240016 Dwgs Part 2.pdf
PDF 36 MB Posted
- Attached to
- Repair BEQ BB250
- Solicitation number
- N408525R9008
About this file
This file contains mechanical drawings and specifications for the Repair BEQ BB250 project at Marine Corps Base Camp Lejeune, North Carolina. The detailed mechanical plans cover the renovation of a barracks building, including comprehensive HVAC, plumbing, and mechanical system replacements. The scope involves installing new dedicated outside air systems (DOAS), air handling units, packaged terminal heat pumps, exhaust fans, chilled and hot water systems, and associated control infrastructure across the building's first, second, third floors, and attic.
The mechanical design includes six DOAS units with cooling, heating, and heat recovery capabilities, three air handling units, multiple unit heaters, and a chilled water system with a 110-ton air-cooled chiller. The project emphasizes energy efficiency, building automation system integration, and system controls with features like variable frequency drives, temperature reset strategies, and comprehensive monitoring and alarm capabilities. The mechanical systems are designed to provide precise environmental control, ventilation, and utility metering for the barracks facility, with extensive attention to seacoast construction requirements and anti-terrorism/force protection considerations.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
CLERKS OFFICE
XO OFFICE
COPY/KITCHENETTE
TOILET
TOILET
ADMINISTRATIVE
OFFICE
CO OFFICE
STORAGE
CLEAN GEAR
ADMINISTRATIVE
OFFICE
LAUNDRY
MECHANICAL
LAUNDRY
JANITOR
STORAGE
VENDING
OFFICE
CORRIDOR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
MECHANICAL CHASE
MECHANICAL CHASE
STAIR #3
S013
STAIR #1
S011
STAIR #2
S012
MECHANICAL CHASE
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
4" DCW
3" DHW
2" DHWR
P-106
B1
P-106
C4
P-106
B2
P-106
C1
EX 4" DCW
EX 3" DHW
EX 2" DHWR
P-106
B4
4 4 4 4 4
WH
WH
3/4" DCW
3/4" DCW
WH
WH
3/4" DCW
3/4" DCW
2" DHW2" DHW2" DHW
2" DHW
3" DHW
3" DHW1 1/2" DHW 2" DHW
2 1/2" CW 3" DCW 3" DCW 2" DCW2 1/2" DCW3" DCW3" DCW
4" DCW
2 1/2" DHW
3/4" DHWR3/4" DHWR
3/4" DHWR
1 1/2" DHWR
1 1/4" DHWR
1 1/4" DHWR
1" DHWR
3/4" DHWR 3/4" DHWR
CIRCUIT
SETTERS
FOR EACH
BRANCH
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
LOUNGE
LAUNDRY
JANITOR
STORAGE
VENDING
COMM
CORRIDOR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
237SLEEPING ROOM
SLEEPING ROOM
STAIR #3
S023
MECHANICAL CHASE
MECHANICAL CHASE
STAIR #1
S021
STAIR #2
S022
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
SLEEPING ROOM
MECHANICAL
P-107
B1
P-107
B3
P-107
B5
5 55 5 5 5 5 5 5
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
LOUNGE
LAUNDRY
JANITOR
STORAGE
VENDING
OFFICE
CORRIDOR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
STAIR #3
S033
MECHANICAL CHASE
MECHANICAL CHASE
STAIR #1
S031
STAIR #2
S032
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
MECHANICAL
P-108
B1
P-108
B3
P-108
B5
6 6 6 6 6 6 6 6 6
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-105
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
FLOOR PLANS - WATER
60041591 N40085-24-B-0016
05-24-0016 87 OF 174
N
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
3/32" = 1'-0" A3
FIRST FLOOR PLAN - WATER
3/32" = 1'-0" C3
SECOND FLOOR PLAN - WATER
3/32" = 1'-0" D3
THIRD FLOOR PLAN - WATER
N
N
PLAN NOTES - P-105
1 SEE SITE PLAN FOR CONTINUATION OF EXISTING
DOMESTIC WATER PIPING.
2 ALL PLUMBING PIPING IN THIS BUILDING IS
EXISTING TO REMAIN.
3 4"DCW, 3"DHW, AND 2"DHWR TO SITE UTILITY. SEE
SITE PLAN FOR CONTINUATION OF DOMESTIC
WATER PIPING. SEE ENLARGED OUTDOOR
MECHANICAL BUILDING FOR LOCATION OF
BACKFLOW PREVENTER.
4 2"DCW, 1-1/4"DHW, AND 1/2"DHWR UP. SEE FIRST
FLOOR ENLARGED PLAN - TYPICAL SLEEPING
ROOMS - WATER" FOR MORE DETAILS.
5 2"DCW DOWN AND 1-1/2"DCW UP. 1-1/4"DHW DOWN
AND 1"DHW UP. 1/2"DHWR UP AND DOWN. SEE
"SECOND FLOOR ENLARGED PLAN - CENTRAL
CORE - WATER" FOR MORE DETAILS.
6 1-1/2"DCW UP FROM BELOW. 1"DHW UP FROM
BELOW. 1/2"DHWR DOWN. SEE "THIRD FLOOR
ENLARGED PLAN - TYPICAL CENTRAL CORE -
WATER" FOR MORE DETAILS.
7 DROP 3/4"DCW DOWN TO WALL HYDRANT.
8 PROVIDE SHUTOFF VALVE IN VERTICAL FOR
EXTERIOR WALL HYDRANT.
user.dj.german Model
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
P-1P-2
P-3
P-1 P-2
P-3
P-1P-2
P-3
P-1 P-2
P-3
SA
1 1/2" DHW
2 1/2" CW
1 1/2" DHW
3/4" DHW
3/4" DHWR3/4" DHWR
MECHANICAL CHASE
COPY/KITCHENETTE
XO OFFICE
CO OFFICE
STORAGE
TOILET
TOILET
CLEAN GEAR
ADMINISTRATIVE
OFFICE
LAUNDRY
MECHANICAL
STAIR #3
S013
CORRIDOR
LAUNDRY
JANITOR
STORAGE
VENDING
OFFICE
SLEEPING ROOM
SLEEPING ROOM
ADMINISTRATIVE
OFFICE
P-1P-2
P-3
P-1P-2
P-3
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
HB
HB3/4" DCW
SASA
P-5
P-5
P-5
P-5
P-6
P-7
P-8
SA
1/2" DCW
P-2 P-1
P-1
P-2
SA
SA
SA
SA
HB
2" DCW
/4
D H
W
1 1/2" DCW
D C
W
3" DHW
4" DCW 3" DCW 3" DCW
2 1/2" DHW2 1/2" DHW 1 1/4" DHW
1 1/4" DCW
2 1/2" DHW
3" DCW
2 1/2" DHW
3" DCW
2 1/2" DHW
3" DCW
1 1/4" DHWR 1 1/4" DHWR 1 1/4" DHWR
/2
D
H W
R
1 1/4" DHWR
P-1 P-2
P-3
P-1 P-2
P-3
1 1/4" DHWR
2" DHW
3" DCW
MECHANICAL
D H
W R
D H
W
D C
W
HB
MECHANICAL
HB
/4
D
C W
BFP-1
BFP-2
4" DCW
D C
W
HB
MECHANICAL
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-106
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
PARTIAL ENLARGED FLOOR PLANS - FIRST FLOOR - WATER
60041592 N40085-24-B-0016
05-24-0016 88 OF 174
GRAPHIC SCALE: 1/4"=1'-0"
4' 0 2' 4' 8'
N
NOTE: ALL DCW & DHW DROPS FROM
MAINS TO FIXTURES OR BRANCHES
TO BE PROVIDED WITH SHUT-OFF
VALVES IN THE VERTICAL.
1/4" = 1'-0" C1
FIRST FLOOR ENLARGED PLAN - TYPICAL SLEEPING ROOMS
1/4" = 1'-0"
C4
FIRST FLOOR ENLARGED PLAN - CENTRAL CORE - WATER
1/4" = 1'-0" B1
FIRST FLOOR - WEST MECH. ROOM - WATER
1/4" = 1'-0"
B2
FIRST FLOOR - EAST MECH. ROOM - WATER
N
N N
PLAN NOTES - P-106
1 TURN 4"DCW, 3"DHW, AND 2"DHWR UP ABOVE SLAB
AT THIS LOCATION. PROVIDE MAIN SHUT OFF
VALVES IN ACCESSIBLE LOCATIONS.
2 4"DCW TO MAIN BUILDING. SEE SITE PLAN FOR
CONTINUATION OF DOMESTIC COLD WATER
PIPING.
3 TURN 4"DCW MAIN UP ABOVE SLAB AT THIS
LOCATION. PROVIDE MAIN SHUTOFF VALVE IN
ACCESSIBLE LOCATION.
4 4" RPZ TYPE BACKFLOW PREVENTER FOR MAIN
BUILDING. SEE BACKFLOW PREVENTER DETAIL
FOR MORE INFORMATION.
5 3/4" RPZ TYPE BACKFLOW PREVENTER STACKED
ABOVE BFP-1 FOR MECHANICAL MAKEUP WATER.
SEE BACKFLOW PREVENTER DETAIL FOR MORE
INFORMATION.
6 SEE MECHANICAL PLANS FOR CONTINUATION OF
COLD MECHANICAL MAKEUP WATER PIPING.
7 4"DCW FROM SITE UTILITY TO NEW OUTDOOR
MECHANICAL BUILDING. SEE SITE PLAN FOR
CONTINUATION OF DOMESTIC COLD WATER
PIPING.
8 2"DCW AND 1-1/4"DHW UP.
9 3/4"DCW UP.
10 DROP 1-1/4"DCW AND 1-1/4"DHW DOWN INTO
CHASE TO SUPPLY WASHER BOXES. PROVIDE
SHUTOFF VALVES IN DROPS WITH ACCESS PANEL.
11 1/2"DCW UP.
12 1"DCW & 1"DHW UP.
13 SEE WATER RISER DIAGRAMS FOR TYPICAL
CIRCUIT SETTER AND SHUT OFF VALVE
LOCATIONS AT THE BASE OF ALL DHWR RISERS.
EACH CIRCUIT SETTER MUST BE SET FOR 1/11th OF
THE TOTAL DOMESTIC HOT WATER
RECIRCULATION FLOW.
14 PROVIDE SHUTOFF VALVE IN VERTICAL FOR HOSE
BIB.
1/4" = 1'-0" B4
ENLARGED PLAN - OUTDOOR MECH. BUILDING - WATER
N
HB
MECHANICAL
MECHANICAL
247 STAIR #3
S023
LAUNDRY
LOUNGE
CORRIDOR
JANITOR
STORAGE
VENDING
COMM
SLEEPING ROOM
SLEEPING ROOM
P-1P-2
P-3
P-1P-2
P-3
HB
P-5
P-5
P-5
P-5
P-6
P-7
P-8
SA
SA
SA
HB
1" DCW
1" DHW
P-1 P-2
P-3
P-1 P-2
P-3
MECHANICAL
HB
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-107
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
PARTIAL ENLARGED FLOOR PLANS - SECOND FLOOR - WATER
60041593 N40085-24-B-0016
05-24-0016 89 OF 174
1/4" = 1'-0" B1
SECOND FLOOR WEST - MECH. ROOM - WATER
1/4" = 1'-0"
B3
SECOND ENLARGED FLOOR PLAN - CENTRAL CORE - WATER
1/4" = 1'-0" B5
SECOND FLOOR - EAST MECH. ROOM - WATER
GRAPHIC SCALE: 1/4"=1'-0"
4' 0 2' 4' 8'
N NN
PLAN NOTES - P-107
1 2"DCW DOWN AND 1-1/2"DCW UP. 1-1/4"DHW DOWN
AND 1"DHW UP.
2 3/4"DCW UP AND DOWN.
3 1"DCW & 1"DHW UP AND DOWN.
4 1/2"DCW UP AND DOWN.
5 1/2"DHWR UP AND DOWN.
HB
MECHANICAL
STAIR #3
S033
LOUNGE
CORRIDOR
LAUNDRY
JANITOR
STORAGE
VENDING
OFFICE
SLEEPING ROOM
SLEEPING ROOM
P-1P-2
P-3
P-1P-2
P-3
HB P-5
P-5
P-5
P-5
P-6
P-7
P-8
SA
SA
SA
HB
1" DCW
1" DHW
P-1 P-2
P-3
P-1 P-2
P-3
MECHANICAL
HB
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-108
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
PARTIAL ENLARGED FLOOR PLANS - THIRD FLOOR - WATER
60041594 N40085-24-B-0016
05-24-0016 90 OF 174
1/4" = 1'-0" B1
THIRD FLOOR - WEST MECH. ROOM - WATER
GRAPHIC SCALE: 1/4"=1'-0"
4' 0 2' 4' 8'
N
1/4" = 1'-0" B3
THIRD FLOOR ENLARGED PLAN - CENTRAL CORE - WATER
1/4" = 1'-0"
B5
THIRD FLOOR - EAST MECH. ROOM - WATER
N N
PLAN NOTES - P-108
1 1-1/2"DCW AND 1"DHW UP FROM BELOW.
2 3/4"DCW UP FROM BELOW.
3 1"DCW & 1"DHW UP FROM BELOW.
4 1/2"DCW UP FROM BELOW.
5 1/2"DHWR DOWN.
CONCRETE SLAB, SEE
ARCH. AND STRUCT.
DWGS FOR DETAILS
FLOOR DRAIN
PROVIDE TRAP GUARD TO ENSURE
SEWER GASES CANNOT ESCAPE
SANITARY PIPE
DEEP SEAL "P" TRAP FOR ROOF DETAILS SEE
ARCH. & STRUCT. DWGS.
VENT PIPE SEE FLOOR
PLAN/RISER FOR SIZES
SCREW TO
ROOF DECK
WOOD BLOCK
GALVANIZED METAL FLASHING
HOOD W/ STAINLESS STEEL
CLAMP
WEATHERPROOF
SEALANT
GALVANIZED METAL
COUNTER SECURED TO
ROOF MEMBRANE
W/ ROOF MASTIC
BARREL FABRICATED OF HARD DRAWN
TYPE "K" COPPER
PISTON TO PROVIDE A PERMANENT
MECHANICAL BARRIER BETWEEN
FLUID AND PRE-LOAD AIR CHARGE
BRASS FREE TURNING PISTON ASTM
B-16 WITH O-RINGS
JOINTS TO BE MADE WITH 95-5
LEAD FREE SOLDER.
BRASS THREADED ADAPTOR
A
B
NPT
SIZE
P.D.I.
SYMBOL
FIXTURE UNIT
RATINGS
A SIZE
1/2" A 1 - 11 5"
B SIZE
1/2" 3/4" B 12 - 32 5" 3/4" 1" C 33 - 60 7" 1"
1-1/4" D 60 - 113 7" 1-1/4" 1-1/2" E 114 - 154 9" 1-1/2"
2" F 155 - 330 9" 2"
PIPE
W-L-5039
PIPE
W-J-1010
THROUGH STUD WALL
UL SYSTEM NUMBER
THROUGH CONCRETE WALL
RATED WALL
U.L. APPROVED SLEEVE
SHEET METAL SCREW
4"O.C. PIPING
APPROVED & LISTED
FIRE SAFETY
MATERIAL - U.L.
LISTED
INSULATION
WHERE
APPLICABLE
AT INSULATED PIPE
FIRE CAULK ALL
AROUND (BOTH SIDES)
WALL STRUCTURE
PIPE
SIZE TO ACCOMMODATE
INSULATION AS REQUIRED
SCHEDULE 40 STEEL SLEEVE
PIPE SUPPORT
FRAME
BASE PLATE W/
ANCHOR
PLAN
M A
X
FIN. FLOOR
M
IN
4" RPZ TYPE
BACKFLOW
PREVENTER.
"BFP-1"
ROUTE TO FLOOR
DRAIN (INDIRECT)
U-BOLT
(TYP)
STUD
ANGLE
ELEVATION SEE SITE PLAN FOR CONTINUATION
OF DOMESTIC WATER SUPPLY PIPING
AWWA C701 TURBINE TYPE WITH
REGISTER READING IN LITERS
AND U.S. GALLONS WITH REMOTE
READY CAPABILITY TO DDC FOR
MONITORING.
PRESSURE
GAUGE MAIN SHUT
OFF VALVE
3" DIAMETER STD.
PIPE SUPPORT POST.
(TYP. OF 2)
1/4" STIFFENER
PLATE EA. SIDE
1/2"x10"x10" BASE PLATE W/
(4) 5/8" EPOXY ADHESIVE
ANCHORS, MIN. EMBED = 3"
BUILDING DOMESTIC
WATER MAIN. SEE SHEET
P-106 FOR CONTINUATION.
4"
4"
4"4"
SHUTOFF
VALVE
PIPE SUPPORT
FRAME
BASE PLATE W/
ANCHOR
PLAN
M A
X
FIN. FLOOR
M
IN
3/4" RPZ TYPE
BACKFLOW
PREVENTER.
"BFP-2"
3/4" SEE PLANS FOR
CONTINUATION
ROUTE TO FLOOR
DRAIN (INDIRECT)
U-BOLT
(TYP)
STUD
ANGLE
ELEVATION
PRESSURE
GAUGE
3/4" COLD MECHANICAL MAKEUP WATER.
SEE MECH. DWGS FOR CONTINUATION
3" DIAMETER STD.
PIPE SUPPORT POST.
(TYP. OF 2)
1/4" STIFFENER
PLATE EA. SIDE
1/2"x10"x10" BASE PLATE W/
(4) 5/8" EPOXY ADHESIVE
ANCHORS, MIN. EMBED = 3"
SHUTOFF
VALVE
AWWA C701 TURBINE TYPE WITH
REGISTER READING IN LITERS
AND U.S. GALLONS WITH REMOTE
READY CAPABILITY TO DDC FOR
MONITORING. 3/4"
3/4"
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-501
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
PLUMBING DETAILS
60041595 N40085-24-B-0016
05-24-0016 91 OF 174
NTS
D1
FLOOR DRAIN DETAIL
NTS
D2
VENT THRU ROOF DETAIL
NTS
D3
SHOCK ABSORBER DETAIL NTS
D4
PIPE THRU FIRE WALL DETAIL
NTS
D5
PIPE THRU NON-RATED DETAIL
NTS
C1
BACKFLOW PREVENTER DETAIL (BFP-1)
NTS
C2
BACKFLOW PREVENTER DETAIL (BFP-2)
1/2"P-5 WASHER BOX 3"1/2"
REMARKSWASTEHWCW
PIPE SERVICE AND CONN. SIZE
MARK DESCRIPTION
PLUMBING FIXTURE SCHEDULE
4"1"P-1 -
1/2"P-3 SHOWER 2"1/2"
P-2 1/2"1/2" 1-1/4"
1/2"1/2" 1-1/4"P-4
2"1/2"
SINKP-6
LAUNDRY
1/2"
WATER CLOSET
FLR. MTD.
BACK OUTLET
LAVATORY
UNDERMOUNT
LAVATORY
WALL MTD.
SEE SPECIFICATIONS
SEE SPECIFICATIONS
SEE SPECIFICATIONS
SEE SPECIFICATIONS
SEE SPECIFICATIONS
SEE SPECIFICATIONS
1-1/2"1/2"
COOLER (SINGLE LEVEL)
P-7
ELECTRIC WATER
- SEE SPECIFICATIONS
1/2"P-8 SERVICE SINK 2"1/2" SEE SPECIFICATIONS
LOCATIONTAG TYPE
PLUMBING EQUIPMENT SCHEDULE
DESCRIPTION
LAUNDRY 133
LINT INTERCEPTOR
BASKET STYLE SOLIDS INTERCEPTOR, MAX FLOW 35 GPM, 3
INCH INLET AND OUTLET, REMOVEABLE COVER.LI-1
LAUNDRY 135
BACKFLOW
PREVENTER
(MAIN RPZ)
THE ASSEMBLY SHALL MEET THE REQUIREMENTS OF ASSE 1013
AND BE PROVIDED TO PREVENT BACKFLOW DUE TO
BACKSIPHONAGE AND/OR BACKPRESSURE. THIS DEVICE WILL BE
A REDUCED PRESSURE ZONE (RPZ) TYPE.
BFP-1
(4")
MECHANICAL ADDITION 102BACKFLOW
PREVENTER
(FOR CW MAKEUP)
THE ASSEMBLY SHALL MEET THE REQUIREMENTS OF ASSE 1013
AND BE PROVIDED TO PREVENT BACKFLOW DUE TO
BACKSIPHONAGE AND/OR BACKPRESSURE. THIS DEVICE WILL BE
A REDUCED PRESSURE ZONE (RPZ) TYPE, "N" CONFIGURATION.
BFP-2
(3/4")
MECHANICAL ADDITION 102
WCO WALL CLEAN OUT
SA SHOCK ABSORBER
VB VACUUM BREAKER
WALL CLEANOUT, COATED CAST IRON BODY WITH GAS AND WATERTIGHT ABS
TAPERED THREAD PLUG AND ROUND SMOOTH STAINLESS STEEL ACCESS COVER
WITH SECURING SCREW.
WATER HAMMER ARRESTOR TO MEET ALL REQUIREMENTS OF ASSE 1010 AS
REQUIRED BY 2018 IPC, PLUMBING CODE, SECTION 604.9.
VACUUM BREAKER TO MEET ALL REQUIREMENTS OF ASSE 1022
MARK DESCRIPTION BASIS OF DESIGN FIXTURE SPECIFICATIONS
PLUMBING ACCESSORIES SCHEDULE
FCO FLOOR CLEAN OUT ADJUSTABLE FLOOR CLEANOUT, CAST IRON BODY WITH GAS AND
WATERTIGHT ABS TAPERED THREAD PLUG AND ROUND POLISHED NICKEL
BRONZE TOP ADJUSTABLE TO FINISHED FLOOR.
FD-A FLOOR DRAIN
CAST IRON BODY WITH BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE
CLAMP AND ADJUSTABLE COLLAR WITH 6" POLISHED NICKEL BRONZE STRAINER.
PROVIDE DEEP SEAL TRAP WITH FLOOR DRAIN.
GCO GRADE CLEAN OUT ADJUSTABLE GROUND CLEANOUT, CAST IRON BODY WITH GAS AND
WATERTIGHT ABS TAPERED THREAD PLUG AND ROUND POLISHED NICKEL
BRONZE TOP ADJUSTABLE TO FINISHED GRADE.
WH WALL HYDRANT - KEYED WALL HYDRANT WITH ANTI-SIPHON VACUUM BREAKER, AND LOOSE TEE KEY OPERATION.
HB HOSE BIBB EXPOSED ANTI-SIPHON AUTOMATIC DRAINING WALL HYDRANT COMPLETE WITH
INTEGRAL BACKFLOW PREVENTER, ALL BRONZE INTERIOR PARTS, AND
POLISHED CHROME FACE WITH OPERATING KEY.
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-601
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
PLUMBING SCHEDULES
60041596 N40085-24-B-0016
05-24-0016 92 OF 174
FCO
4" 4"
4" 4"
4"
4" 4" 4"
SEE PLANS FOR
CONTINAUTION
2"
SEE PLANS FOR
CONTINAUTION
P-2
P-2 2"
CV
2"
CV
2"
CV
2"
P-1
P-1
4"
P-3
P-3
P-3
P-3
P-1
P-1
4"
4"
OFFSET RISER IN
VERTICAL FOR
HYDRAULIC JUMP
CV
2"
CV
2"
CV
2"
2" 2"
2" 2"
2"
P-2
P-2
4"
3"
3"
4"
2"
P-2
P-2
CV
2"
CV
2"
CV
2"
P-1
P-1
4"
P-3
P-3
P-3
P-3
P-1
P-1
CV
2"
CV
2"
CV
2"
2" 2"
2" 2"
P-2
P-2
2"
2" 4"
4" 4"
4"
4"
2"
3"
4"
2" 2"
2" 2"
3"
2"
P-2
P-2
CV
2"
CV
2"
CV
2"
P-1
P-1 4"
P-3
P-3
P-3
P-3
P-1
P-1
CV
2"
CV
2"
CV
2"
2" 2"
2" 2"
P-2
P-2
2"
2" 4"
4" 4"
4"
4"
2"
2" 2"
3"
3" 3"
3"
3"
3"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
3"
3"FD-A
3" 3"
3"
3"VTR
3"
3"FD-A
3" 3"
3"
3"
WCO
3"
3"FD-A
3"FD-AFCO
4"
4"
3" 3"
2"
2" 2"
2"
2"
2"
2"
2"V BELOW
SLAB
3"FD-A
3"
2"
P-5 P-5
P-5 2"
P-5
2"
P-5
P-5
P-5 P-5
2"
2"
2"
2"
2" 4"
4"
FCO
3"
P-5
4"
P-5
4"
LI-1
FCO
FCO
6"
4"
4"
6"
8"
SEE SITE PLAN FOR
CONTINUATION
6"
A/A
A/A
3"FD-A
WCO
3"
3" 3"
3"
2"
P-5
P-5
P-5
P-5 2"
2"
2"
2" 2"
3"
2"
2"
2"
6"
P-7
P-7
P-7
3"
3"
3"
2"V
BELOW
SLAB
2" 2"
WCO
2"LI-1
P-8
WCO
P-6
2"
2"
2"
2"
3"FD-A
3"
WCO
3"
3"
3"
3"
2"
P-5
P-5
P-5
P-5
2"
2"
2"
2" 2"
2"
2"
2"
2"
2"
2"
3"FD-A
3"
WCO
3"
3" 3"
3"
P-6
P-8
2"
3"
2"
P-6
P-8
2"
2"
3"
3"VTR
3"
2"
P-5
P-5
P-5
P-5 2"
2" 2"
2"
2"
2"
2"
3"
3"
2"
2"
3"
2"
3"
2"
6"
SEE PLANS FOR
CONTINUATION6"
6"
6" 6"
6" 6"
4"
OFFSET RISER IN
VERTICAL FOR
HYDRAULIC JUMP
4"
2"
4"
P-2
P-1
P-3
CV
2"
1-1/2" P-2
4" CV
2"
CV
2"
CV
2"
CV
2"
CV
2"
P-3
P-3
P-3 P-1
4"
3"
2" 2"
4"
2"
P-1
P-1
P-2
1-1/2"
P-2
2" 2"
2" 2"
2" 2"
2"
P-2
P-1
CV
2"
1-1/2"
P-2
CV
2"
CV
2"
CV
2"
CV
2"
CV
2"
P-3
P-3
P-3 P-1
4"
3"
2" 2"
4"
2"
P-1
P-1
P-2 1-1/2"
P-2
2" 2"
2" 2"
2"
2"
2" 4"
4" 4"
4"
4"
3"
2"
P-2
P-1
CV
2"
1-1/2"
P-2
CV
2"
CV
2"
CV
2"
CV
2"
CV
2"
P-3
P-3
P-3 P-1
4" 2" 2"
4"
2"
P-1
P-1
P-2 1-1/2"
P-2
2" 2"
2" 2"
2"
2" 4"
4" 4"
4"
P-3
SEE PLANS FOR
CONTINUATION
3"
4"
3"
4"VTR
3"
3" 3"
3"
3"
4"
2"
4"
2"
3"
SEE SITE PLAN FOR
CONTINUATION
4"FD-A
4"FD-A
4"FD-A
FCO
GCO
4"
4" 4"
4"4"
4"
4"
2"
2"VTR
4"
4"
SEE PLANS FOR
CONTINUATION
P-2
P-1
P-1P-2
A/A
A/A
2"
4"VTR
6"
2" 2"
6" 6"
6"
6"
OFFSET RISER IN
VERTICAL FOR
HYDRAULIC JUMP
4"
4"
2" 2"
2"2" 2"
2" 2"
4"
4"
3" 4"
4" 4"
4" 2"
P-2
P-1 P-3
P-2
2"
1-1/2"
4" P-1
CV
2"
2" 2"
CV
2"
CV
2"
CV
2"
CV
2"
P-3
P-3
P-3
2" 2"
4"
4"
2"
P-2
P-2 1-1/2"
4"
3"
CV
2"
2" 2"
P-1
P-1
P-1
4" 4"
4" 2"
P-2
P-1 P-3
P-2
2"
1-1/2"
4" P-1
CV
2"
2" 2"
CV
2"
CV
2"
CV
2"
CV
2"
P-3
P-3
P-3
2" 2"
4"
4"
2"
P-2
P-2 1-1/2"
3"
3"
CV
2"
2" 2"
P-1
P-1
P-1
4"
3"
3"
3"
4"
4"
4"
4"
3"
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-701
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
RISER DIAGRAMS - WASTE AND VENT
60041597 N40085-24-B-0016
05-24-0016 93 OF 174
NTS
B2
3D RISER - TYPICAL SLEEPING ROOMS - WASTE AND VENT
NTS
B4
3D RISER - CENTRAL CORE AREAS - WASTE AND VENT
NTS
A3
3D RISER - OUTDOOR MECH. BUILDING - WASTE AND VENT
SEE SITE PLAN
FOR CONTINUATION
SEE SITE PLAN
FOR CONTINUATION
BFP-1
HB
BFP-2
SEE MECH. PLANS FOR
CONTINUATION
SHUTOFF
VALVE
4"
4"
SHUTOFF
VALVE
3/4"
4"
4"
4"
4"
SEE PLANS FOR
CONTINUATION
1-1/4"
4" 3"
P-2 P-1
P-2
P-1
1/2"
1-1/4"
1-1/4"
SA
SA
2-1/2"
3"
2" 1-1/4"
3"
3"
2-1/2"
2-1/2" 3"
HB
3/4"
3/4"
3/4"
3/4"
3/4"
HB
HB
P-2
P-2
P-1
P-1
P-3
P-3 P-3
P-3 P-1
P-1
P-2
P-2
SA
1/2" 1-1/4"
1/2" 1-1/2"
1/2"
1-1/4"
3/4"
3/4" 1-1/2"
1-1/2"
1"
1/2"
1/2"
1/2"
HB
SA
P-5 P-5
P-5
P-5
P-5
P-5
1-1/4"
1" P-5
P-5
P-5
P-5
1-1/4"
1-1/4"
3"
3" 3"
P-7
HB
P-8
1/2" P-6
SA
1/2"
1/2"
P-5
P-5
P-5 P-5
SA
SA
2"
1/2"
1" 3/4"
1/2" 1-1/2"
1/2"
HB
1/2"
3/4"
1"
3/4"
1/2" 3/4"
3"
2-1/2"
1-1/4"
2"
SA
P-71/2"
1"
P-8
P-6
3/4"
P-5
P-5
P-5 P-5
SA
1/2" 1"
3/4"
1/2"
1/2"
3/4"
1" 3/4"
1/2"
HB
P-8
P-6
3/4"
1/2"
P-7
SA
P-5
P-5
P-5
P-5
1/2"
SA
1/2" 3/4"
3/4"
1"
3/4"
1/2"
1-1/4"
1"
1/2"
1"
1-1/4"
P-2
P-1 P-3
P-3 P-1
P-2 P-2
P-1
P-3 P-3
P-1 P-2
1/2"
1-1/4"
SA
SEE PLANS FOR
CONTINUATION2"
3"2"
1-1/4"
3"
3"
1-1/4"
1/2" 1/2"
1/2"
P-2
P-1 P-3
P-3 P-1
P-2 P-2
P-1
P-3 P-3
P-1 P-2
1/2"
1-1/4"
SA
1-1/4"
1/2" 1/2"
1/2"
1/2" 1"
1-1/2" 3/4"
3/4"
1-1/2"
1/2"
1/2"
P-2
P-1 P-3
P-3 P-1
P-2 P-2
P-1
P-3 P-3
P-1 P-2
1/2"
1-1/4"
SA
1-1/4"
1/2" 1/2"
1/2"
1-1/2" 3/4"
3/4"1-1/2"
1/2"
1/2"
1-1/4"
SHUTOFF
VALVES
1/2"
CIRCUIT
SETTER
1-1/4"
1-1/4"
1-1/4"
1-1/4"
2-1/2"
2-1/2"
1-1/4"
1/2"
1-1/4"
2-1/2"
P-2
P-2
P-1
P-1
P-3
P-3 P-3
P-3 P-1
P-1
P-2
P-2
SA
1/2" 1-1/4"
1/2" 1-1/2"
1-1/4"
3/4"
3/4" 1-1/2"
1/2"
1/2"
1/2" 1/2"
1/2"
CIRCUIT SETTER
SHUTOFF VALVE
SHUTOFF VALVE
1/2"
1-1/4"
1-1/4"
2-1/2" 1-1/4"
2"
1/2" CIRCUIT
SETTERSHUTOFF
VALVES
1-1/2"
1/2"
1-1/4"
SHUTOFF VALVE
P-2
P-1
P-3
P-2
P-1 P-3
P-3
P-3 P-1
P-1 P-2
P-2
1/2"
SA
1-1/4"
SEE PLANS FOR
CONTINUATION
1/2"
1-1/4"
1/2" 1/2"
3/4"
1-1/2"
3/4"
3/4"
1-1/4" 1-1/2" 2-1/2"
2"
1-1/4"P-2
P-1
P-3
P-2
P-1 P-3 P-3
P-3
P-1
P-1 P-2
P-2
1/2"
1-1/4"
1/2"
1-1/4"
1/2" 1/2"
1/2" 1-1/2"
3/4" 3/4" 1-1/2"
SA 1/2"
1-1/2" 1"
P-2
P-1
P-3
P-2
P-1 P-3
P-3
P-3
P-1
P-1
P-2
P-2
1/2"
1-1/4"
1/2"
1-1/4"
1/2"
1/2" 1-1/2"
3/4" 3/4" 1-1/2"
SA
1/2"
1/2"
3/4" 3/4"
2-1/2" 1-1/2"
CIRCUIT
SETTER
SHUTOFF
VALVES
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
DESIGN DIR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
P-702
Approver
DJG
DLB
PRC
REPAIR BEQ BB250
RISER DIAGRAMS - WATER
60041598 N40085-24-B-0016
05-24-0016 94 OF 174
NTS
A3
3D RISER - OUTDOOR MECH. BUILDING - WATER
NTS
B4
3D RISER - CENTRAL CORE AREAS - WATER
NTS
B2
3D RISER - TYPICAL SLEEPING ROOMS - WATER
AS AIR SEPARATOR
EF EXHAUST FAN
CEILING SUPPLY DIFFUSER
SIDEWALL SUPPLY DIFFUSER
CEILING RETURN GRILLE
SIDEWALL RETURN/EXHAUST GRILLE
CEILING EXHAUST GRILLE
WXH
RECTANGULAR DUCT
DIA."
ROUND DUCT
(D = DIAMETER)
(W = WIDTH, H = HEIGHT)
SPIN-IN TAP WITH TRANSITION
FROM HARD TO FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RECTANGULAR DUCT TURNS DOWN
RECTANGULAR DUCT TURNS UP
ROUND DUCT TURNS DOWN
ROUND DUCT TURNS UP
FIRE DAMPER
HVAC SYSTEM EMERGENCY
SD DUCT MOUNTED SMOKE DETECTOR
A
DIFFUSER TAG
DIFFUSER
CFM
EXISTING DUCT, DIFFUSER
OR EQUIPMENT TO DEMOLISH
DRAWING LEGEND MARKS
EXISTING DUCT, DIFFUSER
OR EQUIPMENT
ET EXPANSION TANK
DOAS DEDICATED OUTSIDE AIR SYSTEM
SHUTDOWN SWITCH
E
FD
MOTORIZED DAMPERM
T WALL MOUNTED THERMOSTAT
DRAWING LEGEND
AUTOMATIC AIR VENT
CONCENTRIC REDUCER
DIRECTION OF FLOW
TEMPERATURE TRANSMITTER
PRESSURE TRANSMITTER ORPT/PS
TH
TT
THERMOMETER
PRESSURE SWITCH
THREE WAY CONTROL VALVE
BALANCING VALVE
SWING CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
FS FLOW SWITCH
GATE VALVE
UNION - SCREWED OR FLANGED
PRESSURE INDICATOR
PI
TWO WAY CONTROL VALVE
STRAINER WITH BLOW OFF VALVE
CHWP CHILLED WATER PUMP
PHWP PRIMARY HOT WATER PUMP
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MONITORING STATION
BAS BUILDING AUTOMATION SYSTEM
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBIC FEET PER MINUTE
CU. FT. CUBIC FEET
DB DRY BULB
EA, E/A EXHAUST AIR FLOW
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
W.G. INCHES OF WATER GAUGE
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FOT FLAT ON TOP
HP HORSEPOWER
HZ HERTZ
IN. WC INCHES OF WATER COLUMN
KW TOTAL POWER INPUT, KILOWATTS
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LRA LOCKED ROTOR AMPS
LWT LEAVING WATER TEMPERATURE
MC MECHANICAL CONTRACTOR
MFG MANUFACTURER
MCA MINIMUM CIRCUIT AMPS
MOCP MAXIMUM OVER CURRENT PROTECTION
MVD MANUAL VOLUME DAMPER
OA, O/A OUTSIDE AIR FLOW
PH PHASE
PSI POUNDS PER SQUARE INCH
RA, R/A RETURN AIR FLOW
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SA, S/A SUPPLY AIR FLOW
SP STATIC PRESSURE
TEMP TEMPERATURE
TON 12,000 BTUH OF COOLING CAPACITY
TYP TYPICAL
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB TEMPERATURE
TA, T/A TRANSFER AIR FLOW
ABBREVIATIONS
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
BFP BACKFLOW PREVENTER
FD FIRE DAMPER
DR FLOOR DRAIN
STM STEAM
COND CONDENSATE
HPC HIGH PRESSURE CONDENSATE
HPS HIGH PRESSURE STEAM (ABOVE 15 PSI)
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM (15 PSI AND LESS)
PC PUMPED CONDENSATE
GENERAL NOTES
1. COORDINATE THE INSTALLATION OF EQUIPMENT, PIPING, AND DUCTWORK
UNDER THIS CONTRACT WITH THE BUILDING STRUCTURE. CONTRACTOR MUST
MAKE ADJUSTMENTS WHERE NECESSARY WITHOUT ADDITIONAL COST TO
GOVERNMENT.
2. COORDINATE SUPPLY, RETURN AND EXHAUST GRILLE LOCATIONS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
3. VERIFY PIPE SIZES AND LOCATIONS OF PIPE ROUTING.
4. PROVIDED BUILDING CONTROLS MUST TIE INTO THE EXISTING BASEWIDE EMCS
WITH ONE OF THE THREE ATO APPROVED BMS (FX, DISTECH, OR METASYS).
PROVIDED WATER AND ELECTRIC METERS MUST BE BACNET COMPATIBLE AND
MUST COMMUNICATE WITH THE BAS HEADEND. COORDINATE WITH THE
INSTALLATION ENERGY MANAGER ON THE TIE-IN OF THE UTILITY METERS TO THE
ECMS.
5. UNLESS OTHERWISE INDICATED, MECHANICAL PIPING MUST BE RUN IN THE
DESIGNATED OR MAIN SERVICE CHASES. PIPING MUST NOT BE RUN OVERHEAD
IN THE SLEEPING AREAS OF THE ROOM, BUT MAY BE RUN IN SOFFITS OVER
BATHROOMS, SINK AND CLOSET AREAS.
6. WHERE SMALLER DUCTS ARE INSTALLED REUSING EXISTING LARGER
WALL/FLOOR OPENINGS, THE EXISTING OPENINGS MUST BE FILLED TO
ADJACENT CONSTRUCTION AND BE FIRE PROOFED TO MEET APPLICABLE CODES
AND REGULATIONS.
7. DEMOLISH MATERIALS AS SHOWN AND NOTED ON THE DEMOLITION PLANS FOR
THIS BUILDING. SUBSTANCES FOUND IN, ON OR AROUND THESE DEMOLISHED
MATERIALS MUST BE SAFELY HANDLED AND DISPOSED OF TO SATISFY
ENVIRONMENTAL REGULATIONS.
8. EXPOSED DUCTWORK MUST BE INSULATED WITH RIGID DUCT BOARD
INSULATION IN ACCORDANCE WITH SPECIFICATIONS.
BT BUFFER TANK
(EX) EXISTING
UNDERGROUND PIPING
SUPPLY/RETURN PIPING
LOUVER
AHU AIR HANDLING UNIT
PTHP PACKAGED TERMINAL HEAT PUMP
UH HOT WATER UNIT HEATER
DAC DUCTLESS SPLIT AIR CONDITIONING UNIT
DCU DUCTLESS SPLIT CONDENSING UNIT
CH AIR-COOLED CHILLER
L LOUVER
B BOILER
SHWP SECONDARY HOT WATER PUMP
DH DEHUMIDIFIER
DDC DIRECT DIGITAL CONTROL
B-BC BACNET-BUILDING CONTROLLER
EUH ELECTRIC UNIT HEATER
POINT OF DEMOLITION
CONNECT TO EXISTING
DHP DUCTLESS SPLIT HEAT PUMP
BP BOILER PUMP
DBP DOMESTIC WATER BOILER PUMP
DWB DOMESTIC WATER BOILER
MIN. MINIMUM
DIA DIAMETER
HW HOT WATER
GA GAUGE
GPM GALLONS PER MINUTE
I.E. IN OTHER WORDS
LBM POUNDS MASS
NOM NOMINAL
PCF POUNDS PER CUBIC FOOT
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-001
PJR
MAS
LWM
REPAIR BEQ BB250
MECHANICAL NOTES, LEGEND, AND ABBREVIATIONS
60041599 N40085-24-B-0016
05-24-0016 95 OF 174
DESIGN DIR.
KELLY ROOT
T T
T
T
T
T T
T T
T T
T T
T T
T
T
T T
T T
MD104
A3
T
T
MD105
A2
MD105
A4
MD106
A2
MD401
C2
MD401
A2
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
T T
T T
T T
T T
T
T
T
T T
T T
T T
T T
T T
T
T
T T
T T
T
T
T T
T T
T
MD107
A2
MD107
A4
MD108
A2
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD101
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL FIRST AND SECOND FLOOR PLANS - HVAC
60041600 N40085-24-B-0016
05-24-0016 96 OF 174
3/32" = 1'-0" A1
FIRST FLOOR PLAN - MECHANICAL HVAC DEMOLITION
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
# DEMO NOTES
3/32" = 1'-0" D1
SECOND FLOOR - DUCTWORK - DEMO
1 REMOVE EXISTING SERIES FAN POWERED
TERMINAL UNIT AND ASSOCIATED SUPPLY AIR
DUCTWORK, GRILLES AND CONTROLS.
(TYPICAL)
2 REMOVE EXISTING VERTICAL DUCT AND
ASSOCIATED BRANCH DUCTWORK AND
GRILLES. (TYPICAL)
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
N
N
T T
T T
T
T
T
T T
T T
T T
T T
T T
T
T
T T
T T
T
T
T T
T T
T
MD109
A2
MD109
A4
MD110
A2
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
(EX)
EF
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD102
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL THIRD FLOOR AND ROOF PLANS - HVAC
60041601 N40085-24-B-0016
05-24-0016 97 OF 174
3/32" = 1'-0" B1
THIRD FLOOR PLAN - MECHANICAL HVAC DEMOLITION
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
# DEMO NOTES
3/32" = 1'-0" D1
ROOF - DUCTWORK - DEMO
1 REMOVE EXISTING SERIES FAN POWERED
TERMINAL UNIT AND ASSOCIATED SUPPLY AIR
DUCTWORK, GRILLES AND CONTROLS. (TYPICAL)
2 REMOVE EXISTING VERTICAL DUCT AND
ASSOCIATED BRANCH DUCTWORK AND
GRILLES. (TYPICAL)
3 REMOVE EXISTING DUCTWORK UP TO ROOF
MOUNTED EXHAUST FAN OR ROOF VENTILATOR.
REMOVE EXHAUST EQUIPMENT AND
ASSOCIATED WIRING AND CONTROLS. PATCH
ROOF PENETRATION. SEE ARCHITECTURAL
SHEETS FOR MORE INFORMATION. (TYPICAL)
N
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
MD401
C2
MD401
A2
1 1
(EX)
AHU
(EX)
AHU
(EX)
UH
(EX)
FCU
1 1
(EX)
AHU
(EX)
UH
(EX)
AHU(EX)
FCU
(EX)
FCU
3 3
(EX)
AHU
(EX)
UH
(EX)
AHU(EX)
FCU
(EX)
FCU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD103
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL FIRST, SECOND & THIRD FLOOR PLANS - PIPING
60041602 N40085-24-B-0016
05-24-0016 98 OF 174
3/32" = 1'-0" A1
FIRST FLOOR PLAN - MECHANICAL PIPING DEMOLITION
3/32" = 1'-0" C1
SECOND FLOOR PLAN - MECHANICAL PIPING DEMOLITION
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
# DEMO NOTES
1 REMOVE EXISTING AIR HANDLING UNIT AND
ASSOCIATED PIPING, VALVES AND CONTROLS.
2 REMOVE EXISTING DUAL TEMPERATURE PIPING
RISERS AND PIPING THAT SERVES EACH FLOOR.
3 REMOVE EXISTING AIR HANDLING UNIT AND
ASSOCIATED PIPING, VALVES AND CONTROLS.
4 REMOVE EXISTING DUAL TEMPERATURE PIPING
RISERS AND PIPING THAT SERVES EACH FLOOR.
N
N
3/32" = 1'-0" D1
THIRD FLOOR PLAN - MECHANICAL PIPING DEMOLITION
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
T
T
(EX)
FCU
(EX)
FCU
(EX)
FCU
(EX)
FCU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD104
PJR
MAS
LWM
REPAIR BEQ BB250
TYPICAL SLEEPING ROOM ENLARGED FLOOR PLAN
60041603 N40085-24-B-0016
05-24-0016 99 OF 174
GRAPHIC SCALE: 3/8"=1'-0"
3' 0 2' 6'
# DEMO NOTES
3/8" = 1'-0" A3
TYPICAL SLEEPING ROOM ENLARGED FLOOR PLAN - MECHANICAL DEMOLITION
1 REMOVE EXISTING SERIES FAN POWERED
TERMINAL UNIT AND ASSOCIATED SUPPLY AIR
DUCTWORK, GRILLES AND CONTROLS. (TYPICAL)
2 REMOVE EXISTING WALL-MOUNTED
THERMOSTAT. (TYPICAL)
3 REMOVE EXISTING VENTILATION SUPPLY AIR
DUCTWORK.
4 REMOVE EXISTING BATHROOM EXHAUST RISER,
WALL-MOUNTED FAN, DUCTWORK AND
ASSOCIATED WIRING AND CONTROLS. (TYPICAL)
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
(EX)
FCU
(EX)
AHU 11
T
(EX)
FCU
(EX)
AHU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD105
PJR
MAS
LWM
REPAIR BEQ BB250
FIRST FLOOR PLAN MECHANICAL ROOMS ENLARGED
60041604 N40085-24-B-0016
05-24-0016 100 OF 174
GRAPHIC SCALE: 1/2"=1'-0"
2' 0 1' 2' 4'
# DEMO NOTES
1/2" = 1'-0" A2
FIRST FLOOR PLAN - WEST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1/2" = 1'-0" A4
FIRST FLOOR PLAN - EAST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1 REMOVE EXISTING DUAL TEMPERATURE PIPING
FROM LEVEL BELOW TO AIR HANDLERS AND
PIPING RISERS IN MECHANICAL ROOMS AS
SHOWN. EXISTING PIPING FLOOR
PENETRATIONS MUST BE REUSED.
2 REMOVE FLOOR MOUNTED AIR HANDLING UNIT
AND ASSOCIATED DUCTWORK, LOUVERS,
PIPING, VALVES, DUCT DETECTOR, CONTROLS
AND WIRING. REMOVE EXISTING EQUIPMENT
SUPPORT PAD.
3 REMOVE EXISTING HVAC CONTROL CABINET
AND WIRING, CONDUIT, AND CONTROL DEVICES
ASSOCIATED WITH THE PANEL.
4 REMOVE EXISTING PIPING ROUTED IN CHASE
FROM MECHANICAL ROOM TO EQUIPMENT IN
CENTRAL CORE. SEE ENLARGED CENTRAL CORE
SHEET FOR CONTINUATION.
N N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
T
B3
M-304
B1
M-304
(EX)
FCU
(EX)
FCU
(EX)
EF
(EX)
UH
A2
M-302
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD106
PJR
MAS
LWM
REPAIR BEQ BB250
FIRST FLOOR PLAN CENTRAL CORE ENLARGED
60041605 N40085-24-B-0016
05-24-0016 101 OF 174
GRAPHIC SCALE: 3/8"=1'-0"
3' 0 2' 6'
# DEMO NOTES
3/8" = 1'-0" A2
FIRST FLOOR CENTRAL CORE ENLARGED FLOOR PLAN - MECHANICAL DEMOLITION
1 REMOVE EXISTING WALL-MOUNTED
THERMOSTAT.
2 REMOVE EXISTING WALL MOUNTED EXHAUST
FAN, ASSOCIATED DUCTWORK, AND CONTROLS.
3 REMOVE EXISTING HOT WATER UNIT HEATER.
REMOVE ASSOCIATED PIPING BACK TO
MECHANICAL ROOM, VALVES AND CONTROLS.
4 REMOVE EXISTING SUSPENDED FAN COIL UNIT,
ASSOCIATED OUTSIDE AIR DUCTWORK, LOUVER,
PIPING, VALVES, CONTROLS AND WIRING.
5 REMOVE EXISTING FLOOR MOUNTED FAN COIL
UNIT, ASSOCIATED OUTSIDE AIR DUCTWORK,
LOUVER, PIPING, VALVES AND CONTROLS.
6 REMOVE EXISTING DUAL TEMPERATURE PIPING
IN CENTRAL CORE AREA BACK TO MECHANICAL
ROOM. SEE ENLARGED MECHANICAL ROOM
SHEET FOR CONTINUATION.
7 REMOVE EXISTING DRYER DUCTS, DRYER
EXHAUST PLENUM, AND ASSOCIATED LOUVER.
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
(EX)
FCU
(EX)
AHU
T
(EX)
FCU
(EX)
AHU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD107
PJR
MAS
LWM
REPAIR BEQ BB250
SECOND FLOOR PLAN MECHANICAL ROOMS ENLARGED
60041606 N40085-24-B-0016
05-24-0016 102 OF 174
GRAPHIC SCALE: 1/2"=1'-0"
2' 0 1' 2' 4'
# DEMO NOTES
1/2" = 1'-0" A2
SECOND FLOOR PLAN - WEST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1/2" = 1'-0" A4
SECOND FLOOR PLAN - EAST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1 REMOVE EXISTING DUAL TEMPERATURE PIPING
FROM LEVEL BELOW TO AIR HANDLERS AND
PIPING RISERS IN MECHANICAL ROOMS AS
SHOWN. EXISTING PIPING FLOOR
PENETRATIONS MUST BE REUSED.
2 REMOVE FLOOR MOUNTED AIR HANDLING UNIT
AND ASSOCIATED DUCTWORK, LOUVERS,
PIPING, VALVES, DUCT DETECTOR, CONTROLS
AND WIRING. REMOVE EXISTING EQUIPMENT
SUPPORT PAD.
3 REMOVE EXISTING HVAC CONTROL CABINET
AND WIRING, CONDUIT, AND CONTROL DEVICES
ASSOCIATED WITH THE PANEL.
N N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
T
(EX)
FCU
(EX)
FCU
(EX)
UH
(EX)
EF
A2
M-302
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD108
PJR
MAS
LWM
REPAIR BEQ BB250
SECOND FLOOR PLAN CENTRAL CORE ENLARGED
60041607 N40085-24-B-0016
05-24-0016 103 OF 174
GRAPHIC SCALE: 3/8"=1'-0"
3' 0 2' 6'
# DEMO NOTES
3/8" = 1'-0" A2
SECOND FLOOR CENTRAL CORE ENLARGED FLOOR PLAN - MECHANICAL DEMOLITION
1 REMOVE EXISTING WALL-MOUNTED
THERMOSTAT.
2 REMOVE EXISTING WALL MOUNTED EXHAUST
FAN, ASSOCIATED DUCTWORK, AND CONTROLS.
3 REMOVE EXISTING HOT WATER UNIT HEATER.
REMOVE ASSOCIATED VALVES, CONTROLS AND
PIPE RISER FROM LEVEL BELOW TO LEVEL
ABOVE.
4 REMOVE EXISTING DRYER DUCTS, DRYER
EXHAUST PLENUM, AND ASSOCIATED LOUVER.
5 REMOVE EXISTING FLOOR MOUNTED FAN COIL
UNIT, ASSOCIATED OUTSIDE AIR DUCTWORK,
LOUVER, PIPING, VALVES AND CONTROLS.
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
(EX)
FCU
(EX)
AHU
T
(EX)
AHU
(EX)
FCU
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD109
PJR
MAS
LWM
REPAIR BEQ BB250
THIRD FLOOR PLAN MECHANICAL ROOMS ENLARGED
60041608 N40085-24-B-0016
05-24-0016 104 OF 174
GRAPHIC SCALE: 1/2"=1'-0"
2' 0 1' 2' 4'
# DEMO NOTES
1/2" = 1'-0" A2
THIRD FLOOR PLAN - WEST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1/2" = 1'-0" A4
THIRD FLOOR PLAN - EAST MECHANICAL
ROOM ENLARGED - MECHANICAL
DEMOLITION
1 REMOVE EXISTING DUAL TEMPERATURE PIPING
FROM LEVEL BELOW TO AIR HANDLERS AND
PIPING RISERS IN MECHANICAL ROOMS AS
SHOWN. EXISTING PIPING FLOOR
PENETRATIONS MUST BE REUSED.
2 REMOVE FLOOR MOUNTED AIR HANDLING UNIT
AND ASSOCIATED DUCTWORK, LOUVERS,
PIPING, VALVES, DUCT DETECTOR, CONTROLS
AND WIRING. REMOVE EXISTING EQUIPMENT
SUPPORT PAD.
3 REMOVE EXISTING HVAC CONTROL CABINET
AND WIRING, CONDUIT, AND CONTROL DEVICES
ASSOCIATED WITH THE PANEL.
N N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
T
T
(EX)
FCU
(EX)
FCU
(EX)
EF
(EX)
UH
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD110
PJR
MAS
LWM
REPAIR BEQ BB250
THIRD FLOOR PLAN CENTRAL CORE ENLARGED
60041609 N40085-24-B-0016
05-24-0016 105 OF 174
GRAPHIC SCALE: 3/8"=1'-0"
3' 0 2' 6'
# DEMO NOTES
3/8" = 1'-0" A2
THIRD FLOOR CENTRAL CORE ENLARGED FLOOR PLAN - MECHANICAL DEMOLITION
1 REMOVE EXISTING WALL-MOUNTED
THERMOSTAT.
2 REMOVE EXISTING WALL MOUNTED EXHAUST
FAN, ASSOCIATED DUCTWORK, AND CONTROLS.
3 REMOVE EXISTING HOT WATER UNIT HEATER.
REMOVE ASSOCIATED VALVES, CONTROLS AND
PIPE RISER FROM LEVEL BELOW.
4 REMOVE EXISTING DRYER DUCTS, DRYER
EXHAUST PLENUM, AND ASSOCIATED LOUVER.
5 REMOVE EXISTING FLOOR MOUNTED FAN COIL
UNIT, ASSOCIATED OUTSIDE AIR DUCTWORK,
LOUVER, PIPING, VALVES AND CONTROLS.
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
MD401
A2
MD401
C2
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
MD111
PJR
MAS
LWM
REPAIR BEQ BB250
SITE PLAN MECHANICAL DEMOLITION
60041610 N40085-24-B-0016
05-24-0016 106 OF 174
GRAPHIC SCALE: 1/8"=1'-0"
8' 0 4' 8' 16'
# DEMO NOTES
1/8" = 1'-0" B1
SITE PLAN - MECHANICAL DEMOLITION
1 REMOVE EXISTING UNDERGROUND DUAL
TEMPERATURE PIPING FROM BB250A
MECHANICAL BUILDING TO INSIDE BUILDING
BB250 MECHANICAL ROOMS. SEE ENLARGED
MECHANICAL ROOM SHEETS FOR MORE
INFORMATION.
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PRIOR TO DEMOLITION, PROVIDE
CONTRACTING OFFICER WITH LIST AND
CONDITION OF MECHANICAL EQUIPMENT AND
DDC CONTROLS PENDING DEMOLITION FOR
REVIEW. EQUIPMENT DESIGNATED AS
SALVAGABLE WILL BE REMOVED BY
CONTRACTOR AND TURNED OVER TO THE
CONTRACTING OFFICER.
PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP
PTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHP
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
CLERKS OFFICE
XO OFFICE
COPY/KITCHENETTE
154 TOILET
TOILET
ADMINISTRATIVE OFFICE
CO OFFICE
STORAGE
CLEAN GEAR
ADMINISTRATIVE OFFICE
LAUNDRY
MECHANICAL
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
STAIR #1
S011
STAIR #2
S012
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
PTHP PTHP
PTHP PTHP PTHP
DHP-1
8"x8" 10"x8" 12"x10"
12"x10"10"x10"10"x8"8"x8"8"x6" 10"x8" 8"x8" 8"x6"
10"x10"10"x8"8"x8" 10"x10" 10"x8" 8"x8" 8"x6"
10"x10"10"x8" 12"x10"
10"x8" 12"x8" 12"x10"
12"x10"10"x10"10"x8"
M-105
A3
M-106
A2
M-106
A3
M-107
A1
PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP
PTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHP PTHP PTHP PTHP
PTHP PTHP
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
LOUNGE
STORAGE
COMM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
STAIR #1
S021
STAIR #2
S022
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
SLEEPING ROOM
MECHANICAL
10"x10"10"x8"8"x8"8"x6" 12"x10"
10"x10"10"x8"8"x8"8"x6"
10"x10" 10"x8" 8"x8" 8"x6"
10"x6" 10"x8" 12"x8" 12"x10"
10"x10" 10"x8" 8"x8"
12"x10" 10"x10" 10"x8" 8"x8"
12"x10"10"x10"10"x8"8"x8"8"x6" 10"x8" 8"x8" 8"x6"
10"x10" 10"x8" 8"x8" 8"x6"10"x10"10"x8"8"x8"
8"x8" 10"x8" 12"x10"
M-108
A2
M-108
A3
M-109
A2
12"x10"
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-101
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL FIRST AND SECOND FLOOR PLANS - HVAC
60041611 N40085-24-B-0016
05-24-0016 107 OF 174
3/32" = 1'-0" A1
FIRST FLOOR PLAN - MECHANICAL WORK
3/32" = 1'-0" C1
SECOND FLOOR PLAN - MECHANICAL WORK
# PLAN NOTES
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PLAN DRAWINGS ARE DIAGRAMMATIC IN
NATURE AND DO NO ILLUSTRATE SPECIFIC
DUCT TAKE-OFF CONFIGURATIONS AND TAPS.
PROVIDE FLEXIBLE DUCTWORK RUNOUTS TO
SUPPLY AND RETURN GRILLES WITH A
MAXIMUM LENGTH OF 5 FEET AND SINGLE
BENDS NO GREATER THAN 45 DEGREES.
REFER TO PROJECT SPECIFICATIONS AND
DUCTWORK DETAILS FOR SPECIFIC
REQUIREMENTS.
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
1 PROVIDE PTHP UNIT WITH LIGATURE PROOF
PROTECTIVE COVER, CORROSION RESISTANT
CHASSIS, AND 3/4" CONDENSATE DRAIN WITH
EXTERIOR CLEANOUT. PAINT DDC CONDUIT
EXPOSED IN OCCUPIED AREAS TO MATCH
INTERIOR. COORDINATE WITH ARCHITECTURAL
AND INTERIOR PLANS. (TYP)
2 PROVIDE EXHAUST AND SUPPLY (VENTILATION)
MAINS AS SHOWN. SEE ENLARGED PLANS FOR
BRANCH DUCTS TO DIFFUSERS/GRILLES.
(TYPICAL EXHAUST AND SUPPLY MAINS)
N
N
PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP
PTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHP PTHP PTHP PTHP
PTHP PTHP
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
LOUNGE
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
STAIR #1
S031
STAIR #2
S032
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
MECHANICAL
12"x10"10"x10"10"x8"8"x8"8"x6" 10"x8" 8"x8" 8"x6"
10"x10" 10"x8" 8"x8" 8"x6"12"x10"10"x10"10"x8"8"x8"
8"x8" 10"x8" 12"x10"
10"x10"10"x8"8"x8"8"x6" 12"x10"
10"x6" 10"x8" 12"x8" 12"x10"
12"x10"10"x10"10"x8"8"x8"8"x6"
10"x10" 10"x8" 8"x8" 8"x6"
12"x10" 10"x10" 10"x8" 8"x8"
12"x10" 10"x10" 10"x8" 8"x8"
M-110
A2 M-110
A3
M-111
A2
EF-5
8"x8"
8" x8
"x
"x
24"x18"
20"x20" 20"x20"
"x
"x
20"x20"20"x20"
24"x18" 24"x18"
"x
"x
L-5L-4 L-6 L-7
L-8 L-9 L-10 L-11
MMD-5
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-102
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL THIRD FLOOR AND ATTIC PLANS - HVAC
60041612 N40085-24-B-0016
05-24-0016 108 OF 174
3/32" = 1'-0" A1
THIRD FLOOR PLAN - MECHANICAL WORK
3/32" = 1'-0" C1
ATTIC PLAN - MECHANICAL WORK
# PLAN NOTES
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
1 PROVIDE EXHAUST AND SUPPLY (VENTILATION)
MAINS AS SHOWN. SEE ENLARGED PLANS FOR
BRANCH DUCTS TO DIFFUSERS/GRILLES.
(TYPICAL EXHAUST AND SUPPLY MAINS)
2 PROVIDE PTHP UNIT WITH LIGATURE PROOF
PROTECTIVE COVER, CORROSION RESISTANT
CHASSIS, AND 3/4" CONDENSATE DRAIN WITH
EXTERIOR CLEANOUT. PAINT DDC CONDUIT
EXPOSED IN OCCUPIED AREAS TO MATCH
INTERIOR. COORDINATE WITH ARCHITECTURAL
AND INTERIOR PLANS. (TYP)
3 EXHAUST AND SUPPLY (VENTILATION) MAIN
DUCT RISER UP FROM LEVELS BELOW. ROUTE
TO EXTERIOR LOUVERS AS SHOWN.
4 PROVIDE 1'-0" DEEP INSULATED PLENUM SIZED
TO MATCH DIMENSIONS OF THE LOUVER AND
CONNECT TO EXHAUST LOUVER. PROVIDE
MANUAL DAMPER IN EACH DUCT PRIOR TO
PLENUM CONNECTION. SEE ARCHITECTURAL
DRAWINGS FOR LOUVER LOCATION AND
SPECIFICATION. STRUCTURAL MODIFICATION TO
WOODEN ROOF TRUSSES, SUPPORTS AND
BRACING WILL BE REQUIRED TO ROUTE DUCT
TO LOUVERS AND TO INSTALL LOUVERS IN
GABLE/DORMER WALL.
5 PROVIDE 1'-0" DEEP INSULATED PLENUM SIZED
TO MATCH DIMENSIONS OF THE LOUVER AND
CONNECT TO INTAKE LOUVER. PROVIDE
MANUAL DAMPER IN EACH DUCT PRIOR TO
PLENUM CONNECTION. SEE ARCHITECTURAL
DRAWINGS FOR LOUVER LOCATION AND
SPECIFICATION. STRUCTURAL MODIFICATION TO
WOODEN ROOF TRUSSES, SUPPORTS AND
BRACING WILL BE REQUIRED TO ROUTE DUCT
TO LOUVERS AND TO INSTALL LOUVERS IN
GABLE/DORMER WALL.
6 ROUTE CENTRAL CORE EXHAUST DUCT RISER
TO INLINE EXHAUST FAN ON PLATFORM IN
ATTIC. ROUTE EXHAUST FROM FAN TO LOUVER
AS SHOWN.
N
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PLAN DRAWINGS ARE DIAGRAMMATIC IN
NATURE AND DO NO ILLUSTRATE SPECIFIC
DUCT TAKE-OFF CONFIGURATIONS AND TAPS.
PROVIDE FLEXIBLE DUCTWORK RUNOUTS TO
SUPPLY AND RETURN GRILLES WITH A
MAXIMUM LENGTH OF 5 FEET AND SINGLE
BENDS NO GREATER THAN 45 DEGREES.
REFER TO PROJECT SPECIFICATIONS AND
DUCTWORK DETAILS FOR SPECIFIC
REQUIREMENTS.
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
CLERKS OFFICE
XO OFFICE
COPY/KITCHENETTE
TOILET
TOILET
ADMINISTRATIVE OFFICE
CO OFFICE
STORAGE
CLEAN GEAR
ADMINISTRATIVE OFFICE
LAUNDRY
MECHANICAL
LAUNDRY
JANITOR
STORAGE
VENDING
OFFICE
CORRIDOR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
MECHANICAL CHASE
MECHANICAL CHASE
STAIR #3
S013
STAIR #1
S011
STAIR #2
S012
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP
PTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHP
D O
A S
-1
D O
A S
-2
AHU-1
PTHP
PTHP PTHP
PTHP PTHP PTHP
EF-2
UH-2
3/4"ø HWS 3/4"ø HWR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
LOUNGE
LAUNDRY
JANITOR
STORAGE
VENDING
COMM
CORRIDOR
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
SLEEPING ROOM
237SLEEPING ROOM
SLEEPING ROOM
STAIR #3
S023
MECHANICAL CHASE
MECHANICAL CHASE
258STAIR #1
S021
STAIR #2
S022
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
MECHANICAL
SLEEPING ROOM
SLEEPING ROOM
MECHANICAL
PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP PTHP
PTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHPPTHP PTHP PTHP PTHP
PTHP PTHP
D O
A S
-4
D O
A S
-3
AHU-2
EF-3
UH-3
3/4"ø HWS 3/4"ø HWR
SYM. DESCRIPTION DATE APP.
REVISIONS
DR.
DES.
CHK.
SUBMITTED BY:
APPROVED: PWO OR OICC
SATISFACTORY TO:
DATE
DATE
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
CAMP LEJEUNE, NORTH CAROLINA
MARINE CORPS BASE
SIZE CODE IDENT. NO. NAVFAC DRAWING NO.
E1 80091
CONSTR. CONTR. NO.
AS NOTEDSCALE SHEET
M B
F A
N O
SPEC.
M-103
PJR
MAS
LWM
REPAIR BEQ BB250
OVERALL FIRST AND SECOND FLOOR PLANS - PIPING
60041613 N40085-24-B-0016
05-24-0016 109 OF 174
3/32" = 1'-0" A1
FIRST FLOOR PLAN - MECHANICAL PIPING WORK
3/32" = 1'-0" C1
SECOND FLOOR PLAN - MECHANICAL PIPING WORK
# PLAN NOTES
GRAPHIC SCALE: 3/32"=1'-0"
8' 0 8' 16' 24'
1 CHILLED WATER (CHW) AND HOT WATER (HW)
PIPING UP FROM UNDERGROUND INTO
MECHANICAL ROOM. ROUTE CHW AND HW
PIPING TO FLOOR MOUNTED DOAS IN
MECHANICAL ROOM AND CONTINUE MAIN
PIPING UP TO LEVEL ABOVE. SEE ENLARGED
PLANS FOR MORE INFORMATION.
2 CHILLED WATER (CHW) AND HOT WATER (HW)
PIPING UP FROM UNDERGROUND INTO
STORAGE ROOM. ROUTE CHW AND HW PIPING
TO FLOOR MOUNTED AIR HANDLER AND
CONTINUE MAIN PIPING UP TO LEVEL ABOVE.
SEE ENLARGED PLANS FOR MORE
INFORMATION.
3 CHILLED WATER (CHW) AND HOT WATER (HW)
PIPING UP FROM LEVEL BELOW. ROUTE CHW
AND HW PIPING TO DOAS IN MECHANICAL ROOM
AND CONTINUE MAIN PIPING UP TO THIRD
LEVEL. SEE ENLARGED PLANS FOR MORE
INFORMATION.
N
N
GENERAL NOTES:
1. SEE SHEET M-001 FOR GENERAL NOTES,
LEGEND & ABBREVIATIONS
2. PLAN DRAWINGS ARE…