This specification book outlines products and services required for an EHRM Infrastructure Upgrades construction project located at the Edward P. Boland VA Medical Center in Central Western Massachusetts. The project involves thermal and moisture protection, openings, finishes, specialties, furnishings, fire suppression, plumbing, and HVAC systems. Key items include modified bituminous sheet waterproofing, bentonite panel waterproofing, roof and deck insulation, fluid-applied membrane air barriers, slate shingles, and structural insulated panels. Submittals are due within 30 days of the pre-installation meeting. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 47
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOOK TWO OF FOUR
Thermal and Moisture Protection, Openings, Finishes, Specialties, Furnishings, Fire Suppression, Plumbing, HVAC
SPECIFICATION
PROJECT TITLE: EHRM Infrastructure Upgrade Central Western Massachusetts
PROJECT NUMBER: 621-21-700
LOCATION: Edward P. Boland VA Medical Center 421 North Main Street Leeds, MA 01053
PHASE: 100% Construction Documents
DATE: June 6th, 2023
621-21-700 - EHRM Infrastructure Upgrades Date:06/06/2023 USDVA – Edward P. Boland VA Medical Center 100% Bid Documents
01-01-21
07 13 52 - 1
SECTION 07 13 52
MODIFIED BITUMINOUS SHEET WATERPROOFING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Self-adhering, self-healing, modified bituminous sheet material used for exterior waterproofing and split slab waterproofing.
1.2 RELATED SECTIONS
A. Section 03 15 00 – Concrete Accessories B. Section 03 30 00 - Cast-In-Place Concrete C. Section 07 90 00 – Joint Sealers D. Division 30 - Civil E. Division 25 – Electrical F. Division 20 - Mechanical
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. Federal Specifications (Fed. Spec.):
UU-B-790A Notice 2 v04-1992 Building Paper, Vegetable Fiber: (Kraft, Waterproofed, Water Repellent, and Fire
Resistant).
C. ASTM International (ASTM):
C578-19.................Rigid, Cellular Polystyrene Thermal Insulation.
D41/D41M-11(2016).......Asphalt Primer Used in Roofing, Dampproofing and Waterproofing.
D. American Hardboard Association (AHA):
A135.4-(r2020)..........Basic Hardboard.
E. ASTM E 154 Puncture Resistance
F. ASTM E 96 (B) Water Vapor Transmission of Materials
G. ASTM D 882 Test Method for Tensile Properties
H. UL 790 Tests for Fire Resistance of Roof Covering Materials
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings: Show size, configuration, and installation details.
01-01-21
07 13 52 - 2
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
3. Warranty.
D. Test reports: Certify products comply with specifications.
E. Certificates: Certify products comply with specifications.
F. Qualifications: Substantiate qualifications comply with specifications:
1. Installer with project experience list.
1.5 QUALITY ASSURANCE
A. Installer Qualifications:
1. Regularly installs specified products.
2. Installed specified products with satisfactory service on five similar installations for minimum five years.
a. Project Experience List: Provide contact names and addresses for completed projects.
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment:
1. Product Temperature: Minimum 4 degrees C (40 degrees F) for minimum 48 hours before installation.
2. Weather Limitations: Install waterproofing only during dry current and forecasted weather conditions.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."
B. Manufacturer's Warranty: Warrant waterproofing system against material and manufacturing defects and agree to repair any leak caused by a
01-01-21
07 13 52 - 3 defect in the waterproofing system materials or workmanship of the installer.
1. Warranty Period: 10 years.
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Waterproofing System: Modified bituminous sheet material for exterior below grade and split slab waterproofing basis of design is Carlisle
CCW MIRADRI 860/861 self-adhered sheet waterproofing.
2.2 PRODUCTS - GENERAL
A. Provide each product from one manufacturer.
B. Sustainable Construction Requirements:
1. Insulation Recycled Content: Rigid Foam: 9 percent total recycled content, minimum.
2.3 BITUMINOUS SHEET
A. Cold applied waterproofing membrane composed primarily of modified bituminous material prefabricated in sheet form designed for below grade exterior and split slab waterproofing. Sheet reinforced with fibers at manufacturer's option.
B. Thickness: Not less than 1.5 mm (60 mils)//), plus or minus 0.13 mm (5 mils), and bonded to 0.1 mm (4 mil) thick plastic sheet.
C. Provide release sheet to prevent bonding of bituminous sheet to itself.
2.4 PROTECTION MATERIAL
A. Polystyrene Insulation: ASTM C578, Type I or VIII, 13 mm (1/2 inch) minimum thickness.
B. Hardboard: AHA A135.4, Service Type, 6 mm (1/4 inch) thick.
C. Waterproofed Building Paper: Fed. Spec. UU-B-790A Notice 2, Type I, Grade C.
D. Roll Roofing: ASTM D6380/D6380M, Class S (smooth), Type III with minimum net mass per unit area of roofing, 2495 g/sq. m
(51 lbs./100 sq. ft.).
2.5 ACCESSORIES
A. Patching Compound: Factory-prepared, non-shrinking, fast-setting, cementitious adhesive compound containing no ferrous metal or oxide.
B. Primer: ASTM D41/D41M.
C. Roof Cement: ASTM D4586/D4586M.
01-01-21
07 13 52 - 4
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Concrete surfaces cured minimum time recommended by waterproofing manufacturer.
2. Substrate to be dry as recommended by waterproofing manufacturer.
B. Protect existing construction and completed work from damage.
C. Correct substrate deficiencies.
1. Fill voids, joints, and cracks with patching compound.
D. Clean substrates. Remove contaminants capable of preventing full adhesion.
E. Priming:
1. Prime concrete and masonry surfaces.
2. Application method, amount of primer and condition or primer before installation of bituminous sheet as recommended by primer manufacturer.
3. Reprime when required according to manufacturer's instructions.
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions and approved submittal drawings.
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
3.3 WATERPROOFING INSTALLATION
A. Bituminous Sheet Installation:
1. Remove release sheet before application.
2. Lay bituminous sheet from low point to high point so laps shed water.
3. Treat expansion, construction and control joints and evident working cracks as expansion joints. Apply bituminous sheet in double thickness over joint by first applying a strip of bituminous sheet minimum 200 mm (8 inches) wide, centered over joint.
4. Lap seams minimum 50 mm (2 inches).
5. Lay succeeding sheet with laps, and roll or press into place.
6. Repair misaligned or inadequately lapped seams according to manufacturer’s instructions.
7. Seal seams and terminations according to sheet manufacturer’s instructions.
01-01-21
07 13 52 - 5
B. Corner Treatment:
1. At inside and outside corners, apply double cover using an initial strip minimum 280 mm (11 inches) wide, centered along axis of corner.
2. Cover each strip completely by the regular application of bituminous sheet.
3. Provide a fillet or cant on inside corners.
4. Form cants using patching compound.
5. Do not use wood, fiber, and insulating materials for cants.
C. Projection Treatment:
1. Apply a double layer of bituminous sheet around pipes and similar projections at least 150 mm (6 inches) wide.
2. At drains, apply a bead of roof cement over a double layer of bituminous sheet under clamping rings.
D. Patching:
1. Repair tears, punctures, air blisters, and inadequately lapped seams, according to manufacturer’s instructions before protection course is applied.
E. Permanent Protection:
1. Vertical Surfaces:
a. Install hardboard, polystyrene insulation, or roll roofing protection material.
b. Extend protection full height from footing to top of backfill.
c. If graded backfill is used, use roll roofing or hardboard.
F. Horizontal Surfaces:
1. Install roll roofing protection under concrete wearing courses.
2. Install roll roofing, hardboard, or polystyrene insulation under earth backfill.
3. Where no concrete wearing course occurs or when surfaces will bear heavy traffic and will not immediately be covered with a wearing course, use protection specified for vertical surfaces.
G. Temporary Protection:
1. When waterproofing materials are subjected to damage by sunlight and cannot be immediately protected as specified, protect waterproofing materials by waterproof building paper or suitable coating approved by manufacturer of waterproofing system used.
3.4 FIELD QUALITY CONTROL
01-01-21
07 13 52 - 6
A. Field Tests: Performed by testing laboratory specified in Section
01 45 29, TESTING LABORATORY SERVICES.
B. Testing:
1. Before any protection or wearing course is applied, test all horizontal applications of waterproofing with a minimum of 25 mm
(1 inch) head of water above highest point and leave for 24 hours.
2. Mark leaks and repair when waterproofing is dry.
3. Certify, to COR, that water tests have been made and that areas tested were found watertight.
C. Inspection:
1. Do not cover waterproofed surfaces by other materials or backfill until work is approved by Contracting Officer's Representative.
3.5 CLEANING
A. Remove excess adhesive before adhesive sets.
B. Clean exposed waterproofing surfaces. Remove contaminants and stains.
3.6 PROTECTION
A. Protect waterproofing from construction operations.
B. Remove protective materials immediately before acceptance.
C. Repair damage.
- - - E N D - - -
07 17 13 - 1
07 17 13 - 2
SECTION 07 17 13
BENTONITE PANEL WATERPROOFING
RELATED DOCUMENTS
The general provision of the Contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this section.
1.1 DESCRIPTION OF WORK
The extent of Geotextile/Bentonite Clay waterproofing membrane for all exterior concrete conduit connections at the buildings, Data Center underpinning, and for the existing foundation work of building 9.
1.2 RELATED SECTIONS
A. Section 03 10 00 – Concrete Forming and Accessories B. Section 03 20 00 – Concrete Reinforcing C. Section 03 30 00 – Cast-In-Place Concrete D. Section 04 22 00 – CMU - Concrete Unit Masonry E. Section 31 23 00 – Excavation and Fill F. Section 31 20 00 – Earth Moving G. Section 31 40 00 – Shoring and Underpinning H. Section 31 50 00 – Excavation Support and Protection I.
1.3 REFERENCE STANDARDS
A. Comply with references to extent specified in this section.
B. ASTM D75. . . . . . Standard Test Methods for Coated Fabrics
C. ASTM D903. . . . . Standard Test Method for Peel or
Stripping Strength of Adhesive Bonds
D. ASTM D1970. . . . Standard Specification for Self- Adhering Polymer Modified
Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection (Low Temperature Flexibility)
E. ASTM D4632. . . . Standard Test Method for Grab Breaking Load and Elongation of Geotextiles
F. ASTM D5261. . . .Standard Test Method for Measuring Mass per Unit Area of Geotextiles
G. ASTM D5887. . . .Standard Test Method for Measurement of Index Flux Through Saturated Geosynthetic Clay
Liner Specimens Using a Flexible Wall Permeameter
07 17 13 - 3
H. ASTM D5890. . . .Standard Test Method for Swell Index of Clay Mineral Component of
Geosynthetic Clay Liners
I. ASTM D5891. . . .Standard Test Method for Fluid Loss of Clay Component of Geosynthetic Clay Liners
J. ASTM D5993. . . .Standard Test Method for Measuring Mass per Unit Area of Geosynthetic Clay Liners
K. ASTM D4643. . . .Standard Test Method for Determination of Water Content of Soil and Rock by Microwave Oven Heating
L. ASTM D6243. . . .Standard Test Method for Determining the Internal and
Interface Shear Strength of Geosynthetic Clay Liner by the Direct Shear Method
1. ASTM D6496. . . .Standard Test Method for Determining Average Bonding
Peel Strength Between Top and Bottom Layers of Needle-Punched Geosynthetic Clay Liners
M. ASTM D6768. . . .Standard Test Method for Tensile Strength of Geosynthetic Clay Liners
1.4 PREINSTALLATION MEETINGS
A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.
1. Required Participants:
• COR
• Architect/Engineer.
• Inspection and Testing Agency.
• Contractor.
• Installer.
• Manufacturer's field representative.
• Other installers responsible for adjacent and intersecting work, including substrate, and flashing installers.
2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.
• Installation schedule.
• Installation sequence.
• Preparatory work.
• Protection before, during, and after installation.
• Installation.
• Terminations.
• Transitions and connections to other work.
• Inspecting and testing.
• Other items affecting successful completion.
3. Document and distribute meeting minutes to participants to record decisions affecting installation.
07 17 13 - 4
1.5 SUBMITTALS
A. Submittal Procedures: Submit in accordance with Section
01 33 00 SHOP DRAWINGS, PRODUCT DATA AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
3. Warranty.
C. Water Sample Test Result: A water sample (2 liters) is required on projects that have ground water and should be submitted to the waterproofing manufacturer to test for contamination and compatibility with waterproofing membrane. Submit to COR a letter of compatibility recommending which formulation to use.
D. Certificates: Certify products comply with specifications
E. Qualifications: Substantiate qualifications comply with specifications:
1. Installer with project experience list.
1.6 QUALITY ASSURANCE
A. Manufacturer: Provide Geotextile/Bentonite Clay waterproofing membrane produced by a manufacturer with a minimum of 5 years experience in the waterproofing industry.
B. Installer: A firm with a minimum of 2 years experience in installing bentonite clay or other related waterproofing products.
1.7 PRODUCT DELIVERY, STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Coordination between various trades is essential to avoid unnecessary traffic to prevent damage to the membrane.
Heavily traveled areas must be protected by placing temporary protection courses to prevent damage to the membrane.
B. Coordinate waterproofing work with other trades. The applicator shall have sole right of access to the specified areas for the time needed to complete the application.
C. Protect adjoining surfaces not to be waterproofed against damage or soiling. Protect plants, vegetation and animals which might be affected by waterproofing operations.
D. Wear applicable protective clothing and respiratory protection gear.
E. Maintain work area in a neat and orderly condition, removing empty containers, rags, and rubbish daily from the site.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."
B. Manufacturer's Warranty: Warrant waterproofing system against material and manufacturing defects and agree to repair any leak caused by a defect in the waterproofing system materials or workmanship of the installer
C. Warranty Period: 10 years.
PART 2 - PRODUCTS
07 17 13 - 5
2.1 SYSTEM DESCRIPTION
A. Water Proof System: Bentonite sheet membrane panel system for exterior below grade foundations basis of design to be CCW MiraClay Bentonite Clay Waterproofing Membrane by Carlise or approved equivalent.
2.2 GENERAL
A. Provide each product from one manufacturer
2.3 SHEET MEMBRANE
A. Bentonite panel sheet membrane.
2.4 RELATED ACCESSORY PRODUCTS
A. Sealant: Sealant used for detailing at terminations and penetrations, to fill minor voids in concrete, and as a fillet in angle changes
B. Granules: Granules used for horizontal to vertical transitions and for detailing at seams and slab penetrations
C. Pre-formed, high-impact resistant, heavy-duty thermoplastic tie-back cover: Shall be for protecting the integrity at soil retention tie-back systems
D. Swellable Sealant: Shall be for use in non-moving joints to create watertight concrete joints and as an adhesive for waterstop strips
E. Pre-formed Bentonite hydrophilic waterstop strip: for use in non-moving joints to create watertight concrete joints
F. Pre-formed Non-Bentonite hydrophilic waterstop strip: Shall be for use in non-moving joints to create watertight concrete joints
G. Injectable waterstop (grout tube): Shall be for use as an injectable waterstop for use in non-moving joints to create watertight concrete joints
H. Membrane to Substrate Fasteners: Fasteners, of the type and length suitable for the substrate, shall be used in conjunction with washers, of at least 1” diameter to attach the bentonite membrane to the substrate.
I. Membrane to Membrane Fasteners: Mechanically fasten membrane sheets together with a box stapler or similar device for horizontal applications.
J. The Geotextile/Bentonite membrane shall consist of geotextile panels of sodium bentonite clay sandwiched between two layers of needle-punched woven and non-woven polypropylene fabrics.
K. Drainage Composite: Shall be as recommended by the manufacturer for each condition
L. Perimeter Drainage System: As per manufacturer
2.5 PHYSICAL PROPERTIES FOR CLAY
Property Method Unit Value Thickness - In. 0.25 Bentonite Mass/Unit Area
ASTM
D5993 lb/ft2
MARV
(kg/m2
MARV)
0.893 (0.123)
Nonwoven ASTM D5261 oz/yd²
MARV
(g/m²
MARV)
6.0 (200)
Woven ASTM D5261 oz/yd²
MARV
(g/m²
MARV)
3.1 (105)
Swell Index, Minimum ASTM - 24 ml
07 17 13 - 6
D5890 (2 g) Moisture Content ASTM
D4643 %, maximum 12
Fluid Loss ASTM D5891 ml, maximum
Tensile Strength ASTM D6768 lb/in MARV (kN/m
MARV)
(5)
Peel Strength ASTM D6496 lbs/in
MARV
(N/m MARV)
3.5 (610)
Permeability, Maximum ASTM D5887 m/s 5 x 10-9
Index Flux, Maximum ASTM D5887 m³/m²/s 1 x 10-8
Internal Shear Strength ASTM D6243 psf (kPa)
(24)
Elongation ASTM D4632
% 150
Low Temperature Low Temperature
ASTM
D1970
@ -25°F (- 32°C)
Unaffected
Hydrostatic Head Pressure
ASTM D751 ft (meter)
(69.49)
Adhesion to Concrete ASTM D903 lb/in (kg/cm)
17.7 (8)
*@ 12% moisture content
PART 3 - EXECUTION
3.1 PREPARATION
A. The substrate must be relatively even without noticeable high spots or depressions, relatively smooth, free of protrusions, debris, sharp edges or foreign materials and must be free of accumulated water, ice and snow. Earth, crushed stone, or soil shall be compacted to a minimum of 85% modified Proctor.
B. Before any waterproofing work is started the waterproofing applicator shall thoroughly examine all surfaces for any deficiencies. Should any deficiencies exist, the architect, owner, or general contractor shall be notified in writing and corrections made.
C. All surface preparation shall be performed in accordance with application instructions which include but are not limited to:
1. Subbase/Grade Substrates (concrete, earth, or crushed stone)
a. Concrete working slab/mud slab/rat slab must be relatively even without noticeable high spots or depressions, relatively smooth, free of protrusions, debris, sharp edges, or foreign materials.
a. Honeycombing, voids and aggregate pockets exceeding 1" in diameter or have a depth greater than ¾" should be filled with a non-shrink cementitious grout.
b. Earth and stone substrates should be compacted to a minimum 85% modified Proctor.
a. Crushed stone should not be larger than ¾"
07 17 13 - 7
(18 mm) in size.
2. Support of Excavation, S.O.E. (Wood Lagging, Concrete Caissons, Sheet Piling, Shotcrete, etc.)
a. All soil retention substrates shall be relatively smooth and even.
b. Gaps or voids greater than 1.0 in. (25mm) shall be filled or covered with CCW approved material.
c. Remove projections greater than ¾" (20 mm).
d. Waterproofing is an acceptable substrate and is installed before the waterproofing.
a. Install the fabric side facing the soil retention system.
3. Concrete Foundation Wall:
a. The substrate must be properly prepared to receive the waterproofing membrane.
b. All honeycombs, form-tie cavities and indentations should be filled with Sealant or filled with latex Portland Cement.
c. Substrate must be smooth and uniform removing any protrusions over ½" (12 mm) from the surface.
d. Apply Sealant to all construction joints at a minimum of ¼" (7 mm) thickness and a 3" (8
cm) minimum width.
e. Footings must be free of soil, rocks or debris to provide a suitable substrate to receive the waterproofing membrane.
3.2 INSTALLATION
A. Install products according to manufacturer's instructions and approved submittal drawings.
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for COR consideration.
B. Underslab Application: (Structural concrete slab shall be reinforced and have a minimum thickness of 4" (10 cm)).
1. Install waterproofing membrane with the white non-woven side up, facing the installer.
2. Overlap edges a minimum of 4” (10 cm).
3. Protect waterproofing membrane from damage caused by rebar chairs with sharp edges or points by placing a patch of waterproofing membrane under the rebar chair.
4. Staple joints often enough to prevent excessive movement.
5. Pour Granules or trowel Sealant around all penetrations and press in “cut-to-fit” collars of waterproofing membrane.
6. Inspect and repair any damaged material before concrete pour.
C. Pre-Applied (i.e. Blindside) Application for Foundation Wall against S.O.E.:
1. Install waterproofing membrane with the white non-woven side facing the installer.
2. Secure the waterproofing membrane into position with fasteners and 1” (25 mm) washers.
a. Use the appropriate fasteners for the type of substrate used to receive the waterproofing membrane.
3. Install succeeding courses of waterproofing by
07 17 13 - 8 overlapping the previous course a minimum of 4" (100 mm).
a. Install in shingle fashion so that the upper roll of waterproofing overlaps the lower roll.
b. Stagger the seams a minimum of 24" (600 mm).
4. Fasten membrane once every 18" (45 cm) on seams or as required to prevent blousing.
5. Extend waterproofing membrane to 6" below grade and fasten membrane to the substrate to maintain constant compression using a 1⁄8" x 1" (3 x 25 mm) minimum termination bar.
6. Embed the top edge of and termination bar with a thick bead of Sealant 2" (50 mm) wide by ½" (12
mm) thick
D. Concrete Foundation Wall Application (i.e. post-applied):
1. The waterproofing membrane should be installed with the white non-woven side facing the applicator.
2. Create a cant at any vertical to horizontal transition by applying a 1½" (39 mm) to 2" (50 mm) of Granules or Sealant along that junction.
3. At the base of the foundation wall where the vertical wall meets the horizontal footing, install waterproofing membrane in a horizontal manner extending out onto the footing a minimum of 12" (300 mm).
4. Fasten the waterproofing membrane in place with concrete fasteners and 1" (25 mm) washers.
5. Install succeeding courses of waterproofing by overlapping the previous course a minimum of 4" (100 mm).
a. Install in shingle fashion so that the upper roll of waterproofing overlaps the lower roll.
b. Stagger the seams a minimum of 12" (300 mm).
6. Fasten membrane once every 18" (45 cm) to 3'
(90 cm) on seams or as required to prevent blousing.
7. At grade line, terminate waterproofing with a rigid termination bar or fasten 12" (300 mm) on center.
a. Embed the top edge of waterproofing and termination bar with a thick bead of sealant 2" (50 mm) wide by ½" (12 mm) thick.
8. Backfill must be compactible soils free of construction debris
a. Backfill should be placed in 6-12” lifts
b. Each lift should be uniformly compacted to a minimum 85% modified Proctor.
E. Detail Conditions
1. For standard installation details, follow the detail drawings.
2. For non-standard installation instructions, contact your Waterproofing representative
3.3 PROTECTION AND DRAINAGE
A. Prevent geotextile/bentonite clay waterproofing membrane from hydrating before being covered with overburden.
1. When threat of rain is imminent or backfill is not immediate, geotextile/bentonite clay
07 17 13 - 9 waterproofing membrane should be covered with polyethylene sheeting.
B. Protect waterproofing as per manufacturer’s recommendations until concrete or backfill placement.
C. For underslab applications, inspect waterproofing for damage after steel reinforcement placement and just prior to concrete placement.
D. Repair waterproofing as per manufacturer’s recommendations
E. Protect the geotextile/bentonite clay waterproofing membrane with CCW MiraDRAIN Drainage Composite.
F. Install the CCW MiraDRAIN Drainage Composite according to the detailed drawings for the specific installation requirements of the project.
3.4 INSPECTION
A. Examine substrate and condition under which waterproofing will be installed. Do not proceed with the work until unsatisfactory conditions have been corrected.
3.5 PROTECTION
A. Protect waterproofing from construction operations.
B. Remove protective materials immediately before acceptance.
C. Repair damage.
01-01-21
07 22 00 - 1
SECTION 07 22 00
ROOF AND DECK INSULATION
A. Section Includes:
B. Roof and deck insulation, substrate board, vapor retarder, and cover board on new concrete and metal deck substrates ready to receive roofing or waterproofing membrane.
C. Structural insulated panels.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Non-Flooring Adhesives and Sealants VOC Limits.
B. Section 06 10 00, ROUGH CARPENTRY: Wood Cants, Blocking, and Edge Strips.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American Society of Civil Engineers
ASCE 7-16...............Minimum Design Loads and Associated Criteria for Buildings and Other Structures
C. American Society of Heating, Refrigeration and Air Conditioning
(ASHRAE):
Standard 90.1-13........Energy Standard for Buildings Except Low-Rise
Residential Buildings.
D. ASTM International (ASTM):
C208-12(2017)e2.........Cellulosic Fiber Insulating Board.
C552-17e1...............Cellular Glass Thermal Insulation.
C726-17.................Mineral Fiber Roof Insulation Board.
C728-17a................Perlite Thermal Insulation Board.
C1177/C1177M-17.........Glass Mat Gypsum Substrate for Use as
Sheathing.
C1278/C1278M-17.........Fiber-Reinforced Gypsum Panel.
C1289-19................Faced Rigid Cellular Polyisocyanurate Thermal
Insulation Board.
C1396/C1396M-17.........Gypsum Board.
D41/D41M-11 (2016)......Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing.
D312/D312M-16a..........Asphalt Used in Roofing.
07 22 00 - 2
D1970/D1970M-20.........Self-Adhering Polymer Modified Bituminous Sheet
Materials Used as Steep Roofing Underlayment for Ice Dam Protection.
D2178/D2178M-15a........Asphalt Glass Felt Used in Roofing and
Waterproofing.
D2822/D2822M-05(2011)e1.Asphalt Roof Cement, Asbestos Containing.
D4586/D4586M-07(2018)...Asphalt Roof Cement, Asbestos-Free.
E84-20..................Surface Burning Characteristics of Building
Materials.
F1667-18a...............Driven Fasteners: Nails, Spikes, and Staples.
E. National Roofing Contractors Association (NRCA):
Manual-15...............The NRCA Roofing Manual: Membrane Roof Systems-
2019.
F. UL LLC (UL):
Listed Online Certifications Directory.
G. U.S. Department of Agriculture (USDA):
USDA BioPreferred Program Catalog.
H. U.S. Department of Commerce National Institute of Standards and Technology (NIST):
DOC PS 1-19.............Structural Plywood.
DOC PS 2-18.............Performance Standard for Wood-Based
Structural-Use Panels.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and installation details.
a. Nailers, cants, and terminations.
b. Layout of insulation showing slopes, tapers, penetrations, and edge conditions.
c. Show elevations of each high point and low point an perimeter elvations.
d. Provide details at roof drains specific to drains to be installed at roof.
C. Manufacturer's Literature and Data:
1. Description of each product.
D. Sustainable Construction Submittals:
07 22 00 - 3
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
2. Biobased Content:
a. Show type and quantity for each product.
3. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
b. Certify each composite wood and agrifiber product contain no added urea formaldehyde.
E. Qualifications: Substantiate qualifications meet specifications.
1. Installer.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Same installer as Division 07 roofing section installer.
1.6 DELIVERY
A. Comply with recommendations of NRCA Manual.
B. Deliver products in manufacturer's original sealed packaging.
C. Mark packaging, legibly. Indicate manufacturer's name or brand, type, and manufacture date.
D. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Comply with recommendations of NRCA Manual.
B. Store products indoors in dry, weathertight facility.
C. Protect products from damage during handling and construction operations.
D. When storing, panels shall be stored in a protected area and elevated to prevent ground contact and covered to prevent exposure to sunlight, moisture and the elements. Do not allow panels to be stored in an unsupported manner. Improper storage may cause materials damage or decomposition and tolerance problems in the field.
1.8 FIELD CONDITIONS
A. Environment: Install products when existing and forecasted weather permit installation according to manufacturer's instructions.
1.9 WARRANTY
07 22 00 - 4
B. Manufacturer's Warranty: Warrant substrate board, vapor retarder, insulation, and cover board against material and manufacturing defects as part of Division 07 roofing system warranty.
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Insulation Thermal Performance:
1. Overall Average R-Value: RSI-57 (R-38), minimum.
2. Any Location R-Value: RSI-17 (R-10), minimum.
B. Fire and Wind Uplift Resistance: Provide roof insulation complying with requirements specified in Division 07 roofing section.
C. Insulation on Metal Decking: UL labeled indicating compliance with one of the following:
1. UL Listed.
2. Insulation Surface Burning Characteristics: When tested according to
ASTM E84.
a. Flame Spread Rating: 75 maximum.
b. Smoke Developed Rating: 150 maximum.
2.2 PRODUCTS - GENERAL
A. Provide each product from one manufacturer.
B. Sustainable Construction Requirements:
1. Insulation Recycled Content:
a. Mineral Fiber: 75 percent total recycled content, minimum.
b. Fiberglass: 20 percent total recycled content, minimum.
c. Cellulose: 75 percent post-consumer recycled content, minimum.
d. Rigid Foam: 9 percent total recycled content, minimum.
e. Glass Fiber Reinforced Rigid Foam: 6 percent total recycled content, minimum.
2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Non-flooring adhesives and sealants.
b. Composite wood and agrifiber.
3. Bio-Based Materials: Where applicable, provide products designated by USDA and meeting or exceeding USDA recommendations for bio-based content, and products meeting Rapidly Renewable Materials and certified sustainable wood content definitions; refer to www.biopreferred.gov.
http://www.biopreferred.gov/
07 22 00 - 5
2.3 ADHESIVES
A. Primer: ASTM D41/D41M.
B. Asphalt: ASTM D312, Type III or IV for vapor retarders and insulation.
C. Modified Asphaltic Insulation Adhesive: Insulation manufacturer's recommended modified asphaltic, asbestos-free, cold-applied adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
D. Bead-Applied Urethane Insulation Adhesive: Insulation manufacturer's recommended bead-applied, low-rise, one- or multicomponent urethane adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
E. Full-Spread Applied Urethane Insulation Adhesive: Insulation manufacturer's recommended spray-applied, low-rise, two-component urethane adhesive formulated to adhere roof insulation to substrate or to another insulation layer.
F. Roof Cement: Asbestos free, ASTM D2822/D2822M, Type I or Type II; or, ASTM D4586/D4586M, Type I or Type II.
2.4 ROOF AND DECK INSULATION
A. Roof and Deck Insulation, General: Preformed roof insulation boards approved by roofing manufacturer.
B. Polyisocyanurate Board Insulation: ASTM C1289, Type II, Class 1, Grade 2, faced with glass fiber reinforced cellulosic felt facers on both major surfaces of the core foam.
C. Cellulosic Fiber Board Insulation: ASTM C208, Type II, Grade 1 for built-up asphalt or modified bitumen roofing and Grade 2 for single-ply roofing.
D. Tapered Roof Insulation System:
1. Fabricate of mineral fiberboard, polyisocyanurate, perlite board, or cellular glass. Use only one insulation material for tapered sections. Use only factory-tapered insulation.
2. Cut to provide high and low points with crickets and slopes as shown.
3. Minimum thickness of tapered sections; 38 mm (1-1/2 inch).
4. Minimum slope 1/48 (1/4 inch per 12 inches).
E. Composite Nail Base Insulated Roof Sheathing:
07 22 00 - 6
1. Oriented-Strand-Board-Surfaced, Polyisocyanurate-Foam Sheathing:
Polyisocyanurate thermal insulation ASTM C1289, Type V, insulation thickness as shown, with oriented strand board laminated to top surface.
2. Oriented Strand Board: NIST DOC PS 1, Exposure 1, 16 mm (5/8 inch) thick.
3. Bottom surface faced with felt facers.
2.5 STRUCTURAL INSULATED PANELS
A. System Description:
1. Structural insulated panels are component product stick framing module consisting of conventional 2x4, 2x6, or 2x8’s spf lumber studs prepositioned 16” or 24” on center with polyurethane foam insulation molded in place between studs and foil radiant air barrier applied to the exterior sides of the panels.
2. Structural insulated panels are installed using conventional stick frame construction methods and practices per UCC, IBC, IRC and ICC standards. Panels are to be combined with standard dimensional lumber studs, plates, nailers, headers and sills, as required, supplied onsite by contractor as detailed in manufacturer’s installation details meeting all 2019 building codes.
B. Design Requirements:
1. Panels which have been manufactured to standard taking care to maintain performance criteria stated by manufacturer without defects, damage or failure. Provide labeling of all insulation used in the manufacture of panels. Manufacturer’s listing programs shall cover both flame and physical properties.
2. Panel manufacturer will provide R-value documents for building owner acceptance and execution upon request. Manufacturer’s standard forms will be submitted.
3. ASTM C518 Standard 75 Degrees R39.
4. Structural Testing: Each RAY-CORE Structural Insulated Panel type shall meet or exceed performance standards, values, testing and applicable technical data reports when tested in accordance with:
a. ASTM E84 Surface burning characteristics for the rigid insulation core.
b. ASTM E84 Surface burning characteristics conducted for the interior and exterior surfaces of the finished panel.
07 22 00 - 7
2.6 INSULATION ACCESSORIES
A. Glass (Felt): ASTM D2178/D2178M, Type VI, heavy duty ply sheet.
B. Cants and Tapered Edge Strips:
1. Insulation Cant Strips: ASTM C208, Type II, Grade 1, cellulosic-fiber insulation board.
2. Tapered Edge Strips: 1/12 (1 inch per 12 inches), from 0 mm (0 inches), 300 mm to 450 mm (12 inches to 18 inches) wide.
a. Cellulosic Fiberboard: ASTM C208.
b. Mineral Fiberboard: ASTM C726.
c. Perlite Board: ASTM C728.
C. Vapor Retarder:
1. Glass-Fiber Felts: ASTM D2178/D2178M, Type IV, asphalt impregnated.
2. Self-Adhering Sheet Vapor Retarder: ASTM D1970/D1970M, minimum
1.0 mm (40 mils) thick membrane of HDPE film fully coated with asphalt adhesive, or 0.76 to 1.0 mm (30 to 40 mils) thick membrane of butyl rubber based adhesive backed by a layer of high density cross-laminated polyethylene; maximum permeance rating of
6 ng/Pa/s/sq. m (0.1 perms).
D. Substrate Board:
1. Glass-Mat, Water-Resistant Gypsum Roof Board: ASTM C1177/C1177M, Type X, 16 mm (5/8 inch) thick, factory primed.
2. Cellulosic-Fiber-Reinforced, Water-Resistant Gypsum Roof Board:
ASTM C1278/C1278M, 16 mm (5/8 inch) thick.
E. Cover Board:
1. Glass-Mat, Water-Resistant Gypsum Roof Board: ASTM C1177/C1177M, 16 mm (5/8 inch) thick, factory primed.
2.7 ACCESSORIES
A. Fasteners: Corrosion-resistant carbon steel fasteners and galvalume-coated steel or plastic round plates for fastening substrate board and insulation to roof deck.
B. Nails: ASTM F1667; type to suit application.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Comply with requirements of Division 07 roofing section.
3.2 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
07 22 00 - 8
3.3 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions.
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for COR consideration.
B. Comply with requirements of UL for insulated steel roof deck.
C. Attach substrate board and other products to meet requirements of
Division 07 roofing section.
3.4 SUBSTRATE BOARD INSTALLATION
A. Fasten substrate board to top flanges of steel decking to resist uplift pressures according requirements for specified roofing system.
1. Locate the long dimension edge joints solidly bearing on top of decking ribs.
3.5 VAPOR RETARDER INSTALLATION
A. Vapor Retarder Installation, General:
1. Install continuous vapor retarder on roof decks where indicated.
2. At vertical surfaces, turn up vapor retarder to top of insulation or base flashing.
3. Seal penetrations through vapor retarder with roof cement to prevent moisture entry from below.
B. Cast in Place Concrete Decks, Except Insulating Concrete:
1. Prime deck as specified.
2. Apply two plies of asphalt saturated felt mopped down to deck.
C. Precast Concrete Unit Decks Without Concrete Topping, Hollow Core Precast Planks:
1. Prime deck as specified.
2. Apply two plies of asphalt saturated felt.
3. Mop to deck, keeping bitumen 100 mm (4 inches) away from joints of precast units. Bridge joints with felt. Mop between plies as specified.
3.6 INSULATION INSTALLATION
A. Insulation Installation, General:
1. Base Sheet: Where required by roofing system, install one lapped base sheet specified in Division 07 roofing section by mechanically fastening to roofing substrate before installation of insulation.
2. Cant Strips: Install preformed insulation cant strips at junctures of roofing system with vertical construction.
07 22 00 - 9
3. Use same insulation as existing for roof repair and alterations unless specified otherwise.
B. Insulation Thickness:
1. Thickness of roof insulation shown on drawings is nominal. Provide thickness required to comply with specified thermal performance.
2. Insulation on Metal Decks: Provide insulation in minimum thickness recommended by insulation manufacturer to span deck flutes. Support edges of insulation on metal deck ribs.
3. When actual insulation thickness differs from drawings, coordinate alignment and location of roof drains, flashing, gravel stops, fascias and similar items.
4. Where tapered insulation is used, maintain insulation thickness at high points and roof edges shown on drawings.
a. Low Point Thickness: Minimum 38 mm (1-1/2 inches).
5. Use minimum two layers of insulation when required thickness is
68 mm (2.7 inch) or greater.
C. Lay insulating units with close joints, in regular courses and with end joints staggered.
1. Stagger joints between layers minimum 150 mm (6 inches).
D. Lay units with long dimension perpendicular to the rolled
(longitudinal) direction of the roofing felt.
E. Seal cut edges at penetrations and at edges against blocking with bitumen or roof cement.
F. Cut to fit tightly against blocking or penetrations.
G. Cover all insulation installed on the same day; comply with temporary protection requirements of Division 07 roofing section.
H. Installation Method:
1. Mechanically Fastened Insulation:
a. Fasten insulation according to requirements in Division 07 roofing section.
b. Fasten insulation to resist uplift pressures specified in Division 07 roofing section and ASCE-7.
2. Mechanically Fastened and Adhered Insulation:
a. Fasten first layer of insulation according to "Mechanically
Fastened Insulation" requirements.
b. Fasten each subsequent layer of insulation according to "Adhered Insulation" requirements.
07 22 00 - 10
3.7 COVER BOARD INSTALLATION
A. Install cover boards over insulation with long joints in continuous straight lines with staggered end joints.
B. Offset cover board joints from insulation joints 150 mm (6 inches), minimum.
C. Secure cover boards according to "Adhered Insulation" requirements.
3.8 STRUCTURAL INSULATED PANELS
A. Manufacturer’s Instruction
1. Compliance: Installation shall be in strict accordance with manufacturer’s published instructions and conventional construction methods and practices, and compliance per local code requirements.
Deviations from conventional building methods and practices should be calculated, signed and sealed by a registered professional engineer.
2. Certification: Builders plans and panel manufacturer’s installationinstructions.
B. Installation
1. Installation shall be in strict accordance with manufacturer’s published instructions and conventional construction methods and practices and compliance per local code requirements. Deviations from conventional construction methods and practices should be calculated, signed and sealed by a registered professional engineer.
a. Panel Supports: Provide level and square foundation/structural system/substrate to support wall and/or roof panels. Provide adequate bracing of panels during erection. Remove debris from panel edge prior to attachment of plates.
b. Panel Fastening: Connect panels to plates by construction adhesive, nails, staples or screws as required. Where screw fasteners are used, provide a minimum of 2” penetration into support. Join panels using plates. Apply adhesive and foam sealant to all joints, penetrations, cracks and voids to fill and seal, following manufacturer recommendations.
c. Tape: Provide tape at joints between panels and at intersection of roof and wall.
d. Thermal Barriers: Internal surfaces of panels shall be finished with a minimum 15-minute thermal barrier, such as ½ ” gypsum
07 22 00 - 11 wallboard other approved materials as required by local code requirements.
e. External Finishes: External surfaces of panels shall be finished with materials that provide protection from sunlight, weather, moisture and all elements.
f. Restrictions: Panels shall be protected from exposure to sunlight, moisture, the elements, solvents and their vapors, and any other substance that will damage the aluminum vapor barrier or polyurethane foam.
2. Protection
a. Panels used on walls must be covered by an external finish to fully protect from sunlight, moisture and the elements.
b. Panels used on roof must be fully protected from sunlight, moisture and the elements utilizing tarps, roofing materials or other means to provide temporary protection at the end of the day, or when rain or snow is imminent, and permanently upon completion of construction.
c. Remove and replace panels, which have become excessively wet or damaged before proceeding with installation of additional panels or other work.
d. The contractor shall remove all refuse created by the installation of work in this section.
e. Ordinary care and safety precautions should be followed when handling panels, as with other construction materials. Proper lifting techniques should be followed. Extra caution should be taken in wet, icy or windy conditions. Panel surface can be slippery. Exercise caution walking on panels and always use appropriate and approved fall protection. Do not walk on panels in wet, icy or windy conditions. Wear appropriate eye and dust protection when cutting panels.
- - E N D - -
01-01-21
07 27 27 - 1
SECTION 07 27 27
FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR RETARDING
A. Section Includes:
1. Fluid-applied vapor-retarding air barrier at exterior above grade wall assemblies.
2. Connection to adjacent air barrier components providing a durable, continuous, full building air barrier.
1.2 RELATED REQUIREMENTS
A. General Quality Assurance and Quality Control Requirements: Section
01 45 29 TESTING LABORATORY SERVICES.
B. General Sustainable Construction Requirements: Section 01 81 13
SUSTAINABLE CONSTRUCTION REQUIREMENTS.
C. Masonry Unit Air Barrier Substrates: Section 04 20 00 UNIT MASONRY.
D. Membrane Base Flashings and Stripping Air Barriers Requiring Air
Barrier Transitions: Section 07 51 00, BUILT-UP BITUMINOUS ROOFING
E. Flashing Components of Factory Finished Roofing and Wall Systems Air Barriers Requiring Air Barrier Transitions: Division 07 roofing and wall system sections.
F. Metal Flashing Requiring Air Barrier Transitions: Section 07 60 00
FLASHING AND SHEET METAL.
G. Joint Sealants: Section 07 92 00 JOINT SEALANTS.
H. Wall Sheathings Air Barrier Substrates: Section 09 29 00 GYPSUM BOARD.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. Air Barrier Association of America (ABAA):
Quality Assurance Program.
C. ASTM International (ASTM):
C920-18.................Elastomeric Joint Sealants.
C1193-16................Use of Joint Sealants.
D412-16.................Vulcanized Rubber and Thermoplastic
Elastomers-Tension.
E84-20..................Surface Burning Characteristics of Building
Materials.
E96/E96M-16.............Water Vapor Transmission of Materials.
01-01-21
07 27 27 - 2
E162-16.................Surface Flammability of Materials Using a
Radiant Heat Energy Source.
E783-02(2018)...........Field Measurement of Air Leakage Through
Installed Exterior Windows and Doors.
E1186-17................Air Leakage Site Detection in Building
Envelopes and Air Barrier Systems.
E2178-13................Air Permanence of Building Materials.
E2357-18................Determining Air Leakage of Air Barrier
Assemblies.
D. U.S. Environmental Protection Agency (EPA):
40 CFR 59, Subpart D National Volatile Organic
Compound Emission Standards for Consumer and
Commercial Products.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
1. Indicate size, configuration, and fabrication and installation details.
B. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
C. Sustainable Construction Submittals:
1. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
D. Test reports:
1. Submit field inspection and test reports.
E. Certificates: Certify each product complies with specifications.
F. Qualifications: Substantiate qualifications comply with specifications.
1. Manufacturer with project experience list .
2. Installer with project experience list .
a. Certify installer approval by air barrier manufacturer.
G. Installation Audit:
1. Submit audit report in writing to COR.
1.5 QUALITY ASSURANCE
A. Coordinate work with adjacent and related work to provide continuous, unbroken, durable air barrier system.
01-01-21
07 27 27 - 3
B. Manufacturer Qualifications:
1. Regularly and presently manufactures specified products.
2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight, conditioned facility.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment:
1. Work Area Ambient Temperature Range: 4 to 32 degrees C (40 to 90 degrees F) continuously, beginning 48 hours before installation.
B. Surface Requirements: visibly dry, and complying with manufacturer's instructions.
1.9 WARRANTY
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Air-Barrier Assembly Air Leakage: Maximum 0.2 L/s/square meter
(0.04 cfm/square feet) of surface area at 75 Pa (1.57 psf) differential pressure when tested according to ASTM E2357.
B. ccommodate substrate movement and seal expansion and control joints, construction material transitions, opening transitions, penetrations, and perimeter conditions without moisture deterioration and air leakage exceeding performance requirements.
2.2 PRODUCTS - GENERAL
A. Provide air barrier system components from one manufacturer.
B. Sustainable Construction Requirements:
07 27 27 - 4
1. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13 SUSTAINABLE CERTIFICATION REQUIREMENTS for the following products:
a. Non-Flooring Adhesives and Sealants.
2.3 AIR BARRIER
A. Fluid-Applied, Vapor-Retarding Membrane Air Barrier:
1. Elastomeric, modified bituminous or synthetic polymer membrane.
2. Air Permeance: ASTM E2178: 0.02 L/s/square meter
(0.004 cfm/square feet) of surface area at 75 Pa (1.57 psf) differential pressure.
3. Vapor Permeance: ASTM E96/E96M: Maximum 5.8 ng/Pa/s/square meter (0.1 perms).
4. Elongation: Ultimate, ASTM D412, Die C: 500 percent, minimum.
5. Thickness: Minimum 1.0 mm (40 mils) dry film thickness, applied in single continuous coat.
6. Surface Burning Characteristics: When tested according to ASTM E84S.
a. Flame Spread Rating: 25 maximum.
b. Smoke Developed Rating: 450 maximum.
2.4 ACCESSORIES
A. Primer: Waterborne primer complying with VOC requirements, recommended air barrier manufacturer to suit application.
B. Counterflashing Sheet: Modified bituminous, minimum 1.0 mm (40 mils) thick, self-adhering composite sheet consisting of minimum 0.8 mm
(33 mils) of rubberized asphalt laminated to polyethylene film.
C. Substrate Patching Material: Manufacturer's standard trowel-grade filler material.
D. Sprayed Polyurethane Foam Sealant: Foamed-in-place, 24 to 32 kg/cu. m (1.5 to 2.0 pcf) density, with maximum flame-spread index of 25 when tested according to ASTM E84.
E. Joint Sealant: ASTM C920, single-component,…