835-CD1-U 30 OFFICES/CORRIDORS
F3 4' STRIPLIGHT LENSED LED W/DRIVER, 3500K, 5200 LUMENS METALUX OR EQUAL: SNLED-LD1-52-LW-UNV-L835-CD1-U 53 CORRIDORS/JANITOR
F4
METALUX OR EQUAL: CLPF-24-2-A12125-LD3-3-HI-35-UNV
108 CORRIDORS
F5 2'X2' CLEAN RM LED W/DRIVER, FLANGED, 3500K, 5400 LUMENS 72 CLEAN RM
F6 2'X4' CLEAN RM LED W/DRIVER, FLANGED, 3500K, 7200 LUMENS METALUX OR EQUAL: CLPF-24-4-A12125-LD3-2-HI-35-UNV 94 CLEAN RM
F7 (10) INTERIOR CEILING PENDANT LED W/DRIVER, 4000K STILE OR EQUAL: PAVO SIP 1145762 (10) 1L13WDMT PTXX 130 CORRIDORS
S1 EXTERIOR WALL PACK LED W/PHOTOCONTROL LUMARK OR EQUAL: XT0R5APC1 40 EXTERIOR WALL
S2 BOLLARD LED W/DRIVER, 4000K, 1545 LUMENS FORMS & SURFACES OR EQUAL: LBLCO-604 17 EXTERIOR
EXIT LED EXIT SIGNAGE SURE-LITES OR EQUAL: LPX-6
9.5 W/LF
EXTERIOR
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
2'X4' RECESSED LED TROFFER W/DRIVER, 3500K, 4500 LUMENS
2'X2' RECESSED LED TROFFER W/DRIVER, 3500K, 2900 LUMENS
8' SURFACE STRIPLIGHT LENSED LED W/DRIVER, 3500K, 9900 LUMENS METALUX OR EQUAL: 8TSNLED-LD1-99-LW-UNV-L835-CD2-U
HWP-4 STANDBY
SUMP PUMP
VOLTAGE
F8
F9
8' INDUSTRIAL FLUOR LUMINAIRE W/(4) T5 LAMPS METALUX OR EQUAL: 8IAF-228T5-UNIV-EB2 136 PENTHOUSE/CRAWLFLUOR 120
RECESSED, FLANGED LINEAR LED W/ DRIVER 9.5 W/LFLED 120
F10 SURFACE LINEAR WITH DRIVER OPTOLUM OR EQUAL: FLLP-HO-35-C-S 4.5 W/FT GALLERY*LED 120
S3 RECESSED LED 6" DOWNLIGHT 28
EXTERIOR, BOXED CEILING
LED 120
HALO COMMERICAL OR APPROVED EQUAL
PD62OED0101EM - PDM6A835 - 61VL
FOCUL POINT OR EQUAL: SEEM2
FSM2L-TF-625-35K-IC-UNV
HISTORY WALL, FLANGED
FOR DRYWALL
NOTES
LENGTH AS PER PHYSICAL DIMENSIONS. HISTORY WALL RECESSED LTG. DETAIL, DWG. AS-311, DETAIL #04. AVAILABLE IN INCREMENTS OF 1.33".
S4 5' RECESSED STRIPLIGHT LENSED W/ DRIVER, 3500K, WET LOCATION FOCAL POINT OR EQUAL: SEEM2 #FSM2LWLFL62535K1CUNV
LED 120
INTERIOR
TEF-3 UL 150 WATTS - RP-UL 2 120/1EXHAUST FAN 2#12, #12GRD, 3/4"CTOGGLE
PART #SIP 145762.M (JOB ID# 95959)
PENDANT
LENGTH AS PER PHYSICAL DIMENSION. AVAILABLE IN INCREMENTS OF 1'.
PERFORATED 360° DESIGN
PACKAGED LOWER LEVEL PP-LL 1/3/5 3#3,#8GRD, 1-1/4"C 208/3
PACKAGED ROOF 2 & 3 HP 25/18 DP-PENTHOUSE 1 3#10,#10GRD, 3/4"C 208/3
PACKAGED ROOF 2 & 10 HP 60/44 EM-DP-LL 3 3#6,#10GRD, 1"C 208/3
LOAD
LEAVE WIRES COILED AND TAPED IN A BOX IN THE PENTHOUSE FOR FUTURE AHU-5
LEAVE WIRES COILED AND TAPED IN A BOX IN THE PENTHOUSE FOR FUTURE STRF-3
S5 35 EXTERIOR18" SURFACE MOUNTED LED LIGHT FIXTURE MCGRAW EDISON OR APPROVED EQUAL: TT-B2-LED-E1-MQ-AP LED 120
LEAVE WIRES COILED AND TAPED IN A BOX IN THE PENTHOUSE FOR FUTURE GMU-2
EF-6 UL TOOGLE RP-UL2 18 2#12, #12GRD, 3/4"C 120/11/8 HPEXHAUST FAN
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
100% BID DOCUMENT
/1
5/
2:
:2
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
LIGHTING FIXTURES AND
ELECTRICAL/MECHANICAL SCHEDULE
E003
13-127
FPNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
OS
VS
OS
VS
VS
VS
OS OS
VS
VS
OSD
OSD
.1
.5
G KFE
D E.3
F1 F1 F1
F1 F1 F1
F1 F1 F1
F1 F1 F1
F1a F1a F1a
F1a
F1a
F2 F2
F2
F2
F2
F2
F2F2
F2
F2
F2
F2
F2
F2
F1a
F1a
F1a
F1a
F1a
F1a
F1a
F1a
F2
F2
F2
F2
2d
2d
2d
2d
EM-2
2d
2d
2f
2f
EM-2
2f
2f
2f
2f5b
5b EM-25bEM-2
2c
2c
2c
F3
F3
F3
4a
EM-2
3W 5a
EM-1
5a
5b
3W 5b
3W 5a
EM-1
EM-1
5b
5b
5b
5b
EM-2
3W 5b
EM-1
EM-2EM-1
5c
F3
F3
4b
4b 4b
5d
5d
EM-2
4c
4c
4d
4d5d
2a 2b
2b
2bEM-2
2b2b
2b
2a
2a2a
EM-22a
2a
EM-1
F3 2f
EM-2
'EM-LTG-LL' 100A M.L.O.
120/208V, 3PH,4W
'LP-LL' 100A M.L.O.
120/208V, 3PH,4W
2c
ELEVATOR
EM-1
4d
4c
4a
2f2d
F3
F2
SWITCH FOR ELEVATOR
CAR LTG. & RECEPTACLE,
PANEL 'EM-LTG-LL', CCT.
EM-15
TIME
CLOCK
EM-2F3
F3
S1
S1
F3
F3
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
AREA
'A'
AREA
'C'
BUILDING
BUILDING
MIRACLE MILE
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:2
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
LOWER LEVEL LIGHTING PLAN
EL101
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EL101
1 LIGHTING PLAN - LOWER LEVEL
ELECTRICAL NOTES
A. ALL NORMAL LIGHTING TO PANEL 'LP-LL', U.N.O.
B. ALL EMERGENCY (EM) LIGHTING TO PANEL 'EM-LTG-LL', U.N.O.
OS
OS
OS
OS OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
VS
D B
D B
O S D
OS
O S D
O S D
OS OS
OS OS
OS OS
OSD
OSD
O S D
O S D
O S D
O S D
OS
OS
.1
.5
G KFE
D E.3
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F2
F2
F1 F1F1
F1
F5 F5 F5 F5
F2 F2F2F2F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
4W
F2 F2
F2F2F2
F2 F2
F2 F2
F2
F2
F2
F1
F2
F3
3w3w4w
F2
4w4w
4w4w
4w
3w
F2
F2
F2 F2
F2 F2
F2
F2
F3 F3
4w
EM-4 EM-4 EM-4
EM-4 EM-4 EM-4
EM-4 EM-4 EM-4
EM-4 EM-4 EM-4
EM-4 EM-4 EM-4
EM-4 EM-4 EM-4
EM-4
EM-4
EM-4
EM-4
EM-4
EM-4EM-3
EM-3
EM-4
EM-10 EM-3
13a
EM-6 EM-6
EM-6 EM-6
EM-6 EM-6EM-6 EM-6
EM-6 EM-6EM-6
EM-6 EM-6EM-6
EM-6 EM-6EM-6
EM-6EM-6 EM-6
EM-3
EM-10
EM-3
13f
13f EM-6
8u 8v
8r 8s
8s 8t
8t 8p
8v
8m 8n 8x
EM-38x8x
EM-3
EM-3
13f
13f
EM-3
EM-10
E
M -8
EM-6
EM-3
8a8a
8b8b
8c 8c 13g
13g
13g
EM-10 13g 13g 13g EM-10EM-10EM-3
8e
8e
8f
8f
8g
8g
8h
8h
8j
8j
8l
8l
8k
8k
EM-8
EM-8
EM-8
EM-8
EM-8
E M
-6
EM-6
EM-6
EM-6
EM-6
EM-8
EM-8
E
M -8
EM-3
8w
8w
F2
8d
F6
EM-8
F6
EM-8
F2
Em-10
F2
13e
F2
13f
F2 Em-10
F2
13d F2
13b
13c
F2 8q
EM-10
13a
13a 13a
13a
13a
13a
13a
EM-10
13a
13a
13a
ELEVATOR
F2 F2
EM-3
F2 F2 F2 F2 F2
F2F2F2F2F2
F2 F2 F2 F2
EM-3
EM-4
E M
-4
4w
'24 HOUR' EMERGENCY LTG
(UNSWITCHED)
SWITCHED EMERGENCY LTG.
(TYPICAL IN LAB & PHARMACY)
8x8x 8n
8m
8p 8q
8r
8t
8v8u
8w
8a
8b
8c
8d
8k 8l
13e13d
13b
13c
F3 EM-2
EM-2F3
13a 13a 13a
F2 F2
S1
13g
F5 F5
EM-8EM-8
EM-8
F5
F5
EM-8
EM-8
EM-8
EM-8
F5
EM-8
EM-8
F1
S1
S1
S1
S1
S1
S1
S1
3w
S3
S3
EL104
F1
EM-4
OPEN AIR ENTRANCE
3W
3W
3W
3W
SWITCH BANK
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
AREA
'A'
AREA
'B'
AREA
'C'
BUILDING
BUILDING
MIRACLE MILE
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:2
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
UPPER LEVEL LIGHTING PLAN
EL102
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EL102
1 LIGHTING PLAN - UPPER LEVEL
ELECTRICAL NOTES
A. NORMAL LIGHTING TO PANEL 'LP-LL' LOCATED ON LOWER LEVEL.
B. EMERGENCY LIGHTING TO PANEL 'EM-LTG-LL' LOCATED ON LOWER LEVEL.
C. REFER TO DRAWING 'CS-102', REMOVE AND RELOCATE LIGHTING POLE
APPROXIMATELY 70'. EXTEND CIRCUITRY AS REQUIRED.
ELECTRICAL KEY NOTES
1. PROVIDE OCCUPANCY SENSOR TO BE COMPATIBLE WITH TOILET EXHAUST FAN. CONNECT
TOILET EXHAUST TO SAME OCCUPANCY SENSOR AS LIGHTING FIXTURES.
.5
G K
24a
24a
EM-2
24a
24a
24a
24a
24a
EM-2
24a
24a
OS
OS
OS
EM-1
F8
F8
F8
F8
F8
F8
F8F8
F8
F8
F8
F8
24aEM-224b 24b
NORMAL LIGHTING TO PANEL 'LP-LL', LOCATED ON LOWER LEVEL.
'EM' LIGHTING TO PANEL 'EM-LTG-LL' LOCATED ON LOWER LEVEL.
NORMAL LIGHTING TO PANEL "LP-LL" LOCATED ON LOWER LEVEL.
'EM' LTG TO PANEL 'EM-LTG-LL' LOCATED ON LOWER LEVEL.
S4
S4
S4
S4
S4
F3
24b
EM-2
S1 S1
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
BUILDING
BUILDING
MIRACLE MILE
PE
N
TH
O
US
E
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:2
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
PENTHOUSE LIGHTING PLAN
EL103
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EL103
1 LIGHTING PLAN - PENTHOUSE
ELECTRICAL NOTES
A. NORMAL LIGHTING TO PANEL 'LP-LL', LOCATED ON LOWER LEVEL.
B. 'EM' LIGHTING TO PANEL 'EM-LTG-LL'' LOCATED ON LOWER LEVEL.
.5
OPEN AIR ENTRANCE
S2
S2
S2
S2
S2
LINE OF ROOF ABOVE. SEE
ROOF PLAN THIS SHEET.
.5
S5
S5
S5
S5
S5
S5
S5
S5
S5
S5
S5
S5
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
AREA
'B'
AREA
'C'
BUILDING
BUILDING
MIRACLE MILE
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:3
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
OPEN AIR ENTRANCE LIGHTING PLAN
EL104
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
ELECTRICAL NOTES
A. PROVIDE 2 #10 & #10 GRD TO ALL EXTERIOR RECEPTACLES.
1/8" = 1'-0"EL104
1 OPEN AIR ENTRANCE LIGHTING PLAN - DEDUCT ALTERNATE 12
1/8" = 1'-0"EL104
2 OPEN AIR ENTRANCE ROOF LIGHTING PLAN - DEDUCT ALTERNATE 1
REF.REF.
R E
F.
FE
C
FE
C
FEC
FEC
FEC
FECFEC
R E
F.
GFI
SD
GFI
GFI
A
TS
G F I
G F I
G F I
G F I
G F I
G F I
GFI
GFI
.1
.5
G KFED E.3
REFER TO ELECTRICAL RISER
FOR QUANTITY, DWG. 164-EP601.
CORE THRU WALLS.
LAB
STORAGE
164-009
CORRIDOR
164-006
WOMEN'S
TOILET
164-004
MEN'S
TOILET
164-003
ELECTRICAL
ROOM
164-002
FUTURE
SPACE
164-007
PHARMACY
STORAGE
164-010
CORRIDOR
164-006
CORRIDOR
164-001
CORRIDOR
164-006
STAIR
S-1
MACHINE
ROOM
164-008
HAC
164-005
DELIVERY
164-017
IT
CLOSET
164-011
OFFICE
164-013
OFFICE
164-014
CORRIDOR
164-012
FUTURE
SPACE
164-015
PROVIDE (2) 4" SLEEVES
TO UPPER LEVEL
30A TWIST LOCK
RECEPTACLES, EM-LTG-LL,
CCT. EM-17
FUSED DISCONNECT SWITCH
AND SHUNT TRIP BREAKER.
DIESEL GENERATOR
175KW/219kVA, 120/208V, 3PH, 4W
SOUND ATTENUATION ENCLOSURE
1200 GALLON TANK.
TRANSFORMER IN UTILITY
YARD
MSB-1, 2500A MCB
120/208V, 3PH, 4W
DP-LL, 400A MLO
120/208V, 3PH, 4W
RP-LL, 200A MLO
120/208V, 3PH, 4W
LP-LL, 100A MLO
120/208V, 3PH, 4W
PP-LL, 200A MLO
120/208V, 3PH, 4W
600A, 120/208V, 3PH, 4W
EM-DP-LL, 600A MLO,
120/208V, 3PH,4W
EM-LTG-LL, 100A MLO
120/208V, 3PH,4W
CUH
31 AHU
ELEV.
HUM
VFD FOR SF-2
VFD FOR SF-2
DSS
VFD FOR RF-2
PROVIDE CAB LTG BRANCH
CCT & TELEPHONE FOR
ELEVATOR CAB.
SUMP PUMP & CONTROLLER PNL
'EM-LTG-LL', CCT. EM-11 & EM-13
PROVIDE PIT LTG W/WIREGUARD &
RECEPTACLE PNL 'EM-LTG-LL', CCT. EM-9
GFIGFI
UH
UH
EF
SP
4'x8' PLYWOOD FOR PHONE
SECURITY PNL EM-LTG-LL
CCT. 20
CCTV PNL EM-LTG-LL
CCT. 18
PP-LL CCT.41
30A TWIST LOCK
RECEPTACLES, EM-LTG-LL,
EM-19
8" REINFORCED STEEL
CONCRETE PAD
FRONT ACCESS ONLY
EXISTING MANHOLE #1
(2) 4" C IN
CONCRETE
DUCT BANK.
500kVA
12.47 kV:208/120V
3PH,4W
X
X
MECHANICAL
ROOM
164-016
EF
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
AREA
'A'
AREA
'C'
BUILDING
BUILDING
MIRACLE MILE
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:3
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
LOWER LEVEL POWER PLAN
EP101
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EP101
1 POWER PLAN - LOWER LEVEL
ELECTRICAL NOTES
A. ALL RECEPTACLES TO PANEL RP-LL, U.N.O.
B. REFER TO DRAWING 164-E003 FOR ELECTRICAL/MECHANICAL SCHEDULE FOR FOR
FEEDER SIZING AND CIRCUITS.
C. PROVIDE CONCRETE PADS FOR TRANSFORMER, MSB-1 AND GENERATOR. SIZES OF
PAD SHOWN APPROXIMATE. VERIFY W/ MANUFACTURER.
ELECTRICAL KEY NOTES
1. PROVIDE ELECTRICAL CONNECTION TO PHOTOELECTRIC 'EYE' OF SINKS AND TOILETS.
PANEL RP-LL, CCT.40
2. REFER TO DRAWING 164-T-101 FOR ADDITIONAL WORK.
3. REFER TO DRAWING 164-EP104 FOR PHYSICAL LOCATION OF EXISTING MANHOLE MH1
AND PROVIDE DUCT BANK AS SHOWN ON DRAWING 164-EP104.
FEC
FEC
SH
AR
PS
FEC
GFI GFI
GFI
GFI
GFI
G F I
GFI GFI
GFI GFI
GFI
GFI
G F I
G F I
GFI
G F I
J
HD
G F I
GFI
G F I
GFI
GFI
GFI
G F I
JJ
J
J
J
.1
.5
G KFE
D E.3
EXISTING CASEWORK TO
RECEIVE WIREMOLD,TYP
L70 L50 L54
L55 L52 L53 L73
L59
L47
L46
L72
L48
L43
L49
L44
L45
L86
L71
L8
L17
L15
L16
L41
L40
L39
L42
L74
L32
L30
L29
L38
L34
L33
L35
L36
L37 3
L56
L62
L57L58L66L67L68L69
L60
L19 L85 L83 L84
L63 L64
L28
L23L10L4L3L1L5L22
L26 L25 L24L27
3 5 26 28 30 7 7 9 7 7
181818
24 24 20
1616161414141414141212
25 252525 27 27 27 2929 29
19 191919 19 21 21 23 40 42
27 29
21 23
1515 1515 17 17 1717
9 9 9 9 11 13 13
16 16 2516 18 18
1212121214 14 14
7 7 7 7 5 55 5
1 1 1 31 3 3 3
6 6 6 86 8 36 8
2 2 10 2 4 4 4 4
22 22
L61
TO PANEL EM-UL2, U.N.O.TO PANEL EM-UL1, U.N.O.
TO PANEL EM-UL2, U.N.O.
26 26
P25
P67
P33
P32 P39 P52 P40
P37
P38
P36
P24
P28
P46
P19
P18
P15 P17 P16
P57
P54
P53 P55
P56
P13 P14
P30
P29
P2
P3
P6
P12
P11 P8
P9
P10P5P7
P50 P51
P49 P48 P47
P41P42
P31
20 39 16
LAB
164-115
40 40
3838383838
24 24 24 24
34 36
30 30 30 30
42 42
23 23 25 2525 25
1919191917171515
44222
PHARMACY
164-124
STERILE
PREP
164-126
CHEMO
164-125
MANAGER
OFFICE
164-137
SECRETARY
OFFICE
164-138
CORRIDOR
164-127
TOILET
164-131
LAB
MANAGER
OFFICE
164-130
PSA
OFFICE
164-129
IT
CLOSET
164-128
STAIR
S-2
VAULT
NARCOTICS
164-121
ASSISTANT
OFFICE
164-120
CORRIDOR
164-119
STORAGE
BH & AR
164-117
PASS-THRU
164-122
PROCUREMENT
STATION
164-118
PRIVATE
CONSULTATION
164-123
BLOOD
DRAW
164-112
WOMEN'S
TOILET
164-113
BLOOD
DRAW
164-114
PHLEBOTOMY
164-109
WAITING
164-104
ALCOVE
164-103
WOMEN'S
TOILET
164-105
MEN'S
TOILET
164-106
FAMILY
TOILET
164-107
HAC
164-108
BLOOD
DRAW
164-110
BLOOD
DRAW
164-111
DELIVERY
STORAGE
164-116
24/26 208V
28/30 208V
ELECTRICAL CONTRACTOR SHALL PROVIDE WIREMOLD.
RECEPTACLES SHALL BE 18" O.C.
9 9
21 21
3432323020
28282624
DOORBELL
CONNECTED TO
PUSHBUTTONS FROM
LOWER LEVEL, 120V.
30A TWIST LOCK RECEPTACLES
"EM-UL-2", CCT. 39 & 41
(2) 4" SLEEVE TO LOWER LEVEL
RP-UL 200A MLO
120/208V, 3PH, 4W
'EM-UL1' 200A MLO
120/208V, 3PH,4W
'EM-UL2' 200A MLO
120/208V, 3PH,4W
'EM-UL4',
200A MLO
120/208V, 3PH,4W
TO PANEL EM-UL3, U.N.O.
TO PANEL EM-UL3, U.N.O.
ELEVATOR
P81
TYPICAL POWER POLE W/ DIVIDER FOR COMMUNICATIONS
TYPICAL RECEPTACLE AT 18" A.F.F.
TYPICAL RECEPTACLE ABOVE COUNTERTOP
L20
72"AFF
42 42
WIREMOLD 4000 W/
DIVIDER BY ELECTRICAL
CONTRACTOR.
(TYP.)
VOICE EVACUATION
CONTROL PANEL
PANEL "EM-LTG-LL"
CCT.7
REFRIDGERATOR
RP-UL2, CCT.5
2 11
1 1
TEF
DSS
TEF
TEF
PNEUMATIC TUBE
RP-UL2 100A MLO
120/208V, 3PH, 4W
RP-UL2
RP-UL2
TO PANEL RP-UL2
RP-UL2
(2) RECEPTACLES, 65" AND 96" A.F.F.
PANEL "RP-UL2", CCT.3
(2) RECEPTACLES, 65" AND 96" A.F.F.
PANEL "RP-UL2", CCT.3
RECEPTACLE @ 72" A.F.F.
PANEL, "RP-UL2" CCT.3
35 33
4'x8' PLYWOOD
FOR PHONE
20 20 20 2024 24 24
LOW HEIGHT PARTITION
PROVIDE FLOOR CORES & FIRE
RATES STOP.
L87
L88
L12L12
L11L14
P82
L75
L31
L65
L2
L9L13
L89 L90
P64 P63
P62
P65
P68
P70
P71
P72 P69
P76 P77 P79
P80
'EM-UL5',
200A MLO
120/208V, 3PH,4W
'EM-UL3' 200A MLO
120/208V, 3PH,4W
OPEN
OFFICE
164-132
CLOSET
164-135
STERILE
PREP AIR
LOCK
164-134
CHEMO
AIR
LOCK
164-133
P27P26P60P58
P22 P21
P20 P23
P45 P44
P1
PPPPPPPP
PP PP
6 EM-UL-5
EM-UL-5
EM-UL-5
EM-UL-5
EM-UL-5
PP
PP
EF
OPEN AIR ENTRANCE
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
AREA
'A'
AREA
'B'
AREA
'C'
BUILDING
BUILDING
MIRACLE MILE
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:4
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
UPPER LEVEL POWER PLAN
EP102
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EP102
1 POWER PLAN - UPPER LEVEL
ELECTRICAL NOTES
A. RECEPTACLES IN LAB & PHARMACY AREAS TO RESPECTIVE 'EM' PANELS AS
INDICATED. RECEPTACLES IN OTHER AREAS (NON-LAB AND NON-PHARMACY) TO PANEL
'RP-UL', U.N.O.
B. REFER TO ELECTRICAL SCHEDULE DRAWING 164-E003 FOR
ELECTRICAL/MECHANICAL SCHEDULE FOR FEEDER SIZING AND CIRCUITS.
C. REFER TO DRAWING Q601 & Q602 FOR LAB & PHARMACY EQUIPMENT LIST.
D. MAXIMUM OF 30 CONDUCTORS IN WIREWAY SYSTEM. PROVIDE VERTICAL DROP AS
REQUIRED.
E. COORDINATE WITH MECHANICAL DRAWING AND INSTALL MECHANICAL CONTRACTOR
FURNISHED DISCONNECT SWITCHES TO COMPLY WITH NEC CODE REQUIREMENTS.
F. FURNISH AND INSTALL DISCONNECT SWITCHES AS REQUIRED TO COMPY WITH NEC
REQUIREMENTS.
ELECTRICAL KEY NOTES
1. IN ISLANDS ONLY, POWERPOLE FROM FLOOR TO TABLE AND WIRETROUGH BY
FURNITURE VENDOR. WIRING AND RECEPTACLE BY ELECTRICAL CONTRACTOR.
ELECTRICAL CONTRACTOR TO PROVIDE FLOOR CORES FOR ISLANDS. VERIFY EXACT
LOCATION WITH FURNITURE VENDOR AND OWNER PRIOR TO CORING FLOOR. PROVIDE
HORIZONTAL RUN OF CABLE & CONDUIT BELOW FLOOR. PROVIDE FIRE RATED STOP.
2. CONNECT TEF ALSO TO OCCUPANCY SENSOR/SWITCH. OCCUPANCY SENSOR SHALL BE
RATED FOR TEF.
3. PROVIDE ELECTRICAL CONNECTIONS TO PHOTOELECTRIC 'EYE' OF SINKS AND TOILETS.
PNL "RP-UL2", CCT.1
4. FLOOR CORES & PROVIDE CONDUIT & WIRING BELOW FLOOR. PROVIDE (1) 3/4"C FOR
POWER & 1-1/4"C FOR COMMUNICATIONS.
5. FLOOR CORES & PROVIDE CONDUIT & WIRING BELOW FLOOR. PROVIDE (1) 3/4"C FOR
POWER & (2) 1-1/4"C FOR COMMUNICATIONS.
6. ADA DOOR CONTROL OPERATOR ABOVE DOOR.
FE
C
G F I
G F I
G F I
.1
.5
GFE
D E.3
PENTHOUSE
164-201
STAIR
S-3
AHU
AHU
PP-PENT-1, 400A MLO, 120/208V, 3PH, 4W
ROS
DP-PENTHOUSE, 800A MLO, 120/208V, 3PH, 4W
PP-PENT-2, 200A MLO, 120/208V, 3PH, 4W
GMU
CP
HWP
HWP
STRF
STRF
ACCU
ACCU
VFD
VFD
CONTROL PANEL HUM-4
VFD FOR STRF-2
EF-5
CONTROL PANEL FOR HUM-3CONTROL PANEL FOR HUM-1
VFD FOR STRF-1
EF
VFD FOR SF-3VFD FOR SF-1
EF
EWH
EWH
VFD FOR SF-4
VFD FOR RF-4
VFD FOR HWP-1
VFD FOR HWP-2
HWP
HWP
(FOR RF-3)
BLOWER FOR TUBE
COORDINATE POWER
REQUIREMENTS WITH SWISSLOG.
(FOR RF-1)
HWCP
VFD FOR HWP-4
VFD FOR HWP-3
AHU
FUTURE
AHU
EF
EF
Project Number
Pl ot
D a te
Date
Location
ARCHITECT + ENGINEERS:CONSULTANTS: Drawing Title:
Approved: Project Director
Project Title
Checked Drawn
Drawing Number
Dwg. of
Building Number
Date:Revisions:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot on e qu a rte r i nc h on e fo ot th re e ei gh th s i nc h on e fo ot on e ha lf in ch o ne fo ot th re e qu a rte rs in ch o ne fo ot on e in ch o ne fo ot on e a nd o ne h a lf in ch es o ne fo ot th re e in ch es o ne fo ot
6"
6"
6"
6"
PRESCOTT, ARIZONA
KEY PLAN
NORTH
Fi le
-201 W. CUS HING S TREET
TUCS ON, AZ 85 718
T: 520.882.4484 F: 520.882.5560
BUILDING
BUILDING
MIRACLE MILE
PE
N
TH
O
US
E
100% BID DOCUMENT
O
PE
N A
IR
E
N
TR
A N
C E
/1
5/
2:
:4
P M
C :\U se rs
\d bi bb s\
D oc um en ts \1
3-
E
LC
D
_d bi bb s.
rv t
PENTHOUSE POWER PLAN
EP103
13-127
JSNS
CLINICAL LABORATORY AND
PHARMACY BUILDING
12/03/2015
1/8" = 1'-0"EP103
1 POWER PLAN - PENTHOUSE
ELECTRICAL NOTES
A. ALL RECEPTACLES TO PANEL PP-PENT-2, U.N.O.
B. REFER TO ELECTRICAL SCHEDULE DWG. 164-E003 FOR FEEDER SIZES AND CIRCUITS FOR
MECHANICAL/PLUMBING LOADS.
1/8" = 1'-0"EP103
2 PENTHOUSE ELECTRICAL ROOF PLAN
PLASTIC
SPACER
INNERDUCT,
SEE NOTE 5
DUCT
[SIZE AS
INDICATED
ON DWGS.] 6-WAY DUCT LINE 4-WAY DUCT LINE
2-WAY DUCT LINE
GENERAL NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF
DUCTS WHEN CROSSING OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24")
OR AS OTHERWISE SPECIFIED IN SECTION 26 05 41.
PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
TIE WIRE
(3")
(3")
76mm
(3 m m m
76mm
(3")
76mm m m
(3 m m
(3")
(3")
76mm
(3")
76mm76mm m m m m
76mm
(3")
76mm (3")
(3") 76mm
152mm
(6")(SEE NOTE 4)
(T Y P
EXISTING ELECTRICAL
EQUIPMENT
EXISTING MOTOR CONTROL
CENTER
EXISTING
TRANSFORMER
PM
EXISTING ONAN
GENERATOR
EXISTING MH1
PM
EXISTING
TRANSFORMER
EXISTING ELECTRICAL
EQUIPMENT
EXISTING CHILLER EXISTING CHILLER EXISTING CHILLER
EXISTING PUMPS
NEW DIESEL GENERATOR
NEW SWITCHGEAR
EXISTING AHU
NEW MEDIUM VOLTAGE
DUCTBANK (2) 4"C
SEE DETAIL 2 BELOW
EXISTING MEDIUM
VOLTAGE DUCT BANK
EXISTING UNDERGROUND
CHW LINES
NEW B164 TRANSFORMER
DEDUCT ALTERNATE 14