This is Amendment 0005 to a federal construction contract (N40085-26-R-9050) issued by NAVPAC Mid-Atlantic for a repair project at Camp Lejeune, North Carolina. The amendment was effective July 23, 2026, and extends the deadline for receipt of proposals to August 12, 2026, at 2 PM EST. The amendment modifies the original solicitation and must be acknowledged by contractors upon proposal submission; failure to acknowledge may result in proposal rejection.

The amendment consists primarily of a Questions and Answers document addressing clarifications for two Building Equipment Quotations (BEQ G702 and BEQ G703). Key technical clarifications include: vandal proof hood vents are not required; adhesive pipe labels are not acceptable alternatives to snap-on or wrap-around labels; specification section 33 61 14 applies to all underground piping including hot domestic water, recirculating hot domestic water, and chilled water piping; minimum-security type grilles (not face plates with tamperproof screws) are required for air distribution; manual dampers are not required on branches to terminals equipped with opposed blade dampers; TMV-2 thermostatic mixing valves apply only to lavatories at 110°F, not to service sinks or mop sinks; domestic water connections must be provided for 12 washers per side; and pre-insulated piping must be routed to Mechanical Room 123b rather than 123A. All other contract terms and conditions remain unchanged.

View the file

Other files

File Type Posted
Amend 0013.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
25-0010 SID.pdf PDF
25-0051 GEO.pdf PDF
25-0010 DM for Repair BEQ 702.pdf PDF
RFP 250010.pdf PDF
25-0051 SID.pdf PDF
25-0051 BOD.pdf PDF
25-0010 BOD.pdf PDF
25-0010 APPD.pdf PDF
N4008525B0051 DWG_Signed.pdf PDF
N4008525B0051 Specs.pdf PDF
N4008525B0010 Specs.pdf PDF
25-0010 GEO.pdf PDF
25-0051 Asbestos and Lead Report.pdf PDF
25-0051 APPD.pdf PDF
N4008525B0010 DWG_Signed.pdf PDF
25-0010 Lead and Asbestos Report.pdf PDF
25-0051 DM.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N40085-26-R-9050 Amendment 0005

CONTINUATION SHEET

1. QUESTION: BEQ G702: Note 6 on P-001 indicates that all vents to have vandal proof hoods. Detail C6 on drawing P-501 indicates for the vent to be installed without a vandal proof hood. Are we to install the vents per detail B4 on drawing P-501?

ANSWER: No. Vandal proof hood vents are not required for this project.

2. QUESTION: BEQ G702: Adhesive labels with arrows in the specified colors have been sufficient for pipe designation at Camp Lejeune. Will adhesive labels be allowed in lieu of snap on or wrap around labels shown on detailC1 on drawing P-504 and detail A4 on drawing M-505?

ANSWER: Adhesive labels are not a sufficient alternative to snap-on or wrap-around labels.

The Contractor (KTR) shall adhere to the labeling requirements as specified in the contract drawings and specifications.

3. QUESTION: BEQ G702: Section 33 61 14 Exterior Buried Preinsulated Water Piping, paragraph 1.2-mention of heating hot water piping. What are the requirements for the exterior buried preinsulated heated hot water piping?

ANSWER:

includes hot domestic water piping, recirculating hot domestic water piping, chilled water piping,

4. QUESTION: BEQ G702: Note 5 on Air Distribution Schedule on drawing M-601 calls for a minimum-security face plate with tamperproof screws. Is the intent for these pieces of air distribution to have a minimum-security face plate?

ANSWER: Design intent is to provide minimum-security type grille.

5. QUESTION: BEQ G702: All pieces of Air Distribution per the schedule on drawing M-601 are to be provided with Factory Installed Opposed Blade Dampers. There are several area where the duct branches to said pieces of air distribution show a manual hand damper (for example see duct branch to S3 diffuser in Open Bay Sleeping Rooms 127A and 127B on drawing M-101).

There are no access doors shown to be provided on Reflected Ceiling Plans. Are the manual dampers required on branches to Air Distribution that are provided with Opposed Blade Dampers? If so, what type of access doors will need to be provided?

ANSWER: Manual dampers are not required for branches to terminals with OBD.

6. QUESTION:

point-of-use mixing valve in accordance with ASSE 1070 at lavatories, hand-wash sinks, and washfountain locations. Point-of-use mixing valve must limit the tempered water to not greater

-2 Thermostatic Mixing Valve on Plumbing Equipment Schedule on drawing P-provided for P-8 Service Sink Wall Mounted or P-10 Mop Sink? If so, will it be a TMV-2 or different mixing valve due to flow rates?

ANSWER: TMV-2 is intended to only ensure 110 deg F water is provided at the lavatories.

There is no requirement for this at service sinks or mop sinks.

7. QUESTION: BEQ G702: Detail B4 on drawing P-403 does not show domestic water hookup to the P-11 washer boxes shown on each side of the bottom 2 washers on each row. Laundry water riser diagram of drawing P-702 does not show the domestic water hookup either. Should each row include 10 each washers per the riser diagram, and floor plan, or should we include 12 each washers per row and include domestic water hookup not shown?

ANSWER: Domestic water should be provided for 12 washers on each side.

8. QUESTION: BEQ G702: Detail A3, drawing M-105, Note 4 shows the location where the pre-insulated HWS & HWR, and CHWS & CHWR is to pop up in Mechanical Room 123A.

This routing is the same as shown on drawing CG101. Drawing M-111 shows HWS/HWR & CHWS/CHWR pre-insulated piping entering the building at Duty Room 124A. Please advise the routing of exterior pre-insulated pipe and where pipe will enter the building.

ANSWER: Piping is to be routed to 123b Mechanical, the closest mechanical room to the new mechanical building. This is also reflected on M-111 and CG101 & CU101. Note 4 on A3/M- 105 can be omitted. It was intended to apply to A1/M-105.

9. QUESTION: BEQ G703: Note 6 on P-001 indicates that all vents to have vandal proof hoods. Detail C6 on drawing P-501 indicates for the vent to be installed without a vandal proof hood. Are we to install the vents per detail B4 on drawing P-501?

ANSWER: No. Vandal proof hood vents are not required for this project.

10: QUESTION: BEQ G703: Adhesive labels with arrows in the specified colors have been sufficient for pipe designation at Camp Lejeune. Will adhesive labels be allowed in lieu of snap on or wrap around labels shown on detailC1 on drawing P-504 and detail A4 on drawing M-505?

ANSWER: Adhesive labels are not a sufficient alternative to snap-on or wrap-around labels.

The Contractor (KTR) shall adhere to the labeling requirements as specified in the contract drawings and specifications.

11. QUESTION: BEQ G703: Section 33 61 14 Exterior Buried Preinsulated Water Piping, paragraph 1.2-mention of heating hot water piping. What are the requirements for the exterior buried preinsulated heated hot water piping?

ANSWER: Use 33 61 14 for all underground piping. Spec includes hot domestic water piping, recirculating hot domestic water piping, chilled water piping,

12. QUESTION: BEQ G703: Note 5 on Air Distribution Schedule on drawing M-601 calls for a minimum-security face plate with tamperproof screws. Is the intent for these pieces of air distribution to have a minimum-security face plate?

ANSWER: Design intent is to provide minimum-security type grille.

13. QUESTION: BEQ G703: All pieces of Air Distribution per the schedule on drawing M-601 are to be provided with Factory Installed Opposed Blade Dampers. There are several area where the duct branches to said pieces of air distribution show a manual hand damper (for example see duct branch to S3 diffuser in Open Bay Sleeping Rooms 127A and 127B on drawing M-101).

There are no access doors shown to be provided on Reflected Ceiling Plans. Are the manual dampers required on branches to Air Distribution that are provided with Opposed Blade Dampers? If so, what type of access doors will need to be provided?

ANSWER: Manual dampers are not required for branches to terminals with OBD.

14. QUESTION:

a point-of-use mixing valve in accordance with ASSE 1070 at lavatories, hand-wash sinks, and washfountain locations. Point-of-use mixing valve must limit the tempered water to not greater

-2 Thermostatic Mixing Valve on Plumbing Equipment Schedule on drawing P-provided for P-8 Service Sink Wall Mounted or P-10 Mop Sink? If so, will it be a TMV-2 or different mixing valve due to flow rates?

ANSWER: TMV-2 is intended to only ensure 110 deg F water is provided at the lavatories.

There is no requirement for this at service sinks or mop sinks.

15. QUESTION: BEQ G703: Detail B4 on drawing P-403 does not show domestic water hookup to the P-11 washer boxes shown on each side of the bottom 2 washers on each row.

Laundry water riser diagram of drawing P-702 does not show the domestic water hookup either.

Should each row include 10 each washers per the riser diagram, and floor plan, or should we include 12 each washers per row and include domestic water hookup not shown?

ANSWER: Domestic water should be provided for 12 washers on each side.

16. QUESTION: BEQ G703: Detail A3, drawing M-105, Note 4 shows the location where the pre-insulated HWS & HWR, and CHWS & CHWR is to pop up in Mechanical Room 123A.

This routing is the same as shown on drawing CG101. Drawing M-111 shows HWS/HWR & CHWS/CHWR pre-insulated piping entering the building at Duty Room 124A. Please advise the routing of exterior pre-insulated pipe and where pipe will enter the building.

ANSWER: Piping is to be routed to 123b Mechanical, the closest mechanical room to the new mechanical building. This is also reflected on M-111 and CG101 & CU101. Note 4 on A3/M- 105 can be omitted. It was intended to apply to A1/M-105 only.

17. All other terms and conditions remain unchanged.