MIN. 4 SHOWERS
4 WC
2 URINALS
4 LAVS
MIN. 3 SHOWERS
4 WC
3 LAVS
BILLETING
X
BILLETING
X
HEAD CORRIDOR
X
MECHANICAL
X
MEN
X
TELEPHONE
X
VIP SLEEPING
X
VIP SLEEPING
X
VIP HEAD
X
VIP HEAD
X
MECHANICAL
X
JANITOR
X
WOMEN
X
CONFERENCE
X
BILLETING
X
BILLETING
X
GALLEY
X
LAUNDRY
X
JANITOR
X
STORAGE
X
LINEN
X
DUTY HUT
X
LOBBY
X
STAIR
X
STAIR
X
D
O A
S
D
H P
D
O A
S
D
H P
D
H P
D
H P
D
A C
D
A C
PROGRESS
DRAWING - DO NOT
USE FOR
CONSTRUCTION
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266 www.cbhfengineers.com
NC# P-0506
c
Copyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
DISCLOSURE OF INFORMATION:
CONTRACTOR SHALL COMPLY AS FOLLOWS:
A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED
INFORMATION, REGARDLESS OF MEDIUM (E.G. FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT
OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-
1. THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL;
OR
2. THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF THE RELEASE.
B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT ITS REQUEST TO THE CONTRACTING
OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.
C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER THIS CONTRACT.
SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION TO RELEASE THROUGH THE PRIME CONTRACTOR
TO THE CONTRACTING OFFICER.
1/8" = 1'-0"
0 8' 16'4'
FIRST FLOOR PLAN
PLAN
NORTH
KEYED NOTES
PLANS INDICATE SUGGESTED HVAC ZONES. REFER TO PLAN 1/M-102 FOR SUGGESTED
SECOND DECK ZONING.
THE EXISTING STRUCTURE WILL LIMIT CEILING HEIGHTS. CONTRACTOR SHALL MAKE
EVERY EFFORT TO MAXIMIZE CEILING HEIGHTS. UNDER NO CIRCUMSTANCES WILL THE
CEILINGS BE BELOW 7'-6” ABOVE FINISHED FLOOR.
MOUNT DEDICATED OUTSIDE AIR SYSTEM (DOAS) ON A CONCRETE HOUSEKEEPING PAD
PROVIDING 6-INCH CLEARANCE FROM GRADE IN GENERAL LOCATION INDICATED ON
PLANS. ADJACENT HOUSEKEEPING PADS CAN BE COMBINED. CONDENSATE DRAINAGE
PIPING SHALL BE INDIRECTLY DRAINED THEN ROUTED TO EXISTING STORM DRAIN
CATCH BASIN OR MANHOLE. OUTSIDE AIR SUPPLY DUCTWORK AND EXHAUST
DUCTWORK SHALL PENETRATE THE EXTERIOR WALL THROUGH THE EXISTING
MECHANICAL ROOM WINDOWS, PREFERABLY THE FIRST FLOOR. EXHAUST DUCTWORK
SHALL EXTEND TO THE RESTROOM AREAS AND THE VENTILATION DUCTWORK SHALL
EXTEND TO EACH INDIVIDUAL ZONE FOR VENTILATION. THE VENTILATION AIR SHALL BE
COMPLETELY DECOUPLED FROM THE VRF SYSTEM FAN COIL UNITS.
MOUNT THE OUTDOOR UNITS ON A CONCRETE HOUSEKEEPING PAD PROVIDING 6-INCH
CLEARANCE FROM GRADE IN GENERAL LOCATION INDICATED ON PLANS. EXISTING
SIDEWALKS MAY NEED REROUTING TO ACCOMMODATE THESE UNITS AND ASSOCIATED
MECHANICAL ENCLOSURE (NOT SHOWN). THE REFRIGERANT PIPING SHALL PENETRATE
THE EXTERIOR WALL AT THE EXISTING MECHANICAL ROOMS. THE REFRIGERANT PIPING
SHALL EXTEND TO BRANCH CIRCUIT CONTROLLERS SUSPENDED OVERHEAD,
PREFERABLY IN THE MECHANICAL SPACES. THE REFRIGERANT PIPING SHALL EXTEND
FROM THE BRANCH CIRCUIT CONTROLLERS TO EACH INDIVIDUAL FAN COIL UNIT PER
SYSTEM DIAGRAMS.
DUCTWORK, BRANCH CIRCUIT CONTROLLERS AND REFRIGERANT PIPING SHALL
ROUTED/INSTALLED IN MECHANICAL SPACES. CONTRACTOR SHALL MAXIMIZE AVAILABLE
SPACE FOR FUTURE IN THOSE AREAS. MECHANICAL ROOM SHALL HOUSE THE NATURAL
GAS-FIRED DOMESTIC HOT WATER PLANT. THE DOMESTIC HOT WATER PLANT SHALL BE
SIZED PER UFC REQUIREMENTS. NATURAL GAS SERVICE MUST BE BROUGHT TO THE
BUILDING FOR DOMESTIC HOT WATER PLANT. COORDINATE WITH LOCAL GAS UTILITY.
CONTRACTOR MAY GATHER FAN COIL UNIT CONDENSATE PIPING INTO GROUPS, BUT
EACH FAN COIL MUST REMAIN INDIVIDUALLY GRAVITY DRAINED. CONDENSATE PIPING
SHALL BE ROUTED DOWN INSIDE EXTERIOR WALLS AND PENETRATE THE EXTERIOR
WALL JUST ABOVE THE FIRST FLOOR. CONDENSATE DRAINS MUST SPILL ONTO A SPLASH
BLOCK.
REMOVE AND DISPOSE OF LEGACY CONCRETE MOUNTING PAD FOR CHILLER. PROVIDE
SEED AND/OR SOD AS DIRECTED BY RFP.
CHILLER/PAD
1 2
TYP.
1 2
TYP.
1 2
TYP.
1 2
TYP.
1 2
TYP.
1 2
TYP.
AutoCAD SHX Text
SYM
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SATISFACTORY TO: DATE
AutoCAD SHX Text
APPROVED: PWO OR OICC DATE
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
CONST. CONTR.
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text F
AutoCAD SHX Text
SIZE
AutoCAD SHX Text 80091
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text 18168
AutoCAD SHX Text
RENOVATION TO
AutoCAD SHX Text
BUILDING 309
AutoCAD SHX Text 19-0155
AutoCAD SHX Text N/A
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
DRAFT
AutoCAD SHX Text
T H BURTON, PE
AutoCAD SHX Text M-101
AutoCAD SHX Text
BUILDING 309
AutoCAD SHX Text
FIRST FLOOR PLAN
AutoCAD SHX Text
AutoCAD SHX Text
GRM
AutoCAD SHX Text
GRM
AutoCAD SHX Text
DMH
AutoCAD SHX Text