The document removes Specification 00 22 13.00 20 (Supplementary Instructions to Offerors) in its entirety. Three cybersecurity specifications have been revised to add paragraph 1.1 "CONTROL SYSTEM APPLICABILITY": Specification 25 05 11.01 for HVAC Facility-Related Control Systems, Specification 25 05 11.02 for Fire and Life Safety Facility-Related Control Systems, and Specification 25 05 11.03 for Electrical Facility-Related Control Systems. Additionally, a "UFC PROCESS CHECKLIST" has been added as an attachment to Specification 25 05 11.02. A clarification has been issued for NAVFAC Drawing No. 14147213 (A-302) Building Section, specifying that in Detail A1, the note "FIRE BARRIER TO EXTEND ONE METER ABOVE LOW ROOF MIN" is typical where fire-rated hangar walls extend above adjacent low roof areas, with specific references to drawing locations A4/A-310, A1/A-505, A1/A-507, and A3/A-507.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Continuation Sheet
SPECIFICATION 00 22 13.00 20 SUPPLEMENTARY INSTRUCTIONS TO OFFERORS
Specification section removed in its entirety.
SPECIFICATION 25 05 11.01 CYBERSECURITY FOR HVAC FACILITY-RELATED
CONTROL SYSTEMS
Added paragraph 1.1 “CONTROL SYSTEM APPLICABILITY”.
SPECIFICATION 25 05 11.02 CYBERSECURITY FOR FIRE AND LIFE SAFETY FACILITY-
RELATED CONTROL SYSTEMS
Added paragraph 1.1 “CONTROL SYSTEM APPLICABILITY”. “UFC PROCESS CHECKLIST” added to end of specification as an attachment.
SPECIFICATION 25 05 11.03 CYBERSECURITY FOR ELECTRICAL FACILITY-RELATED
CONTROL SYSTEMS
Added paragraph 1.1 “CONTROL SYSTEM APPLICABILITY”.
NAVFAC DWG NO. 14147213 (A-302) BUILDING SECTION
In Detail A1, “FIRE BARRIER TO EXTEND ONE METER ABOVE LOW ROOF MIN” note is typical where fire rated hangar wall extends above adjacent low roof areas, such as A4/A-310, A1/A-505, A1/A- 507, and A3/A-507.