This document is a Lightning Protection Plan drawing for the Marine Corps Base Camp Lejeune, specifically for repairs to BEQ BB250. The detailed technical drawing (E-801) provides comprehensive lightning protection system specifications, including:

Key technical details include a roof-mounted lightning protection system with #1/0 bare copper conductors, air terminals with cast bronze or aluminum bases, and ground rod connections. The plan specifies multiple connection types such as cross run connectors, parallel connectors, and bi-metal connectors. The lightning protection system is designed to be installed on a metal roof with conductors routed down steel downspouts, with a minimum ground rod installation of 3 feet from concrete edges. The drawing is part of the Naval Facilities Engineering Command project associated with Contract No. N40085-18-B-0044, prepared for final repairs at the Marine Corps Base.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOF HATCH

E15

TYP

#1/0 BARE COPPER

NLP LIGHTNING PROTECTION CONDUCTORS:

CLASS 1 - USE #28R COPPER CONDUCTOR

CLASS 2 - USE #28 COPPER CONDUCTOR.

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - USE #28A ALUMINUM CONDUCTOR

CLASS 2 - USE #19A ALUMINUM CONDUCTOR

FASTEN COPPER CONDUCTORS WITH NLP #1430 COPPER STANDING SEAM

METAL ROOF FASTENER. FASTEN ALUMINUM CONDUCTORS WITH NLP

#1430A ALUMINUM STANDING SEAM METAL ROOF FASTENER. LIGHTNING

PROTECTION CONDUCTORS SHALL BE FASTENED AT INTERVALS NOT MORE

THAN 36" ON CENTER.

NLP #833 CAST BRONZE STANDING SEAM METAL ROOF

AIR TERMINAL BASE. FOR SURFACES NOT

COMPATIBLE WITH COPPER USE #833A CAST ALUMINUM

STANDING SEAM METAL ROOF AIR TERMINAL BASE.

NLP FLATHEAD(TM) AIR TERMINAL:

CLASS 1 - USE #FH-C3 NP 12 NS

CLASS 2 - USE #FH-C2 NP 12 NS

FOR SURFACES NOT COMPATIBLE WITH COPPER:

CLASS 1 - USE #FH-A2 NP 12 NS

CLASS 2 - USE #FH-A2 NP58 12 NS

NO. 210 STYLE CROSS RUN

CONNECTOR

NO. B1BC STYLE PARALLEL

CONNECTOR

NO. 208 STYLE BONDING

CONNECTOR

NO. 204 STYLE PARALLEL

CONNECTOR

NO. 211, BI-METAL CONNECTOR

GROUND ROD (3/4"x10'), MIN. OF

3' FROM EDGE OF CONCRETE

GROUND CLAMP

#1/0 BARE COPPER

DOWN CONDUCTOR IN

3/4"C

TO LIGHTNING

AIR TERMINAL

CONNECT AND ROUTE

DOWN THE SIDE OF

DOWNSPOUT

SHEET KEYNOTES

GENERAL NOTES

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY

MARINE CORPS BASE

CAMP LEJEUNE, NORTH CAROLINA

NAVAL FACILITIES ENGINEERING COMMAND

SIZE CODE IDENT NO. NAVFAC DRAWING NO.

SCALE: SPEC. SHEET OF

E1 80091

CONSTR. CONTR. NO.:

AS NOTED

FINAL

REPAIRS BEQ BB250

LIGHTNING PROTECTION PLAN AND

DETAILS

E-801

148A 148A

60041678A N40085-18-B-0044

05-18-0044

SCALE: 3/32" = 1'-0"1 LIGHTNING PROTECTION PLAN

SCALE: NOT TO SCALE2 TYPICAL AIR TERMINAL WITH BASE

SCALE: NOT TO SCALE3 TYPICAL CABLE CONNECTIONS

SCALE: 3/32"=1'-0"

816 16

GRAPHIC SCALE

1. SEE SHEET E-001 FOR GENERAL NOTES

AND LEGEND.

E15 LIGHTNING PROTECTION DOWN

CONDUCTOR TO BE INSTALLED ON STEEL

DOWNSPOUT TUBE.

SCALE: NOT TO SCALE4 ROOF CONNECTION DOWN LEAD TO GROUND ROD CONNECTIONS

REVISIONS

SYM. DESCRIPTION DATE APPROVED

KELLY ROOT

J. REED

Sheets and Views
Layout1