This architectural construction document set pertains to the MacLaren Youth Correctional Facility Infirmary & Pharmacy Renovation project for the Oregon Youth Authority located at 2630 N Pacific Highway, Woodburn, Oregon. The project consists of the renovation of 2,985 square feet and expansion of 1,865 square feet within the existing infirmary, for a total project area of 4,850 square feet. The renovation and expansion work includes expanding the medical laboratory, establishing a security station, relocating and expanding the medical room and supply areas, creating a receiving and storage area, constructing four patient rooms with one AII (airborne infection isolation) room, adding a shared day room, establishing a new nurse station, creating two supervisor offices, and constructing a meeting room. Upon completion of the medical room relocation, existing walls will be removed to create an enlarged general storage room. The construction documents are dated June 27, 2025, and include comprehensive architectural, structural, mechanical, plumbing, electrical, and telecommunications drawings prepared by Clark/Kjos Architects under Project No. 25015.
The project is classified as Occupancy B (institutional) with a total facility square footage of 9,052 square feet and operates under the 2022 Oregon Structural Specialty Code and NFPA 101-Chapter 38. The facility is designed as Construction Type V-B with full sprinkler protection and an active fire alarm system, accommodating a maximum occupant load of 1,201 sleeping area occupants at 120 square feet per occupancy and 7,187 outpatient occupants at 100 square feet per occupancy. The project includes a three-hour fire separation wall with smoke barrier provisions. The contractor is responsible for verifying all existing conditions and dimensions prior to construction, coordinating all subcontractor work, ensuring security of the site during construction, maintaining weather-tight conditions, and complying with all fire and life safety standards. Key project contacts include Andre Billingsley (Facility Manager, Oregon Youth Authority), William Sloman (Project Manager, Clark/Kjos Architects), and Lance Cerny (Structural Engineer, Lewis & Van Vleet, Inc.), with delegated design efforts for fire alarm and fire sprinkler systems identified as requiring deferred submittals.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
PROJECT SITE
PROJECT CONTACTS
OREGON YOUTH AUTHORITY
530 CENTER ST NE, STe. 500
SALEM, OR 97301
TEL: (971) 719-6580
ATTN: ANDRE BILLINGSLEY, FACILITY MANAGER
EMAIL: ANDRE.L.BILLINGSLEY@OYA.OREGON.GOV
CLARK/KJOS ARCHITECTS
421 SW SIXTH AVE. SUITE 1300
PORTLAND, OR 97204
TEL: (503) 206-3825
ATTN: WILLIAM SLOMAN, PROJECT MANAGER
EMAIL: WILLSLOMAN@CKARCH.COM
OWNER:
ARCHITECT:
LEWIS & VAN VLEET, INC.
18660 SW BOONES FERRY RD.
TUALTIN, OR 97062
TEL: (503) 885-8605
ATTN: LANCE CERNY, PE
EMAIL: LANCEC@LVVI.COM
SAZAN GROUP
111 SW 5TH AVE., SUITE 3210
PORTLAND, OR 97204
TEL: (503) 416-2400
ATTN: CHRIS LARSON, PE
EMAIL: CLARSON@SAZAN.COM
STRUCTURAL:
MEP:
DIMENSION TO FACE OF
FRAMING, FACE OF
CONCRETE, GRID
LINE, OR AS NOTED.
CLEAR DIMENSION TO
FINISH FACE OR AS NOTED
SURFACE SLOPE
NORTH ARROW
PROJECT NORTH (SEE CIVIL
FOR TRUE NORTH)
DRAWING REVISION
NEW SPOT ELEV
WINDOW TYPE -
REF WINDOW SCH
DOOR TAG
WINDOW TAG
CALLOUT
DRAWING NUMBER
DRAWING NUMBER
EXTERIOR ELEVATION
DOOR NUMBER -
REF DOOR SCH
SHEET NUMBER
EXISTING SPOT ELEV
ELEVATION TAG
KEYNOTE
BUILDING SECTION
WALL SECTION
SHEET NUMBER
ROOM TAG
(E) 98.75'
INTERIOR ELEVATION
1 1/4"
1 1/4"
DRAWING NUMBER
SHEET NUMBER
98.75'
ROOM NUMBER
1/4:12
SLOPE
SYMBOLS AND FILL PATTERNS
EARTH
GRAVEL
ASPHALT
METAL - STEEL
MASONRY - CONCRETE BLOCK
WOOD - FINISH
*WOOD - CONTINUOUS
INSULATION - BATT
INSULATION - RIGID
INSULATION - ACOUSTICAL
WOOD - PLYWOOD
GYPSUM BOARD
GLASS
WOOD - PARTICLE BOARD
METAL - ALUMINUM
CONCRETE
MASONRY - BRICK
SAND
*WOOD - BLOCKING
INSULATION - SEMI RIGID
A3.00
A3.00
FINISH TAG
WALL TAG
CEILING HEIGHT ABOVE
FINISHED FLOOR- ALL
CEILINGS 9'-0" UNLESS
OTHERWISE NOTED.
CEILING MATERIAL
CEILING TAG
A-1
A3AX
WALL ASSEMBLY
STUD SIZE
MODIFIER
W1
A1.01
Room Name
150 SF
Name Elevation
ACT-1
9'-0"
A1.01
A7.01
PROJECT DESCRIPTION
THIS PROJECT CONSISTS OF THE RENOVATION OF 2,985 SF AND EXPANSION OF 1,865 SF FOR THE INFIRMARY AT OREGON YOUTH AUTHORITY’S MACLAREN FACILITY. THE RENOVATION WILL INCLUDE EXPANDING THE MEDICAL LAB, A SECURITY STATION, MED ROOM AND SUPPLY, AND A RECEIVING/STORAGE AREA. THE EXPANSION WILL INCLUDE FOUR PATIENT ROOMS, A SHARED DAY ROOM, A NEW NURSE STATION, TWO SUPERVISOR OFFICES, AND A MEETING ROOM. AFTER MOVING THE EXISTING MED ROOM, THE WALLS WILL BE REMOVED FOR AN ENLARGED
GENERAL STORAGE ROOM.
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
, L
LC
C O
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:1
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
GEN. NOTES, SYMBOL,
ABBRE. & FINISH CODE
06.27.2025
G0.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
2630 N PACIFIC HWY. WOODBURN, OR 97071
MacLAREN INFIRMARY & PHARMACY RENOVATION
OREGON YOUTH AUTHORITY
CONSTRUCTION DOCUMENTS
GENERAL
G0.01 GEN. NOTES, SYMBOL, ABBRE. & FINISH CODE
G1.01 FIRE AND LIFE SAFETY
G1.02 SITE PLAN
G2.01 PARTITION, WALL AND ROOF ASSEMBLIES
G2.02 PARTITION DETAILS
ARCHITECTURAL
A1.01 ARCHITECTURAL SITE PLAN
A2.01 FLOOR PLAN - LEVEL 1
A2.02 ROOF PLAN
A2.11 ENLARGED PLAN - PATIENT AREA
A2.12 ENLARGED PLAN - STORAGE AREA
A2.21 ENLARGED PLANS
A2.51 ENLARGED FINISH PLAN- PATIENT AREA
A2.52 ENLARGED FINISH PLAN - STORAGE AREA
A3.11 ENLARGED RCP - PATIENT AREA
A3.12 ENLARGED RCP - STORAGE AREA
A4.01 EXTERIOR ELEVATIONS
A4.21 BUILDING SECTIONS
A4.31 WALL SECTIONS
A5.01 INTERIOR ELEVATIONS
A5.02 INTERIOR ELEVATIONS
A5.03 INTERIOR ELEVATIONS
A6.01 EXTERIOR DETAILS- WINDOW, STOREFRONT
A6.02 EXTERIOR DETAILS- ROOF DETAILS
A6.03 EXTERIOR DETAILS
A6.04 EXTERIOR DETAILS
A6.05 EXTERIOR DETAILS
A7.01 INTERIOR DETAILS - CASEWORK
A7.02 INTERIOR DETAIL
A8.01 DOOR SCHEDULE & WINDOW TYPES
STRUCTURAL
S1.00 STRUCTURAL NOTES
S1.01 FDN. PLAN - LEVEL 1
S1.02 FOUNDATION DETAILS
S1.03 FOUNDATION DETAILS
S2.01 ROOF FRMG PLAN - LEVEL 1
S2.02 ROOF FRMG. DETAILS
S2.03 ROOF FRMG. DETAILS
S2.04 ROOF FRMG. DETAILS
MECHANICAL
M0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
M0.01 MECHANICAL LEGEND
M2.00 MECHANICAL SCHEDULE
MD1.01 MECHANICAL DEMOLITION - FIRST FLOOR PLAN - OVERALL
MD1.02 MECHANICAL DEMOLITION - ROOF PLAN - OVERALL
M3.01 MECHANICAL HVAC - FIRST FLOOR PLAN - OVERALL
M3.02 MECHANICAL - ROOF PLAN - OVERALL
M3.11 MECHANICAL HVAC - FIRST FLOOR PLAN - PATIENT AREA
M3.12 MECHANICAL HVAC - FIRST FLOOR PLAN - STORAGE AREA
M4.01 MECHANICAL PIPING - FIRST FLOOR PLAN - OVERALL
M4.11 MECHANICAL PIPING - ROOF PLAN - OVERALL
M5.01 MECHANICAL ENLARGED PLANS - PHASE 1
M6.00 MECHANICAL DIAGRAMS
M7.00 MECHANICAL DETAILS
PLUMBING
P0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
P2.00 PLUMBING SCHEDULES
PD1.11 PLUMBING DEMOLITION - FIRST FLOOR PLAN - PATIENT AREA
PD1.12 PLUMBING DEMOLITION - FIRST FLOOR PLAN - STORAGE AREA
P3.01 PLUMBING WASTE & VENT - UNDERGROUND PLAN - PATEINT AREA
P3.02 PLUMBING WASTE & VENT - UNDERGROUND PLAN - STORAGE AREA
P3.11 PLUMBING WASTE & VENT - FIRST FLOOR PLAN - PATINET AREA
P3.12 PLUMBING WASTE & VENT - FIRST FLOOR PLAN - STORAGE AREA
P4.11 PLUMBING DOMESTIC WATER - FIRST FLOOR PLAN - PATEINT AREA
P4.12 PLUMBING DOMESTIC WATER - FIRST FLOOR PLAN - PATIENT AREA
P7.00 PLUMBING DETAILS
ELECTRICAL
E0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E0.01 ELECTRICAL LEGEND
E0.02 ELECTRICAL LIGHTING SCHEDULES
E0.03 ELECTRICAL EQUIPMENT SCHEDULE
ED1.00 ELECTRICAL DEMOLITION - SITE PLAN
ED1.01 ELECTRICAL DEMOLITION - FIRST FLOOR PLAN - OVERALL
ED3.00 ELECTRICAL DEMOLITION - LIGHTING PLAN - OVERALL
ED4.11 ELECTRICAL DEMOLITION - FIRST FLOOR PLAN - PATIENT AREA
ED4.12 ELECTRICAL DEMOLITION - FIRST FLOOR PLAN - STORAGE AREA
ED4.13 ELECTRICAL DEMOLITION - ROOF PLAN - OVERALL
E1.00 ELECTRICAL - SITE PLAN
E3.01 ELECTRICAL LIGHTING - FIRST FLOOR PLAN - OVERALL
E3.11 ELECTRICAL LIGHTING - FIRST FLOOR PLAN - PATIENT AREA
E3.12 ELECTRICAL LIGHTING - FIRST FLOOR PLAN - STORAGE AREA
E4.01 ELECTRICAL POWER - FIRST FLOOR PLAN - OVERALL
E4.02 ELECTRICAL POWER - ROOF PLAN - OVERALL
E4.11 ELECTRICAL POWER - FIRST FLOOR PLAN - PATIENT AREA
E4.12 ELECTRICAL POWER - FIRST FLOOR PLAN - STORAGE AREA
E4.13 ELECTRICAL POWER - ROOF PLAN - PATIENT AREA
E4.14 ELECTRICAL POWER - ROOF PLAN - STORAGE AREA
E6.00 ELECTRICAL ONE-LINE DIAGRAM
E8.00 ELECTRICAL PANEL SCHEDULES
TELECOM
T0.00 SYSTEMS GENERAL NOTES AND LEGEND
T3.01 SYSTEMS - FIRST FLOOR PLAN - OVERALL
T3.11 SYSTEMS - FIRST FLOOR PLAN - PATIENT AREA
T3.12 SYSTEMS - FIRST FLOOR PLAN - STORAGE AREA
T7.00 SYSTEMS DETAILS
Ø DIAMETER
┴ PERPENDICULAR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACC ACCESSIBLE
ACT ACOUSTICAL TILE
ADD ADDENDUM
AFF ABOVE FINISH FLOOR
AL ALUMINUM
ALT ALTERNATE
ANOD ANODIZED
AP ACCESS PANEL
ARCH ARCHITECT(URAL)
AUTO AUTOMATIC
B.O. BOTTOM OF
BATT BATT INSULATION
BIT BITUMINUS
BLDG BUILDING
BM BENCH MARK
BOL BOLLARD
BP BUILDING PAPER
CCTV CLOSED CIRCUIT TV
CF CUBIC FOOT
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CG CORNER GUARD
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR(ANCE)
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS, CONTINUE
CT CERAMIC TILE
CTR CENTER
DA DOUBLE ACTING
DEMO DEMOLISH/DEMOLITION
DEP DEPRESSED
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DIV DIVISION
DMT DEMOUNTABLE
DN DOWN
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DTL DETAIL
DW DISHWASHER
DWG DRAWING(S)
DWR DRAWER
(E) EXISTING
E EAST
EA EACH
EJT EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
EMER EMERGENCY
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXP EXPANSION
EXP EXPOSED
EXT EXTERIOR
ABBREVIATIONS
DEMOLITION
D0.01 DEMO SITE PLAN
D1.01 DEMO PLAN- LEVEL 1
EQUIPMENT (for reference only)
Q2.11 ENLARGED EQUIPMENT PLAN - PATIENT AREA
Q2.12 ENLARGED EQUIPMENT PLAN - STORAGE AREA
DRAWING INDEX
DELEGATED DESIGN
DELEGATED DESIGN EFFORTS ARE AS FOLLOWS AND
AS INDICATED IN DRAWINGS:
• FIRE ALARM
• FIRE SPRINKLER SYSTEM
DEFERRED SUBMITTALS
1 County Comments 08/19/2025
CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING WITH THE WORK.
DO NOT SCALE DRAWINGS. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE WORK.
CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND COORDINATION OF SUBCONTRACTOR'S WORK, COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS, ACCURATE LOCATION OF STRUCTURAL MEMBERS, AND OPENINGS FOR MECHANICAL, ELECTRICAL, AND
MISCELLANEOUS EQUIPMENT.
CONTRACTOR SHALL VERIFY DIMENSIONS AND CLEARANCES FROM MANUFACTURER PRIOR TO THE CONSTRUCTION AND INSTALLATION
OF ALL EQUIPMENT, FURNISHINGS, AND ACCESSORIES.
CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE SECURITY OF THE SITE DURING CONSTRUCTION AND UNTIL PROJECT COMPLETION.
PROVIDE BACKING, BLOCKING, OR STRAPPING AS REQUIRED FOR GRAB BARS, SHELVING, EQUIPMENT, HANDRAILS, ACCESSORIES, AND
CABINETS.
COORDINATE LOCATIONS OF IN-WALL ITEMS TO AVOID BACK TO BACK INSTALLATION.
ALL SAFETY GLAZING SHALL BE PERMANENTLY LABELED WITH THE MANUFACTURER'S NAME AND TEST APPROVAL INFORMATION.
REF. STRUCTURAL FOR REQUIRED SPECIAL INSPECTIONS.
REF. MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL AND EQUIPMENT INFORMATION.
UNLESS OTHERWISE NOTED, ALL MATERIAL AND DESIGN SPECIFICATIONS CITED HEREIN SHALL CONFORM TO THE MOST RECENT
BUILDING CODE FOR THE AUTHORITY HAVING JURISDICTION.
THESE ARCHITECTURAL NOTES ARE A SUPPLEMENT TO THE PROJECT SPECIFICATIONS. ANY DISCREPANCY FOUND AMONG THE DRAWINGS, SPECIFICATIONS, THESE NOTES, AND ANY SITE CONDITIONS SHALL BE REPORTED IN A TIMELY MANNER AND IN WRITING TO THE ARCHITECT WHO SHALL CLARIFY ANY DISCREPANCY IN WRITING. ANY WORK DONE BY THE CONTRACTOR AFTER DISCOVERY OF
SUCH DISCREPANCY SHALL BE DONE AT THE CONTRACTOR'S RISK.
CONTRACTOR SHALL VERIFY AND COORDINATE THE DIMENSIONS SHOWN ON DRAWINGS PRIOR TO PROCEEDING WITH ANY WORK OR
FABRICATION.
THE ARCHITECTURAL DRAWINGS REPRESENT THE DESIGN INTENT AND ARE NOT INTENDED TO INDICATE THE MEANS AND METHOD OF CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCING, AND
SAFETY REQUIRED FOR THIS PROJECT.
ALL FEATURES OF CONSTRUCTION NOT FULLY SHOWN SHALL BE THE SAME TYPE AND CHARACTER AS SHOWN FOR SIMILAR CONDITIONS
SUBJECT TO REVIEW BY THE ARCHITECT.
ALL PRODUCTS AND MATERIALS BEING PROVIDED BY THE CONTRACTOR SHALL BE APPLIED, PLACED, ERECTED, OR INSTALLED IN STRICT
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
THESE DOCUMENTS CONTAIN NOTES THAT MAY APPLY GENERALLY TO ALL DESIGN ELEMENTS, SPECIFICALLY TO ONE SHEET, OR SPECIFICALLY TO ONE OR MORE DESIGN ELEMENTS. THE NOTES ARE NOT MERE GUIDELINES, THEY ARE PART AND PARCEL OF THE DESIGN. ANY WORK THAT IS PERFORMED THAT IS NOT IN COMPLIANCE WITH THE NOTES IS NOT IN COMPLIANCE WITH THE DESIGN AND IS SUBJECT TO REJECTION. ANY ALTERATION, MODIFICATION, DELETION, OR ADDITION TO THE NOTES BY WRITING, ACT OR FAILURE TO ACT, SHALL BE CARRIED OUT ONLY WITH THE PRIOR EXPRESS WRITTEN CONSENT AND APPROVAL OF THE ARCHITECT.
CONTRACTOR TO MAINTAIN WEATHER TIGHT FACILITY AT ALL TIMES.
WHERE MATERIALS ARE STORED ON SITE PRIOR TO INSTALLATION, CONTRACTOR SHALL PROTECT THOSE MATERIALS FROM WEATHER
DAMAGE.
CONTRACTOR SHALL WORK WITH FACILITIES TO ENSURE WORKSITE SECURITY AT ALL TIMES.
GENERAL NOTES
F.O. FACE OF
FA FIRE ALARM
FAF FLUID APPLIED FLOORING
FD FLOOR DRAIN, FIRE DAMPER
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FGL FIBERGLASS
FHC FIRE HOSE CABINET
FIN FINISH(ED)
FLOUR FLOURESCENT
FLR FLOOR(ING)
FND FOUNDATION
FP FIREPROOFING
FRP FIBER-REINFORCED PLASTIC
FT FIRE TREATED
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GL GLASS, GLAZING
GWB GYPSUM WALL BOARD
GYP GYPSUM
GYP BD GYPSUM BOARD
HB HOSE BIBB
HC HOLLOW CORE
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HOR HORIZONTAL
HR HOUR
HT HEIGHT
HTG HEATING
HVAC HEATING, VENTILATING, AIR
CONDITIONING
HWD HARDWOOD
ID INSIDE DIAMETER
INS INSULATE(D), INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAM LAMINATE(D)
LAV LAVATORY
LH LEFT HAND
LW LIGHTWEIGHT
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURE(R)
MGR MANAGER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODULAR
MP METAL PANEL
MRGB MOISTURE RESISTANT GYPSUM
WALL BOARD
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER(S)
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
OH OVERHEAD
OPP OPPOSITE
P PAINT(ED)
PERF PERFORATE(D)
PLAM PLASTIC LAMINATE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PWD PLYWOOD
QT QUARRY TILE
RA RETURN AIR
RAD RADIUS
RD ROOF DRAIN
REF REFRIGERATOR
REQ REQUIRED
REV REVISION(S), REVISED
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
RV REVERSE
S SOUTH
SAM SELF ADHERED MEMBRANE
SC SOLID CORE
SCHED SCHEDULE
SEC SECTION
SFRM SPRAY-APPLIED FIRE RESISTIVE
MATERIAL
SIM SIMILAR
SPEC SPECIFICATION(S)
SQ SQUARE
STD STANDARD
STL STEEL
STR STRUCTURAL
SUPP SUPPLEMENT, SUPPLY
SV SHEET VINYL
T&G TONGUE AND GROOVE
TB TOWEL BAR
TEL TELEPHONE
TEMP TEMPERED
TKBD TACKBOARD
TO TOP OF
TOC TOP OF CURB OR CONCRETE
TOF TOP OF FRAMING
TOW TOP OF WALL
TS TUBE STEEL
TV TELEVISION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VG VERTICAL GRAIN
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WH WATER HEATER
WP WATERPROOF(ING)
WRB WEATHER RESISTIVE BARRIER
WS WATERSTOP
WWF WELDED WIRE FABRIC
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
UP
LEGEND
SECURITY SEPARATION
3 HOUR WALL
SMOKE BARRIER
SMOKE PARTITION
NEW EXIT SIGN, ARROW(S) INDICATES
DIRECTION (IF SHOWN)
KEY LOCKED SECURITY GATE
CHAINLINK FENCE AND GATE
OCCUPANT EXIT LOAD
EGRESS TOTAL PATH OF TRAVEL DISTANCE
FIRE EXTINGUISHER
NOT AN EXIT
SEC LK
XX
X'-X"
FE
NE
BB
CC
2 3 4
159' - 9"
NE
NE
COURTYARD
RECEIVING /
STORAGE
MED LAB
SECURITY
MED SUPPLY
MED ROOM
NURSE
STATION
MEETING
ROOM
NURSE
SUPERVISOR
NURSE
SUPERVISOR
PATIENT
ROOM/AII
PATIENT
ROOM
SHOWER
ROOM
PATIENT
ROOM
PATIENT
ROOM
DAY ROOM
CIRCULATION
DENTAL LAB
VAC STORE
DENTAL
OFFICE
OPERATORY
OFFICE /
EXAM ROOM
SHARED
OFFICE
PSYCH
OFFICE
NURSE
SUPER /
EXAM ROOM
JANITOR
CLOSET
YTH TLT
EXAM ROOMMED SUPPLY
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
SHARED
OFFICE
YTH TLT
EXAM ROOM
LOCKERS
BREAK
ROOM
STF TLTSTF TLT
HALLWAY
HALLWAY
GENERAL
STORAGE
KIT
COURTYARD
VESTIBULE
DENTAL VAC
YOUTH
WAITING
ELEC. CLOSET
AREA OF WORK
53.52.3 2.8
AA
A.6A.6
9'
9"
FE
FE
FE
DD
0 4.63.90.9 1.5
AREA OF WORK
6 7
AREA OF WORK
NEW 3-HR FIRE
SEPARATION
1,201 SF
SLEEPING AREA
B
120 SF / OCC
10 OCC
7,187 SF
OUTPATIENT
B
100 SF / OCC
72 OCC
COURTYARD
744 SF
GEN. STORAGE
S1
300 SF / OCC
3 OCC
RECEIVING
/ STORAGE
MED LAB
SECURITY
MED
SUPPLY
MED ROOM
NURSE
STATION
MEETING
ROOM
NURSE
SUPERVISOR
NURSE
SUPERVISOR
PATIENT
ROOM/AII
PATIENT
ROOM
SHOWER
ROOM
PATIENT
ROOM
PATIENT
ROOM
DAY ROOM
CIRCULATION
DENTAL
LAB
VAC
STORE
DENTAL
OFFICE
OPERATORY
OFFICE /
EXAM
ROOM
SHARED
OFFICE
PSYCH
OFFICE
NURSE
SUPER /
EXAM
ROOM
JANITOR
CLOSET
YTH TLT
EXAM
ROOM
MED
SUPPLY
PSYCH
OFFICEPSYCH
OFFICE
PSYCH
OFFICEPSYCH
OFFICE
SHARED
OFFICEYTH TLT
EXAM
ROOM
LOCKERS
BREAK
ROOM
STF TLTSTF TLT
HALLWAY
HALLWAY
GENERAL
STORAGE
KIT
COURTYARD
VESTIBULE
DENTAL
VAC
YOUTH
WAITING
ELEC.
CLOSET
1,604 SF
TRANSPORTATION
OFFICE
B
150 SF / OCC
11 OCC
AREA OF WORK
B - OCCUPANCY - 10,333 SF - 91%
LEGEND - OCCUPANCY
S-1 - OCCUPANCY - 980 SF - 8.7%
OCC. B - [36,000 + (9,000 * .5) ] = 40,500, SF
TOTAL ALLOWABLE 40,500 SF
AT COUNTERTOPS
AT COUNTERTOPS
AT WALL-MOUNT
EQUIPMENT
TOP OF WALL PHONES
PULL STATION
(TOP OF BOX)
HORN /S STROBE
(BOTTOM OF BOX)
AT ALL OTHER
LOCATIONS (INCLUDING
OPEN WORK COUNTERS)
ONE URINAL
MINIMUM AT ADA
HEIGHT
ADDITIONAL
URINALS TO BE
MOUNTED AT
TALLER HEIGHT
MR
PROVIDE ADDITIONAL
WALL FINISH BEHIND
MIRROR FOR A FLUSH
MOUNTING SURFACE
M
AX
1'
- 5
1'
- 1
1"
3' - 0" MIN
2'
- 1
0"
7'
- 5
3'
- 8
1'
- 6
4'
- 0
16"-18" (M
AX
2'
- 1
0"CL
EA
RA
NC
E
" M
IN
KN
EE
SD
W / L
AV
AT
OR
Y
3'
- 4
" M
AX
6'
- 8
4'
- 0
1'
- 6
"3'
- 8
3' - 0"
"-1
9" 3'
- 4
"TPD
1' - 0" MAX
3' - 6" MIN
2'
- 1
0"
1'
- 6
3'
- 3
3' - 3" -41"
OF TP
7"-9" TO
CENTER
CONTROLS MUST BE
WITHIN THIS AREA & 15"
(MAX) LEFT OR RIGHT OF
CENTER LINE OF SEAT.1' - 6"
3'
- 2
4'
- 0
M
AX
2'
- 3
M
AX
3'
- 0
" 4'
- 0
4'
- 2
AUTO DOOR OPENER
CARD READER
M
AX
2'
- 1
0"
M
IN
2'
- 3
TYP 40" TO CONTROLS AND
DISPENSER OPENING (MAX. 48"
FRONT REACH AND 48" SIDE
REACH)
ACCESSIBLE
NON-ACCESSIBLE
PROVIDE ADDITIONAL WALL
FINISH BEHIND PTD FOR A
FLUSH MOUNTING SURFACE
PTD
5'
- 4
4'
- 0
NOTES:
1) ALL DIMENSIONS ARE TYPICAL UNLESS NOTED OTHERWISE ON INTERIOR ELEVATIONS.
2) WALL MOUNTED ACCESSORIES SHALL NOT PROJECT MORE THAN 4" FROM FACE OF WALL WHEN LOCATED BELOW 6'-8".
3) NON USED ITEMS ARE HALFTONE
7'
- 0
(T
YP
1'
- 1 0"
4'
- 4
EXTINGUISHER
HANDLE
3'
- 4
A URINAL (RIM HEIGHT) B WATER CLOSET (SEAT HEIGHT) C SIDE GRAB BAR (TO CENTER) D REAR GRAB BAR (TO CENTER) E TOILET PAPER DISP. F LAVATORY G SOAP DISPENSER H MIRROR
J PAPER TOWEL DISP. K COAT HOOK L SHOWER (REF. BENCH LOCATION) M ELECT. OUTLETS
(CENTER OF BOX) N LIGHT SWITCHES
(TOP OF BOX) O TELE / DATA CONN.
(CENTER OF BOX) P FIRE ALARM DEVICES
R VANITY LIGHT FIXTURE
(CENTER OF BOX) S FIRE EXTINGUISHER CABINET T ADA DRINKING FOUNTAIN U DOOR ACCESSORIES
(TOP OF BOX) V SIGNAGE
(CENTER OF BOX) W BABY CHANGING STATION
PULL CORDS & BUTTONS
(CENTER OF BOX)
STAFF STATIONS
(TOP OF BOX)
DOME LIGHTS
(CENTER OF BOX)
8'
- 0
4'
- 0
Q NURSE CALL
SCD
3'
- 4
8"
I SEAT COVER DISP.
MIN
1' - 0"
1' - 0"
W /O
LA
VA
TO
RY
2'
- 1
1" M
AX
MR
STANDING = 38"-43"
1'
- 5
3'
- 2
" 3'
- 1
0"
5'
- 0
THERMOSTAT
LIGHT SWITCH
DOOR LEVER
DUPLEX, PHONE, AND
DATA OUTLERS TO BE
LOCATED 17" AFF. U.N.O.
NOTE:
CONTRACTOR TO VERIFY
ALL DIMENSIONS AT SITE
EQ
A
T
DO
OR
H
IN
GE
S
EQ
A T
DO
OR
H
IN
GE
S
5"
9"
" M
AX
. B
AS
E
OF
T
OP
LI
NE
" M
IN
. B
AS
E
OF
LO
W
EE
ST
LI
NE
A.D.A. SIGNAGE
1' - 0"
RISK PROFILE FOR SPACES
HIGH RISK - YOUTH LEFT UNATTENDED
MODERATE RISK - YOUTH UNRESTRANINED
BUT ATTENDED
LOW RISK - STAFF ONLY ACCESS
(VIA PHYSICAL SECURITY LIKE DOOR LOCKING)
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:2
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
FIRE AND LIFE SAFETY
06.27.2025
G1.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
GENERAL NOTES: FIRE & LIFE SAFETY
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL
TRADES ARE THOROUGHLY FAMILIAR AND COMPLY WITH THE
REQUIREMENTS LISTED IN THE "FIRE AND LIFE SAFETY STANDARDS"
(FLSS)
2. ALL RATED ASSEMBLIES SHALL BE CONSTRUCTED TO PREVENT THE
MOVEMENT OF FLAME OR GASSES PER CODE
3. INSTALL RATED ENCLOSURES FOR ALL RECESSED ITEMS IN RATED
WALLS PER CODE. SEE ARCHITECTURAL DETAILS.
4. ALL PENETRATIONS THROUGH RATED ASSEMBLIES IN AREA OF WORK
SHALL BE FIRESTOPPED OR SEALED PER CODE.
5. THE CONTRACTOR SHALL FIELD VERIFY THE CONDITION OF THE
EXISTING FLSS SYSTEMS IN THE AREAS OF WORK THAT MAY REQUIRE
UPDATING. AREAS INCLUDE (BUT ARE NOT LIMITED TO) THE
FOLLOWING:
A. CONTRACTOR TO VERIFY THAT ALL EXISTING PENETRATIONS OF
RATED ASSEMBLIES WHICH ARE EXPOSED TO VIEW DURING
CONSTRUCTION ARE COMPLIANT WITH CODE REQUIREMENTS.
B. CONTRACTOR TO EXTEND ANY EXISTING WALL (WITHIN THE AREA OF
WORK) TO STRUCTURE WHICH IS REQUIRED BY FLSS BUT DOES NOT
PRESENTLY EXIST.
C. CONTRACTOR TO VERIFY THAT ALL DUCTWORK PENETRATIONS
THROUGH RATED ASSEMBLIES ARE EQUIPPED WITH FIRE AND/ OR
SMOKE DAMPERS AS REQUIRED BY CODE.
D. VERIFY THAT THE FIRE ALARM, EMERGENCY LIGHTING, AND
EMERGENCY POWER IN THE AREA OF WORK CONFORMS TO THE FLSS
"ELECTRICAL STANDARDS" SECTION FOR THE OCCUPANCY TYPE
INDICATED ON THE FLS PLANS
6. REFER ELECTRICAL FOR EXIT SIGN LOCATIONS
7. ALL EMERGENCY EXIST HARDWARE ARE DELAYED EGRESS.
CODE SUMMARY
PROJECT NAME: MacLaren Infirmary & Pharmacy Renovation
ADDRESS: 2630 N PACIFIC HWY. WOODBURN, OR
97071
OWNER: OREGON YOUTH AUTHORITY
CODES: 2022 OSSC
NFPA 101-CHAPTER 38
OCCUPANCY: B
OCCUPANCY: UNIT HOUSE A MAXIMUM OF 4 DETAINEES
FOR MEDICAL OBSEVATION ONLY FOR
LESS THAN 48 HRS.
NUMBER OF STORIES: ONE
CONSTRUCTION TYPE: V-B
FIRE PROTECTION: FULLY SPRINKLERED
FIRE ALARM SYSTEM: YES
ALLOWABLE SQUARE FOOTAGE: (TABLE 506.2)
TOTAL AREA OF NEW BUILDING: 11,083 SF
TOTAL AREA ALLOWED: 40,500 SF
INFIRMARY SQUARE FOOTAGE: 9,052 SF
RENOVATION SQUARE FOOTAGE: 2,985 SF
ADDITION SQUARE FOOTAGE: 1,865 SF
FIRE SEPARATION DISTANCE: (602) ≥30'-0"
MAXIMUM AREA OF EXTERIOR WALL
OPENINGS (705.8):
≥30'-0"
UNPROTECTED, SPRINKLERED
UNLIMITED
OCCUPANT LOAD: (1004.5) 1/120 SF, SLEEPING AREAS
1/100 SF, OUTPATIENT AREAS
1/300 SF, STORAGE AREAS
MAX. COMMON PATH OF TRAVEL
(1006.2.1): 75 FT
MAX. TRAVEL DISTANCE (1017.2.1): 200 FT
FIRE RESISTIVE RATINGS: (TABLE NO. 601, 705.5 OF THE I.B.C.)
BUILDING ELEMENT (>10'
SEPARATION)
TYPE V-B
STRUCTURAL FRAME 0 HOUR
BEARING WALLS
EXTERIOR 0 HOUR
INTERIOR 0 HOUR
NON BEARING WALLS AND PARTITIONS
EXTERIOR 1 HOUR, IF <30' FIRE SEPARATION DISTANCE
0 HOUR, IF ≥30' FIRE SEPARATION DISTANCE
INTERIOR 0 HOUR
FLOOR CONSTRUCTION
INCLUDING SUPPORTING BEAMS
AND JOISTS
0 HOUR
NON BEARING WALLS AND PARTITIONS
INCLUDING SUPPORTING BEAMS
AND JOISTS
0 HOUR
1" = 10'-0"G1.01
2 LEVEL 1 - FLS & RISK ASSESSMENT
1" = 40'-0"G1.01
1 LEVEL 1
1" = 20'-0"G1.01
3 LEVEL 1 - PROJECT OCCUPANCY
1/4" = 1'-0"G1.01
4 TYPICAL MOUNTING HEIGHTS
1/2" = 1'-0"G1.01
5 STANDARD MOUNTING HEIGHTS
PLUMBING CALCULATIONS
CALCULATION FACTORS
PROJECT OCCUPANTS FOR CALC. 85 OCCUPANTS
PROJECT CLASSIFICATION FOR
CALC.
B CLASSIFICATION
WATER CLOSETS
REQUIRED COUNT 1 PER 25 FOR FIRST 50, 1 PER 50 AFTER
THAT
REQUIRED IN PROJECT 3 WATER CLOSETS
INCLUDED IN PROJECT 5 WATER CLOSETS
LAVATORY
REQUIRED COUNT 1 PER 40 FOR FIRST 80, 1 PER 80-
AFTER THAT
0 HOUR, IF ≥30' FIRE SEPARATION
DISTANCE
REQUIRED IN PROJECT 2 LAVATORIES
INCLUDED IN PROJECT 5 LAVATORIES
SHOWERS/BATHTUBS
INCLUDED IN PROJECT 1 SHOWER STALL
REQUIRED COUNT 0 SHOWER/BATHTUB
DRINKING FOUNTAINS
INCLUDED IN PROJECT 0 DRINKING FOUNTAIN
REQUIRED COUNT 0 DRINKING FOUNTAIN
1 County Comments 08/19/2025
E
- N P
A C
IF
IC
H W
Y
E
- N P
A C
IF
IC
H W
Y
MacLAREN SCHOOL RD NE
INDUSTRIAL AVE
N A
TI
O
N A
L W
A Y
WASTEWATER
TREATMENT PLANT
CITY INDUSTRIAL
WSATE INSPCTNMACLAREN YOUTH
CORECTIONAL
FACILITY
NE CARL RD
WOODBURN ESTACADA HWY NE
PROJECT LOCATION
SECURITY FENCE
LEGEND
PROPERTY LINE
SETBACK
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:2
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
SITE PLAN
06.27.2025
G1.02
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
1" = 200'-0"G1.02
1 ENLARGED ENTRY PLAN
WALL
CEILING - REF RCP FOR HEIGHT AND TYPE
ONE LAYER 5/8" GWB
STEEL FRAMING AS INDICATED BY WALL TYPE
1/2" PLYWOOD
ACOUSTIC SEALANT
ONE LAYER 5/8" GWB
STUD SIZE
F11 = 5/8" R.C.
F11.5= 1 1/2" F12 = 2 1/2" F13 = 3 5/8" F16 = 6"
HILTI X-U PAF @ 16" O.C. (3/4" EMBED)
ACOUSTIC SEALANT
6" M
IN
BRACE STUDS TO STRUCTURE- @ 4'-0" O.C.. USE
SAME GAUGE AS STUDS, MAX. LENGTH 6'-0"
(CONTRACTORS OPTION- EXTEND FRAMING TO
STRUCTURE)
ONE LAYER 5/8" GWB EACH SIDE
ACOUSTIC SEALANT
CEILING - REF RCP FOR HEIGHT AND TYPE
UNDERSIDE OF FLOOR OR ROOF
DECK
STEEL STUDS AT 24" O.C.
STUD SIZE
P13 = 3 5/8" P16 = 6"
GA File No. WP 1072
STC 33 WITH ACOUSTIC BATTS
HILTI X-U PAF @ 16" O.C. (3/4" EMBED)
WALL HEAD
PLAN
WALL BASE
(E) 8" CMU
CMU SIZE
8= 7-5/8 NOMINAL
WEEP SCREED
3 COAT STUCCO SYSTEM
STUCCO LATH
5/8" PLYWOOD SUBSTRATE
3 COAT STUCCO SYSTEM
STUCCO LATH
5/8" PLYWOOD SUBSTRATE
PREFINISHED THROUGH FLASHING
PLAN
WALL BASE
6" M
IN
. DEFLECTION HEAD RUNNER ANCHORED TO
STRUCTURE
ONE LAYER 5/8" GWB EACH SIDE
EXTERIOR RATED PLYWOOD ONE SIDE
ACOUSTIC SEALANT
CEILING - REF RCP FOR HEIGHT AND TYPE
UNDERSIDE OF FLOOR OR ROOF
DECK
2 X 6 @ 16" O.C. WOOD STUD
STUD SIZE
W13 = 3 5/8"
W16 = 6"STC 33 WITH ACOUSTIC BATTS
ONE LAYER 5/8" GWB EACH SIDE
RATED PLYWOOD ONE SIDE
WALL HEAD
PLAN
WALL BASE
ACOUSTIC BATT INSULATION
ACOUSTIC BATT INSULATION
ACOUSTIC BATT INSULATION
ACOUSTIC SEALANT - ONE SIDE
6" M
IN
ACOUSTIC SEALANT - ONE SIDE
ONE LAYER 5/8" GWB EACH SIDE
EXTERIOR RATED PLYWOOD BOTH SIDE
ACOUSTIC SEALANT
CEILING - REF RCP FOR HEIGHT AND TYPE
UNDERSIDE OF FLOOR OR ROOF DECK
2 X 6 @ 16" O.C. WOOD STUD
STUD SIZE
W23 = 3 5/8"
W26 = 6"STC 33 WITH ACOUSTIC BATTS
ONE LAYER 5/8" GWB EACH SIDE
EXTERIOR RATED PLYWOOD
BOTH SIDE
WALL HEAD
PLAN
WALL BASE
ACOUSTIC BATT INSULATION
ACOUSTIC BATT INSULATION
ACOUSTIC BATT INSULATION
DEFLECTION HEAD RUNNER ANCHORED TO
STRUCTURE
3 COAT STUCCO SYSTEM
CONTINUOUS 2" POLY ISO INSULATION
(R-7.5 MIN)
W.R.B.
PLYWOOD SHEATHING PER STRUCTURAL
3 1/2" THERMAL BATT INSULATION (R-13 MIN)
2"X6" WOOS STUDS @16" O.C.
VAPOR RETARDER
5/8" TYPE 'X' GYPSUM WALL BOARD
DRAINAGE MESH
3 COAT STUCCO SYSTEM
PLAN
SECTION
STUCCO LATH
STUCCO LATH
11"
3 5/8"
5/8" PLYWOOD AT ALL PERIMETER WALLS
PAINT TO MATCH EXISTING
STUD SIZE
X16 = 6" X13= 3-5/8"
SINGLE-PLY MEMBRANE ROOFING
(THERMOPLASTIC OLEFIN - 'TPO')
5/8" GLASS MAT
SUBSTRATE COVER
BOARD
3 1/2" POLYISO INSULATION
(R-20 MIN)
ROOF W.R.B.
ROOF SHEATHING PER
STRUCTURE
1/4" GLASS MAT SUBSTRATE
PROTECTION BOARD
FLOOR FINISH AS
SCHEDULED
CONCRETE FLOOR PER STRUCTURAL
VAPOR BARRIER PER SPEC.
CONTINUOUS 2" POLY ISO INSULATION
(R-7.5 MIN)
W.R.B.
PLYWOOD SHEATHING PER STRUCTURAL
3 1/2" THERMAL BATT INSULATION (R-13 MIN)
2"X6" WOOD STUDS @16" O.C.
VAPOR RETARDER
5/8" TYPE 'X' GYPSUM WALL BOARD
DRAINAGE MESH
METAL CLADDING SYSTEM
PLAN
SECTION
5/8" PLYWOOD AT ALL PERIMETER WALLS
STUD SIZE
X26 = 6"
1/2" HAT CHANNEL
VAPOR RETARDER
EXTERIOR SHEATHING
W.R.B.
SHEATHING PER STRUCTURAL
3 1/2" THERMAL BATT INSULATION (R-13 MIN)
2"X6" WOOD STUDS @16" O.C.
VAPOR RETARDER
5/8" TYPE 'X' GYPSUM WALL BOARD
PLAN
SECTION
5/8" PLYWOOD AT ALL PERIMETER WALLS
STUD SIZE
X36 = 6"
CONTINUOUS 2" POLY ISO
INSULATION (R-7.5 MIN)
AT PARAPET LOCATIONS:
-REPLACE G.W.B. WITH GLASS MAT
SUBSTRATE OF EQUAL SIZE
-RUN S.P.M. ROOFING UP WALL TO T.O.
PARAPET PER PARAPET DETAILS
SINGLE-PLY MEMBRENE ROOFING
(THERMOPLASTIC OLEFIN - 'TPO')
SHEATHING PER
STRUCTURAL
FRAMING PER
STRUCTURAL
6" M
IN
ONE LAYER 5/8" GWB EACH SIDE
ACOUSTIC BATTS
ACOUSTIC SEALANT
CEILING - REF RCP FOR HEIGHT AND TYPE
DEFLECTION HEAD RUNNER TRACK ANCHORED TO
STRUCTURE.
UNDERSIDE OF FLOOR OR ROOF
DECK
ACOUSTIC SEALANT - ONE SIDE
EXTEND ONE LAYER OF 5/8" GWB TO DECK ABOVE
ACOUSTIC BATTS
STEEL STUDS AT 24" O.C.
STUD SIZE
P33 = 3 5/8" P36 = 6"
GA File No. WP 1072
STC 45-49 WITH ACOUSTIC BATTS
HILTI X-U PAF @ 16" O.C. (3/4" EMBED)
WALL HEAD
PLAN
WALL BASE
CEILING - REF RCP FOR HEIGHT AND TYPE
ONE LAYER 5/8" GWB
STEEL STUDS AT 24" O.C.
ACOUSTIC BATTS WHERE TAGGED IN PLAN
ACOUSTIC SEALANT
ACOUSTIC BATTS WHERE TAGGED IN PLAN
DEFLECTION HEAD RUNNER TRACK ANCHORED TO
STRUCTURE.
UNDERSIDE OF FLOOR OR ROOF
DECK
ACOUSTIC SEALANT - ONE SIDE
EXTEND ONE LAYER OF 5/8" GWB TO DECK ABOVE
STUD SIZE
P03 = 3 5/8" P06 = 6"
HILTI X-U PAF @ 16" O.C. (3/4" EMBED)
WALL HEAD
PLAN
WALL BASE
(E) 8" CMU
CEILING - REF RCP FOR HEIGHT AND TYPE
1/2" HAT CLIP
ONE LAYER 5/8" GWB BOARD
ONE LAYER 5/8" GWB BOARD
METAL CLIP
1/2" HAT CLIP
(E) 8" CMU
(E) 8" CMU
1/2" HAT CLIP
SEALANT
VAPOR BARRIER
VAPOR BARRIER
VAPOR BARRIER
CMU SIZE
8= 7-5/8 NOMINAL
WALL HEAD
PLAN
WALL BASE
6" METAL STUDS @16" O.C.
5/8" GLASS MAT SUBSTRATE (BOTH
SIDES)
PLAN
SECTION
STUD SIZE
X46 = 6"
AT PARAPET LOCATIONS:
-REPLACE G.W.B. WITH GLASS MAT
SUBSTRATE OF EQUAL SIZE
-RUN S.P.M. ROOFING UP WALL TO T.O.
PARAPET PER PARAPET DETAILS
S.P.M. ROOFING UP SUBSTRATE
TO UNDERSIDE OF PARAPET
(BOTH SIDES)
W.R.B.
SHEATHING PER STRUCTURAL
METAL STUD @16" O.C.
GLASS MAT SUBSTRATE
PLAN
SECTION
STUD SIZE
X46 = 6"
4MM ALUCOBOND PLUS
ALUMINUM COMPOSITE PANELS
ACM SYSTEM EXTRUSIONS AND
CLIPS
4MM ALUCOBOND PLUS
REVEAL, REFER TO EXTERIOR
ELEVATIONS
4MM ALUCOBOND PLUS
REVEAL, REFER TO EXTERIOR
ELEVATIONS
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:2
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
PARTITION, WALL AND
ROOF ASSEMBLIES
06.27.2025
G2.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
1 1/2" = 1'-0"G2.01
FW1 FURRED OUT WALL
1 1/2" = 1'-0"G2.01
P1 NON-RATED PARTITION TYPE 1
WALL TAG
MODIFIER
MODIFIERS
A = PROVIDE CONTINUOUS ACOUSTIC BATTS
B = PROVIDE ABUSE RESISTANT GWB
C = PROVIDE 5/8" RESILIENT FURRING CHANNELS OVER FRAMING
ON ONE SIDE
L = PROVIDE LEAD LINED GYPSUM BOARD- EXTEND 7'-0" AFF MIN.
SEE PHYSICIST REPORT
O= REMOVE INTERIOR SIDE G.W.B. FROM ASEMBLY
P= PROVIDE 5/8" PLYWOOD SUBSTRATE
T = PROVIDE CEMENTITIOUS BACKER BOARD AT TILE FINISHES
S= SHEAR WALL FRAME PER STRUCTURAL
X= REMOVE INTERIOR SIDE PLYWOOD FROM ASSEMBLY
WALL TYPE
STUD SIZE
A3#X
1 1/2" = 1'-0"G2.01
M1 EXTERIOR C.M.U. CLADDING
1 1/2" = 1'-0"G2.01
W1 NON-RATED SHEAR PARTITION
1 1/2" = 1'-0"G2.01
W2 NON-RATED SHEAR PARTITION
3" = 1'-0"G2.01
X1 X1 EXTERIOR WALL - STUCCO
3" = 1'-0"G2.01
R1 R1 ROOF ASSEMBLY #1
3" = 1'-0"G2.01
F1 FL-1 FLOOR ASSEMBLY
3" = 1'-0"G2.01
X2 X2 EXTERIOR WALL - METAL CLADDING
3" = 1'-0"G2.01
X3 X3- EXTERIOR WALL -AT CANOPY
3" = 1'-0"G2.01
R2 R2 ROOF ASSEMBLY #2
1 1/2" = 1'-0"G2.01
P3 NON-RATED PARTITION TYPE 3
1 1/2" = 1'-0"G2.01
P0 NON-RATED PARTITION WALL TYPE 0
1 1/2" = 1'-0"G2.01
M2 INTERIOR C.M.U. CLADDING
3" = 1'-0"G2.01
X5 X5- MID ROOF PARAPET
3" = 1'-0"G2.01
X4 X4- EXTERIOR WALL -AT AWNING
PROJECT TYPE NOTES
A. NO SUBSTITUTIONS ARE ALLOWED FOR ANY WALL ASSEMBLY
UNLESS SPECIFICALLY ALLOWED BY GYPSUM ASSEMBLY, UL,
INTERTEK, OR OTHER AHJ-APPROVED TESTING AGENCY AND WITH
WRITTEN APPROVAL BY THE ARCHITECT.
B. PARTITION TYPE INDICATIONS ARE INDEPENDENT FROM APPLIED
FINISHES. REFER TO FINISH SCHEDULE AND / OR THE
DESIGNATIONS ON THE PLAN FOR ADDITIONAL INFORMATION
REGARDING APPLIED FINISHES.
C. PARTITION CONSTRUCTION ABOVE AND BELOW INTERRUPTIONS
(DOORS, WINDOWS, ETC.) SHALL MATCH THE ASSEMBLY AND
PLANE OF THE PARTITION IN WHICH THE INTERRUPTION
OCCURRED.
D. THE MINIMUM REQUIREMENTS FOR PARTITIONS ARE AS
INDICATED. ADDITIONAL AND / OR MORE RESTRICTIVE
REQUIREMENTS MAY BE INDICATED ELSEWHERE. SUCH
REQUIREMENTS MAY INCLUDE BUT ARE NOT LIMITED TO:
1. STUD SPACING: USE 24" O.C. MAX STUD SPACING, U.N.O. BY
REFERENCED APPROVAL OR TEST REPORT.
2. WHERE COLD-FORMED METAL FRAMING IS USED, USE STUD
GAUGE INDICATED IN THE GENERAL FRAMING NOTES OR PER
STRUCTURAL. THE GAUGE STATED BY REFERENCED ASSEMBLY
OR TEST REPORT SHALL ALWAYS BE MINIMUM GAUGE.
3. USE STANDARDS OF DEPTH INDICATED BY DRAWINGS. DEPTH
STATED BY REFERENCED APPROVAL OR TEST REPORT IS
MINIMUM DEPTH.
E. INSTALL CEMENTITIOUS BACKER BOARD OR WATER-RESISTANT
GYP. BD. AT THE FOLLOWING LOCATIONS:
1. ALL WALL ENCLOSURES ADJACENT TO JANITOR MOP SINKS.
2. AT WET LOCATIONS, SUCH AS SHOWER STALLS WITH A
SURROUND.
3. WHERE CERAMIC TILE FINISHES ARE INDICATED. (REF. FINISH
SCHEDULE, PLANS, AND / OR INTERIOR ELEVATIONS.)
4. AT OTHER LOCATIONS, AS INDICATED BY THE SPECIFICATIONS
OR PER FINISH SCHEDULE.
F. PROVIDE SOUND ATTENUATING INSULATION TO THE FULL HEIGHT
OF WALL AT ALL TOILET ROOM WALLS AND SLEEPING AREAS
ADJACENT TO ANY TYPE OF SHAFT OR ANOTHER SLEEPING AREA.
G. ALL PENETRATIONS IN S.T.C.-RATED ASSEMBLIES (PIPING,
ELECTRICAL DEVICES, RECESSED ITEMS, MECHANICAL ITEMS ETC.)
SHALL BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO
MAINTAIN THE S.T.C. RATING.
H. S.T.C.-RATED PARTITIONS SHALL NOT HAVE WALL PENETRATIONS
LOCATED BACK TO BACK OR IN THE SAME STUD CAVITY.
I. REFERENCE DETAILS FOR BACKING PLATE, WALL INTERSECTION,
AND HEAD CONDITIONS.
J. AT RATED WALLS ABOVE CEILING, PROVIDE STENCILED LETTERING
IN CONTRASTING COLORS, MIN. 3" TALL WITH MIN. 3/8" STROKE, TO
READ "FIRE AND / OR SMOKE BARRIER. PROTECT ALL OPENINGS"
OR EQUIVALENT. REFERENCE I.B.C. SECTION 703.7.
GENERAL NOTES: STEEL FRAMING
1. ALL ASSEMBLIES ARE FULL HEIGHT, U.N.O.
2. ALL NON-LOADBEARING METAL WALL FRAMING SHALL BE 20ga
(33Mils) OR 25ga STUDS, U.N.O.
3. PROVIDE 20ga METAL STUD WALL FRAMING AT THE FOLLOWING
LOCATIONS
A. DOUBLE STUD JAMB ASSEMBLIES AT OPENINGS.
B. FIRST STUD IN THE PARTITION BEYOND THE DOUBLE STUD JAMB
ASSEMBLY. LOCATE STUD 6" FROM THE DOUBLE STUD
ASSEMBLY.
C. STUDS INSTALLED FOR OPENING HEADS BETWEEN DOUBLE
STUD JAMB ASSEMBLIES.
D. STUDS ON WHICH CEMENTITIOUS BACKER BOARD IS INSTALLED
FOR WET AREAS.
E. STUDS ON WHICH WALL-MOUNTED EQUIPMENT, INCLUDING
OWNER-FURNISHED EQUIPMENT, IS TO BE INSTALLED.
F. STUD INFILL AND SILL TRACK BELOW WINDOW OPENINGS
G. WALLS THAT EXCEED THE FOLLOWING HEIGHT LIMITATIONS:
A. 2-1/2" METAL STUDS: 10' - 9"
B. 3-5/8" METAL STUDS: 14' - 0"
C. 4" METAL STUDS: 15' - 0"
D. 6" - 8" METAL STUDS: 20' - 0"
ASSEMBLIES
GA WP 1072 (Generic) One layer 5/8" type X gypsum wallboard or gypsum veneer applied parallel or at right angles to each side of 3-5/8" steel studs 24" O.C.. with 1" type S drywall screws 8" O.C.. at vertical joints and 12" O.C.. at floor and ceiling runners and intermediate studs.
Joints staggered 24" on each side and on opposite sides. Sound tested with 3 1/2" glass fiber friction fit in stud space.
PROVIDE TYPE A1 OR A2 BACKING PLATES:
• AT SMALL ITEMS REQUIRING BACKING SOLELY FOR ATTACHMENT: DOOR STOPS, BUMPER RAILS, CRASH RAILS, SURFACE
MOUNTED LIGHTS, ETC. (SELECT TYPE A1 OR A2 BASED ON DIMENSIONS OF ITEM TO BE MOUNTED.)
• AT WALL-MOUNTED EQUIPMENT AS INDICATED ON THE DRAWINGS
• AT SMALL ITEMS (SUCH AS TOILET ACCESSORIES, MIRRORS, COAT HOOKS, ETC.) WHICH WEIGH, OR SUPPORT WEIGHTS, OF LESS THAN 50 POUNDS TOTAL. (SELECT TYPE A1 OR A2 BASED ON DIMENSIONS OF ITEM TO BE MOUNTED.)
PROVIDE TYPE B1 BACKING PLATE:
• AT ALL BASE CABINETS
• AT ALL FULL HEIGHT CABINETS
• AT WALL-MOUNTED ADJUSTABLE SHELVING
PROVIDE TYPE B2 BACKING PLATE:
• AT ALL UPPER WALL-HUNG CABINETS WITH HEIGHT LESS THAN 30"
• AT ALL UPPER WALL-HUNG CABINETS WITH NO MORE THAN ONE INTERMEDIATE SHELF
• AT ALL WALL-MOUNTED HANDRAILS
• AT ALL WALL-MOUNTED GRAB BARS
• AT WALL-MOUNTED EQUIP WHICH WEIGHS - OR SUPPORTS WEIGHT, WHEN FULLY LOADED - LESS THAN 200 POUNDS
TOTAL AND WHERE THAT WEIGHT IS DISTRIBUTED SO THAT THE PARTITION SUPPORTS A MAXIMUM OF 100 POUNDS PER
LINEAR FOOT
PROVIDE TYPE C1 BACKING PLATE:
• AT ALL UPPER WALL-HUNG CABINETS WITH HEIGHT OF 30" OR GREATER
• AT ALL UPPER WALL-HUNG CABINETS WITH MORE THAN ONE INTERMEDIATE SHELF
• AT WALL-MOUNTED EQUIP WHICH WEIGHS - OR SUPPORTS WEIGHT, WHEN FULLY LOADED - LESS THAN 400 POUNDS
TOTAL AND WHERE THAT WEIGHT IS DISTRIBUTED SO THAT THE PARTITION SUPPORTS A MAXIMUM OF 200 POUNDS PER
LINEAR FOOT
PROVIDE TYPE C2 BACKING PLATE:
• AT WALL-MOUNTED EQUIP WHICH WEIGHS - OR SUPPORTS WEIGHT, WHEN FULLY LOADED - MORE THAN 400 POUNDS
TOTAL AND WHERE THAT WEIGHT IS DISTRIBUTED SO THAT THE PARTITION SUPPORTS A MAXIMUM OF 200 POUNDS PER
LINEAR FOOT
PROVIDE TYPE D BACKING PLATE:
• PROVIDE BACKING PLATES AS INDICATED ON THE DRAWINGS OR, WHERE NOT INDICATED, ACCORDING TO THE
FOLLOWING SCHEDULE:
• COORDINATE LOCATION, LENGTH, HEIGHT, AND NUMBER OF BACKING PLATES REQUIRED WITH ITEM TO BE MOUNTED.
• FOR METHOD OF ATTACHMENT OF ITEM TO BE MOUNTED, REFER TO THE APPLICABLE DETAIL OR, IF NOT DETAILED, THE
INSTRUCTIONS PROVIDED BY THE MANUFACTURER.
BACKING PLATE NOTES
I FOUR-WAY INTERSECTION
PRIORITY PARTITION CHANGES DIRECTION
G FOUR-WAY INTERSECTION
PRIORITY PARTITION CONTINUES WITHOUT INTERRUPTION
E THREE-WAY INTERSECTION
PRIORITY PARTITION CHANGES DIRECTION
C THREE WAY INTERSECTION
PRIORITY PARTITION CONTINUES WITHOUT INTERRUPTION
A TYPICAL RATED CORNERB TYPICAL RATED CORNERD THREE-WAY INTERSECTION
PRIORITY PARTITION CONTINUES WITHOUT INTERRUPTION
F THREE-WAY INTERSECTION
EXAMPLE OF THREE DIFFERENT PARTITION TYPES
H FOUR-WAY INTERSECTION
PRIORITY PARTITION CONTINUES WITHOUT INTERRUPTION
NON-RATED PARTITION
TYPE X GYPSUM BOARD PRIORITY
PARTITION CONTINUES THROUGH
INTERSECTION WITHOUT INTERRUPTION
CENTERLINE OF FIRE-RATED PARTITION
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
NON-RATED PARTITION
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
CONTINUE PRIORITY PARTITION GYPSUM
BOARD INTO PARTITION CORNER
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
FIRST PRIORITY
THIRD PRIORITY
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE
AND FRAMING DETAILS
SECOND PRIORITY
TYPE 'X' GYPSUM BOARD PRIORITY
PARTITION CONTINUES THROUGH
INTERSECTION WITHOUT INTERRUPTION
CENTERLINE OF FIRE-RATED PARTITION
NON-RATED PARTITION
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
CENTERLINE OF FIRE-RATED PARTITION
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
NOTES:
THE PRIORITY OF THE PARTITIONS IS DETERMINED AS FOLLOWS:
1. FIRE-RATED PARTITIONS HAVE PRIORITY OVER NON-RATED PARTITIONS
2. PARTITIONS WITH GREATER FIRE-RATING HAVE PRIORITY OVER THOSE WITH LESSER RATING.
3. SMOKE SEALED PARTITIONS HAVE PRIORITY OVER NON-SMOKE SEALED PARTITIONS.
4. ACOUSTICAL AND LEAD-LINED PARTITIONS HAVE PRIORITY OVER NON-ACOUSTICAL AND
LEAD-LINED PARTITIONS.
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
CENTERLINE OF FIRE-RATED PARTITION
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
NON-RATED PARTITION
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
NON-RATED PARTITION OR LESSER-RATED
PARTITION
TYPE X GYPSUM BOARD PRIORITY PARTITION
CONTINUES THROUGH INTERSECTION
WITHOUT INTERRUPTION
CENTERLINE OF FIRE-RATED PARTITION
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
NON-RATED PARTITION OR LESSER-RATED
PARTITION
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
ATTACHED GYPSUM BOARD TO EACH STUD,
TYP.
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
CENTERLINE OF FIRE-RATED PARTITION
CENTERLINE OF FIRE-RATED PARTITION
TYPE X GYPSUM BOARD PRIORITY
PARTITION CONTINUES THROUGH
INTERSECTION WITHOUT INTERRUPTION
ATTACHED GYPSUM BOARD TO EACH STUD
METAL STUDS OF GAUGE INDICATED AS
MINIMUM (UNO) BY PARTITION TYPE AND
FRAMING DETAILS
CENTERLINE OF FIRE-RATED PARTITION
ALIGN EXPOSED FACES WHERE TWO
PARTITIONS OF DIFFERENT THICKNESS
JOIN, TYPICAL
CONTINUE TYPE X GYPSUM BOARD INTO
PARTITION CORNER
NON-RATED OR LESSER-RATED PARTITION
TYPE A1:
25 GAUGE x6" HIGH
CONTINUOUS METAL
PLATE
TYPE A2:
25 GAUGE x8" HIGH
CONTINUOUS METAL
PLATE
TYPICAL METAL STUD
FRAMING - REFERENCE
PARTITION TYPES AND SPECS
FOR STUD DEPTH AND GAUGE
THREE 3/4" #10 LOW PROFILE PAN
HEAD SHEET METAL SCREWS AT
EACH STUD, TYPICAL
MAX
1/8"
3"
VERTICAL C-STUDS FLANGES TO
BE CONTINUOUS
TYPE B1:
6" 600T150-54 RUNNER TRACK (OR
EQUAL) NOTCHED AROUND STUDS
AND EXTENDING 3" EACH SIDE
BEYOND ONE PAIR OF STUDS
SPACED 16" O.C. MAX
TYPE B2:
SAME AS TYPE B1 EXCEPT
COVERING TWO OR MORE PAIRS OF
STUDS
THREE 3/4" #10 LOW PROFILE
PAN HEAD SHEET METAL SCREW
AT EACH STUD
TYPE C1:
4" 400T150-54 RUNNER TRACK (OR
EQUAL) WELDED TO CONTINUOUS 14
GAUGE BY 6" METAL PLATE AND
EXTENDING OVER 3 STUDS SPACED
AT16" O.C. MINIMUM
TYPE C2:
SAME AS TYPE C1
EXCEPT EXTENDING OVER 4
STUDS MINIMUM
WELD RUNNER TRACK TO CONT
PLATE TOP & BOTTOM
WELD PLATE TO VERTICAL STUD(S)
TOP AND BOTTOM
1/4" MAX. GAP BETWEEN RUNNER
TRACK AND VERT. STUD C- STUD
EXTENDING TO STRUCTURE ABOVE AND
AT PARTITION UP TO 12'-0" HIGH: WELD
PAIR OF C-STUDS FULL HGT.
FOUR 3/4" #10 LOW PROFILE
PAN HEAD SHEET METAL SCREW
AT EACH STUD, TYPICAL AT 6"
O.C. MAX.
" U
.N .O
2-4(1/8")
1/4" THICK BENT
STEEL PLATE
BENT PLATE TO
VERTICAL STUDS
WELDED PAIR OF C-STUDS
EXTENDING TO STRUCTURE
ABOVE
(1/8") 2-4
BENT PLATE TO
VERTICAL STUDS
GYPSUM BOARD (MULTIPLE
LAYERS AS REQ'D FOR RATING)
METAL STUD
METAL STUD SLOTTED DEFLECTION TRACK
(UP TO 3" MOVEMENT)
CLARK/DIETRICH BLAZEFRAME (DSL 2) OR
EQUIVALENT
FASTENER PER MANUF.
RECOMMENDATIONS
FASTENER PER MANUF.
RECOMMENDATIONS
CONCRETE
RE: STRUCTURAL
EXPANSIVE INTUMESCENT FIRE
BARRIER PER MANUF.
GYPSUM BOARD (MULTIPLE LAYERS AS
REQ'D FOR RATING)
METAL STUD
METAL STUD SLOTTED DEFLECTION TRACK (UP
TO 3" MOVEMENT)
CLARK/DIETRICH BLAZEFRAME (DSL 2) OR
EQUIVALENT
FASTENER PER MANUF.
RECOMMENDATIONS
CONCRETE
RE: STRUCTURAL
EXPANSIVE INTUMESCENT FIRE
BARRIER PER MANUF.
WALL PERPENDICULAR TO DECK
WALL PARALLEL TO DECK
GYPSUM WALL BOARD PER
ASSEMBLY
METAL STUD
METAL STUD SLOTTED DEFLECTION TRACK
(UP TO 3" MOVEMENT)
CLARK/DIETRICH SLP-TRK OR EQUIVALENT
FASTENER PER MANUF.
RECOMMENDATIONS
CONCRETE
RE: STRUCTURAL
SEALANT (AS REQUIRED FOR
WALL PARTITION TYPE)
GYPSUM WALL BOARD PER
WALL ASSEMBLY
METAL STUD
METAL STUD SLOTTED DEFLECTION TRACK
(UP TO 3" MOVEMENT)
CLARK/DIETRICH SLP-TRK OR EQUIVALENT
FASTENER PER MANUF.
RECOMMENDATIONS
CONCRETE
RE: STRUCTURAL
SEALANT (AS REQUIRED FOR
WALL PARTITION TYPE)
WALL PERPENDICULAR TO DECK
WALL PARALLEL TO DECK
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:2
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
PARTITION DETAILS
06.27.2025
G2.02
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
1 1/2" = 1'-0"G2.02
7 PARTITION FIRE RATED PRIORITY CONNECTION DETAILS
1 1/2" = 1'-0"G2.02
1 BACKING PLATE TYPE A
1 1/2" = 1'-0"G2.02
2 BACKING PLATE TYPE B
1 1/2" = 1'-0"G2.02
3 BACKING PLATE TYPE C
1 1/2" = 1'-0"G2.02
4 BACKING PLATE TYPE D
1 County Comments 08/19/2025
N.T.S.G2.02
5 FIRE RATED METAL WALL TOP DEFLECTION TRACK @ CONC. SLAB
N.T.S.G2.02
6 METAL STUD WALL TOP DEFLECTION TRACK @ CONC. SLAB
BB
CC
2 3 4
VERIFY EXISTING
TRANSFORMER
LOCATION
53.52.3 2.8
AA
A.6A.6
CONTRACTOR RESPONSIBLE FOR
SITE DEMO IN PREPARATION FOR
ADDITION
D.17
AREA OF WORK
D
D
0 4.63.90.9 1.5
1/2
ZZZZ
THIS AREA REMOVE
S.P.M. ONLY
4'
- 0
4' - 6"
4' - 0"
DEMO ROOF AND PREP TOP OF
WALL 3 HOUR -RATED PARAPET
DEMO ROOF IN THIS AREA
4'
- 0
SALVAGE FASCIA FOR
REINSTALLATION
SALVAGE FASCIA FOR
REINSTALLATION
D.32
PREPARE ROOF EDGE FOR NEW
PARAPET TO MATCH EXISTING
EXISTING PARTITION TO BE REMOVED
EXISTING PARTITION TO REMAIN
LEGEND
DEMO GUTTER AND PREPARE TOP OF WALL
FOR NEW PARAPET
DEMO AWNING, PARAPET, ROOF AS NEEDED
TO PREPARE FOR NEW AWNING
DEMO EXISTING ROOF
AREA OF SITE TO PREPARE FON ADDITION
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:2
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
DEMO SITE PLAN
06.27.2025
D0.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
1" = 10'-0"D0.01
1 DEMO SITE PLAN
GENERAL NOTES: DEMOLITION
1. CONTRACTOR SHALL VERIFY LIMITS OF DEMOLITION WORK
2. THIS DRAWING IDENTIFIES ONLY MAJOR WORK FOR DEMOLITION
AND REMOVAL. ALL AREAS OF DEMOLITION SHALL BE CLEARED OF
ALL ITEMS MAJOR AND MINOR TO RECEIVE INSTALLATION OF NEW
CONSTRUCTION AND FINISHES
3. REF REFLECTED CEILING PLANS FOR WORK THAT MAY IMPACT
DEMOLITION
4. REF STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR
ADDITIONAL DEMOLITION INFORMATION.
5. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER
SIZES AND CONDITIONS PRIOR TO COMMENCING WORK. ALL
DIMENSIONS OF EXISTING CONSTRUCTION ARE INTENDED AS
GUIDELINES ONLY AND MUST BE VERIFIED. REPORT ANY
DISCREPANCIES BETWEEN DIMENSIONS FOUND IN FIELD AND
DIMENSIONS ON DRAWINGS TO ARCHITECT
6. LOCATE ALL WIRES, PIPES, UTILITIES, STRUCTURAL MEMBERS, ETC.
PRIOR TO ANY DEMOLITION. CUTTING OF ANY ITEM WHICH IS NOT
PART OF THIS PROJECT SHALL BE REPAIRED BY THE CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER, INCLUDING ANY TESTING
OR SPECIAL OBSERVATION TO CORRECT THE PROBLEM
7. PATCH AND PAINT WALLS, FLOORS, AND SUBFLOOR TO MATCH
EXISTING WHERE WORK HAS DISTURBED EXISTING CONDITIONS.
8. ALL EXISTING FINISHES ARE TO BE PROTECTED FROM DAMAGE.
DAMAGED AREAS SHALL BE REPAIRED AT NO COST TO THE OWNER.
KEYNOTES
D.17 REMOVE EXISTING CONCRETE SLAB AS REQUIRED. SALVAGE
TRANSFORMER FOR REINSTALATION. REF ELECTRICAL
D.32 DEMOLISH MECHANICAL UNIT AND DUCT, REF MECHANICAL
B
C
2 3 4
D.1
D.1D.1
D.1
D.1
D.1
D.1
D.1
D.1
D.2
D.2
D.2
D.1
D.1
D.2D.2
D.1
D.3 D.3
D.1
D.4
D.4
D.4
D.4
D.11
D.11
D.11
D.6
D.4D.4
53.52.3 2.8
A
A.6
D.4
D.5
D.5
D.13
D.23
D.5
D.4
D.5
D.1
D.5 D.5
D.5
D.12
D.12
D.6
D.5
D.6
D.5
D.6
D.5
D.4 D.4
D.4
D
0 0.9 1.5
D.17
D.24
D.25
D.26
D.26
D.26
D.26
D.26
D.26
D.26
D.26
D.26
D.26
D.26
D.30
D.26 D.26 D.26
D.30
D.30
D.31
D.31 D.32
D.33 D.33
EXISTING PARTITION TO BE REMOVED
EXISTING PARTITION TO REMAIN
LEGEND
DEMO GUTTER AND PREPARE TOP OF WALL
FOR NEW PARAPET
DEMO AWNING, PARAPET, ROOF AS NEEDED
TO PREPARE FOR NEW AWNING
DEMO EXISTING ROOF
AREA OF SITE TO PREPARE FON ADDITION
INFIRMARY
PRIVATE
ROOM
TOILET /
SHOWER
ROOM
BREAK
ROOM
LAB
CENTER
OFFICE
HALLWAY
SHARED
DENTAL
OFFICE
OFFICE /
EXAM ROOM
OPERATORY
HALLWAY
DENTIST
OFFICE
LAB
OFFICE
EXAM ROOM
EXAM ROOM
HALLWAY
STORAGE /
JANITOR
CLOSET
YOUTH
TOILET
YOUTH ADA
TOILET
NURSE
SUPERVISOR
/ FUTURE
EXAM
SHARED
MED OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
(FUTURE)
PSYCH
OFFICE
PSYCH
OFFICE
STAFF TOILET
STAFF TOILET
STAFF ENTRY
/ LOCKERS
MEETING /
BREAK
ROOM
PHARMACY
OFFICE
MEDICATION
EQUIP/MEDS
STORAGE
YOUTH
WAITING
CLINIC
ENTRY
COPY/FILES
NURSE
STATIONS
AREA OF WORK
D
3' - 0"3' - 0"
B
C
2 3 4
D.9
53.52.3 2.8
A
A.6
D.8
D.9
D.8
D.9 D.9
D.9 D.9
D.9
D.9
D.9
D.15
D.15D.15D.15D.15D.15
D.15 D.15
D.15
D.15
D.15 D.15
D.15
D.15D.15
D.15D.15D.15
D.15
D.7
D.7
D.7
D.7
D.7
D.7
D.8
D.8
D.9
D.7
D.8
D
0 4.63.90.9 1.5 6
D.25
D.9
D.27
D.28
D.28
D.28
D.28D.28
D.15
D.15
D.15
D.29
D.29
D.29
INFIRMARY
PRIVATE
ROOM
TOILET /
SHOWER
ROOM
BREAK
ROOM
LAB
CENTER
OFFICE
HALLWAY
SHARED
DENTAL
OFFICE
OFFICE /
EXAM ROOM
OPERATORY
HALLWAY
DENTIST
OFFICE
LAB
OFFICE
EXAM ROOM
EXAM ROOM
HALLWAY
STORAGE /
JANITOR
CLOSET
YOUTH
TOILET
YOUTH ADA
TOILET
NURSE
SUPERVISOR
/ FUTURE
EXAM
SHARED
MED OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
(FUTURE)
PSYCH
OFFICE
PSYCH
OFFICE
STAFF TOILET
STAFF TOILET
STAFF ENTRY
/ LOCKERS
MEETING /
BREAK
ROOM
PHARMACY
OFFICE
MEDICATION
EQUIP/MEDS
STORAGE
YOUTH
WAITING
CLINIC
ENTRY
118 COPY/FILES
NURSE
STATIONS
AREA OF WORK
D
0 4.6 6
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:3
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
DEMO PLAN- LEVEL 1
06.27.2025
D1.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
KEYNOTES
D.1 REMOVE DOOR, FRAME, AND HARDWARE.
D.2 SALVAGE DOOR, FRAME, AND HARDWARE, REINSTALL TO
SWING OUT OF ROOM.
D.3 REMOVE ALL TOILET ROOM FIXTURES, ACCESSORIES, PIPING
AND APPURTENANCES.
D.4 REMOVE CASEWORK / CABINETS, OWNER TO DECIDE ON
REUSE OR REPURPOSE
D.5 REMOVE ALL FURNITURE, EQUIPMENT, AND LOOSE ITEMS.
SALVAGE TO OWNER.
D.6 DEMOLISH FLOORING, PREP SLAB FOR NEW FLOORING.
D.7 REMOVE SECURITY CAMERA, SALVAGE FOR REUSE.
D.8 DEMOLISH GYPSUM CEILING AND LIGHT FIXTURES.
D.9 DEMOLISH CEILING, CEILING GRID, SMOKE DETECTORS AND
LIGHT FIXTURES. PROTECT SPRINKLER HEADS
D.11 CUT OPENING IN CMU WALL PER PLAN.
D.12 REMOVE DOOR, FRAME, AND HARDWARE. SALVAGE FOR
INSTALLATION.
D.13 DEMOLISH EXISTING EXTERIOR WALL, STRUCTURAL COLUMNS
& BEAMS TO REMAIN.
D.15 EXISTING CEILING AND ACCESORIES TO REMAIN WITH
EXCEPTIONS NOTES. PROTECT ALL FROM DAMAGE
D.17 REMOVE EXISTING CONCRETE SLAB AS REQUIRED. SALVAGE
TRANSFORMER FOR REINSTALATION. REF ELECTRICAL
D.23 NO CONSTRUCTION ACCESS THROUGH COURTYARD - INSTALL
PLYWOOD PROTECTION OVER ALL COURTYARDS FACING
OPENINGS PRIOR TO START OF WORK.
D.24 REMOVE EXISTING CONCRETE STEP AND WALKWAY.
D.25 REMOVE WINDOW, FRAME, AND PREPARE OPENING TO BE
CLOSED TO MATCHED EXISTING
D.26 REMOVE WINDOW AND FRAME
D.27 EXISTING SECURITY DOME TO REMAIN
D.28 EXISTING OPEN TO STRUCTURE TO REMAIN
D.29 DEMOLISH LIGHT FIXTURES
D.30 REMOVE EXISTING BUILDING FOUNDATION AS REQUIRED FOR
NEW GRADE BEAM
D.31 DEMOLISH DOWNSPOUT
D.32 DEMOLISH MECHANICAL UNIT AND DUCT, REF MECHANICAL
D.33 CUT OPENING IN CMU WALL PER PLAN FOR SPANDREL
WINDOW, MATCH HEIGHT OF EXISTING ADJACENT WINDOW.
1/8" = 1'-0"D1.01
1 DEMO - LEVEL 1
1/8" = 1'-0"D1.01
3 DEMO - RCP LEVEL 1
1 County Comments 08/19/2025
PROJECT TYPE NOTES
1. DEMOLITION NOTES ARE GENERAL IN NATURE AND IT SHALL BE
USED IN CONJUNCTION WITH FULL CONSTRUCTION DOCUMENTS
FOR PROPER COORDINATION.
2. CONTRACTOR TO VERIFY DIMENSIONS, MEMBER SIZES, AND
LIMITS OF DEMOLITION WORK PER PHASE PRIOR TO
COMMENCEMENT OF WORK.
3. DIMENSIONS OF EXISTING CONSTRUCTION INDICATE DESIGN
INTENT. CONTRACTOR TO NOTIFY ARCHITECT OF DISCREPANCIES
BETWEEN FIELD CONDITIONS AND DRAWINGS TO ARCHITECT.
4. PRIOR TO DEMOLITION ACTIVITIES, CONTRACTOR SHALL
SCHEDULE A WALKTHROUGH WITH OWNER FOR REVIEW OF ITEMS
TO BE REMOVED.
5. CONTRACTOR TO COORDINATE ITEMS TO BE SALVAGED AND
STORED WITH OWNER.
6. OWNER IS RESPONSIBLE FOR REMOVING FURNITURE AND
EQUIPMENT TO BE STORED.
7. ALL AREAS OF DEMOLITION SHALL BE CLEARED OF ITEMS MAJOR
AND MINOR TO RECEIVE INSTALLATION OF NEW CONSTRUCTION
AND FINISHES.
8. DAMAGE TO ANY ITEM WHICH IS NOT PART OF THIS PROJECT
SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL
COST TO THE OWNER.
9. COORDINATE DEMOLITION SCHEDULE AND SHUTDOWNS WITH
OWNER PRIOR TO COMMENCEMENT OF WORK.
10. REMOVAL OF HAZARDOUS WASTE PRIOR TO DEMOLITION
ACTIVITY TO BE BY OWNER UNDER SEPARATE CONTRACT.
11. IN AREAS OF DEMOLITION WORK REMOVE ALL BUILDING SYSTEMS
NOT REUSED, INCLUDING ASSOCIATED MATERIALS AND
ACCESSORIES.
12. MAINTAIN FIRE OR ACOUSTICALLY RATED ASSEMBLIES - PATCH
AND REPAIR AS NEEDED.
13. LOCATE AND MAINTAIN TEMPORARY, LARGE CAPACITY FIRE
EXTINGUISHERS FOR DURATION OF CONSTRUCTION.
EXTINGUISHER TYPE TO BE A-B-C OR AS REQUIRED BY LOCAL FIRE
MARSHAL.
14. REMOVE DEMOLITION WASTE FROM PROJECT SITE DAILY, AND
DISPOSE PER APPLICABLE CODES. IF REQUIRED BY LOCAL CODES,
CONTRACTOR SHALL RECYCLE DEMOLITION DEBRIS IN
ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION.
15. PROTECT ALL FINISHES TO REMAIN FROM DAMAGE. DAMAGED
AREAS SHALL BE REPAIRED AT NO COST TO THE OWNER.
16. PATCH AND PAINT WALLS, FLOORS, AND SUBFLOOR TO MATCH
EXISTING WHERE WORK HAS DISTURBED EXISTING CONDITIONS.
17. WHERE DOOR OPENINGS ARE FILLED, REMOVE FRAME AND
PATCH WALL TO MATCH ADJACENT SURFACES, U.N.O. ALIGN NEW
FINISH FACE WITH ADJACENT, U.N.O.
SECURITY FENCE
PROPERTY LINE
SETBACK
A4.012
A4.01 4
VERIFY EXISTING
TRANSFORMER
LOCATION
A4.01
61' - 6"
3"
A
A1.01
6 EXISTING SPACES9 EXISTING SPACES
EXISTING PAVED AREA
NEW LOCATION FOR
TRANSFORMER AND
PAD
AREA OF WORK
AREA OF WORK
NOTES:
1. START STRIPES IN EACH CORNER
2. ALL STRIPES TO BE 4" WIDE
3. ALL STRIPES TO BE WHITE
4. REPAINT ALL PARKING STALLS AND
LOADING AREAS
4'
- 0
6 7
A2.02
Sim
A2.02
Sim
EXISTING
MECHANICAL
EQUIPMENT
FDC
61' - 6"
DOWNSPOUT TO TIE INTO
EXISTING STORMWATER LINES
THROUGH CAST IRON BOOT. TYP.
VERIFY BOOT IN SPEC.
LINE OF CANOPY (OVERHEAD)
3"
17' - 10" 22' - 9"
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
(E) SIDEWALKNEW F.O. BUILDING
NEW SIDEWALK PROVIDE CJ'S AT
5'-0" INCREMENTS
AL
IG
N
NOTES:
1. START STRIPES IN EACH CORNER
2. ALL STRIPES TO BE 4" WIDE
3. ALL STRIPES TO BE WHITE
4. REPAINT ALL PARKING STALLS AND
LOADING AREAS
ALIGN W TOP OF CURB TO
MATCH EXISTING CURB HEIGHT
EQ EQ EQ EQ
20' - 4"
0"
LINE OF CANOPY
(OVERHEAD)
TYLER P CARLSON
E
PORTLAND, OREGON
R
S T
TA
G R E
I
TES
E
FO OR
N
OG
CDE RA
TE
TC
H I
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
KJ
O
S
AR
C H
IT
EC
TS
PY
R
IG
H
T
SW
S ix th
A ve nu e, S ui te
Po rtl an d, O R
Ph on e:
/2
-4
6/
/2
3:
:4
PM
C :\U se rs
\w ills lo m an \D oc um en ts
\R ev it
\M ac La re n
- 2
_w ills lo m an
.rv t
ARCHITECTURAL SITE
PLAN
06.27.2025
A1.01
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
25015
M ac
L A
R E
N
IN
F
IR
M A
R Y
P
H A
R M
A C
Y R
E N
O V
A T
IO
N
N P
A C
IF
IC
H W
Y . W
O O
D B
U R
N , O
R
O R
EG
O
N Y
O U
TH
A
U
TH
O R
IT
Y
KEYNOTES
GENERAL NOTES
1. REF. ELECTRICAL, MECHANICAL, PLUMBING FOR ADDITIONAL WORK
NOT INDICATED ON THIS DRAWING.
2. CONTRACTOR IS REQUIRED TO PROVIDE UTILITY AND DRAINAGE
CO…