S02 Sol R0036 AttE SOW.Att17_Building 200 Elevator Study Existing Condition Photos.pdf
PDF 3 MB Posted
- Attached to
- Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
- Solicitation number
- 36C25225R0036_3
About this file
This document is a detailed elevator survey report for Building 200 at a facility, containing multiple pages of field survey images and findings. The survey covers eight traction elevators: five passenger elevators with 4,000 lb capacity traveling at 600 fpm serving 16 landings, and three service elevators with 5,000 lb capacity traveling at 600 fpm also serving 16 landings. All units feature Motion Control Engineering (MCE) controllers built in 2000 with 2000 code year software, Montgomery DC gearless machines likely installed in the 60's, and various components like GAL door equipment, Hollister Whitney governors, and rope grippers.
The survey recommends budgeting for elevator modernization, noting the equipment is in poor to average condition and operating at its useful life expectancy. An estimated budget of approximately [redacted] per unit is suggested for modernization, which would involve replacing major components including controllers, machines, governors, door operating equipment, guide assemblies, elevator safeties, hall and car fixtures, and safety buffers. The modernization process is estimated to take 18-20 weeks per unit from the time materials are on-site, and does not include additional non-elevator work such as electrical, fire life safety, or hoistway patching to meet current code requirements.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SouthCo Services, LLC | 1-877-611-5511 4
Building 200 Traction Units
Previous Elevator Survey by South Co
Issue #21 -- OPEN (2/2) Penthouse S6/S7/S8 and P1/P2/P3/P4/P5 Guide Wheel
MP field survey
SouthCo Services, LLC | 1-877-611-5511 4
Rope Grippers
SouthCo Services, LLC | 1-877-611-5511 5
Governor
Issue #19 -- OPEN (2/3)
Governor and Governor Control Box
Issue #19 -- OPEN (3/3)
Governor
Issue #18 -- OPEN (2/2)
Sprinklers located directly above elevator equipment, may need to be rearranged per code
Issue #21 -- OPEN (2/2)
Controller is Microprocessor Type
Issue #19 -- OPEN (2/3)
Issue #19 -- OPEN (3/3)
Hoist "Ropes" measured at 5/8"
Issue #18 -- OPEN (2/2) Penthouse S6/S7/S8 and P1/P2/P3/P4/P5 Gearless type Machine
Issue #10 -- OPEN (2/3)
Issue #10 -- OPEN (3/3)
Issue #7 -- OPEN (2/2) Elevator Number P4/P5 Field Photos
Issue #5 -- OPEN (2/3)
Elevator Number S6/S7/S8 Field Photos
Issue #5 -- OPEN (3/3) Elevator Number S6/S7/S8 Field Photos
Issue #7 -- OPEN (2/2)
Issue #5 -- OPEN (2/3)
Issue #5 -- OPEN (3/3)