PROGRESS
DRAWING - DO NOT
USE FOR
CONSTRUCTION
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com
NC# P-0506
c
Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
DISCLOSURE OF INFORMATION:
CONTRACTOR SHALL COMPLY AS FOLLOWS:
A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED
INFORMATION, REGARDLESS OF MEDIUM (E.G. FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT
OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
1. THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL;
OR
2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF THE RELEASE.
B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING
OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT.
SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR
TO THE CONTRACTING OFFICER.
SINGLE PACKAGE DEDICATED OUTSIDE AIR UNIT SCHEDULE
DRAWING
CODE
SYSTEM
TYPE
OUTSIDE AIR FAN EXHAUST AIR FAN ENTHALPY PLATE - DRY DAY ENTHALPY PLATE - HUMID DAY DX COOLING HG REHEAT ELECTRIC PRE-HEATER ELECTRICAL NOTES ACCESSORIES
OUTSIDE AIR (CFM)
ESP TSP MOTOR MOTOR
EXHAUST AIR (CFM)
TSP ESP MOTOR MOTOR SUMMER LAT WINTER LAT SUMMER LAT SUMMER LAT TOT CAP SENS CAP SA EAT SA LAT CAP EAT EAT CAPACITY VOLTAGE MCA MOCP
RANGE DESIGN
(IN H2O) (IN H2O) (HP) (KW)
RANGE DESIGN
(IN H2O) (IN H2O) (HP) (KW) (°F DB) (°F WB) (°F DB) (°F WB) (°F DB) (°F WB) (°F DB) (°F WB) (MBH) (MBH)
°F °F
(MBH)
°F °F
(KW) (V/PH/HZ) (AMPS) (AMPS)
309-DOAS01 HEAT PUMP
2,500 - 1,800 2,000
1.50 4.16 3.0 - 2,000 - 1,440 1,600
3.26 1.50 3.0 - 80.6 71.5 50.6 40.6 78.0 72.8 50.0 50.0 182.0 76.0 50.0 70.0 54.0 50.6 73.0 20.0 208/3/60 169.0 200.0 1,2,3,4,5 A,B,C,D,E,F,G
309-DOAS02 HEAT PUMP
2,500 - 1,800 2,000
1.50 4.16 3.0 - 2,000 - 1,440 1,600
3.26 1.50 3.0 - 80.6 71.5 50.6 40.6 78.0 72.8 50.0 50.0 182.0 76.0 50.0 70.0 54.0 50.6 73.0 20.0 208/3/60 169.0 200.0 1,2,3,4,5 A,B,C,D,E,F,G
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. OUTDOOR DESIGN CONDITIONS: 91.0F / 77.0F 1%DB/MCWB AND 140 GRAINS/LB WITH AN 84.0F MCDB COOLING/DEHUMIDIFYING CONDITIONS. 26.0F 99% AND 22.0F 99.6% HEATING CONDITIONS. EQUIPMENT SELECTION SHALL MEET ALL CONDITIONS.
3. PERFORMANCE DATA BASED UPON MAXIMUM AIR QUANTITIES SCHEDULED.
4. EFFICIENCY RATED IN ACCORDANCE WITH ANSI/AHRI STANDARD 340/360.
5. EQUIPMENT SCHEDULE REPRESENTS REQUIRED PERFORMANCE AND CONSTRUCTION. AE MUST CONFIRM SIZING AND CAPACITY BASED UPON ACTUAL DESIGN.
ACCESSORIES: A. VARIABLE SPEED COMPRESSOR(S).
B. ONE (1) VFD PER FAN BANK.
C. FACE AND BYPASS.
D. SINGLE POINT ELECTRICAL CONNECTION.
E. MODULATING HOT GAS REHEAT.
F. BMS MSTP INTERFACE TO BACNET.
G. PHASE AND VOLTAGE MONITOR
DUCTLESS SPLIT SYSTEM SCHEDULE
DRAWING CODE (IDU/ODU) SYSTEM TYPE COOLING (AHRI STANDARD) HEATING (AHRI STANDARD) INDOOR UNIT ELECTRICAL REFRIGERANT
PIPING
WEIGHT (LBS.) NOTES ACCESSORIES
TOTAL
(BTUH)
MINIMUM
(BTUH)
EFFICIENCY MOISTURE REMOVAL
(PINTS/HR)
TOTAL
(BTUH)
MINIMUM
(BTUH)
EFFICIENCY SUPPLY
AIRFLOW (CFM)
OUTSIDE
AIRFLOW (CFM)
STYLE ESP
(IN. WG.)
POWER SUPPLY
(V/PH/HZ)
INDOOR
UNIT (MCA)
OUTDOOR UNIT MAXIMUM
LENGTH (FT.)
INDOOR
UNIT
OUTDOOR
UNIT
(V/PH/HZ) (MCA) (MOCP)
309-DAH01 / 309-DHP01 HEAT PUMP
12,000 5,800
SEER 20.8 2.0
18,000 5,500
COP 4.31 370.0 - WALL-MOUNTED - 208/1/60 1.0 208/1/60 11.0 30 70 30 100
1,2,3,4 A,B
309-DAH02 / 309-DHP02 HEAT PUMP
12,000 5,800
SEER 20.8 2.0
18,000 5,500
COP 4.31 370.0 - WALL-MOUNTED - 208/1/60 1.0 208/1/60 11.0 30 70 30 100
1,2,3,4,5 A,B
NOTES:
1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. INDOOR POWERED FROM OUTDOOR UNIT. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTOR FROM OUTDOOR UNIT TO INDOOR UNIT.
3. SUPPLY AIRFLOW VALUES ARE AT MEDIUM SPEED SETTING.
4. MOUNT ON 6" CONCRETE HOUSEKEEPING PAD.
5. PROVIDE ONE SYSTEM PER DATA/COMM ROOM UNLESS LOADS EXCEED SYSTEM CAPACITY.
ACCESSORIES: A. OUTDOOR UNIT SEACOAST PROTECTION
B. WIRED WALL-MOUNT CONTROLLER.
DEDICATED OUTSIDE AIR SYSTEM UNIT POINTS LIST
SOFTWARE POINTS FUNCTIONS ALARMS
INDOOR UNIT CONTROL POINT
DESCRIPTION
NETWORK
VARIABLE INPUT
NETWORK
VARIABLE OUTPUT
SCHEDULE TREND DISPLAY
HIGH
LIMIT
LOW
LIMIT
ABNORMALITY
ON/OFF x x x
SET MODE x x x
SET SUPPLY AIR
TEMPERATURE
x x x x
SET OUTSIDE AIR DEWPOINT x x
SET DX COIL LEAVING
TEMPERATURE
x x x x
ON/OFF STATUS x x x
MODE STATE x x x
OUTSIDE AIR DAMPER
POSITION
x x
OUTSIDE AIR TEMPERATURE x x x x x
OUTSIDE AIR DEWPOINT x x x x
OUTSIDE AIR FILTER STATUS x x
DX LEAVING AIR
TEMPERATURE
x x x x x
SUPPLY FAN SPEED STATE x x
SUPPLY AIR TEMPERATURE x x x x x
EXHAUST FILTER STATUS x x
EXHAUST FAN SPEED STATE x x
LOYTEC
ROUTER
MS/TP
IP
OUTDOOR
AIR
UNIT
VRF
SYSTEM
WATER
HEATER
BACNET
TO
MSTP
GATEWAY
BACNET
BUILDING
SUPERVISORY
CONTROLLER
DEDICATED OUTSIDE AIR SYSTEM UNIT
DESCRIPTION: DEDICATED OUTSIDE AIR SYSTEM UNIT SUPPLYING 100% OUTDOOR AIR DIRECTLY TO
SPACE, WITH DX COOLING, HOT GAS REHEAT, GAS HEATING AND FIXED PLATE ENERGY RECOVERY HEAT
EXCHANGER.
UNIT START/STOP CONTROL: START/STOP UNIT BASED ON (1) USER-DEFINED "ON/OFF" SCHEDULE.
SETPOINTS SHALL BE AS FOLLOWS UNLESS MODIFIED BY USER:
SUPPLY AIR TEMPERATURE: 73ºF (ADJ)
OUTDOOR AIR DEWPOINT TEMPERATURE: 50ºF (ADJ)
DX COIL LEAVING AIR TEMPERATURE: 50ºF (ADJ)
SYSTEM CONTROL:
DURING "ON/OCCUPIED" PERIODS, THE OUTDOOR AND EXHAUST AIR DAMPER SHALL OPEN. THE UNIT
SUPPLY AND EXHAUST FAN SHALL BE ENERGIZED.
DURING "OFF/UN-OCCUPIED" PERIODS, THE SUPPLY AND EXHAUST FAN ARE OFF AND THE OUTSIDE AND
EXHAUST AIR DAMPERS WILL BE CLOSED.
TEMPERATURE AND HUMIDITY CONTROL:
SUPPLY AIR TEMPERATURE CONTROL: A TEMPERATURE CONTROL PROGRAM RAMPS UP AND DOWN
HEATING/COOLING DEMAND VALUES BY USING THE SUPPLY AIR TEMPERATURE CONTROL SET-POINT
AND COMPARING IT WITH A SUPPLY AIR TEMPERATURE SENSOR. THE SUPPLY AIR TEMPERATURE
CONTROL SET-POINT IS DETERMINED BY THE ADJUSTABLE SUPPLY AIR TEMPERATURE SETPOINT AND
ANY APPLICABLE RESET.
DEHUMIDIFICATION: IF THE OUTSIDE AIR DEW-POINT EXCEEDS THE OUTSIDE AIR DEW-POINT SETPOINT
AND THE OUTSIDE AIR TEMPERATURE EXCEEDS THE SUPPLY AIR TEMPERATURE SETPOINT, THEN THE
UNIT WILL ENTER DEHUMIDIFICATION MODE. THE UNIT CONTROLLER WILL MODULATE COOLING
CAPACITY TO MAINTAIN THE DX COIL LEAVING AIR TEMPERATURE SETPOINT AND MODULATE THE HOT
GAS REHEAT VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.
COOLING: IF THE SUPPLY AIR TEMPERATURE EXCEEDS THE SUPPLY AIR TEMPERATURE SETPOINT, THE
UNIT WILL ENABLE THE COMPRESSORS AND MODULATE CAPACITY TO MAINTAIN SUPPLY AIR
TEMPERATURE SETPOINT.
HEATING: IF SUPPLY AIR TEMPERATURE IS LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT, THE
UNIT WILL ENABLE THE INDIRECT GAS FURNACE AND MODULATE CAPACITY TO MAINTAIN SUPPLY AIR
TEMPERATURE SETPOINT.
VRF SYSTEM INDOOR AIR HANDLER POINTS LIST
SOFTWARE POINTS ALARMS
INDOOR UNIT CONTROL POINT DESCRIPTION
NETWORK
VARIABLE
INPUT
NETWORK
VARIABLE
OUTPUT
DISPLAY HIGH LIMIT LOW LIMIT ABNORMALITY
ON/OFF x
SET MODE x
SET TEMPERATURE x x
MODE STATE x x
ROOM TEMPERATURE x x x x
FAN SPEED STATE x x
INDOOR UNIT NOTIFY x x
ERROR CODE x x x
DESCRIPTION: SPLIT SYSTEM, VARIABLE REFRIGERANT HEAT RECOVERY SYSTEM CONSISTING OF
MULTIPLE INDOOR AIR HANDLERS WITH MULTIPLE SPEED AIR VOLUME, UNDER CONTROL OF DDC
SYSTEM. EACH INDOOR UNIT MAY BE IN HEATING OR COOLING MODE INDEPENDENT OF THE OTHER
INDOOR UNITS.
HEAT PUMP INDOOR AIR HANDLER
EACH INDOOR UNIT SHALL BE SCHEDULED ON BY THE BMS SYSTEM AT THE OCCUPIED TIMES DEFINED BY
THE OWNER.
THE INDOOR UNITS SHALL BE SET TO AUTO MODE DURING OCCUPIED TIMES. DURING UNOCCUPIED
TIMES THE INDOOR UNITS SHALL BE SET TO HEAT OR COOL BASED ON OUTSIDE AIR ENTHALPY
CONDITIONS.
THE BMS SHALL SET THE OCCUPIED AND UNOCCUPIED TEMPERATURE SET-POINTS. BMS SHALL
GLOBALLY SET THIS AS A SINGLE HEATING/COOLING SET POINT, WITH AN AMBIENT RESET, 70F AT 50F
AMBIENT, AND 76F AT 80F AMBIENT, LINEAR IN BETWEEN.
DURING UNOCCUPIED TIMES THE BMS SHALL SEND THE OFF COMMAND TO THE INDOOR UNIT AT THE
START OF UNOCCUPIED TIMES AND EVERY TWO HOURS THEREAFTER TO REINFORCE THE SETBACK
CONDITIONS. THE BMS SHALL MONITOR THE ROOM TEMPERATURE AT THE REMOTE CONTROLLER IN THE
SPACE AND COMMAND THE UNIT ON IF THE OWNER SPECIFIED UNOCCUPIED LIMITS ARE EXCEED. THE
BMS SHALL SEND THE COOL MODE COMMAND WHEN THE TEMPERATURE UPPER LIMIT IS EXCEEDED OR
THE HEAT MODE COMMAND WHEN THE TEMPERATURE LOWER LIMIT IS EXCEEDED. THE BMS SHALL SEND
THE TEMPERATURE UPPER OR LOWER LIMIT AS THE SPACE TEMPERATURE SET-POINT DURING
UNOCCUPIED TIME.
VRF SYSTEM
NOT TO SCALE
CONTROL SYSTEM ARCHITECTURE
AutoCAD SHX Text
SYM
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
CONST. CONTR.
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text F
AutoCAD SHX Text
SIZE
AutoCAD SHX Text 80091
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text 18168
AutoCAD SHX Text
RENOVATION TO
AutoCAD SHX Text
BUILDING 309
AutoCAD SHX Text 19-0155
AutoCAD SHX Text N/A
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
DRAFT
AutoCAD SHX Text
T H BURTON, PE
AutoCAD SHX Text M-601
AutoCAD SHX Text
SCHEDULES AND CONTROLS
AutoCAD SHX Text
AutoCAD SHX Text
GRM
AutoCAD SHX Text
GRM
AutoCAD SHX Text
DMH
AutoCAD SHX Text