View the file

Other files

File Type Posted
N6247022R0007 NRL-CBD Amend 0005.pdf PDF
N6247022R0007 NRL-CBD Amend 0004.pdf PDF
J-0200000-13 ELINS NRL Amendment 0004.xlsx XLSX spreadsheet
J-1502000-06 PM Service Matrix - Amendment 0003.xlsx XLSX spreadsheet
J-0200000-13 ELINS NRL Amendment 0003.xlsx XLSX spreadsheet
J-1501000-05 Asset Inventories - Amendment 0003.xlsx XLSX spreadsheet
J-0200000-02-02 Wage Determination No. 2015-4281 Rev. 12272022.pdf PDF
J-0600000 Port Operations - Amendment 0003.pdf PDF
J-1503060 Pavement Clearance - Amendment 0003.pdf PDF
J-1503050 Grounds Maint and Landscaping - Amendment 0003.pdf PDF
J-1502000-16.a Interior and Exterior Lighting Systems Amendment 0003.xlsx XLSX spreadsheet
J-1502000-03 NRL Facilities Description - Amendment 0003.xlsx XLSX spreadsheet
J-1503010-04 CBD Custodial Inventory - Amendment 0003.xlsx XLSX spreadsheet
Attachment F - Section F Deliverables (Amendment 0003).pdf PDF
J-1502000-14.a HVAC and Refrigeration Systems - Amendment 003.xlsx XLSX spreadsheet
J-1002000 Supply Services - Amendment 0003.pdf PDF
N6247022R0007 NRL-CBD Amend 0003.pdf PDF
J-1604000 Wastewater - Amendment 0003.pdf PDF
J-1700000 Transportation NRL Chesa BOSC Amend 0003.pdf PDF
J-0600000-04.a Assets List - Amendment 0003.xlsx XLSX spreadsheet
N6247022R0007 NRL-CBD Amend 0002.pdf PDF
J-0200000-13 Exhibit Line Item Numbers (ELINs) (Amendment 0001).xlsx XLSX spreadsheet
J-1503010-05 CBD Custodial Floor Plans (Amendment 0001).pdf PDF
J-3 Section B Supplies or Services and Prices (Amendment 0001).pdf PDF
J-1503050-03.a Site Maps - CBD Grounds Map (Amendment 0001).pdf PDF
N6247022R0007 NRL-CBD Amend 0001.pdf PDF
J-9 Pre Proposal Conference NRL-CBD.pptx PPTX presentation
J-8 Pre-Proposal Site Visit Sign-In Sheet.pdf PDF
J-1700000 Transportation NRL Chesa BOSC (Amendment 0001).pdf PDF
J-1503050 Grounds Maint and Landscaping (Amendment 0001).pdf PDF
J-1503060 Pavement Clearance NRL.pdf PDF
J-1501000-05 Asset Inventories NRL.xlsx XLSX spreadsheet
J-1601000-07 Specification Attributes.xlsx XLSX spreadsheet
J-1503020 Pest Control NRL.pdf PDF
N6247022R0007 NRL-CBD Solicitation.pdf PDF
J-1502000-03 NRL Facilities Description.xlsx XLSX spreadsheet
J-5 Post-Award Limitations on Subcontracting Report-Deviation-Sept 2021.doc DOC document
J-1501000 Facility Management NRL.pdf PDF
J-2 Corporate Experience Project Data Sheet.pdf PDF
J-0200000 Management and Administration NRL.pdf PDF
J-1502000-06 PM Service Matrix.xlsx XLSX spreadsheet
J-0600000 Port Operations NRL.pdf PDF
J-0200000-13 Exhibit Line Item Numbers (ELINs).xlsx XLSX spreadsheet
J-1501000-03 NRL CBD Site Maps.pdf PDF
J-1601000 Utilities Management NRL.pdf PDF
Attachment F - Section F Deliverables.pdf PDF
J-3 Section B Supplies or Services and Prices.pdf PDF
J-1503010-04 CBD Custodial Inventory.xlsx XLSX spreadsheet
J-1800000 Environmental NRL.pdf PDF
J-1606000 Water NRL.pdf PDF
Show 40 more

Latest 50 of 69 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J - 1502000

FACILITY INVESTMENT

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT

NUMBER ATTACHMENT TITLE

J-1502000-01 DEFINITIONS AND ACRONYMS

J-1502000-02 REFERENCES AND TECHNICAL DOCUMENTS

J-1502000-03 FACILITIES DESCRIPTION

J-1502000-04 MAPS

J-1502000-05 ANTICIPATED SERVICE ORDERS

J-1502000-06 PREVENTIVE MAINTENANCE (PM) PROGRAM SERVICES MATRIX

J-1502000-07 AUXILIARY GENERATORS

J-1502000-08 ROLL-UP DOORS SYSTEMS

J-1502000-09 BACKFLOW PREVENTION DEVICES

J-1502000-10 BOILERS AND UNFIRED PRESSURE VESSELS (UPVS) EQUIPMENT AND

SYSTEMS

J-1502000-11 CATHODIC AND LIGHTNING PROTECTION SYSTEMS

J-1502000-12 COMPRESSED AIR SYSTEMS

J-1502000-13 FIRE PROTECTION SYSTEMS

J-1502000-14 HVAC AND REFRIGERATION SYSTEMS

J-1502000-15 TEMPERATURE STANDARDS FOR HVAC AND REFRIGERATION SYSTEMS

J-1502000-16 INTERIOR AND EXTERIOR LIGHTING SYSTEMS

J-1502000-17 ROOF DRAINS, SCUPPERS AND GUTTER SYSTEMS

J-1502000-18 EXHAUST HOODS AND DUCTS

J-1502000-19 SOLAR PANELS CLEANING

J-1502000-20 ENTRY GATES (MOTORIZED AND MANUAL)

ATTACHMENT J-1502000-01

DEFINITIONS AND ACRONYMS

DEFINITION DESCRIPTION

Crane, Category 1 Portal cranes, Hammerhead cranes, Locomotive cranes, Derricks, Floating cranes

(YD), Tower cranes, Container cranes, Mobile cranes (except those indicated as category 4), including truck, cruiser, crawler, warehouse/industrial cranes, and cranes used for dragline, pile driving, clamshell, magnet, bucket work, and Aircraft crash cranes.

Crane, Category 2 & 3 Cranes with rated capacities of 20,000 pounds or greater are category 2. Examples are Overhead traveling cranes, Gantry cranes (rail mounted), Wall cranes, Jib cranes, Pillar cranes, Pillar jib cranes, Monorails and associated hoists, Fixed hoists including chain falls. Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities less than 2,000 pounds.

Crane, Category 4 Commercial truck mounted cranes, Truck mounted articulating boom cranes, Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities of 2,000 pounds and greater. Commercial truck mounted cranes and truck mounted articulating boom cranes with OEM capacities of 2,000 pounds and greater require a licensed operator even if the cranes are down rated below 2,000 pounds capacity for administrative purposes.

Equipment, Collateral Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.

Equipment, Installed Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.

Equipment, Personal Property

Personal property equipment includes all equipment other than collateral equipment.

Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed.

Facilities Life Cycle A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.

Facilities Maintenance Management

The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”

Life-Cycle Costs A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.

Maintenance, Preventive

Maintenance designed to increase the availability of the facilities/equipment by reducing the number of unexpected breakdowns or service interruptions. It is any planned maintenance activity that improves equipment life and avoid any unplanned maintenance requirements.

Management Information Systems- Maintenance

A computerized system that will provide sufficient information for management to evaluate differences between budgets and actual costs and evaluate performance.

Repair Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term

DEFINITION DESCRIPTION

also applies to replacement of the entire unit or system if beyond economical repair.

The intent of repair is to have the equipment at normal working condition.

Replacement Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters.

Replacement is performed when the equipment has reached the end of its useful life;

when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.

Restoration Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.

Sustainment Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.

ACRONYM TITLE

ACO Administrative Contracting Officer BPVC Boiler and Pressure Vessel Code BW Biweekly CDR Contract Discrepancy Report CIA Controlled Industrial Area CMMS Computerized Maintenance Management System COR Condition of Readiness DBH Diameter at Breast Height DoD Department of Defense DoN Department of Navy DRMO Defense Reutilization Management Office EPA Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act FAR Federal Acquisition Regulation FFP Firm Fixed Price FIFRA Federal Insecticide, Fungicide, and Rodenticide Act FSC Facility Support Contract GFE Government-furnished Equipment GFF Government-furnished Facilities GFM Government-furnished Materials GPWS Guide Performance Work Statements HCA Head Contracting Agency HVAC Heating, Ventilation, and Air Conditioning ICAP Infrastructure Condition Assessment Program ICP Integrated Contingency Plan IDIQ Indefinite Delivery Indefinite Quantity IFLOLS Improved Fresnel Lens Optical Landing System IPM Integrated Pest Management IPMIS Integrated Pest Management Information System IPMP Integrated Pest Management Plan KO Contracting Officer LAN Local Area Network M Monthly MSDS Material Safety Data Sheets NFPA National Fire Protection Association NAVFAC Naval Facilities Engineering Command NMCI Navy Marine Corps Intranet NOSC Navy-On-Scene Coordinator PAP Performance Assessment Plan PAR Performance Assessment Representative PAW Performance Assessment Worksheet PEO Program Executive Officer PM Project Manager PRCSP Permit Required Confined Space Program PWS Performance Work Statement Q Quarterly QC Quality Control RPIE Real Property Inventory Equipment SC Security Clearances SCADA Supervisory Control And Data Acquisition

SM Semimonthly SOP Standard Operating Procedures SPAR Senior Performance Assessment Representative SRM Sustainment, Restoration and Modernization TE Technical Evaluation UFC Unified Facilities Criteria UPV Unfired Pressure Vessel VIQ Variation in Quantity WBS Work Breakdown Structure BPVC Boiler and Pressure Vessel Code HVAC Heating, Ventilation, and Air Conditioning RPIE Real Property Inventory Equipment SCADA Supervisory Control And Data Acquisition SRM Sustainment, Restoration and Modernization UFC Unified Facilities Criteria UPV Unfired Pressure Vessel VTE Vertical Transportation Equipment

ATTACHMENT J-1502000-02

REFERENCES AND TECHNICAL DOCUMENTS

29 CFR 1910.151 Medical Services And First Aid 40 CFR 60 Standards Of Performance For New Stationary Sources (NSPS) 40 CFR 63 National Emission Standards For Hazardous Air Pollutants For Source Categories 40 CFR 89 Control Of Emissions From New And In-Use Nonroad Compression-Ignition Engines

40 CFR 280 Technical Standards And Corrective Action Requirements For Owners And Operators Of Underground Storage Tanks (UST)

40 CFR Part 112 Oil Pollution Prevention

9 VAC 25-91-10 VA AST REGS

API 570 Piping Inspection Code API 653 Aboveground Storage Tank Inspector API 1631 Interior Lining Of Underground Storage Tanks ANSI Z358.1-2009 American National Standard For Emergency Eyewash And Shower Equipment ASTM E 1990 Standard Guide For Performing Evaluations Of Underground Storage Tank Systems MIL-HDBK-419A Grounding, Bonding, And Shielding For Electronic Equipments And Facilities

MIL-STD-188-124B

Grounding, Bonding And Shielding For Common Long Haul/Tactical Communication Systems Including Ground Based Communications-Electronics Facilities And Equipments

NLPA 631 Entry, Cleaning, Interior Inspection, Repair And Lining Of Underground Storage Tanks

NAVFACINST

11230.1 Inspection, Certification And Audit Of Crane And Railroad Trackage-

NAVFACINST

11300.37 Energy And Utilities Policy Manual

NAVFAC MO-200 Facilities Engineering Electrical Exterior Facilities NAVFAC MO-201 Electric Power Distribution Systems Operations NAVFAC MO-206 Maintenance And Operation Of Air Compressor Plants NAVFAC MO-209 Maintenance Of Steam, Hot Water And Compressed Air NAVFAC MO-210 Maintenance And Operation Of Water Supply, Treatment, And Distribution Systems NAVFAC MO-230 Petroleum Fuel Facilities NAVFAC MO-912 Auxiliary Generators NAVFAC MO-322 Inspection Of Shore Facilities, Volume I And II NAVFAC P-307 Management Of Weight Handling Equipment NAVFAC MO-230 Petroleum Fuel Facilities NAVFAC MO-102 Maintenance And Repair Of Surface Areas NAVMED P-5010-4 Manual Of Naval Preventive Medicine Swimming Pools And Bathing Places NAVSEA OP-5 Ammunition And Explosives Safety Ashore NFPA 30 Flammable And Combustible Liquids Code NFPA 30A Code For Motor Fuel Dispensing Facilities And Repair Garages NFPA 780 Standard For The Installation Of Lightning Protection Systems NFPA 99 Health Care Facilities Code NFPA Standard 96 National Fire Protection Association, NAVSUP P-558 Fuel Management Ashore NAVSUPINST 4750.1 Automated Fuel Maintenance System OPNAVINST 5090.1 Environmental Readiness Program Manual

TM 5-693

Uninterruptible Power Supply System Selection, Installation, And Maintenance For Command, Control, Communications, Computer, Intelligence, Surveillance, And Reconnaissance (C4ISR) Facilities

STI SP001 Inspection Of Aboveground Storage Tanks (ASTS) UFC 3-230-02 Operation And Maintenance: Water Supply Systems UFC 3-240-13FN Industrial Water Treatment Operation And Maintenance

ATTACHMENT J-1502000-02

REFERENCES AND TECHNICAL DOCUMENTS

UFC 3-250-08FA Standard Practice For Sealing Joints And Cracks In Rigid And Flexible Pavements UFC 3-270-01 Asphalt Maintenance And Repair Of Surface Areas UFC 3-270-01 Asphalt Maintenance And Repair UFC 3-270-02 Asphalt Crack Repair UFC 3-410-01 Design: Petroleum Fuel Facilities UFC 3-410-06N Central Heating Plants Operation And Maintenance

UFC 3-430-07 Operations And Maintenance: Inspection And Certification Of Boilers And Unfired Pressure Vessels

UFC 3-460-03 O&M: Maintenance Of Petroleum Systems UFC 3-540-07 Operation And Maintenance (O&M): Generators UFC 3-570-06 O&M: Cathodic Protection Systems UFC 3-560-01 Operation And Maintenance: Electrical Safety UFC 4-010-06 Cybersecurity Of Facility-Related Control Systems

UFC 3-600-02 Operations And Maintenance: Inspection, Testing, And Maintenance Of Fire Protection Systems

UG-2029-ENV Cross-Connection Control And Backflow Prevention Program Implementation At Navy Shore Facilities

UL 58 Standard For Steel Underground Tanks For Flammable And Combustible Liquids 29 CFR 1910.151 Medical Services And First Aid 40 CFR 60 Standards Of Performance For New Stationary Sources (NSPS) 40 CFR 63 National Emission Standards For Hazardous Air Pollutants For Source Categories 40 CFR 89 Control Of Emissions From New And In-Use Nonroad Compression-Ignition Engines

40 CFR 280 Technical Standards And Corrective Action Requirements For Owners And Operators Of Underground Storage Tanks (UST)

40 CFR Part 112 Oil Pollution Prevention

9 VAC 25-91-10 VA AST REGS

API 570 Piping Inspection Code API 653 Aboveground Storage Tank Inspector

Facilities description is provided as a separate file. Refer to Excel file “J-1502000-03 NRL Facilities Description”.

ATTACHMENT J-1502000-03

FACILITIES DESCRIPTION

ATTACHMENT J-1502000-04

MAPS

Naval Research Lab Chesapeake Beach

ATTACHMENT J-1502000-05

ANTICIPATED SERVICE ORDERS

ANNUAL ANTICIPATED SERVICE ORDERS

EMERGENCY URGENT ROUTINE

25 50 350

HISTORICAL BREAKDOWN BY TRADE

Option Year 6 Electrical Plumbing Mechanical General Maintenance Roof Fire

Alarm Fuel

Emergency 6 0 7 2 0 0 0 Urgent 6 2 18 2 0 1 1 Routine 14 11 29 48 3 0 2

Option Year 5 Electrical Plumbing Mechanical General Maintenance Roof Fire

Alarm Fuel

Emergency 2 2 7 0 0 0 0 Urgent 2 3 20 5 0 0 0 Routine 28 12 38 76 5 0 2

Option Year 4 Electrical Plumbing Mechanical General Maintenance Roof Fire

Alarm Fuel

Emergency 0 5 1 2 0 0 0 Urgent 4 4 13 0 3 4 0 Routine 23 24 43 80 6 4 2

ATTACHMENT J-1502000-06

PREVENTIVE MAINTENANCE (PM) PROGRAM SERVICES MATRIX

Preventive maintenance program services matrix is provided as a separate attachment. Refer to Excel file “J- 1502000-06 Preventive Maintenance (PM) Program Services Matrix”.

ATTACHMENT J-1502000-07

AUXILIARY GENERATOR SYSTEMS

Auxiliary Generator Systems commence at and include the utility isolation point of connection. The Contractor shall develop and implement a PM program for the Auxiliary Generator Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Auxiliary Generator Systems, such as:

batteries, fuel tanks, generator, inverters, rectifiers, regulators, prime mover, pumps, piping, transfer switches, switchgear, meters, monitoring and control systems, uninterruptible power supply, wiring, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

BLDG LOCATION SYSTEM

C6 EXTERIOR

SOUTHSIDE

Emergency Propane Generator up to 15

KVA

C50 WEST SIDE

Emergency Propane Generator up to 15

KVA

C75 WEST SIDE

Emergency Diesel generator, over 15

KVA

C84 SOUTH SIDE

Emergency Diesel generator, over 15

KVA

C202elmr 201GEN WEST

SIDE

Emergency Diesel Generator, over 15

KVA

C331 30 Emergency Diesel

Generator, 20KW/25KVA/60HZ

C331 31 Emergency Diesel Generator, 50

KW/63KVA/60HZ

ATTACHMENT J-1502000-08

ROLL-UP DOORS SYSTEMS

The Contractor shall develop and implement a PM program for Roll-Up Doors Support Systems both manual and motorized, and all mechanically and electrically interlocked ancillary parts, equipment, and components of Roll- Up Door Systems. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

BLDG LOCATION TYPE

C4 NORTH WALL Door, Overhead, manual, up to 24’ high x 25’ wide C4 137 Overhead, manual, up to 24’ high x 25’ wide

C29 WEST WALL Overhead, manual, up to 24’ high x 25’ wide C47 EAST WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C49 SOUTH WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C50 NORTH WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C50 SOUTH WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C75 EAST WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C76 WEST WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C76 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C76 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C76 EAST WALL Overhead, manual, up to 24’ high x 25’ wide

C218 WEST WALL Overhead, manual, up to 24’ high x 25’ wide C243 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C243 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C243 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C244 EAST WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C250 NORTH WALL Overhead, manual, up to 24’ high x 25’ wide C286 NORTH WALL Overhead, manual, up to 24’ high x 25’ wide C309 EAST WALL Overhead, manual, up to 24’ high x 25’ wide C309 NORTH WALL Overhead, manual, up to 24’ high x 25’ wide C313 WEST WALL Overhead, manual, up to 24’ high x 25’ wide C314 SOUTH WALL Overhead, manual, up to 24’ high x 25’ wide C335 EAST WALL Door, overheard, roll-up, electric, up to 24’ high x 35’ wide C331 FENCE GATES Rolling (1) – Fence Gate C331 FENCE GATES Swing (3) – Fence Gate

C331 SECURITY

ENTRANCE

Modular Security System – (2 Turn Stiles, 1 Door, 2 Way Point

DC Out Door Power Supplies: 12V, 24V)

ATTACHMENT J-1502000-09

BACKFLOW PREVENTION DEVICES

Backflow Prevention Devices commence at, and includes the utility isolation point of connection. The Contractor shall develop and implement a Preventive Maintenance (PM) Program to maintain, inspect, test and certify, and make all necessary repairs to the Backflow Prevention Devices and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Backflow Prevention Devices, such as: bleeders, regulators, valves, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

BLDG LOCATION TYPE

C75 B1 Backflow prevention device, up to 4” C76 124 Backflow prevention device, up to 4” C81 INTERIOR Backflow prevention device, over 4” C84 PUMP ROOM Backflow prevention device, up to 4” C313 EXTERIOR Backflow prevention device, over 4” C314 100 Backflow prevention device, over 4”

ATTACHMENT J-1502000-10

BOILER AND UPV SYSTEMS

Boiler and UPV Systems commence at, and includes the utility isolation point of connection and terminate at the steam/hot water point of delivery. The Contractor shall develop and implement a Preventive Maintenance (PM) Program for the Boilers and UPV Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Boiler and UPV Systems, such as: burners, heat exchangers, flash tanks, meters, pressure vessel, pumps, piping, valves, steam regulating valves, steam traps, distribution lines, insulation, chemical feed system, condensation return lines, condensate meters, monitoring and controls systems, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

BLDG LOCATION SYSTEM BLDG LOCATION SYSTEM

C1 B1 Domestic Water Heater (electrical) C75 B 10 Expansion Tank / Hot Water

C1 200 Instant Hot C75 B1 Expansion Tank / Hot Water

C2 B2 Boiler / Hot Water C75 B1 Expansion Tank / Cold Water

C2 B2 Expansion Tank / Hot Water C75 B1 Heat Exchanger

C2 B2 Expansion Tank / Hot Water C75 B12 Domestic Water Heater (electrical)

C2 206 Instant Hot C76 124 Boiler / Hot Water / CEMLINE CORP, V300EHB12C3-RL

C2 B2 Domestic Water Heater C76 124 Expansion Tank / Hot Water

C4 130 Domestic Water Heater (electrical) C76 106 Domestic Water Heater (electrical)

C4 119 Domestic Water Heater (electrical) C84 Basement Boiler / Hot Water / Burnham, PV77WC-TBWN

C5 B4 Boiler / Hot Water / West McLain, CEW-48

C84 Pump Room Expansion Tank / Hot Water

C5 B4 Expansion Tank / Hot Water C84 Pump Room Heat Exchanger

C5 B4 Expansion Tank / Hot Water C84 102 Domestic Water Heater (electrical)

C5 B4 Domestic Water Heater (electrical) C244 101 Domestic Water Heater (electrical)

C6 B1 Domestic Water Heater (electrical) C249 103 Domestic Water Heater (electrical)

C6 110 Instant Hot C301 107 Domestic Water Heater (electrical)

C35 100 Domestic Water Heater (electrical) C307 Mech Rm Domestic Water Heater (electrical)

C47 102 Domestic Water Heater (electrical) C309 Mech Rm Domestic Water Heater (electrical)

C49 Closet Domestic Water Heater (electrical) C310 100 Domestic Water Heater (electrical)

C59 (TI) Restroom Instant Hot C314 Mech Rm Domestic Water Heater (electrical)

C75 B10 Boiler / Hot Water / Columbia, HT275 C331 31 / Outside Dry Air Tank

C331 30 Dry Air Tank

ATTACHMENT J-1502000-11

CATHODIC AND LIGHTNING PROTECTION SYSTEMS

Cathodic Protection Systems commence at, and includes the utility isolation point of connection and terminate at and includes the anode. Lightning Protection Systems commence at, and includes the utility isolation point of connection and terminate at foundation.

The Contractor shall develop and implement a Preventive Maintenance (PM) Program for the Cathodic Protection Systems and Lightning Protection Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Cathodic Protection Systems, such as: anodes, cathodes, rectifiers, wiring, monitoring and controls systems, etc. and of the Lightning Protection Systems such as: lightning rods, conductor cables, ground electrodes, utility bonding clamps, surge protection., etc.

BLDG LOCATION CATHODIC PROTECTION SYSTEM

C80 STAND PIPE RECTIFER/ANOID

BLDG LIGHTNING PROTECTION

SYSTEM

C331 30" Mast (4) 50" Mast (4)

ATTACHMENT J-1502000-12

COMPRESSED AIR SYSTEMS

Compressed Air Systems commence at and includes the utility isolation point of connection and terminate at the compressed air point of delivery. The Contractor shall develop and implement a PM program for the Compressed Air Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Compressed Air Systems, such as: compressors, regulators, unfired pressure vessels, air drying systems, distribution systems, air supply connectors, monitoring and control systems, electrical disconnects, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be

C4 137 Air Compressor C4 137 Air Compressor C4 Air Compressor

C75 B3 Air Compressor C75 107 Air Compressor C75 ROOM B3 Compressed Air Dryer C76 124 Air Compressor C84 Air Compressor C242 Air Compressor C250 Air Compressor C309 Bay Air Compressor C313 High Bay Air Compressor C313 High Bay Air Compressor C314 Mech Room Air Compressor

1001 Generator Skid Air Compressor C331 31 Air Compressor C331 31 Air Compressor C331 31 Compressed Air Dryer C331 31 Compressed Air Dryer C331 30 Air Compressor

ATTACHMENT J-1502000-13

FIRE PROTECTION SYSTEMS

Fire Protection Systems commence at and include the utility isolation point of connection. The Contractor shall develop and implement a PM program for the Fire Protection Systems and all mechanically and electrically interlocked ancillary parts, equipment and components of the Fire Protection Systems; such as: AFFF Foam, air compressors, alarm devices, alarm valves, annunciators, antennas, backflow prevention devices, Dry Chemicals, batteries, connections, control panels, detectors, diesel engines, electric motors, fuses, gauges, initiating devices, meters, notification appliances, nozzles, piping, pumps, receivers, sensors, sprinkler heads, tanks, transmitters, voice communication devices, valves (including post indicator valves), Wet Chemicals, monitoring and controls systems, emergency lights, modems, pull stations, smoke detectors, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

***Informational Note: AFFF drainage trenches shall be maintained clear and automatic valves, which close the sanitary drain and divert AFFF to a storage tank in event of activation.

FIRE ALARM LOCATIONS

C1 MISSILE AND SPACE RDT&E FACILITY

C2 ELECTRONIC AND COMMUNICATION RDT&E FACILITY

C4 ELECTRONIC AND COMMUNICATION MAINTENANCE SHOP

C5 ELECTRONIC AND COMMUNICATION RDT&E FACILITY

C6 GENERAL ADMINISTRATIVE BUILDING

C49 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C50 FACILITY ENGINEER MAINTENANCE SHOP

C75 ELECTRONIC AND COMMUNICATION RDT&E FACILITY

C76 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C79 UTILITY BUILDING

C250 RDT&E LABORATORY

C301 ELECTRONIC AND COMMUNICATION RDT&E FACILITY

C307 RDT&E LABORATORY

C309 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C310 RDT&E LABORATORY

C314 RDT&E LABORATORY

C501 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C331 MISCELLANEOUS RDT&E FACILITY

SPRINLER AND STANDPIPE LOCATIONS

C4 ELECTRONIC AND COMMUNICATION MAINTENANCE SHOP

C6 GENERAL ADMINISTRATIVE BUILDING

C49 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C75 ELECTRONIC AND COMMUNICATION RDT&E FACILITY

C76 MISCELLANEOUS ITEM AND EQUIPMENT RDT&E FACILITY

C250 RDT&E LABORATORY

ATTACHMENT J-1502000-14

HVAC AND REFRIGERATION SYSTEMS

HVAC and Refrigeration Systems commence at, and includes the utility isolation point of connection and terminate at the conditioned air point of delivery. The Contractor shall develop and implement an Preventive Maintenance (PM) Program for the HVAC and Refrigeration Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the HVAC and Refrigeration Systems such as: air handling units, blowers, boilers, chillers, compressors (including air compressors), condensers, controls, cooling towers, dehumidifiers, diffusers, driers, ducts, electrical disconnects, evaporators, fans, fan coil units, filters, fire dampers, fresh air dampers, heaters, heat exchangers, heat pumps, hoods, humidification systems, insulation, intakes, package units, piping, pumps, refrigeration boxes, registers, returns, strainers, ultraviolet lighting, valves, VAV boxes, variable frequency drives, water treatment systems, monitoring and control systems.

An assets listing is provided as a separate attachment. Reference to Excel file “J-1502000-14.a HVAC and Refrigeration Systems”

ATTACHMENT J-1502000-15

TEMPERATURE STANDARDS FOR HVAC AND REFRIGERATION SYSTEMS

HVAC Systems

Degrees Fahrenheit dry bulb Area Cooling Season Heating Season

Living & Admin. Areas (Inactive Employment) 73 68 Working Areas (Active Employment) 78 68 Storage Areas 78 40 Computer Areas 70 68 Training Areas 75 68

Refrigeration Systems Type Degrees Fahrenheit

Frozen Meat -5 to 0 Fresh Meat 30 to 34 Ice Storage 28 to 30 Dairy Products 32 to 34 Ice Cream 0 to -5 Beer 35 to 39 Fruits and Vegetables 36 to 42 Chill Room 35 to 39

ATTACHMENT J-1502000-16

INTERIOR AND EXTERIOR LIGHTING SYSTEMS

Interior and Exterior Lighting Systems commence at, and includes the utility isolation point of connection. The Contractor shall develop and implement a Lighting Systems Preventive Maintenance (PM) Program to clean, re-lamp, and make all necessary repairs to the Interior and Exterior Lighting Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the Lighting Systems, such as: replacement of defective bulbs, batteries, lamps, tubes, ballasts, fuses, starters, switches, diffusers, covers, reflectors, photocells, controls, etc. Lighting Systems types include but may not be limited to florescent, incandescent, halide, LED, CFL, flood, wall pack, areal, entrance and perimeter.

Contractor shall clean, re-lamp and repair interior and exterior lights for all C series facilities listed on the NRL Facilities Description J-1502000-03 except those in the C500 series. An assets listing is provided as a separate attachment. Reference to Excel file “J-1502000-16.a Interior and Exterior Lighting Systems.

ATTACHMENT J-1502000-17

ROOF DRAINS, SCUPPERS AND GUTTER SYSTEMS

The Contractor shall develop and implement other recurring services for the Roof Drains, Scuppers, and Gutter Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components such as:

baffles, gaskets, seals, pipes, gutters, drains, downspouts, aprons, hangers, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

FACILITY

NUMBER FACILITY NAME

C1 LABORATORY BLDG/COMM CTR CBD

C2 LABORATORY BLDG

C4 RD&T LAB

C5 ELEC RD-TEST FAC

C6 ADMINISTRATIVE BUILDING

C21 DIESEL GENERATOR HOUSE

C27 GATE HOUSE NO 2

C29 FORMER CHEMISTRY BLDG

C35 RD-TEST, OTHER

C55 LABORATORY STORAGE

C75 E. R&D TEST BUILDING

C79 CENTRAL HEATING PLANT

C84 SEWAGE TREATMENT PLANT

C87 SS PUMP STATION C CBD BLDG

C88 RADAR TOWER BUILDING

C231 BLDG N.OF BLDG C75

C242 RD TEST BUILDING

C244 CRF STORAGE BUILDING

C246 SENTRY BOOTH

C249 HIGH ENERGY FACILITY

C250 EQUIP & LIGHTING BLDG-HEF

C273 FUEL PUMP HOUSE FTF

C286 MULTI MEDIA FILTER BUILDING

C301 CRF BUILDING

C302 FIRE II CHAMBER

C303 WASTEWATER PUMPHOUSE

C307 CHEMISTRY LABORATORY BLDG.

C309 CHEMISTRY LAB/STORAGE BLDG.

C310 CHEMISTRY LABORATORY

C313 FIRE TEST BURN BLDG.

C314 HYDRALIC LABORATORY

C333 T65 ENCLOSURE CBD

ATTACHMENT J-1502000-18

EXHAUST HOODS AND DUCTS

The Contractor shall develop and implement other recurring services for the Exhaust Hoods and Ducts and all mechanically and electrically interlocked ancillary parts, equipment, and components such as: filters, fans, fan housing, plenums, grease removal devices, waterproof covers, access panels, motors, cable, retainers, ducts, baffles, full length of ventilation ducts, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be maintained.

4 142 Dryer Duct 84 201 Dryer Duct

307 Interior Exhaust Fan Fume Hood 309 Mech Room Dryer Duct

C331 31 Exhaust Fan C331 31 Exhaust Fan C331 31 Exhaust Fan C331 30 Exhaust Fan C331 30 Exhaust Fan

ATTACHMENT J-1502000-19

SOLAR PANELS CLEANING

The Contractor shall develop and implement other recurring services for the solar panel systems and all mechanically and electrically interlocked ancillary parts, equipment, and components such as: panels, inverters, breakers, meters, batteries, controllers, combiner boxes, disconnects, cables, connectors, conduit, brackets, etc.

C100 Dam

Solar Panel System

Panel is 66” X 66”.

Power is stored in batteries which powers a small electrical aerator

ATTACHMENT J-1502000-20

ENTRY GATES (MOTORIZED AND MANUAL)

The Contractor shall develop and implement other recurring services for the entry gates systems and all mechanically and electrically interlocked ancillary parts, equipment, and components such as: panels, inverters, breakers, batteries, controllers, combiner boxes, disconnects, cables, connectors, conduit, brackets, etc. The below list is provided to give a general sense of the magnitude of work but may not include all assets required to be

SITE LOCATION SIZE TYPE ELECTRICAL

Tilghman Island WEST FENCE

LINE

50’ Rolling No

Tilghman Island WEST FENCE

LINE

50’ Rolling No

Tilghman Island 229 Up to 4’ Swing Safety No Tilghman Island 229 Up to 4’ Swing Safety No Tilghman Island 229 Up to 4’ Swing Safety No Tilghman Island 229 Up to 4’ Swing Safety No Tilghman Island 229 Up to 4’ Swing Safety No Tilghman Island 229 Up to 4’ Swing Safety No

CBD Gate 1 @246 22’ Rolling Yes CBD Gate 3 West Field 36’ Rolling Yes CBD 76 22’ Rolling Yes CBD 76 22” Rolling No CBD Gate 5 @ 27 42’ Rolling No CBD Gate 6 @ 88 42’ Rolling No