This federal solicitation concerns four construction projects at Tinian International Airport in the Commonwealth of the Northern Mariana Islands. The projects include construction of a cargo pad and taxiway extension using Portland cement concrete, fuel tanks with a receipt pipeline and hydrant system including one 100,000 barrel aboveground storage tank and two 60,000 barrel aboveground storage tanks, repairs and improvements to the haul route from the seaport to the airfield, and an optional maintenance support facility. The solicitation was issued by the Department of the Navy Naval Facilities Engineering Command. The cargo pad and fuel tank projects include site improvements, pavements, utilities, environmental remediation, archaeological and explosive safety monitoring to provide complete and usable facilities. A planned modification is included for munitions and explosives of concern/material potentially presenting an explosive hazard remediation for three of the projects.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
09/24/2021
C 09/24/2021
Lavine, Katherine Typewritten Text 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine Typewritten Text 09/24/2021
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:20
0 200 400 800
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
SCALE: 1:20
0 200 400 800
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:10
0 100 200 400
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:10
0 100 200 400
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C 09/24/2021
Lavine, Katherine Image
Lavine, Katherine Image
Lavine, Katherine
AT
T S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
9-24-21
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:50
0 500 1000 2000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:20
0 200 400 800
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:10
0 100 200 400
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
SCALE: 1:25
0 500 1000
AT
T S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:10
0 100 200 400
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:10
0 100 200 400
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:5
0 50 100 200
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
S
XETE FO
SA
TR
EYD.RICE
26 75 5
R
EG
IS
TE
RED ARCHITEC
T
SCALE: 1:20
0 200 400 800
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
AATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTAA XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEETTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
SCALE: 1:100
0 2000 4000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
SCALE: 1:100
0 2000 4000
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
DIGITALLY SIGNED: 09/17/2021
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSEDOFEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
EEEEENNNNNNNNNGGGGGGGGGGGGGGGGGG
IIIIIIIIIIIIIN
EL ICCCEEEEEENNNNNNNNNNNSED
RRROOOFFFEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEESSSSSSSS EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGIIIIIIIIIINNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
EEEE
EELLLICCCCEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNSSSSSSSSSSSEEEDDD
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIIIIIOOOOONAAAAAAA LLLLLLLLL EEEEEEEEEEEEEEEE
EENNNN
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIIIIIOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOONNNAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAALLLLLLLLLLLLLLLLLLLLL EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
CEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNSSSSSSSSSSSSSSSS
Shifted Hydro-Pneumatic tank T-0301 to the east to allow for electrical clearance.
R W
R W
R W
R W
RW
RW
PW
PW
PW
PW
RW
SS
SS
S
X
X
X
X
C C
SCALE
CONTROL SITE PLAN - AREA 1B2 1:400
D-120
W
AT
ER
T
R
EA
TM
EN
T C
O N
TR
O
L
SI
TE
P
LA
N
AR
EA
S
NORTH
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
TI
N
IA
N
IN
TE
R N
AT
IO
N
AL
A
IR
PO
R
T (T
IQ
TI
N
IA
N
, C N
M I
N
AV
FA
C
P
AC
IF
IC
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
M
AK
AL
AP
A, H
AW
AI
I
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AS SHOWN
1581694
FIRE PROTECTION
N
AV
FA
C
P
AC
IF
IC
FI
N
AL
R
E- D
ES
IG
N S
U
BM
IT
TA
L
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
FY
M C
AF
P
-9
0/
PA
F1
A
PS
I C
AR
G O
P
AD
W
IT
H T
AX
IW
AY
E
XT
EN
SI
O
N
CN
KY
K. YOSHIMOTO
JC
FIBER OPTIC CABLE
ROUTED IN A 27MM
CONDUIT IN INNERDUCT
TO GROUNDWELL PUMP
PANEL SEE DWG. D-121
SCALE
CONTROL SITE PLAN - AREA 3A2 1:400
LE
LSL
LSH
TOP
BOTTOM
FIBER OPTIC CABLE
ROUTED IN A 27MM
CONDUIT IN INNERDUCT
LIT
17230981
SGBBJRH
GENERAL NOTES
A REFER TO SHEET E-001 FOR LEGEND AND NOTES.
B REFER TO SHEET E-701 FOR ONE-LINE DIAGRAM.
C REFER TO OVERALL ELECTRICAL SITE PLAN ES100 FOR
OVERVIEW OF FULL SCOPE OF WORK.
D REFER TO A3/E-504 FOR TYPICAL MANHOLE/HANDHOLE
DUCTBANK RELATION DETAIL
KEYNOTES
001 ELECTRICAL HANDHOLE. REFER TO DETAIL A1/E-504. TYPICAL
(BY ELECTRICAL)
002 DIRECTIONAL BORE UNDER EXISTING PAVED ROAD AND
PROVIDE FLOWABLE FILL. (BY ELECTRICAL)
003 ELECTRICAL MANHOLE. REFER TO DETAIL A1/E-505
004 ELECTRICAL HANDHOLE. REFER TO DETAIL A1/E-504. TYPICAL
(BY ELECTRICAL).
005 = DEVICE LOCATION
006 = BURIED CABLE
007 MOUNT LE IN NOZZLE AT TOP OF TANK. MOUNT LIT AT 120CM
ABOVE GRADE ON FIELD FABRICATED STAND. FIELD ROUTE
CONDUIT BETWEEN LE AND LIT.
D-121
AT
ER
T
R
EA
TM
EN
T C
O N
TR
O
L
PL
AN
A
R
EA
SCALE
KEY PLAN
AREA 17
SGBBJRH
WATER WELL ELECTRICAL
STAND DWG- E102
FCV
FIT
FE
LIT
LE
PU-0100 WELL PUMP
TO FIRE WATER
PUMP HOUSE
SEE DWG. D-120
CONTROL SITE PLAN - AREA 17C2 1:400
17230982
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
PROJECT P-9021
GENERAL NOTES
A REFER TO SHEET E-001 FOR LEGENDS AND NOTES.
B REFER TO OVERALL ELECTRICAL SITE PLAN ES100 FOR
OVERVIEW OF FULL SCOPE OF WORK.
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-122
W
AT
ER
P
U M
PI
N
G /T
R
EA
TM
EN
T
BU
IL
D
IN
G
C O
N
TR
O
LS
P
LA
N
SCALE
SGBBJRH
AIT
FLOOR PLAN - WATER PUMP HOUSEA2 1:50
FS
WATER SOFTENER
SKID LCPFIT
PSL
PSLL
PSH
AIT
PIT
HYDRO-PNEUMATIC
TANK T-0301
DPIT
DOMESTIC WATER
PUMP PACKAGE
CONTROL PANEL
(VENDOR PACKAGE)
DOMESTIC WATER
PUMP PU-0301/0302
(VENDOR PACKAGE)
LSH
LSL
LE/LIT
TOP
LOW ON
TANK
H
H
103mm INNERDUCT WITH (4) 27mm CONDUIT
HANDHOLE (TYP)
TO WATER WELL AREATO MAINTENANCE BUILDING
WIT
PLC-0001
SODIUM HYPOCHLORITE
METERING PUMP 2, PU-0402
SODIUM HYPOCHLORITE
METERING PUMP 1, PU-0401
STARTER FOR MIXER
MXR-0300
M
TANK MIXER
MXR-0300
N O
R
TH
LV
HS
YA
YH
AE
AE
17230983
SAFETY SHOWER
SODIUM
HYPOCHLORITE
DOSING SKID
GENERAL NOTES
A REFER TO SECTION 22 00 00 FOR DOMESTIC WATER PUMP
AND HYDRO-PNEUMATIC TANK SPECIFICATION.
B REFER TO SECTION 40 05 13 FOR PIPING AND VALVE
SPECIFICATION.
C REFER TO SECTION 22 31 00 FOR WATER SOFTENER
SPECIFICATION.
D REFER TO SECTION 46 61 00 FOR WATER FILTER
SPECIFICATION.
E REFER TO SECTION 46 31 11 FOR WATER CHLORINE
EQUIPMENT SPECIFICATION.
FE
D-123
AT
ER
T
R
EA
TM
EN
T M
O
TO
R C
O N
TR
O
L D
IA
G
R
AM
A N
D C
O N
D U
C
TO
R
C O
N D
U
IT
S C
H
ED
U
LE
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
TI
N
IA
N
IN
TE
R N
AT
IO
N
AL
A
IR
PO
R
T (T
IQ
TI
N
IA
N
, C N
M I
N
AV
FA
C
P
AC
IF
IC
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
M
AK
AL
AP
A, H
AW
AI
I
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AS SHOWN
1581694
FIRE PROTECTION
N
AV
FA
C
P
AC
IF
IC
FI
N
AL
R
E- D
ES
IG
N S
U
BM
IT
TA
L
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
FY
M C
AF
P
-9
0/
PA
F1
A
PS
I C
AR
G O
P
AD
W
IT
H T
AX
IW
AY
E
XT
EN
SI
O
N
CN
KY
K. YOSHIMOTO
JC
SGBBJRH
30A MCP
M
M
M
NEMA
SIZE 2
OL
480/120V
CPT
M
PUMP MOTOR
T1
T2
T3
T1
T2
T3 480V
INCOMING
POWER
H O A
HAND
OFF
AUTO
CR1
CR1
Y PUMP
RUNNING
RAW WATER PUMP MOTOR CONTROL DIAGRAMA1 DW TANK MIXER MOTOR CONTROL DIAGRAMA3
7A MCP
M
M
OL
480/120V
CPT
M
T1
T2
T3
T1
T2
T3 480V
INCOMING
POWER
H O A
HAND
CR1
CR1
Y PUMP
RUNNING
CR1
"RUN STATUS"
TO PLC
GG GG
ELECTRONIC
OVERLOAD
L3 L2 L1
R2
R1
M
NEMA
SIZE 1
ELECTRONIC
OVERLOAD
L3 L2 L1
R2
R1
CR2 CR2
CR2
MOTOR T-STAT
CR2
NOTE 1
MOTOR T-STAT
NOTE 1
PU-0100 MIX-0300
CR3
"IN AUTO"
TO PLC
MOTOR STARTER TERMINAL
INSTRUMENT JUNCTION BOX (IJB) TERMINAL
PU-0100
CR3
CR1
"RUN STATUS"
TO PLC
CR3
"IN AUTO"
TO PLC
MOTOR STARTER TERMINAL
INSTRUMENT JUNCTION BOX (IJB) TERMINAL
CR3
OFF
AUTO
"START/STOP"
FROM PLC
"START/STOP"
FROM PLC
17230984
NOTE 2
KEYNOTES
1 REMOVE JUMPER FOR MOTORS PROVIDED WITH WINDING
THERMOSTATS.
2 STARTER PROVIDED AS PART OF PACKAGE 9021. THIS
SCOPE INCLUDES WIRING FROM INSTRUMENT JUNCTION
BOX TO THE REMOTE I/O CABINET.
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ROFEEEEEESSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS NNNNNNG
INNN
ELICEEEEEEENNNSSED
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIOOOOOOOOOOOOOONNNNNNNNNAAAAAAA LLLLLLLLLLL EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNN
1 2 3 4 5
D
C
B
A
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK
AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO
ENSURE THE INSTALLATION OF ALL WORK WITHIN THE AVAILABLE SPACE.
IF SHEET IS LESS THAN 559 X 864
REDUCED PRINT. USE GRAPHIC SCALES
1 2 3 4 5
D
C
B
A
DIGITALLY SIGNED: 09/17/2021
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ROFEEEEESSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS NNNNNNGG
IN
EL ICEEEEEEENNNNSSSED
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIOOOOOOOOOOOOOOOONNNNNNNNNNNAAAAAAAAAA LLLLLLLLLLL EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNN
Changed above ground piping material from PVC to ductile iron. Added instrument location tags to the tank plan drawing.
FLANGED
OVERFLOW
NOTES:
1. INSTALL IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
TRANSMITTER
WALL NOTES:
FLOW
FLOWTUBE
FLOW
A. PIPING SHALL BE SUPPORTED INDEPENDENT OF THE FLOWTUBE. NO PIPING STRESSES
SHALL BE TRANSFERRED TO OR THRU THE FLOWTUBE. THE FLOWTUBE SHALL BE
SUPPORTED BY ADJACENT PIPING.
B. THE FLOWTUBE SHALL BE LIFTED USING THE FURNISHED LIFTING BOLTS. IN NO CASE
SHALL ANY OBJECT BE INSERTED THRU THE FLOWTUBE.
C. TO AVOID DAMAGE TO LINER ENDS, DO NOT USE SPIRAL-WOUND OR METALLIC GASKETS.
D. SEQUENTIAL BOLT TIGHTENING & TORQUE LIMITS AS RECOMMENDED BY
MANUFACTURER MUST BE FOLLOWED.
E. PROVIDE DEDICATED CONDUIT FROM TRANSMITTER TO FLOWTUBE CONTAINING COIL
DRIVE WIRING & SIGNAL WIRING.
F. GROUNDING RINGS AT EACH END TO BE ELECTRICALLY CONNECTED TO METER
GROUND. JUMPERS TO BE #10 WIRE OR PER MANUFACTURER'S REQUIREMENTS.
G. NEVER INSTALL THE METER IN THE HIGH POINT OF THE LINE.
KEYED NOTES:
1. IF FLOWTUBE IS TO BE INSTALLED IN
VERTICAL LINE, FLUID SHALL FLOW UP INTO
TUBE TO MAINTAIN A FLOODED STATE.
QTYITEM
AR
15 NPT BALL VALVE 316 SS
15 OD TUBING 316 SS
15 OD TUBING TEE 316 SS
TRANSMITTER WITH 2 VALVE MANIFOLD
DESCRIPTION
50 PIPE STAND STEEL
15 T X 15 MALE TUBING CONNECTOR 316 SS
15 PIPE NIPPLE (15 X 80) 316 SS
1 15 OD TUBING PLUG 316 SS
LIST OF MATERIALS
PER FOOT (MIN.) FROM
PIPE TO TRANSMITTER
TUBING, FITTINGS AND
VALVES PER INSTRUMENT
SPECIFICATIONS
OPTIONAL MOUNTING
BRACKET SET
HORIZONTAL
PIPE MOUNTING
VERTICAL
50 PIPE
15 CONDUIT
CONNECTION PLUG
UNUSED CONNECTIONS
REMOVABLE
EYE BOLT
FOR LIFTING
(2 PLACES)
DEDICATED ELECTRICAL
CONDUITS FOR COIL
AND SIGNAL CABLES.
TRANSMITTER
CONNECTION 20
CONDUIT (2 PLACES)
EXPANDING ANCHOR
(HILTI TYPE HVA) (4
REQD.)
UNISTRUT OR
PIPE MOUNT
(2 REQD.)
MINIMUM PIPE LENGTH 5 DIAMETERS UPSTREAM AND 2
DIAMETERS DOWNSTREAM. I/O CONTRACTOR TO
INSTALL FLOW TUBE ACCORDING TO MANUFACTURER'S
INSTRUCTIONS.
LINE OR
VESSEL
PRESSURE TRANSMITTER
MAGNETIC FLOWMETER
A. PIPE, FITTINGS & TUBING SHALL CONFORM WITH MECHANICAL STANDARDS FOR SERVICE CONDITIONS SPECIFIED.
B. CONNECTING TUBING SHALL BE SUPPORTED ON BRACKETS OR HANGERS RIGIDLY FASTENED TO WALLS OR
STRUCTURAL MEMBERS.
C. USE 316 SS MATERIALS UNLESS OTHERWISE NOTED. THEN MATERIAL SHALL CONFORM TO THOSE SPECIFIED IN
THE APPROPRIATE AND PIPING CLASSIFICATION STANDARDS.
NOTES:
QTYITEM DESCRIPTION
LIST OF MATERIALS
1 15 PIPE NIPPLE, 15 X 80 316SS
15 TUBING TEE 316SS
15 NPT BALL VALVE 316SS
15 OD TUBING PLUG 316SS
PRESSURE GAUGE WITH SNUBBER
5 AR 15 OD TUBING 316SS
3 15 T X 15 MALE TUBING CONNECTOR 316 SS6
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
TANK LEVEL RADAR TRANSMITTERA1 A3
C1
B3
17230987
NTSNTS
NTS
NTS
LINE OR
VESSEL
SNUBBER, FURNISHED
WITH GUAGE
VERTICAL
LINE OR
VESSEL HORIZONTAL
SNUBBER, FURNISHED
WITH GUAGE
NTS
INSTRUMENT MOUNTING
STANDS & BRACKETS
50 SCHED. 40
PIPE (TYP)
(OR AS REQ'D)
(OR AS
REQ'D)
FIGURE 1A
WALL OR COLUMN MOUNTED PIPE STAND FOR TWO INSTRUMENTS
(CONFIRM DIMENSIONS PRIOR TO FABRICATION)
FIGURE 1B
SEE TYPE "E" FOR COLUMN MOUNTED
OR TYPE "F" FOR WALL MOUNTED SEE
DETAIL TO RIGHT
FIGURE 1C
TWO INSTRUMENTS
50 SCHED. 40
PIPE
50 SCHED. 40
PIPE
GRATING OR
GRID
ONE INSTRUMENTS
FLOOR MOUNTED PIPE STANDS ON GRATING
WELD CAP, 50 NOM. x SCH 40, ASTM A234, C.S.
A. PRIOR TO STAND MOUNTING, PAINT OR GALVANIZED TO AREA
BUILDING SPECIFICATIONS. IF GALVANIZED, GALVANIZE AFTER
FABRICATION. NO FIELD PAINTING OVER WELDS OR CUT ENDS.
B. USE WALL OR COLUMN MOUNTED TYPE OF SUPPORT IN
PREFERENCE TO FLOOR MOUNTED TYPES WHERE PRACTICAL.
NOTES:
(4) 18 HOLES
FOR 15 BOLTS
FIGURE 1D
FLOOR MOUNTED PIPE STAND
FOR MULTIPLE INSTRUMENT
(I N
D
IC
AT
IN
G
IN
ST
(D /P
C
EL
LS
OPTIONAL SECOND
RACK FOR 6 TO 10
DEVICES
TYPE D
CONCRETE
20 COUPLING
20 CONDUIT (MIN)
B
IC501
B
IC501
A
IC501
A
IC501
B
D-505 NTS
A
D-505 NTS
A
IC501 B
IC501
GROUT (BY
CONTRACTOR)
WALL OR
COLLUMN
SUPPORT
20 RIGID
CONDUIT
20 LIQUID-TITE FLEX
METALLIC CONDUIT
(I N
D
IC
AT
IN
G
IN
ST
(D /P
C
EL
LS
250x250x10 BASE PLATE, ASTM A36, C.S.3
PHILLIPS S-12 ANCHORS OR EQ. W/ 154
QTYITEM DESCRIPTION
LIST OF MATERIALS
A/R PIPE, 50 NOM. x SCH 40, ASTM A53 C.S.
A/R
15 BOLTS, NUTS AND WASHERS, LENGTH5 A/R
A/R
BOLTS (4), NUTS & WASHERS, 316 S.S.
TO SUIT, 316 S.S.
20 CONDULET (PUT DRAIN
WHERE REQUIRED)
NTS
CONDUIT TERMINATION AT INSTRUMENT
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
m m
FLOOR SLAB
SENSOR
MOUNTING BRACKET
CONDUIT TO
ANALYZER/
TRANSMITTER
SECURE TO WALL
WITH 8mm GALVS
CONC ANCHORS
NTS
CHLORINE ANALYZER INSTALLATION
WALL MOUNTED SENSOR
16mm PVC
BALL VALVE
STRAINER
AND FILTER
NOTE 2
SAMPLE FLOW REGULATOR
NOTE 4
AIR GAP
DRAIN
MNPT,
NOTE 3
16mm SST
PIPE FROM
SAMPLING
SYSTEM
CLEAR PIPE TO OBSERVE
BYPASS FLOW
GENERAL NOTES:
A. SAMPLE CONDITIONING SYSTEM PROVIDED WITH ANALYZER.
B. NOT ALL SAMPLE CONDITIONING PARTS SHOWN.
C. USE PVC PIPE CEMENT TO ASSEMBLE.
D. USE TEFLON TAPE ON PIPE THREADS.
E. CUT TUBE ENDS SQUARE WITH A SHARP KNIFE OR CUTTER
F. SAMPLE FLOWRATE TO SAMPLE CONDITIONING. 200-500 mL/MIN.
G. OPTIMAL INLET PRESSURE TO ANALYZER IS 1.5 PSIG. SAMPLE CONDITIONING
SYSTEM (SCS) WORKS BETWEEN 1.5 AND 75 PSIG. BELOW 5 PSIG SCS IS NOT
NECESSARY. ABOVE 75 PISG, PROVIDE PRESSURE REDUCTION ASSEMBLY.
CHLORINE
RESIDUALANALYZER
(NOTE 1)
SPECIFIC NOTES:
1. WALL MOUNT ANALYZER AFF 4'0" USING SST FASTENERS.
2. INSTALL SAMPLE CONDITIONING USING 4 27mm CONDUIT INSTALLATION
HANGERS AND UNISTRUT TO ATTACH TO WALL.
3. UNLESS OTHERWISE NOTED, USE 16mm MNPT PART (HI FLOW
OPTION). USE 8mm FOR MNPT LOW FLOW OPTION.
4. 16mm TEFLON DRAIN TUBE
WALL MOUNT
17230988A4A1
C4
SPECIFIC NOTES:
1. PROVIDE SUNSHADE OF SUITABLE SIZE. SUNSHADE SHALL BE BLENDED
ABS MATERIAL FOR UV PROTECTION AND CORROSION RESISTANCE.
FIGURE 1E
INSTRUMENT SUN SHIELD
WELDED AL
END CAP, TYP
SUNSHADE, NOTE 1
PROTECTION DEVICE;
E,G, TRANSMITTER
50 mm PIPE CLAMP
SST
BASE PLATE,
8" WIDE
SST
MOUNTING
HARDWARE
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-601
PI
PE
S C
H
ED
U
LE
17230989
GENERAL NOTES
A THE SCHEDULE PROVIDED ON THIS DRAWING REFERS ONLY
TO DOMESTIC WATER SYSTEM PIPING AND FIRE
PROTECTION SYSTEM PIPING (FROM FIRE STORAGE TANKS
TO FIRE WATER PUMP STATION DISCHARGE). FOR PIPING
ASSOCIATED WITH OTHER SYSTEMS, REFER TO THEIR
RESPECTIVE DRAWINGS AND SPECIFICATION SECTIONS.
DIGITALLY SIGNED: 09/17/2021
Revised piping schedule to include ductile iron for domestic water above ground.
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-602
VA
LV
E
SC
H
ED
U
LE
17230990
SGBBJRH
GENERAL NOTES
A THE SCHEDULE PROVIDED ON THIS DRAWING REFERS ONLY
TO DOMESTIC WATER SYSTEM PIPING AND FIRE
PROTECTION SYSTEM PIPING (FROM FIRE STORAGE TANKS
TO FIRE WATER PUMP STATION DISCHARGE). FOR PIPING
ASSOCIATED WITH OTHER SYSTEMS, REFER TO THEIR
RESPECTIVE DRAWINGS AND SPECIFICATION SECTIONS.
DEFINITIONS:
VTC VENDOR TO CONFIRM
FC FAIL CLOSED
FO FAIL OPEN
TBC TO BE CONFIRMED
BLD BUILDING
E EXTERNAL
SHC SODIUM HYPOCHLORITE
DW DOMESTIC WATER
RW WELL WATER
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ROFEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEESSSS EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
IIIIIIIIIINNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
EEL ICCEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNSSSSSSSSED SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIIIIOOOOOOOOOOOOOOONNAAAAAAAAAAAAAAA LLLLLLLLLLLL EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
CEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNSSSSSSSSSSSSS
Removed the second well water pump valves and second well water tank valves that were moved to a different project by the client.
Added a provider column to the spreadsheet and added vendor skid valves.
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-603
VA
LV
E
SC
H
ED
U
LE
17230991
SGBBJRH
GENERAL NOTES
A THE SCHEDULE PROVIDED ON THIS DRAWING REFERS ONLY
TO DOMESTIC WATER SYSTEM PIPING AND FIRE
PROTECTION SYSTEM PIPING (FROM FIRE STORAGE TANKS
TO FIRE WATER PUMP STATION DISCHARGE). FOR PIPING
ASSOCIATED WITH OTHER SYSTEMS, REFER TO THEIR
RESPECTIVE DRAWINGS AND SPECIFICATION SECTIONS.
DEFINITIONS:
VTC VENDOR TO CONFIRM
FC FAIL CLOSED
FO FAIL OPEN
TBC TO BE CONFIRMED
BLD BUILDING
E EXTERNAL
SHC SODIUM HYPOCHLORITE
DW DOMESTIC WATER
RW WELL WATER
Removed the second well water pump valves and second well water tank valves that were moved to a different project by the client.
Added a provider column to the spreadsheet and added vendor skid valves.
ST
A T
E OF TEXAS
P
ROFESSIONA L EN
GIN
EE
RL ICENSED
ROFFEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEESSSSS EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
IIIIIIIIIIIIINNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN
EEL ICCEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNSSSSSSSSSSSED SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSIIIIIOOOOOOOOOOOOOOOONNNAAAAAAAAAAAAAAAA LLLLLLLLLLLLLL EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE
CEEEEEEEEEEEEEEEEEEEENNNNNNNNNNNNNNNNNNNNSSSSSSSSSSSSSSSSSS
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-701
G
EN
ER
AL
N O
TE
S
AN
D
L
EG
EN
D
JRH
NOTES:
1. "USER'S CHOICE" IS INTENDED TO COVER UNLISTED MEANINGS THAT WILL BE USED REPEATEDLY.
2. MODIFYING LETTERS USED IN COMBINATION WITH A FIRST LETTER REPRESENT A NEW AND SEPARATE MEASURED VARIABLE.
3. APPLIES TO UNCALIBRATED DEVICES SUCH AS SIGHT GLASSES.
4. APPLIES TO VALUE OF MEASURED VARIABLE.
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
FIRST LETTER
MEASURED OR INITIATING VARIABLE
ANALYSIS
BURNER,COMBUSTION
USER'S CHOICE
USER'S CHOICE
VOLTAGE
FLOW RATE
USER'S CHOICE
HAND
CURRENT(ELECTRICAL)
POWER
TIME, TIME SCHEDULE
LEVEL
USER'S CHOICE
USER'S CHOICE
USER'S CHOICE
PRESSURE, VACUUM
QUANTITY
RADIATION
SPEED, FREQUENCY
TEMPERATURE
MULTIVARIABLE
VIBRATION, MECHANICAL ANALYSIS
WEIGHT, FORCE
UNCLASSIFIED
EVENT, STATE OR PRESENCE
POSITION, DIMENSION
MODIFIER
DIFFERENTIAL
RATIO(FRACTION)
SCAN
TIME RATE OF CHANGE
MOMENTARY
INTEGRATE, TOTALIZE
SAFETY
X AXIS
Y AXIS
Z AXIS
SUCCEEDING LETTERS
READ OUT OR PASSIVE FUNCTION
ALARM
USER'S CHOICE
SENSOR(PRIMARY ELEMENT)
GLASS, VIEWING DEVICE
INDICATE
LIGHT
USER'S CHOICE
ORIFICE, RESTRICTION
POINT (TEST) CONNECTION
RECORD
MULTIFUNCTION
WELL
UNCLASSIFIED
OUTPUT FUNCTION
USER'S CHOICE
CONTROL
CONTROL STATION
USER'S CHOICE
SWITCH
TRANSMIT
MULTIFUNCTION
VALVE, DAMPER, LOUVER
UNCLASSIFIED
RELAY, COMPUTE, CONVERT
DRIVER,ACTUATOR
UNCLASSIFIED FINAL
CONTROL ELEMENT
MODIFIER
HIGH
LOW
MIDDLE, INTERMEDIATE
USER'S CHOICE
MULTIFUNCTION
UNCLASSIFIED
TAG NAMING PER
17230992
BB SG
GATE VALVE
BALL VALVE
GLOBE VALVE
PLUG VALVE
CHECK VALVE
NEEDLE VALVE
BUTTERFLY VALVE
ANGLE VALVE
3 WAY VALVE
4 WAY VALVE
RELIEF VALVE
SELF CONTAINED PRESSURE CONTROL VALVE
AIR RELEASE VALVE
PNEUMATIC SIGNAL
ELECTRICAL SIGNAL
CAPILLARY TUBING
HYDRAULIC
DESCRIPTION
CONTINUATION DRAWING NUMBER
FIELD MOUNTED DISCRETE INSTRUMENT
LOCAL PANEL MOUNTED INSTRUMENT
PLANT CONTROL SYSTEM (PCS)
VENDOR-FURNISHED PLC CONTROL
INTERLOCK
COMMUNICATIONS LINK / SOFTWARE
RW - TC - 0105A
FUNCTION (REFER TO TABLE AT FAR RIGHT)
LOW SELECT
MID SELECT
SUM
2 OUT OF 2 VOTE
AVERAGE
SAME-SHEET CONTROLS CONTINUATION
"OR" SELECT
HIGH SELECT
INSTRUMENT AND CONTROL VALVE PROCESS LOOP NUMBERING RANGES BY SYSTEM
SYSTEM PREFIX TAG NUMBER SERIES
CHLORINE CL 0400-0499
DOMESTIC DW 0300-0399
FIRE WATER FW 0200-0299
RAW WATER RW 0100-0199
DUMP VALVE
AIR OPERATED DIAPHRAM
MOTOR OPERATED
SOLENOID
PISTON OPERATED
BACKFLOW PREVENTER
FAN
PUMP (CENTRIFUGAL)
I/P
TO/FROM P999
HPS FROM STEAM HEADER
ELECTROPNEUMATIC POSITIONER
EXPANSION JOINT
ROUTE TO NEAREST SANITARY DRAIN INLET
BREAK FLANGES
CHANGE IN PIPE SIZE (CONCENTRIC)
SCREWED CAP
BUTTWELD CAP
BLIND FLANGE
ORIFICE METER/RESTRICTION ORIFICE
START-UP STRAINER
MAGNETIC FLOWMETER
VENTURI NOZZLE
CLAMP-ON ULTRASONIC FLOW METER
HOSE CONNECTION
SPRAY NOZZLE
STEAM TRAP
FLEXIBLE HOSE
BASKET STRAINER/FILTER
MECHANICAL SEAL COOLER
PIPING/VENT THRU ROOF
RELIEF VALVE WITH DRIP PAN ELBOW
INJECTION QUILL
MALE CAM LOCK FITTING
TURBINE FLOWMETER
SIGHT GLASS FLOW INDICATOR
UNION
SAFETY SHOWER/EYE WASH
TIE-IN POINT
"Y" STRAINER
TEMPERATURE ELEMENT WITH THERMOWELL
TE
CP CONDENSATE POT
S
CHANGE IN PIPE SIZE (ECCENTRIC)
I
2oo2 n
OR
VORTEX FLOWMETER
M
M
T
SG
GAUGE GLASS VALVE
STOP CHECK VALVE
VALVE SYMBOLS
VALVE ACTUATOR SYMBOLS
PUMP/FAN SYMBOLS
PIPING SYMBOLS
INSTRUMENTATION SYMBOLS
MISCELLANEOUS INLINE EQUIPMENT
CONTROLS SYMBOLOGY
INSTRUMENT & CONTROL VALVE TAG NUMBERING
COMBINATION
PRESSURE
REDUCING/DESUPERHEATING
VALVE
INSTRUMENT LINE TYPE INDENTIFICATION
LINE CONTINUATION DESIGNATION
FLAME ARRESTOR
SILENCER
THERMOWELL
CHEMICAL METERING PUMP
FLUID HAMMER ARRESTOR
V VACUUM BREAKER
ROTOMETER
PLATE/FRAME HEAT EXCHANGER
DUPLEX BASKET STRAINER
PUMP - ROTARY/PD
PRESSURE INSTRUMENT WITH ROOT VALVE - PIT
REFER TO INSTRUMENT INSTALLATION DETAILS
(IC - DRAWINGS) FOR INSTRUMENT VALVE
MANIFOLD REQUIREMENTS
2 OUT OF 3 VOTE2oo3
CORIOLIS FLOW ELEMENTC
ANNUBAR FLOW ELEMENT
SPECTACLE BLIND
# VENDOR NOZZLE/CONNECTION NUMBER
AR
VFD VARIABLE FREQUENCY DRIVE
DRAIN AFTERCOOLER
SYSTEM (REFER TO TABLE AT FAR RIGHT)
SKID PACKAGES
O H A
HAND
OFF
AUTO
PROCESS LOOP NUMBER (REFER TO
TABLE AT FAR RIGHT)
SUFFIX - OPTIONAL
LE LEVEL (RADAR)
LT SUBMERSIBLE HYDROSTATIC
LEVEL INSTRUMENT
M
SUBMERSIBLE PUMP
HAND-OFF-AUTO SWITCH
MIXER
ABBREVIATIONS
MSC - MANUFACTURER SUPPLIED CABLE
HIGH AND LOW ALARM DESIGNATION
Added missing instrument symbols to the legends sheet
V
OF
FIRE WATER TANK, 817.6 kL
V
OF
DOMESTIC WATER TANK, 7570 L
M
ZSC
ZCC
V-0107
LSH
LV
V-0300A
V-0300B LSL
LE/LIT
LIT
H
L
V-0210A
V-0210B
LSH
LSL
LAH
LAL
V-0301
V-0212
D-704
F-504
LAH
LAL
V-0416
V-0302
LIC
H
L
LIC
D
A
C B
V-0417
(NORMALLY CLOSED)
V-0304
AE
CL2
100-RW-C900PVC
250-RW-CS
15-CL-SCH40PVC
-C
L-
SC
H
PV
C
V-0300C
100-RW-SCH40PVC
5-
D W
-S C
H
PV
C
100-DW-SCH40PVC
250-RW-CS
100-RW-CS
5-
R W
-C S
T-0210
T-0300
TO DOMESTIC
WATER PUMPS
FROM FIRE
PUMPS RETURN
FROM SODIUM
HYPOCHLORITE SYSTEM
V-0105
A
D-703C o o o o o o
H AI
0304 (CL2)
LG
LG
TO GRADE
TO
GRADE
HS
HS
YH
YH
YA
YA
BEACON HORN
o o o o o o o o o o
OR o o o o o o o
ORo
AIT
CL2
MSC
1o
YI
0300B
YC
HIS
HOA
YI
RUN STATUS YI
0300A
M
DOMESTIC WATER
TANK MIXER
MXR-0300
oIoY
ALARM SILENCE
OR o I o W
ZCO
ZSO
o o
ED
o o
Z o
LE
RAW WATER PUMP
M
ZT
YC
ZI
FCV
0103V-0102
FIT
FE
FI
PI
LI
PSV
RUN
STATUS
YI
HOA
HIS
YI
0100B
YI
0100A
YC
AUTO
OR
D
B
OR
A
C
M
V
V-0100A V-0100B
CHK-0108
PUMP TO
WASTE
CONNECTION
V-0109 V-0111
AV
50-RW-SS316
-R
W -P
VC
o o o o o o
PU-0100
LT
LI
AR
YC
HIS
D
4o
5o
2o o o o o o3
MSC
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-702
R
AW
W
AT
ER
S
YS
TE
M P
&I D
17230993
SGBBJRH
GENERAL NOTES
A SEE THE LOOP DESCRIPTION ATTACHED TO SECTION
40 95 00 OF THE SPECIFICATIONS FOR A DETAILED
DESCRIPTION OF THE DOMESTIC WATER SYSTEM CONTROL
PHILOSOPHY.
B REFER TO SECTION 33 11 00 FOR PIPING AND VALVES
ASSOCIATED WITH THE FIRE WATER TANKS.
KEYNOTES
1 CHLORINE SUPPLY TO DOMESTIC WATER TANK TO BE IN
DOUBLE CONTAINED PIPE BELOW GROUND.
2 CHLORINE SUPPLY TO FIRE WATER TANKS TO BE SITE RUN
INSIDE THE BUILDING BY CONTRACTOR.
3 LOCATED ON PLC-01.
4 LOCATED OUTSIDE WATER TREATMENT BUILDING.
5 HOA INTEGRAL TO VALVE ACTUATOR.
6 CONNECT DRAIN TO BUILDING DRAINAGE SYSTEM.
Removed second fire water tank, changed the size of the remaining tank, removed well water pump and equipment that was installed as part of another project, revised the alarm connections between sheets, and updated instrument symbols to match the specification requirements.
CL2
pH
TEMP
S
BRINE TANK
PSH
PSL
PAH
PAL
V-0330
V-0331
PSLL
PI
PALL
V-
V-
V-
V-
AIT
PIT
LOCAL
CONTROL
PANEL
DPIT
DPI
V-0314V-0313
H
PI
V-0312
V-0310
V-0306
V-0305
V-0307
V-0311
CHK-0308
CHK-0309
START
/STOP
YC
HOA
HIS
RUN
STATUS
FAULT
YA
YI
START
/STOP
YC
HOA
HIS
RUN
STATUS
FAULT
YA
YI
H
L
L
LL0315
LSH
MINERAL
TANK 2
MINERAL
TANK 1
FE
PI
PI
S
PI
S
PI
D
WATER SOFTENER SYSTEM SKID
DOMESTIC WATER PUMP SKID
PIC
TI
H
L
H
L
AI
0314A
AI
0314B (CL2)(pH)
FE
FI
J
K
J
K
CP
CP
TO PLUMBING
CONNECTIONS
HYDRO
PNEUMATIC
TANK
T-301
-D
W -S
C H
PV
C
80-DW-SCH40PVC
PI
100-DW-SCH40PVC
FROM DOMESTIC
WATER TANK
100-DW-SS316
0-
D W
-S S3
50-DW-SS316
50-DW-SS316
DOMESTIC
WATER PUMP 1
PU-0301
DOMESTIC
WATER PUMP 2
PU-0302
50-DW-SS316
50-DW-SS316
CARTRIDGE
FILTER
FLT-0300
V-031580-DW-SCH40PVC
V-
STR-0300
V-
V-
V-
V-
V-
V-
V-0324
SV-0322
SV-0323V-0325
V-
AV
D
TO SITE
D-702C
P-701
-D
W -S
C H
PV
C
LSL
FIT
Lo
Mo o7
FIT
o 6
CL2
pH
TEMPAE
MSC
o o o o o o o o o o oL oM o o
D
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-703
D O
M
ES
TI
C
W
AT
ER
S
YS
TE
M P
&I D
17230994
SGBBJRH
KEYNOTES
1 VALVE HEAD ASSEMBLY.
2 DIAPHRAGM TANK.
3 DPIT CONNECTIONS INTEGRAL TO CARTRIDGE FILTER
HOUSING.
4 CONNECT DRAIN TO BUILDING DRAINAGE SYSTEM.
Updated the instrument symbols and alarm interconnections and made the skid delineation lines consistent.
FS
P-701
SAFETY SHOWER
AND EYE WASH
FA
25-DW-SCH40PVC V-0350
FROM PLUMBING
CONNECTIONS
SODIUM HYPOCHLORITE DOSING PACKAGE
WE
WIT
WI
0401 L
BUND
V-0406
V-0409
PI
T-0400 50L
15-CL-SCH40PVC 4
V-0401
V-0404 V-0402
V-0405
V-0408
STR-0401
STR-0402
SODIUM HYPOCHLORITE
METERING PUMP 1
PU-0401
SODIUM HYPOCHLORITE
METERING PUMP 2
PU-0402
15-CL-SCH40PVC
15-CL-SCH40PVC
V-0407
V-0410
V-0411
CHK-0412
15-CL-SCH40PVC
TO DOMESTIC
WATER TANK
15-CL-SCH40PVC
D-702A
V-0413
FLUSHING
POINT
V-0414
V-0403
CALIBRATION
TUBE
15-CL-SCH40PVC
15-CL-SCH40PVC
-C
L-
SC
H
PV
C
YI
M
RUN
STATUS
YC
0401 START/
STOP
SI
0401 SPEED
SC
o oIoY oZ
YI
M
RUN
STATUS
YC
0402 START/
STOP
SI
0402 SPEED
SC
o oIoW oX o8 o H o H
1 2 3 4 5
D
C
B
A
1 2 3 4 5
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
AS SHOWN
1581694
FIRE PROTECTION
TEXAS REGISTERED ENGINEERING FIRM F-2966
JACOBS GOVERNMENT SERVICES COMPANY
777 MAIN STREET
FORT WORTH, TEXAS 76102
A/E INFO
D
C
B
A
A/E Contract No. N62742-17-D-0003 A/E Task Order No. N6274218F0340
JEG NO. WFXO6305
DRAWFORM REVISION: 30 APR 2015
DATE
CN
KY
K. YOSHIMOTO
JC
D-704
SO
D
IU
M
H
YP
O C
H
LO
R
IT
E
ST
O R
AG
E
AN
D
D O
SI
N
G S
YS
TE
M P
&I D
GENERAL NOTES
A SEE THE CONTROL LOOP DESCRIPTIONS ATTACHED TO
SECTION 40 95 00 OF THE SPECIFICATIONS FOR A DETAILED
DESCRIPTION OF THE DOMESTIC WATER SYSTEM CONTROL
PHILOSOPHY.
B SODIUM HYPOCHLORITE DOSING SYSTEM VENDOR WILL
PROVIDE EQUIPMENT WITHIN VENDOR PACKAGE LIMITS.
UNLESS OTHERWISE INDICATED ON THE VALVE SCHEDULE
OR THE SPECIFICATIONS, INTERCONNECTING PIPING,
INCLUDING ISOLATION VALVES, TO BE SUPPLIED BY
CONTRACTOR.
C SODIUM HYPOCHLORITE TANK TO BE EMPTIED VIA
FLUSHING POINT BEFORE REFILLING VIA TANK LID.
17230995
SGBBJRH
KEYNOTES
1 SODIUM HYPOCHLORITE TANK AND METERING PUMPS
SHALL BE INSTALLED IN MANUFACTURER OR SUPPLIER
PROVIDED BUND WITH THE PUMPS MOUNTED ON A SHELF
AT AN APPROXIMATE HEIGHT BETWEEN 900 AND 1100 MM
AND OF A MATERIAL COMPATIBLE WITH SODIUM
HYPOCHLORITE.
Updated the drawing notes and made the skid delineation lines consistent.
RAW WATER
WELL PUMP
WATER TREATMENT
BUILDING
PL
C
PO
W
ER
S
U
PP
LY
0 1
D I
D O
3 4 5 6
E/
IP
RACK 01 SP
AR
E
SP
AR
E
AI AO
MEDIA
CONVERTERE E
E
RIO-0001
REMOTE I/O PANEL
120V
FIBER
PATCH
PANEL
SCADA SWITCH
FIBER
PATCH
PANEL
9 10 11 12
PL
C
PO
W
ER
S
U
PP
LY
AI AISP
AR
E
AO
0 1
E/
IP
2 3 4 5 6 7 8
PR
O
C
ES
SO
R
RACK 01 D
I
D I
D O
SP
AR
E
SP
AR
E
SP
AR
E
D O
E E E
E
E
OPERATOR
INTERFACE
TERMINAL
PLC-0001
WATER TREATMENT MAIN PLC
120V
I/O
FO FO FO FO
E
FO FIBEROPTIC
CAT 6
HARDWIRE I/O
LEGEND
SINGLE MODE
6-PAIR FIBER
FO
I/O
INSTRUMENT
JUNCTION BOX
IJB-0001