S-DASOBO-00016020_Addendum-1.pdf

PDF 14 MB Posted

Attached to
MacLaren Youth Correctional Facility Infirmary & Pharmacy Renovation
Solicitation number
S-DASOBO-00016020
Issued by
Oregon

About this file

Solicitation Addendum Summary

This is Solicitation Addendum #001 for Invitation to Bid S-DASOBO-00016020, issued by the Department of Administrative Services (DAS) for the Oregon Youth Authority's MacLaren Youth Correctional Facility Infirmary & Pharmacy Renovation project located in Woodburn, Oregon. The addendum modifies the original bid document and must be acknowledged with a required signature prior to bid closing. The revised bid closing deadline is August 19, 2026, at 2:00 PM (extended from August 12, 2026). Requests for clarification, change requests, and protests regarding addendum provisions must be submitted to DAS by 5:00 PM Pacific time on Wednesday, August 12, 2026. The addendum includes substantial technical and drawing modifications affecting multiple sections of the specifications and construction documents, including Fluid-Applied Waterproofing (Section 07 14 00), Thermoplastic Membrane Roofing (Section 07 54 00), and Door Hardware (Section 08 71 00), along with revised architectural drawings and additional reference documents including civil plans, utility maps, and clinic plans.

The addendum constitutes a material change to the bid and is a mandatory acknowledgment document. The renovation project encompasses approximately 11,083 total square feet, including 9,052 square feet of existing infirmary space, 2,985 square feet of renovation area, and 1,865 square feet of addition space. The facility is classified as Occupancy Type B construction with Type V-B construction type, fully sprinklered and equipped with a fire alarm system. The project includes expansion of medical laboratory, security station, medical rooms, supply areas, receiving/storage, four patient rooms, shared day room, new nurse station, two supervisor offices, and meeting room. Detailed technical specifications and hardware schedules are provided for all construction components, with door hardware groups specified for multiple doors throughout the facility, including specialized security hardware such as anti-ligature locks, delayed egress magnetic locks, and electric strikes.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INVITATION TO BID

S-DASOBO-00016020

SOLICITATION ADDENDUM #001

MacLaren Youth Correctional Facility Infirmary & Pharmacy Renovation, ADDENDUM #001

This Solicitation Addendum modifies the Bid Document(s) for Work only to the extent indicated herein. All other areas not specifically mentioned or affected by this Solicitation Addendum shall remain in full force. This Solicitation Addendum shall be added as a part of the Original Bidding Document.

This Solicitation Addendum must be acknowledged by providing the required signature prior to Bid Closing. Failure to do so may result in rejection of Bid.

Requests for clarification, requests for change, and protests of Solicitation Addendum provisions addressed in this Solicitation Addendum must be received by DAS by 5:00 P.M. (Pacific time) on Wednesday, August 12, 2026, or they will not be considered. DAS will not consider requests or protests of matters not added to or modified by this Solicitation Addendum.

New language is indicated by bold print and underline, deleted language is indicated by brackets [ ].

1 Addition

ITB, Table of Contents (Page 2) is modified as follows:

Attachment E – Reference Documents

• MYCF Geer – Civil

• MacLaren Utility Maps Full Size

• Geer Intake & Processing Clinic Plans

2 Modification ITB, Section A.3 (Page 3) is modified as follows:

Deadline for Bid Submittal (“Closing”) | August [12] 19, 2026 at 2:00 PM

3 Modification ITB Attachment B – Technical Specifications, Section 07 14 00 is deleted in its entirety and replaced with Section 07 14 00 dated August 5, 2026 attached to this Addendum.

4 Modification ITB Attachment B – Technical Specifications, Section 07 54 00 is deleted in its entirety and replaced with Section 07 54 00 dated August 5, 2026 attached to this Addendum.

5 Modification ITB Attachment B – Technical Specifications, Section 08 71 00 is deleted in its entirety and replaced with Section 08 71 00 dated August 4, 2026 attached to this Addendum.

6 Modification ITB Attachment C – Drawings, Sheet G1.01 is deleted in its entirety and replaced with Drawing Sheet G1.01 dated 08/03/2026 attached to this Addendum.

7 Modification

ITB Attachment C – Drawings, Sheet A2.11 is deleted in its entirety and replaced with Drawing Sheet A2.11 dated 08/03/2026 attached to this Addendum.

INVITATION TO BID

S-DASOBO-00016020

SOLICITATION ADDENDUM #001

MacLaren Youth Correctional Facility Infirmary & Pharmacy Renovation, ADDENDUM #001

8 Modification ITB Attachment C – Drawings, Sheet A8.01 is deleted in its entirety and replaced with Drawing Sheet A8.01 dated 08/03/2026 attached to this Addendum.

9 Modification ITB Attachment C – Drawings, Sheet S2.01 is deleted in its entirety and replaced with Drawing Sheet S2.01 dated 02/01/2024 attached to this Addendum.

10 Modification ITB Attachment C – Drawings, Sheet E0.02 is deleted in its entirety and replaced with Drawing Sheet E0.02 dated 08/05/2026 attached to this Addendum.

12 Addition

ADD new MYCF Geer-Civil document to Attachment E, attached to this Addendum 1.

12 Addition

ADD new MacLaren Utility Maps Full Size document to Attachment E, attached to this Addendum 1.

13 Addition

ADD new Geer Intake & Processing Clinic Plans document to Attachment E, attached to this Addendum 1.

This Solicitation Addendum constitutes a MATERIAL CHANGE to the bid; and it MUST BE SIGNED AND RETURNED PRIOR TO THE BID CLOSING DATE AND TIME. ITS RECEIPT MUST ALSO BE ACKNOWLEDGED BY INSERTING ITS NUMBER ON THE APPROPRIATE BLANK LINES IN SECTION H OF THE BID DOCUMENT.

Signature: ___________________________________________________ Date: ____________________

Bidder Name: __________________________________________________________________________ (Please Print)

Attachments:

• ITB Attachment B – Technical Specifications, Section 07 14 00, dated August 5, 2026

• ITB Attachment B – Technical Specifications, Section 07 54 00, dated August 5, 2026

• ITB Attachment B – Technical Specifications, Section 08 71 00, dated August 4, 2026

• ITB Attachment C – Drawings, Sheet G1.01 Addendum 1, dated 08/03/2026

• ITB Attachment C – Drawings, Sheet A2.11 Addendum 1, dated 08/03/2026

• ITB Attachment C – Drawings, Sheet A8.01 Addendum 1, dated 08/03/2026

• ITB Attachment C – Drawings, Sheet S2.01 dated 02/01/2024

• ITB Attachment C – Drawings, Sheet E0.02 Addendum 1, dated 08/05/2026

• ITB Attachment E - MYCF Geer-Civil

• ITB Attachment E - MacLaren Utility Maps Full Size

• ITB Attachment E - Geer Intake & Processing Clinic Plans

FLUID-APPLIED WATERPROOFING 07 14 00

August 05, 2026 OYA-MacLaren Infirmary 1 of 2

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Cold-applied rubberized asphalt waterproofing.

1.02 RELATED REQUIREMENTS

A. Section 03 30 00 - Cast-in-Place Concrete: Concrete substrate.

1.03 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data for membrane.

1.04 QUALITY ASSURANCE

A. Installer Qualifications: Company specializing in performing work of the type specified and with at least three years of documented experience.

1.05 FIELD CONDITIONS

A. Maintain ambient temperatures above 40 degrees F for 24 hours before and during application and until cured.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Polyurethane Waterproofing:

1. Tremco Commercial Sealants & Waterproofing; TREMproof 250GC: www.tremcosealants.com/#sle.

2. GMX: Ultra-Guard Elastomeric HB: https://gmxco.com/commercial-products/ultra-guard-elastomeric-hb/

3. Substitutions: See Section 01 60 00 - Product Requirements.

2.02 FLUID-APPLIED WATERPROOFING MATERIALS

A. Sprayed Thin-Film Elastomeric Waterproofing: Elastomeric, UV-resistant coating capable of being applied to damp masonry and green concrete without adverse effect on adhesion;

complying with requirements of ASTM C 836 except for minimum film thickness.

2.03 ACCESSORIES

A. Surface Conditioner: As recommended by membrane manufacturer.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting work.

B. Verify substrate surfaces are free of frozen matter, dampness, loose particles, cracks, pits, projections, penetrations, or foreign matter detrimental to adhesion or application of waterproofing system.

C. Verify that items penetrating surfaces to receive waterproofing are securely installed.

3.02 PREPARATION

A. Protect adjacent surfaces from damage not designated to receive waterproofing.

B. Clean and prepare surfaces to receive waterproofing in accordance with manufacturer's instructions; vacuum substrate clean.

C. Do not apply waterproofing to surfaces unacceptable to waterproofing manufacturer.

3.03 INSTALLATION

A. Install waterproofing to specified minimum thickness in accordance with manufacturers instructions and NRCA (WM) applicable requirements.

FLUID-APPLIED WATERPROOFING 07 14 00

August 05, 2026 OYA-MacLaren Infirmary 2 of 2

B. Apply primer or surface conditioner at a rate recommended by manufacturer, and protect conditioner from rain or frost until dry.

C. Apply waterproofing in accordance with manufacturer's instructions .

1. Applied Thickness: Nominal thickness of 60 mils; minimum thickness at any point of 50 mils.

D. Apply extra thickness of waterproofing material at corners, intersections, and angles.

END OF SECTION

THERMOPLASTIC MEMBRANE ROOFING 07 54 00

August 05, 2026 OYA-MacLaren Infirmary 1 of 5

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Adhered system with thermoplastic roofing membrane.

B. Insulation, flat and tapered.

C. Vapor retarder.

D. Cover boards.

E. Flashings.

F. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads.

1.02 RELATED REQUIREMENTS

A. Section 06 10 00 - Rough Carpentry: Wood cant strips and deck sheathing.

1.03 REFERENCE STANDARDS

A. ASTM C208 - Standard Specification for Cellulosic Fiber Insulating Board; 2022.

B. ASTM C578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation; 2023.

C. ASTM C1325 - Standard Specification for Fiber-Mat Reinforced Cementitious Backer Units;

2025.

D. ASTM D4434/D4434M - Standard Specification for Poly(Vinyl Chloride) Sheet Roofing; 2021.

E. ASTM D6878/D6878M - Standard Specification for Thermoplastic Polyolefin-Based Sheet Roofing; 2021.

F. FM (AG) - FM Approval Guide; Current Edition.

G. FM DS 1-28 - Wind Design; 2015, with Editorial Revision (2022).

H. NRCA (RM) - The NRCA Roofing Manual; 2023.

I. NRCA (WM) - The NRCA Waterproofing Manual; 2021.

1.04 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data indicating membrane materials, flashing materials, insulation, vapor retarder, surfacing, and fasteners.

C. Shop Drawings: Submit drawings that indicate joint or termination detail conditions, conditions of interface with other materials, and paver layout.

D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.

E. Manufacturer's qualification statement.

F. Installer's qualification statement.

G. Warranty Documentation:

1. Submit manufacturer warranty and ensure that forms have been completed in Owner's name and registered with manufacturer.

2. Submit installer's written verification that installation complies with warranty conditions for waterproof membrane.

1.05 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with minimum three years of documented experience.

1.06 DELIVERY, STORAGE, AND HANDLING

A. Deliver materials in manufacturer's original containers, dry and undamaged, with seals and labels intact, unless otherwise indicated.

B. Store materials in weather protected environment, clear of ground and moisture.

August 05, 2026 OYA-MacLaren Infirmary 2 of 5

C. Ensure storage and staging of materials does not exceed static and dynamic load-bearing capacities of roof decking.

D. Protect foam insulation from direct exposure to sunlight.

1.07 FIELD CONDITIONS

A. Do not apply roofing membrane during unsuitable weather.

B. Do not apply roofing membrane when ambient temperature is below 40 degrees F or above 140 degrees F.

C. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring.

D. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day.

E. Schedule applications so that no partially completed sections of roof are left exposed at end of workday.

1.08 WARRANTY

A. See Section 01 78 00 - Closeout Submittals for additional warranty requirements.

B. System Warranty: Provide manufacturer's system warranty agreeing to repair or replace roofing that leaks or is damaged due to wind or other natural causes.

1. Warranty Term: 20 years.

2. For repair and replacement include costs of both material and labor in warranty.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Thermoplastic Polyolefin (TPO) Membrane Roofing Materials:

1. Carlisle SynTec: www.carlisle-syntec.com.

2. GAF Materials Corporation; EverGuard TPO: www.gaf.com.

3. GenFlex Roofing Systems, LLC: www.genflex.com/#sle.

4. Versico Roofing Systems: www.versico.com/#sle.

5. Duro Last: Duro-Tech 60 Mil Fully Adhered Reinforce TPO Roofing System:

https://duro-last.com/duro-tech-tpo/

6. Substitutions: See Section 01 60 00 - Product Requirements.

B. Insulation:

1. BASF Corporation; BASF Neopor GPS: www.neopor.basf.us/#sle.

2. Carlisle SynTec Systems; SecurShield Insulation: www.carlisle-syntec.com/#sle.

3. DuPont de Nemours, Inc: building.dupont.com/#sle.

4. GAF: www.gaf.com/#sle.

5. Owens Corning Corporation: www.ocbuildingspec.com/#sle.

6. Versico Roofing Systems: www.versico.com/#sle.

7. Substitutions: See Section 01 60 00 - Product Requirements.

2.02 ROOFING

A. Thermoplastic Membrane Roofing: One ply membrane, fully adhered, over insulation.

B. Roofing Assembly Requirements:

1. Insulation Thermal Resistance (R-Value): 5.5 per inch, minimum; provide insulation of thickness required.

a. Total Minimum R-Value: R-32

C. Acceptable Insulation Types - Constant Thickness Application: Any type that meets requirements and is approved by membrane manufacturer for application.

D. Acceptable Insulation Types - Tapered Application: Any of types specified.

1. Tapered polyisocyanurate or extruded polystyrene board.

August 05, 2026 OYA-MacLaren Infirmary 3 of 5

2. Uniform thickness polyisocyanurate or extruded polystyrene board covered with tapered polyisocyanurate or extruded polystyrene board.

2.03 MEMBRANE ROOFING AND ASSOCIATED MATERIALS

A. Membrane Roofing Materials:

1. TPO: Thermoplastic polyolefin (TPO) complying with ASTM D6878/D6878M, sheet contains reinforcing fabrics or scrims.

a. Thickness: 60 mil, 0.060 inch, minimum.

2. Sheet Width:

B. Seaming Materials: As recommended by membrane manufacturer.

C. Vapor Retarder: Reinforced Kraft paper laminate complying with requirements of fire rating classification; compatible with roofing and insulation materials.

D. Flexible Flashing Material: Same material as membrane.

2.04 COVER BOARDS

A. Cover Board: Cement board complying with ASTM C1325.

1. Board Size: 48 by 96 inches.

2. Board Thickness: 7/16 inch.

3. Thermal Resistance: R-value of 1.6, nominal, at 7/16 inch thick.

4. Products:

a. PermaBASE Building Products, LLC provided by National Gypsum Company;

DEXcell Cement Roof Board: www.permabase.com/#sle.

b. Substitutions: See Section 01 60 00 - Product Requirements.

2.05 INSULATION

A. Extruded Polystyrene (XPS) Board Insulation: Comply with ASTM C578, with natural skin surface and drainage channels on one face.

1. Board Size: 48 by 96 inches.

2. Tapered Board: Slope as indicated; minimum thickness 1 inch; fabricate of fewest layers possible.

3. Products:

a. DuPont de Nemours, Inc: building.dupont.com/#sle.

b. Owens Corning Corporation: www.ocbuildingspec.com/#sle.

4. Substitutions: See Section 01 60 00 - Product Requirements.

2.06 ACCESSORIES

A. Cant Strips: Wood, pressure preservative treated; see Section 06 10 00.

B. Insulation Joint Tape: Glass fiber reinforced type as recommended by insulation manufacturer, compatible with roofing materials; 6 inches wide; self adhering.

C. Insulation Fasteners: Appropriate for purpose intended and approved by roofing manufacturer.

D. Membrane Adhesive: As recommended by membrane manufacturer.

E. Thinners and Cleaners: As recommended by adhesive manufacturer, compatible with membrane.

F. Insulation Adhesive: As recommended by insulation manufacturer.

G. Sealants: As recommended by membrane manufacturer.

H. Walkway Pads: Suitable for maintenance traffic, contrasting color or otherwise visually distinctive from roof membrane.

1. Composition: Asphaltic with mineral granule surface.

2. Surface Color: White or Yellow.

3. Products:

a. W.R. Meadows, Inc; Whitewalk: www.wrmeadows.com/#sle.

b. Substitutions: See Section 01 60 00 - Product Requirements.

August 05, 2026 OYA-MacLaren Infirmary 4 of 5

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that surfaces and site conditions are ready to receive work.

B. Verify deck is supported and secure.

C. Verify deck is clean and smooth, flat, free of depressions, waves, or projections, properly sloped and suitable for installation of roof system.

D. Verify deck surfaces are dry and free of snow or ice.

E. Verify that roof openings, curbs, and penetrations through roof are solidly set, and cant strips are in place.

3.02 PREPARATION - WOOD DECK

A. Verify flatness and tightness of joints in wood decking; fill knot holes with latex filler.

B. Confirm dry deck by moisture meter with 12 percent moisture maximum.

3.03 INSTALLATION, GENERAL

A. Perform work in accordance with manufacturer's instructions, NRCA (RM), and NRCA (WM) applicable requirements.

B. Do not apply roofing membrane during cold or wet weather conditions.

C. Do not apply roofing membrane when ambient temperature is outside the temperature range recommended by manufacturer.

D. Do not apply roofing membrane to damp or frozen deck surface or when precipitation is expected or occurring.

E. Do not expose materials vulnerable to water or sun damage in quantities greater than can be weatherproofed the same day.

3.04 INSTALLATION - VAPOR RETARDER AND INSULATION, UNDER MEMBRANE

A. Install vapor retarder to deck surface with adhesive in accordance with manufacturer's instructions.

1. Extend vapor retarder under cant strips and blocking to deck edge.

2. Install flexible flashing from vapor retarder to air seal material of wall construction, lap and seal to provide continuity of the air barrier plane.

B. Ensure vapor retarder is clean and dry, continuous, and ready for application of insulation.

C. Attachment of Insulation:

1. Mechanically fasten insulation to deck in accordance with roofing manufacturer's instructions and FM DS 1-28 Factory Mutual requirements.

D. Cover Boards: Mechanically fasten cover boards in accordance with roofing manufacturer's instructions and FM (AG) Factory Mutual requirements.

E. Lay subsequent layers of insulation with joints staggered minimum 6 inches from joints of preceding layer.

F. Place tapered insulation to the required slope pattern in accordance with manufacturer's instructions.

G. Lay boards with edges in moderate contact without forcing. Cut insulation to fit neatly to perimeter blocking and around penetrations through roof.

H. Tape joints of insulation in accordance with roofing and insulation manufacturers' instructions.

I. Do not install more insulation than can be covered with membrane in same day.

3.05 INSTALLATION - MEMBRANE

A. Roll out membrane, free from wrinkles or tears. Place sheet into place without stretching.

B. Shingle joints on sloped substrate in direction of drainage.

August 05, 2026 OYA-MacLaren Infirmary 5 of 5

C. Fully Adhered Application: Apply adhesive to substrate at rate of 40-60 square feet per gallon. Fully embed membrane in adhesive except in areas directly over or within 3 inches of expansion joints. Fully adhere one roll before proceeding to adjacent rolls.

D. Overlap edges and ends and seal seams by contact adhesive, minimum 3 inches. Seal permanently waterproof. Apply uniform bead of sealant to joint edge.

E. At intersections with vertical surfaces:

1. Extend membrane over cant strips and up a minimum of 4 inches onto vertical surfaces.

2. Fully adhere flexible flashing over membrane and up to nailing strips.

F. Around roof penetrations, seal flanges and flashings with flexible flashing.

G. Coordinate installation of roof drains and sumps and related flashings.

3.06 FIELD QUALITY CONTROL

A. See Section 01 40 00 - Quality Requirements for additional requirements.

B. Owner will provide testing services, and Contractor to provide temporary construction and materials for testing in accordance with requirements.

C. Provide daily on-site attendance of roofing and insulation manufacturer's representative during installation of this work.

3.07 CLEANING

A. See Section 01 70 00 - Execution and Closeout Requirements for additional requirements.

B. Remove bituminous markings from finished surfaces.

C. In areas where finished surfaces are soiled by work of this section, consult manufacturer of surfaces for cleaning advice and comply with their documented instructions.

D. Repair or replace defaced or damaged finishes caused by work of this section.

3.08 PROTECTION

A. Protect installed roofing and flashings from construction operations.

B. Where traffic must continue over finished roof membrane, protect surfaces using durable materials.

DOOR HARDWARE 08 71 00

April 24, 2026 OYA-MacLaren Infirmary 1 of 6

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Hardware for wood and hollow metal doors.

B. Lock cylinders for doors that hardware is specified in other sections.

1.02 RELATED REQUIREMENTS

A. Section 08 06 71 - Door Hardware Schedule: Schedule of door hardware sets.

B.A. Section 08 14 16 - Flush Wood Doors.

C.B. Section 10 26 00 - Wall and Door Protection: Door and frame protection.

1.03 REFERENCE STANDARDS

A. ADA Standards - 2010 ADA Standards for Accessible Design 2010.

B. BHMA A156.1 - Standard for Butts and Hinges 2021.

C. BHMA A156.2 - Bored and Preassembled Locks and Latches 2022.

D. BHMA A156.4 - Door Controls - Closers 2019.

E. BHMA A156.8 - Door Controls - Overhead Stops and Holders 2021.

F. BHMA A156.13 - Mortise Locks & Latches Series 1000 2022.

G. BHMA A156.16 - Auxiliary Hardware 2018.

H. BHMA A156.18 - Materials and Finishes 2020.

I. BHMA A156.30 - High Security Cylinders 2020.

J. BHMA A156.115W - Hardware Preparation in Wood Doors with Wood or Steel Frames 2006.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordinate the manufacture, fabrication, and installation of products that door hardware is installed on.

B. Keying Requirements Meeting:

1. Schedule meeting at project site prior to Contractor occupancy.

2. Attendance Required:

a. Contractor.

b. Owner.

3. Agenda:

a. Establish keying requirements.

b. Verify locksets and locking hardware are functionally correct for project requirements.

c. Verify that keying and programming complies with project requirements.

d. Establish keying submittal schedule and update requirements.

4. Incorporate "Keying Requirements Meeting" decisions into keying submittal upon review of door hardware keying system including, but not limited to, the following:

5. Record minutes and distribute copies within two days after meeting to participants, with two copies to Architect, Owner, participants, and those affected by decisions made.

6. Deliver established keying requirements to manufacturers.

1.05 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.

B. Product Data: Manufacturer's catalog literature for each type of hardware, marked to clearly show products to be furnished for this project, and includes construction details, material descriptions, finishes, and dimensions and profiles of individual components.

C. Shop Drawings - Door Hardware Schedule: Submit detailed listing that includes each item of hardware to be installed on each door. Use door numbering scheme as included in Contract Documents.

August 4, April 24, 2026 OYA-MacLaren Infirmary 2 of 6

1. Provide complete description for each door listed.

2. Provide manufacturer's and product names, and catalog numbers; include functions, types, styles, sizes and finishes of each item.

3. Include account of abbreviations and symbols used in schedule.

PART 2 PRODUCTS

2.01 DESIGN AND PERFORMANCE CRITERIA

A. Provide specified door hardware as required to make doors fully functional, compliant with applicable codes, and secure to extent indicated.

B. Provide individual items of single type, of same model, and by same manufacturer.

C. Provide door hardware products that comply with the following requirements:

1. Applicable provisions of federal, state, and local codes.

2.02 HINGES

A. Manufacturers:

1. McKinney; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Stanley, dormakaba Group: www.stanleyhardwarefordoors.com/#sle.

3. Ives - Allegion: us.alegion.com.

4. Substitutions: See Section 01 60 00 - Product Requirements.

B. Hinges: Comply with BHMA A156.1, Grade 1.

1. Provide hinges on every swinging door.

2. Provide following quantity of butt hinges for each door:

a. Doors up to 60 inches High: Two hinges.

b. Doors From 60 inches High up to 90 inches High: Three hinges.

2.03 LOCK CYLINDERS

A. Lock Cylinders: Provide key access on outside of each lock, unless otherwise indicated.

1. Provide cylinders from same manufacturer as locking device.

2. Provide cams and/or tailpieces as required for locking devices.

2.04 CYLINDRICAL LOCKS

A. Manufacturers:

1. Best, dormakaba Group: www.bestaccess.com/#sle.

2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Cylindrical Locks (Bored): Comply with BHMA A156.2, Grade 1, 4000 Series.

1. Bored Hole: 2-1/8 inch diameter.

2. Latchbolt Throw: 1/2 inch, minimum.

3. Backset: 2-3/4 inch unless otherwise indicated.

4. Strikes: Provide manufacturer's standard strike for each latchset or lockset with strike box and curved lip extending to protect frame in compliance with indicated requirements.

a. Finish: To match lock or latch.

2.05 MORTISE LOCKS

A. Manufacturers:

1. Best, dormakaba Group: www.bestaccess.com/#sle.

2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Mortise Locks: Comply with BHMA A156.13, Grade 1, Security, 1000 Series.

1. Latchbolt Throw: 3/4 inch, minimum.

2. Deadbolt Throw: 1 inch, minimum.

3. Backset: 2-3/4 inch unless otherwise indicated.

4. Strikes: Provide manufacturer's standard strike for each latchset or lockset with strike box and curved lip extending to protect frame in compliance with indicated requirements.

a. Finish: To match lock or latch.

April 24, 2026 OYA-MacLaren Infirmary 3 of 6

2.06 CLOSERS

A. Manufacturers; Surface Mounted:

1. Norton; an Assa Abloy Group company: www.assaabloydss.com/#sle.

1. Substitutions: See Section 01 60 00 - Product Requirements.

B. Closers: Comply with BHMA A156.4, Grade 1.

1. Type: Surface mounted to door.

2. Provide door closer on each exterior door.

2.07 OVERHEAD STOPS AND HOLDERS

A. Manufacturers:

1. Rixson; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Glynn-Johnson, an Allegion brand: www.allegion.com/us/#sle.

2.3. Substitutions: See Section 01 60 00 - Product Requirements.

B. Overhead Stops and Holders (Door Checks): Comply with BHMA A156.8, Grade 1.

1. Provide stop for every swinging door, unless otherwise indicated.

2.08 FLOOR STOPS

A. Manufacturers:

1. Rockwood; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Floor Stops: Comply with BHMA A156.16, Grade 1 and Resilient Material Retention Test as described in this standard.

1. Type: Manual hold-open, with pencil floor stop.

2. Material: Aluminum housing with rubber insert.

2.09 WALL STOPS

A. Manufacturers:

1. Rockwood; an Assa Abloy Group company: www.assaabloydss.com/#sle.

1.2. Substitutions: See Section 01 60 00 - Product Requirements.

B. Wall Stops: Comply with BHMA A156.16, Grade 1 and Resilient Material Retention Test as described in this standard.

1. Type: Bumper, concave, wall stop.

2. Material: Aluminum housing with rubber insert.

2.10 FINISHES

A. Finishes: Provide door hardware of same finish, unless otherwise indicated.

1. Primary Finish: 652; satin chromium plated over nickel, with steel base material (formar US equivalent US26D); BHMA A156.18.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that doors and frames are ready to receive this work; labeled, fire-rated doors and frames are properly installed, and dimensions are as indicated on shop drawings.

3.02 INSTALLATION

A. Install hardware in accordance with manufacturer's instructions and applicable codes.

B. Use templates provided by hardware item manufacturer.

C. Door Hardware Mounting Heights: Distance from finished floor to center line of hardware item. As indicated in following list; unless noted otherwise in Door Hardware Schedule or on drawings.

D. Set exterior door thresholds with full-width bead of elastomeric sealant at each point of contact with floor providing a continuous weather seal; anchor thresholds with stainless steel countersunk screws.

April 24, 2026 OYA-MacLaren Infirmary 4 of 6

3.03 ADJUSTING

A. Adjust hardware for smooth operation.

B. Adjust gasketing for complete, continuous seal; replace if unable to make complete seal.

3.04 CLEANING

A. Clean adjacent surfaces soiled by hardware installation.

B. Replace items that cannot be cleaned to manufacturer's level of finish quality at no additional cost.

3.05 PROTECTION

A. Do not permit adjacent work to damage hardware or finish.

3.06 DOOR HARDWARE

HARDWARE GROUP NO. 01

FOR USE ON DOOR #(S):

101E

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 EA CLOSER 7500 689 NOR

BALANCE OF HARDWARE

EXISTING

HARDWARE GROUP NO. 02

FOR USE ON DOOR #(S):

103 112

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

1 EA CLOSER 7500 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA SECURITY WALL STOP 412 630 ROC

3 EA SILENCER SR64 GRY IVE

HARDWARE GROUP NO. 03

104 105 107 109

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

HARDWARE GROUP NO. 01

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK

W/INDICATOR

45H7TD3H-VIN 626 BES

1 EA OH STOP 100S 630 GLY

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 SET SEALS S44D

(FOR SOUND)

DKB PEM

HARDWARE GROUP NO. 02

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

1 EA CLOSER 7500PA 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CVX 630 IVE

April 24, 2026 OYA-MacLaren Infirmary 5 of 6

HARDWARE GROUP NO. 04

FOR USE ON DOOR #(S):

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

HARDWARE GROUP NO. 05

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK

W/INDICATOR

45H7TD3H-VIN 626 BES

1 EA CLOSER 7500 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CVX 630 IVE

1 SET SEALS S44D

(FOR SOUND)

DKB PEM

HARDWARE GROUP NO. 06

109A

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

2 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA DEADBOLT 45H7AD 626 BES

1 EA FLUSH PULL 955 626 IVE

1 EA OH STOP 90S 630 GLY

2 EA SILENCER SR64 GRY IVE

HARDWARE GROUP NO. 07

110E

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

1 EA CLOSER 7500PA 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

HARDWARE GROUP NO. 03

20.1 44 45A 45B

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

1 EA ELECTRIC STRIKE 6210 FSE CON 24VDC 630 VON

1 EA LOCK GUARD LG14 630 IVE

1 EA CLOSER 7500PA 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CVX 630 IVE

3 EA SILENCER SR64 GRY IVE

1 EA WIRE HARNESS CON-6W

(FROM EPT OR STRIKE TO

POWER)

SCH

1 EA ACCESS CONTROL PROVIDED BY DIV 28

HARDWARE GROUP NO. 04

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA PASSAGE MORTISE 45H0N3H 626 BES

HARDWARE GROUP NO. 05

47 48

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA OFFICE MORTISE LOCK 45H7AT3H 626 BES

April 24, 2026 OYA-MacLaren Infirmary 6 of 6

HARDWARE GROUP NO. 08

FOR USE ON DOOR #(S):

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 652 IVE

1 EA ANTI LIGATURE

STOREROOM LOCK

45H7DSPSL 626 BES

1 EA OH STOP 100S 630 GLY

HARDWARE GROUP NO. 09

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

HARDWARE GROUP NO. 06

FOR USE ON DOOR #(S):

54B 50A

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA PASSAGE MORTISE 45H0N3H 626 BES

1 EA DELAYED EGRESS MAG M490DE 12/24 VDC 628 SCE

1 EA CLOSER 7500PA 689 NOR

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CVX 630 IVE

3 EA SILENCER SR64 GRY IVE

1 EA POWER SUPPLY PS902 900-2RS 120/240 VAC VON

2 EA ACCESS CONTROL PROVIDED BY DIV 28

POWER SUPPLY REQUIRES 120VAC. DELAYED EGRESS MAGNETIC LOCK REQUIRES 24V FROM

POWER SUPPLY, ACCESS CONTROL AND FIRE ALARM INPUT.

HARDWARE GROUP NO. 07

49 50 52 53

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 HARDWARE BY DOOR

MANUFACTURER

HARDWARE GROUP NO. 08

PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 652 IVE

1 EA STOREROOM LOCK 45H7D3H 626 BES

1 EA OH STOP 90S 630 GLY

UP

LEGEND

SECURITY SEPARATION

3 HOUR WALL

SMOKE BARRIER

SMOKE PARTITION

NEW EXIT SIGN, ARROW(S) INDICATES

DIRECTION (IF SHOWN)

KEY LOCKED SECURITY GATE

CHAINLINK FENCE AND GATE

OCCUPANT EXIT LOAD

EGRESS TOTAL PATH OF TRAVEL DISTANCE

FIRE EXTINGUISHER

NOT AN EXIT

SEC LK

XX

X'-X"

FE

NE

BB

CC

2 3 4

159' - 9"

NE

NE

COURTYARD

RECEIVING /

STORAGE

MED LAB

SECURITY

MED SUPPLY

MED ROOM

NURSE

STATION

MEETING

ROOM

NURSE

SUPERVISOR

NURSE

SUPERVISOR

PATIENT

ROOM/AII

PATIENT

ROOM

SHOWER

ROOM

PATIENT

ROOM

PATIENT

ROOM

DAY ROOM

CIRCULATION

DENTAL LAB

VAC STORE

DENTAL

OFFICE

OPERATORY

OFFICE /

EXAM ROOM

SHARED

OFFICE

PSYCH

OFFICE

NURSE

SUPER /

EXAM ROOM

JANITOR

CLOSET

YTH TLT

EXAM ROOMMED SUPPLY

PSYCH

OFFICE

PSYCH

OFFICE

PSYCH

OFFICE

PSYCH

OFFICE

SHARED

OFFICE

YTH TLT

EXAM ROOM

LOCKERS

BREAK

ROOM

STF TLTSTF TLT

HALLWAY

HALLWAY

GENERAL

STORAGE

KIT

COURTYARD

VESTIBULE

DENTAL VAC

YOUTH

WAITING

ELEC. CLOSET

AREA OF WORK

53.52.3 2.8

AA

A.6A.6

9'

9"

FE

FE

FE

DD

0 4.63.90.9 1.5

AREA OF WORK

6 7

AREA OF WORK

NEW 3-HR FIRE

SEPARATION

1,201 SF

SLEEPING AREA

B

120 SF / OCC

10 OCC

7,187 SF

OUTPATIENT

B

100 SF / OCC

72 OCC

COURTYARD

744 SF

GEN. STORAGE

S1

300 SF / OCC

3 OCC

RECEIVING

/ STORAGE

MED LAB

SECURITY

MED

SUPPLY

MED ROOM

NURSE

STATION

MEETING

ROOM

NURSE

SUPERVISOR

NURSE

SUPERVISOR

PATIENT

ROOM/AII

PATIENT

ROOM

SHOWER

ROOM

PATIENT

ROOM

PATIENT

ROOM

DAY ROOM

CIRCULATION

DENTAL

LAB

VAC

STORE

DENTAL

OFFICE

OPERATORY

OFFICE /

EXAM

ROOM

SHARED

OFFICE

PSYCH

OFFICE

NURSE

SUPER /

EXAM

ROOM

JANITOR

CLOSET

YTH TLT

EXAM

ROOM

MED

SUPPLY

PSYCH

OFFICEPSYCH

OFFICE

PSYCH

OFFICEPSYCH

OFFICE

SHARED

OFFICEYTH TLT

EXAM

ROOM

LOCKERS

BREAK

ROOM

STF TLTSTF TLT

HALLWAY

HALLWAY

GENERAL

STORAGE

KIT

COURTYARD

VESTIBULE

DENTAL

VAC

YOUTH

WAITING

ELEC.

CLOSET

1,604 SF

TRANSPORTATION

OFFICE

B

150 SF / OCC

11 OCC

AREA OF WORK

B - OCCUPANCY - 10,333 SF - 91%

LEGEND - OCCUPANCY

S-1 - OCCUPANCY - 980 SF - 8.7%

OCC. B - [36,000 + (9,000 * .5) ] = 40,500, SF

TOTAL ALLOWABLE 40,500 SF

AT COUNTERTOPS

AT COUNTERTOPS

AT WALL-MOUNT

EQUIPMENT

TOP OF WALL PHONES

PULL STATION

(TOP OF BOX)

HORN /S STROBE

(BOTTOM OF BOX)

AT ALL OTHER

LOCATIONS (INCLUDING

OPEN WORK COUNTERS)

ONE URINAL

MINIMUM AT ADA

HEIGHT

ADDITIONAL

URINALS TO BE

MOUNTED AT

TALLER HEIGHT

MR

PROVIDE ADDITIONAL

WALL FINISH BEHIND

MIRROR FOR A FLUSH

MOUNTING SURFACE

M

AX

1'

- 5

1'

- 1

1"

3' - 0" MIN

2'

- 1

0"

7'

- 5

3'

- 8

1'

- 6

4'

- 0

16"-18" (M

AX

2'

- 1

0"CL

EA

RA

NC

E

" M

IN

KN

EE

SD

W / L

AV

AT

OR

Y

3'

- 4

" M

AX

6'

- 8

4'

- 0

1'

- 6

"3'

- 8

3' - 0"

"-1

9" 3'

- 4

"TPD

1' - 0" MAX

3' - 6" MIN

2'

- 1

0"

1'

- 6

3'

- 3

3' - 3" -41"

OF TP

7"-9" TO

CENTER

CONTROLS MUST BE

WITHIN THIS AREA & 15"

(MAX) LEFT OR RIGHT OF

CENTER LINE OF SEAT.1' - 6"

3'

- 2

4'

- 0

M

AX

2'

- 3

M

AX

3'

- 0

" 4'

- 0

4'

- 2

AUTO DOOR OPENER

CARD READER

M

AX

2'

- 1

0"

M

IN

2'

- 3

TYP 40" TO CONTROLS AND

DISPENSER OPENING (MAX. 48"

FRONT REACH AND 48" SIDE

REACH)

ACCESSIBLE

NON-ACCESSIBLE

PROVIDE ADDITIONAL WALL

FINISH BEHIND PTD FOR A

FLUSH MOUNTING SURFACE

PTD

5'

- 4

4'

- 0

NOTES:

1) ALL DIMENSIONS ARE TYPICAL UNLESS NOTED OTHERWISE ON INTERIOR ELEVATIONS.

2) WALL MOUNTED ACCESSORIES SHALL NOT PROJECT MORE THAN 4" FROM FACE OF WALL WHEN LOCATED BELOW 6'-8".

3) NON USED ITEMS ARE HALFTONE

7'

- 0

(T

YP

1'

- 1 0"

4'

- 4

EXTINGUISHER

HANDLE

3'

- 4

A URINAL (RIM HEIGHT) B WATER CLOSET (SEAT HEIGHT) C SIDE GRAB BAR (TO CENTER) D REAR GRAB BAR (TO CENTER) E TOILET PAPER DISP. F LAVATORY G SOAP DISPENSER H MIRROR

J PAPER TOWEL DISP. K COAT HOOK L SHOWER (REF. BENCH LOCATION) M ELECT. OUTLETS

(CENTER OF BOX) N LIGHT SWITCHES

(TOP OF BOX) O TELE / DATA CONN.

(CENTER OF BOX) P FIRE ALARM DEVICES

R VANITY LIGHT FIXTURE

(CENTER OF BOX) S FIRE EXTINGUISHER CABINET T ADA DRINKING FOUNTAIN U DOOR ACCESSORIES

(TOP OF BOX) V SIGNAGE

(CENTER OF BOX) W BABY CHANGING STATION

PULL CORDS & BUTTONS

(CENTER OF BOX)

STAFF STATIONS

(TOP OF BOX)

DOME LIGHTS

(CENTER OF BOX)

8'

- 0

4'

- 0

Q NURSE CALL

SCD

3'

- 4

8"

I SEAT COVER DISP.

MIN

1' - 0"

1' - 0"

W /O

LA

VA

TO

RY

2'

- 1

1" M

AX

MR

STANDING = 38"-43"

1'

- 5

3'

- 2

" 3'

- 1

0"

5'

- 0

THERMOSTAT

LIGHT SWITCH

DOOR LEVER

DUPLEX, PHONE, AND

DATA OUTLERS TO BE

LOCATED 17" AFF. U.N.O.

NOTE:

CONTRACTOR TO VERIFY

ALL DIMENSIONS AT SITE

EQ

A

T

DO

OR

H

IN

GE

S

EQ

A T

DO

OR

H

IN

GE

S

5"

9"

" M

AX

. B

AS

E

OF

T

OP

LI

NE

" M

IN

. B

AS

E

OF

LO

W

EE

ST

LI

NE

A.D.A. SIGNAGE

1' - 0"

RISK PROFILE FOR SPACES

HIGH RISK - YOUTH LEFT UNATTENDED

MODERATE RISK - YOUTH UNRESTRANINED

BUT ATTENDED

LOW RISK - STAFF ONLY ACCESS

(VIA PHYSICAL SECURITY LIKE DOOR LOCKING)

TYLER P CARLSON

E

PORTLAND, OREGON

R

S T

TA

G R E

I

TES

E

FO OR

N

OG

CDE RA

TE

TC

H I

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

, L

LC

C O

PY

R

IG

H

T

SW

S ix th

A ve nu e, S ui te

Po rtl an d, O R

Ph on e:

/2

-4

8/ 5/

:2

8:

P M

C :\U se rs

\w ills lo m an \D oc um en ts

\R ev it

\M ac La re n

- 2

_w ills lo m an

.rv t

FIRE AND LIFE SAFETY

06.27.2025

G1.01

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

25015

M ac

L A

R E

N

IN

F

IR

M A

R Y

P

H A

R M

A C

Y R

E N

O V

A T

IO

N

N P

A C

IF

IC

H W

Y . W

O O

D B

U R

N , O

R

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

GENERAL NOTES: FIRE & LIFE SAFETY

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL

TRADES ARE THOROUGHLY FAMILIAR AND COMPLY WITH THE

REQUIREMENTS LISTED IN THE "FIRE AND LIFE SAFETY STANDARDS"

(FLSS)

2. ALL RATED ASSEMBLIES SHALL BE CONSTRUCTED TO PREVENT THE

MOVEMENT OF FLAME OR GASSES PER CODE

3. INSTALL RATED ENCLOSURES FOR ALL RECESSED ITEMS IN RATED

WALLS PER CODE. SEE ARCHITECTURAL DETAILS.

4. ALL PENETRATIONS THROUGH RATED ASSEMBLIES IN AREA OF WORK

SHALL BE FIRESTOPPED OR SEALED PER CODE.

5. THE CONTRACTOR SHALL FIELD VERIFY THE CONDITION OF THE

EXISTING FLSS SYSTEMS IN THE AREAS OF WORK THAT MAY REQUIRE

UPDATING. AREAS INCLUDE (BUT ARE NOT LIMITED TO) THE

FOLLOWING:

A. CONTRACTOR TO VERIFY THAT ALL EXISTING PENETRATIONS OF

RATED ASSEMBLIES WHICH ARE EXPOSED TO VIEW DURING

CONSTRUCTION ARE COMPLIANT WITH CODE REQUIREMENTS.

B. CONTRACTOR TO EXTEND ANY EXISTING WALL (WITHIN THE AREA OF

WORK) TO STRUCTURE WHICH IS REQUIRED BY FLSS BUT DOES NOT

PRESENTLY EXIST.

C. CONTRACTOR TO VERIFY THAT ALL DUCTWORK PENETRATIONS

THROUGH RATED ASSEMBLIES ARE EQUIPPED WITH FIRE AND/ OR

SMOKE DAMPERS AS REQUIRED BY CODE.

D. VERIFY THAT THE FIRE ALARM, EMERGENCY LIGHTING, AND

EMERGENCY POWER IN THE AREA OF WORK CONFORMS TO THE FLSS

"ELECTRICAL STANDARDS" SECTION FOR THE OCCUPANCY TYPE

INDICATED ON THE FLS PLANS

6. REFER ELECTRICAL FOR EXIT SIGN LOCATIONS

7. ALL EMERGENCY EXIST HARDWARE ARE DELAYED EGRESS.

CODE SUMMARY

PROJECT NAME: MacLaren Infirmary & Pharmacy Renovation

ADDRESS: 2630 N PACIFIC HWY. WOODBURN, OR

97071

OWNER: OREGON YOUTH AUTHORITY

CODES: 2022 OSSC

NFPA 101-CHAPTER 38

OCCUPANCY: B

OCCUPANCY: UNIT HOUSE A MAXIMUM OF 4 DETAINEES

FOR MEDICAL OBSEVATION ONLY FOR

LESS THAN 48 HRS.

NUMBER OF STORIES: ONE

CONSTRUCTION TYPE: V-B

FIRE PROTECTION: FULLY SPRINKLERED

FIRE ALARM SYSTEM: YES

ALLOWABLE SQUARE FOOTAGE: (TABLE 506.2)

TOTAL AREA OF NEW BUILDING: 11,083 SF

TOTAL AREA ALLOWED: 40,500 SF

INFIRMARY SQUARE FOOTAGE: 9,052 SF

RENOVATION SQUARE FOOTAGE: 2,985 SF

ADDITION SQUARE FOOTAGE: 1,865 SF

FIRE SEPARATION DISTANCE: (602) ≥30'-0"

MAXIMUM AREA OF EXTERIOR WALL

OPENINGS (705.8):

≥30'-0"

UNPROTECTED, SPRINKLERED

UNLIMITED

OCCUPANT LOAD: (1004.5) 1/120 SF, SLEEPING AREAS

1/100 SF, OUTPATIENT AREAS

1/300 SF, STORAGE AREAS

MAX. COMMON PATH OF TRAVEL

(1006.2.1): 75 FT

MAX. TRAVEL DISTANCE (1017.2.1): 200 FT

FIRE RESISTIVE RATINGS: (TABLE NO. 601, 705.5 OF THE I.B.C.)

BUILDING ELEMENT (>10'

SEPARATION)

TYPE V-B

STRUCTURAL FRAME 0 HOUR

BEARING WALLS

EXTERIOR 0 HOUR

INTERIOR 0 HOUR

NON BEARING WALLS AND PARTITIONS

EXTERIOR 1 HOUR, IF <30' FIRE SEPARATION DISTANCE

0 HOUR, IF ≥30' FIRE SEPARATION DISTANCE

INTERIOR 0 HOUR

FLOOR CONSTRUCTION

INCLUDING SUPPORTING BEAMS

AND JOISTS

0 HOUR

NON BEARING WALLS AND PARTITIONS

INCLUDING SUPPORTING BEAMS

AND JOISTS

0 HOUR

1" = 10'-0"G1.01

2 LEVEL 1 - FLS & RISK ASSESSMENT

1" = 40'-0"G1.01

1 LEVEL 1

1" = 20'-0"G1.01

3 LEVEL 1 - PROJECT OCCUPANCY

1/4" = 1'-0"G1.01

4 TYPICAL MOUNTING HEIGHTS

1/2" = 1'-0"G1.01

5 STANDARD MOUNTING HEIGHTS

PLUMBING CALCULATIONS

CALCULATION FACTORS

PROJECT OCCUPANTS FOR CALC. 85 OCCUPANTS

PROJECT CLASSIFICATION FOR

CALC.

B CLASSIFICATION

WATER CLOSETS

REQUIRED COUNT 1 PER 25 FOR FIRST 50, 1 PER 50 AFTER

THAT

REQUIRED IN PROJECT 3 WATER CLOSETS

INCLUDED IN PROJECT 5 WATER CLOSETS

LAVATORY

REQUIRED COUNT 1 PER 40 FOR FIRST 80, 1 PER 80-

AFTER THAT

0 HOUR, IF ≥30' FIRE SEPARATION

DISTANCE

REQUIRED IN PROJECT 2 LAVATORIES

INCLUDED IN PROJECT 5 LAVATORIES

SHOWERS/BATHTUBS

INCLUDED IN PROJECT 1 SHOWER STALL

REQUIRED COUNT 0 SHOWER/BATHTUB

DRINKING FOUNTAINS

INCLUDED IN PROJECT 0 DRINKING FOUNTAIN

REQUIRED COUNT 0 DRINKING FOUNTAIN

1 County Comments 08/19/2025

2 ADDENDUM 01 08/03/2026

60"

LEGEND

EXISTING PARTITION

NEW PARTITION

CARD READER

A4.012

BB

CC

2 3 4

RECEIVING /

STORAGE

MED LAB

SECURITY

C20.1

MED SUPPLY

MED ROOM

NURSE

STATION

MEETING

ROOM

NURSE

SUPERVISOR

NURSE

SUPERVISOR

PATIENT

ROOM/AII

PATIENT

ROOM

SHOWER

ROOM

PATIENT

ROOM

PATIENT

ROOM

DAY ROOM

CIRCULATION

C20

VAC STORE

40.1DENTAL

OFFICE

D21

PSYCH

OFFICE

NURSE

SUPER /

EXAM ROOM

JANITOR

CLOSET

YTH TLT

75EXAM ROOM

PSYCH

OFFICE

PSYCH

OFFICE

PSYCH

OFFICE

PSYCH

OFFICE

SHARED

OFFICE

YTH TLT

LOCKERS

BREAK

ROOM

STF TLT

STF TLT

HALLWAY

C30

CHECK-IN

KIT

41.1

A5.01

A5.01

A5.02 4

A5.02

A5.01 14

A5.01

A5.02

A5.01 5

A5.0218

A5.03

A5.02

A5.02

A5.02

A2.21

A4.01

A .1

A .1

A .1

A .1

54B

.1

45A

45B

78 77

A A

B

B

B C

DE

A4.21

A4.21

A4.21

A4.21

A8.01 F

A8.01G

A8.01H

A8.01

J

A8.01

K

A8.01

L

10' - 2 1/4"

W26

W26

P33

P33 P33P

P33P33 P36

W26

W26

P33P

P33P

P33P

A.1

ALIGN

AL

IG

N

YOUTH

WAITING

C10.1

ENTRY

C10

ALIGN

7' - 8 1/2"

135.00°

ALIGN

8' - 1 3/4" 4' - 9"

F13

W16

CLEAR

5' - 0"

53.52.3 2.8

AA

A.6

FR

OM

F

AC

E

OF

E

XI

ST

IN

G 9'

- 5 1/

2" 1'

- 6

A4.21

A4.21

A2.21

ALIGN

9'

- 2

1/ 4"

5'

- 9

8"

21' - 5 1/2" 24' - 3 1/4" 19' - 11 1/4" 29' - 6 1/2"

13' - 5" 12' - 9 1/2" 12' - 11 1/2" 10' - 7 1/4" 18' - 0" 12' - 3"

3/4

1"

3/4

6' - 10" 6' - 3" 5' - 8 1/2" 5' - 0 3/4" 7' - 2 1/2" 10' - 6"

AL

IG

N

ALIGN

8'

- 4

3/ 4"

4"

6"

5"

6'

- 5

1/ 2"

1/2

7'

- 1

1/4

8'

- 0

1/ 4"

2'

- 1

3/4

9' - 0 1/2"

X16

X16X

P13 P33

P13

P13

P13

P13

P13

P13

P13

P13

86R

85R

LINE OF CANOPY (ABOVE)LINE OF CANOPY

(ABOVE)

4" 4' - 8 1/4"

2' - 9 1/2"

5'

0" A8.01 H R V

P16

P13

P13 P13

P16

P13

P16

FR

OM

F

AC

E

OF

E

XI

ST

IN

G

P13

7'

- 1

1/2

5' - 1 1/4"

1'

- 1

DD

A4.31

A4.31

12' - 10 3/4"

8'

- 3

1/ 2"

1' - 6"

6"

1/ 2"

11' - 8 1/4"

18' - 0"

4.63.9

B

M1 X16

F13AO

F11.5

D.S. D.S.

D.S.D.S.D.S.

ALIGN

M1

ETR

M1

M2

M2

M2 M2 M2

FO

F

0.9 1.54 A4.21

F.O.M.

3'

- 3

3/ 4"

3'

- 5

3/ 4"

3'

- 5

3/ 4"

1/4"

1/

2"

F.O.M.

6'

- 1

1/2

F.O.M.

.50

2 1 /2"5"

50A

PLYWOOD ON BOTH

SIDES OF WALL TYPE

P13P

5' - 0"

2' - 2 1/4"

ALIGN

CL

EA

R

4'

- 3

1' - 11" 5'

- 9

1/ 2"

ALIGN

M2

P13P13

2'

- 6

3/ 4"

5' - 3 1/2"

1' - 8 1/4" 1' - 7 3/4"

X26

MT2

A6.04

A6.04

SIM

A6.05

A6.05

TYLER P CARLSON

E

PORTLAND, OREGON

R

S T

TA

G R E

I

TES

E

FO OR

N

OG

CDE RA

TE

TC

H I

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

SW

S ix th

A ve nu e, S ui te

Po rtl an d, O R

Ph on e:

/2

-4

8/ 5/

:2

8:

P M

C :\U se rs

\w ills lo m an \D oc um en ts

\R ev it

\M ac La re n

- 2

_w ills lo m an

.rv t

ENLARGED PLAN -

PATIENT AREA

06.27.2025

A2.11

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

25015

M ac

L A

R E

N

IN

F

IR

M A

R Y

P

H A

R M

A C

Y R

E N

O V

A T

IO

N

N P

A C

IF

IC

H W

Y . W

O O

D B

U R

N , O

R

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

KEY PLAN

KEYNOTES

A.1 PROVIDE ANTI-LIGATURE FITTINGS AND FIXTURES IN PATIENT

TOILET - REF SPECS

GENERAL NOTES: PLAN

1. REFER TO PARTITION TYPES SHEET FOR LEGEND AND

CONSTRUCTION ASSEMBLIES.

2. REFER TO PARTITION DETAILS FOR DEFLECTION TRACK, BACKING

PLATE FOR BLOCKING AND FIRE RATED CONNECTION DETAILS

3. REFER TO ELEVATIONS FOR ACCESSORIES AND EQUIPMENT

REQUIRING BLOCKING AND WHEN USING METAL STUDS REFER TO

DETAIL SHEETS FOR BLOCKING REQUIREMENTS AND REGULATIONS.

4. REFER TO STRUCTURAL FOR SHEAR WALLET, MECHANICAL AND

ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. NOTIFY

ARCHITECT OF ANY CONFLICTS FOR WRITTEN RESOLUTION.

5. INTEGRAL BASE TO BE INSTALLED IN ALL HOUSEKEEPING CLOSETS,

SOILED HOLD ROOMS, AND TOILET ROOMS (UNLESS NOTED

OTHERWISE).

6. VERIFY ALL EXISTING DIMENSIONS IN FIELD PRIOR TO ORDERING OR

MANUFACTURING ANY COMPONENT.

7. FOR METAL FRAMED WALLS- LOCATE HINGE SIDE OF ALL DOORS 4"

FROM PERPENDICULAR FRAMING AND FOR WOOD FRAMED

WALL-LOCATE HINGE SIDE OF DOOR 4-1/2" FROM PERPENDICULAR

FRAMING U.N.O.

8. ALL DIMENSIONS TO FACE OF STUD UNLESS OTHERWISE NOTED.

9. ALL RESTROOMS, HOUSEKEEPING AREAS AND OTHER AREAS

REQUIRING FLOOR DRAINS SHALL HAVE AN INTEGRAL BASE COVING

U.N.O.

10. GENERAL NOTES ON THIS PAGE DO NOT EXCLUDE NOTES

ELSEWHERE; THIS DOCUMENT SET IS COMPLIMENTARY. NOTES ON

OTHER SHEETS MAY HAVE BEARING/ APPLICATION TO WORK SHOWN

ON THIS SHEET

1/4" = 1'-0"A2.11

1 LEVEL 1 - OPTION 01

1 County Comments 08/19/2025

FINISH FLOOR

SEE

SCHEDULE

SE

E

SC

HE

DU

LE

SEE

SCHEDULE

SE

E

SC

HE

DU

LE2'

- 9

9"

6"8"

SEE

SCHEDULE

SE

E

SC

HE

DU

LE2'

- 9

9"

8" 8"

SEE

SCHEDULE

SE

E

SC

HE

DU

LE

6" 6"

SF

SINGLE FLUSH

VL

VISION LITE

(NON RATED)

HL

HALF LITE

FG

FULL LITE

M

IN

6"

6"

FINISH FLOOR

2" SEE

SCHEDULE

2"

SE

E

SC

HE

DU

LE

2"

SINGLE/DOUBLE

HM FRAME

2"

SEE

SCHEDULE 2" SEE

SCHEDULE

HM FRAME W/

SIDELITE

SE

E

SC

HE

DU

LE

2"

FINISH FLOOR

4'

- 0

4'

- 0

2' - 10"

4'

- 0

3'

- 2

4' - 0"

A

FIXED

DOUBLE LITE

1 7/16" GLASS

4'

- 0

4'

- 0

4' - 0"

B

FIXED

DOUBLE LITE

1 7/16" GLASS

C

FIXED

SINGLE LITE

11/16" GLASS

4'

- 0

3'

- 2

3' - 0"

D

FIXED

SINGLE LITE

11/16" GLASS

4'

- 6

2'

- 8

4' - 7"

E

FIXED

SINGLE LITE

11/16" GLASS

IG

IG

IGIG

7'

- 0

2" 3' - 0" 2" 4" 5' - 11" 4"

FINISH FLOOR

1'

- 6

3'

- 2

2'

- 6

"12

A8.01

A8.01

A8.01

A8.01

IG IG

IG

IG

4'

- 6

3'

- 0

AF

F

FINISH FLOOR

EQ EQ EQ EQ

A8.01

A8.01

A8.01

A8.01

Sim

A8.01

IG IG IG IG

2" 3'

- 8

3'

- 4

AF

F

4" 2' - 2 1/2" 2" 3' - 0" 0"

FINISH FLOOR

A8.01

A8.01

A8.01

IG

4'

- 6

23' - 5 3/4"

FINISH FLOOR

EQ EQ EQ EQ

A8.01

Sim

A8.01

A8.01

A8.01

A8.01

IG IG IG IG

2" 7'

- 1 0"

A

FF

FINISH FLOOR

A8.01

A8.01

A8.01

A8.01

FINISH FLOOR

TOP OF WINDOW

LV-4

4' - 0" - WIDE

LOUVERS

LV-2

2' - 10" - WIDE

LOUVERS

1'

- 9

4' - 0" 2' - 10"

1'

- 9

2" 4'

- 2

2" 3'

- 6

AF

F

EQ EQ EQ EQ EQ

A8.01

A8.01

A8.01

S1

SOLID SURFACE SINKS

CORIAN SINK

805P

1'

- 3

3/ 4"

1' - 5 3/4"

METAL STUD

BASKER ROD AND BH SEALANT

SHIM

NEW WINDOW, PER

SCHEDULE

5/8" GYPSUM BOARD

5"

DATA

CONDUIT

ELECTRICAL

CONDUIT

4 1 /2"

NEW WINDOW, PER SCHEDULE

3 1/2" X 3 1/2" HSS COLUMN

5/8" GYP, SEE PARTITIAN TYPES

SEALANT AND BACKER ROD

SHIM

5/8" GYP, SEE PLAN FOR WALL TYPE

NEW WINDOW, PER SCHEDULE

BH SEALANT AND BACKER ROD

SHIM

METAL STUD

BASKER ROD AND BH SEALANT

SHIM

NEW WINDOW, PER

SCHEDULE

5/8" GYPSUM BOARD

NEW WINDOW, PER SCHEDULE

3 1/2" X 3 1/2" HSS COLUMN

5/8" GYP, SEE PARTITIAN TYPES

SEE WINDOW SCHEDULE FOR TYPE

NEW WINDOW, PER SCHEDULE

NEW WINDOW, PER SCHEDULE

SECURITY METAL MULLION

NEW WINDOW, PER SCHEDULE

SECURITY METAL MULLION

NEW WINDOW, PER SCHEDULE

NEW WINDOW, PER SCHEDULE

CONTINUOUS BACKER ROD AND

SEALANT BOTH SIDES

SHIM

FLOOR MATERIAL OVER

CONCRETE SLAB

NEW WINDOW, PER

SCHEDULE

BACKER ROD AND BH

SEALANT

SHIM

5/8" GYP, REF PLAN FOR WALL

TYPE

TYLER P CARLSON

E

PORTLAND, OREGON

R

S T

TA

G R E

I

TES

E

FO OR

N

OG

CDE RA

TE

TC

H I

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

SW

S ix th

A ve nu e, S ui te

Po rtl an d, O R

Ph on e:

/2

-4

8/ 5/

:2

9:

P M

C :\U se rs

\w ills lo m an \D oc um en ts

\R ev it

\M ac La re n

- 2

_w ills lo m an

.rv t

DOOR SCHEDULE &

WINDOW TYPES

06.27.2025

A8.01

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

25015

M ac

L A

R E

N

IN

F

IR

M A

R Y

P

H A

R M

A C

Y R

E N

O V

A T

IO

N

N P

A C

IF

IC

H W

Y . W

O O

D B

U R

N , O

R

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

DOOR SCHEDULE

MARK

ROOM

NUMBER ROOM NAME

DOOR FRAME

FIRE

RATING HDWR COMMENTS

SIZE

TYPE MATERIAL TYPE MATERIALWIDTH HEIGHT

20.1 40 MED LAB 3' - 0" 7' - 0" VL SC 1 HM 03

40 C20 CIRCULATION 3' - 0" 7' - 0" VL SC 1 HM 02

41 41 RECEIVING / STORAGE 3' - 0" 7' - 0" SF SC 1 HM 08

43 44 MED SUPPLY 3' - 0" 7' - 0" -- 1 HM

44 43 MED ROOM 3' - 0" 7' - 0" HL SC 1 HM 03

45A 42 NURSE STATION 3' - 0" 7' - 0" HL SC 1 HM 03

45B 42 NURSE STATION 3' - 0" 7' - 0" HL SC SF-H HM 03

46 45 MEETING ROOM 3' - 0" 7' - 0" HL SC 1 HM 04

47 46 NURSE SUPERVISOR 1 3' - 0" 7' - 0" HL SC 1 HM 05

48 47 NURSE SUPERVISOR 2 3' - 0" 7' - 0" HL SC 1 HM 05

49 54 PATIENT ROOM/AII 3' - 0" 7' - 0" FG SC SF-H HM 07

50 53 PATIENT ROOM 3' - 0" 7' - 0" FG SC SF-F HM 07

50A 50 DAY ROOM 3' - 6" 7' - 0" HL SC 2 HM 06

51 55 SHOWER ROOM 3' - 0" 7' - 0" SF SC 1 HM 01

52 52 PATIENT ROOM 3' - 0" 7' - 0" FG SC SF-F HM 07

53 51 PATIENT ROOM 3' - 0" 7' - 0" FG SC SF-F HM 07

54B 50 DAY ROOM 3' - 0" 7' - 0" HL SC 1 HM 06

58 D21 DENTAL OFFICE 3' - 0" 7' - 0" HL SC (E) (E) REUSE DOOR HARDWARE

61 D22 SHARED OFFICE 3' - 0" 7' - 0" HL SC (E) (E) REUSE DOOR HARDWARE

64 77 JANITOR CLOSET 3' - 0" 7' - 0" SF SC (E) (E) REUSE DOOR HARDWARE

77 83 STF TLT 3' - 0" 7' - 0" SF SC (E) (E) REUSE DOOR HARDWARE

78 82 STF TLT 3' - 0" 7' - 0" SF SC (E) (E) REUSE DOOR HARDWARE

80 80 LOCKERS 3' - 0" 7' - 0" (E) (E) (E) (E) REUSE DOOR HARDWARE

85R 41 RECEIVING / STORAGE 5' - 0" 7' - 0" (E) (E) (E) (E) REUSE DOOR HARDWARE

86R 41 RECEIVING / STORAGE 5' - 0" 7' - 0" (E) (E) (E) (E) REUSE DOOR HARDWARE

1/4" = 1'-0"

DOOR TYPES

1/4" = 1'-0"

FRAME TYPES

GENERAL NOTES: DOORS

1. FIELD VERIFY ALL DIMESIONS

2. COORDINATE FRAME SIZES WITH WALL THICKNESS AT NEW AND EXISTING

CONDITIONS

3. WINDOW DIMENSIONS ARE UNIT SIZE NOT ROUGH OPENINGS.

4. PROVIDE SAFETY GLAZING WHERE REQUIRED BY BUILDING CODE.

5. ALL DOORS SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

6. DOORS SHALL BE PREPARED AND COORDINATED FOR INSTALLATION OF

HARDWARE. DOOR HAND SHALL BE PER PLANS, REFER TO DRAWINGS FOR

DOOR SWING AND RELATIONSHIP TO FRAME.

7. TOPS AND BOTTOMS OF ALL NON-STAINED DOORS EXPOSED TO WEATHER

SHALL BE PRIMED AND PAINTED.

8. CONTRACTOR SHALL COORDINATE ALL DOOR HARDWARE, FINISHES AND

MANUFACTURER PER OWNER. HARDWARE IS OWNER-SELECTED;

CONTRACTOR FURNISHED AND INSTALLED.

9. WHERE INDICATED – SECURITY ACCESS CONTROLS ARE FURNISHED BY

CONTRACTOR; ACCESS CONTROLS TO BE VERIFIED BY OWNER.

10. SHOP DRAWINGS SHALL BE PROVIDED FOR ALL DOORS AND HARDWARE

FOR REVIEW AND APPROVAL PRIOR TO INSTALL.

11. CONTRACTOR TO COORDINATE TRIM PACKAGE AND COLORS WITH

INTERIOR DESIGN DRAWINGS, FINISH SCHEDULE, AND DEVELOPMENT

REVIEW APPROVALS FOR EXTERIOR COLORS.

12. EXTERIOR HOLLOW METAL DOORS SHALL BE INSULATED.

13. HOLLOW METAL DOORS AND FRAMES SHALL BE SHOP PRIMED AND FIELD

PAINTED, TYPICAL UNLESS OTHERWISE NOTED.

14. JAMB ANCHORS AT HOLLOW METAL FRAMES: PROVIDE NUMBER AND

SPACING OF ANCHORS AS FOLLOWS: A.

14.A. A. STUD-WALL TYPE: LOCATE ANCHORS NOT MORE THAN 18-INCHES FROM

TOP AND BOTTOM OF FRAME. SPACE ANCHORS NOT MORE THAN 32-INCHES

O.C. AND AS FOLLOWS:

14.A.i. i. THREE ANCHORS PER JAMB UP TO 60-INCHES HIGH.

14.A.ii. ii. FOUR ANCHORS PER JAMB FROM 60 TO 90-INCHES HIGH.

14.A.iii. iii. FIVE ANCHORS PER JAMB FROM 90 TO 96-INCHES HIGH.

14.A.iv. iv. FIVE ANCHORS PER JAMB PLUS ONE ADDITIONAL ANCHOR PER JAMB FOR

EACH 24-INCHES OR FRACTION THEREOF ABOVE 96-INCHES HIGH.

14.B. B. POST INSTALLED EXPANSION TYPE: LOCATE ANCHORS NOT MORE THAN

6-INCHES FROM TOP AND BOTTOM OF FRAME. SPACE ANCHORS NOT MORE

THAN 26-INCHES ON CENTER.

15. ALL SMOKE DOORS TO BE CONNECTED TO BUILDING FIRE ALARM SYSTEM.

15. HEAD ANCHORS AT HOLLOW METAL FRAMES: PROVIDE TWO ANCHORS PER

HEAD FOR FRAMES MORE THAN 42-INCHES WIDE

16. GENERAL NOTES LISTED ON THIS PAGE ARE NOT INTENDED TO BE AT THE

EXCLUSION OF NOTES LISTED ELSEWHERE; THIS DOCUMENT SET IS MEANT

TO BE COMPLIMENTARY, AND NOTES LISTED ON OTHER SHEETS MAY HAVE

BEARING/ APPLICATION TO WORK SHOWN ON THIS SHEET.

16. MAGNETIC HOLD-OPEN DEVICES SHALL BE TIED TO THE FIRE ALARM

SYSTEM.

17. ALL SMOKE DOORS TO BE CONNECTED TO BUILDING…