Amen04 dwg 60039111r1.pdf
PDF 417 KB Posted
- Attached to
- Repair By Replacement TC601 Federal contract opportunity
- Solicitation number
- N4008523R2850
About this file
This document contains mechanical, electrical, and control schematics for a federal contract opportunity with the Department of the Navy to repair by replacement an air handling unit and associated HVAC components at facility TC601. Key specifications include replacement of a single zone VAV air handler with a 4-pipe unit providing a maximum airflow of 7,200 CFM, addition of three ductless split systems ranging in cooling capacity from 21-30 MBH, and replacement of existing louvers, registers, unit ventilators and fans. Electrical and controls work is also specified. The solicitation number is N4008523R2850 and responses are due on the date listed on the documents.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amen 07 Photos3of3.pdf | ||
| Amen07 Photos1of3.pdf | ||
| Amen07 Photos2of3.pdf | ||
| Amen07 220049.pdf | ||
| Amen06 Dwg SKS-1.pdf | ||
| Amen06 220049.pdf | ||
| Amen05 220049.pdf | ||
| Amen04 220049.pdf | ||
| Amen04 Spec 23 07 00r1.pdf | ||
| Amen04 dwg 60039100r2.pdf | ||
| Amen03 220049.pdf | ||
| Amen02 220049.pdf | ||
| Amen02 220049.pdf | ||
| Amen02 dwg 60039115r1.pdf | ||
| Amen02 dwg 60039105r1.pdf | ||
| Amen02 dwg 60039100r1.pdf | ||
| Amen01 220049.pdf | ||
| 22-0049 APPD.pdf | ||
| 22-0049 PIS.pdf | ||
| 22-0049 Design Analysis.pdf | ||
| 22-0049 Geotechnical Report.pdf | ||
| N4008522B0049 DRWGS.pdf | ||
| RFP 220049.pdf | ||
| N4008522B0049 SPECS.pdf |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
043801
TROY O. GRADY
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
SEE DISCLOSURE OF INFORMATION STATEMENT ON SHEET G-001
2246 Yaupon Drive Wilmington, NC 28401
Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2023CBHF Engineers, PLLC
Engineers, PLLC
06-08-2023
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
M-601
MECHANICAL
SCHEDULES
BLOWER COIL SCHEDULE
DRAWING CODE
(IDU/ODU)
SYSTEM TYPE FAN COOLING COIL CHILLED WATER REHEAT COIL ELECTRICAL WEIGHT
(LBS)
NOTES ACCESSORIES
SUPPLY
AIRFLOW (CFM)
BHP PER
FAN (HP)
MOTOR
(HP)
ESP
(IN.WG.)
AIRFLOW MAX
(CFM)
VELOCITY
(FPM)
TOTAL CAP
(MBH)
SENSIBLE CAP
(MBH)
EAT
(°F db/wb)
LAT
(°F db/wb)
APD
(IN. H20)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
WPD
(FT. H20)
PIPE CONN.
(IN)
AIRFLOW
(CFM)
VELOCITY
(FPM)
TOTAL CAP
(MBH)
EAT
(°F )
LAT
(°F)
APD
(IN. H20)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
WPD
(FT. H20)
PIPE CONN.
(IN)
POWER (V/PH/HZ) (MCA) (MOCP)
BC01 4-PIPE BLOWER COIL 1,045 1 0.5 1,045 392 46.8 29.8 77.7 / 65.7 51.7 / 50.4 0.605 44.0 54.0 9.7 8.05 1 1/4 1045 392 42.20 58.3 95.6 0.127 130 100 2.68 1.89 3/4 208/1/60 9.7 15 317 1-4 A,B,C,D BC02 4-PIPE BLOWER COIL 260 0.5 0.5 260 293 8.4 6.5 75.9 / 63.4 53.1 / 52.1 0.319 44.0 54.0 1.7 1.34 3/4 260 293 9.33 63.1 96.3 0.08 130 100 0.59 0.32 3/4 208/1/60 5.3 15 205 1-4 A,B,C,D BC03 4-PIPE BLOWER COIL 645 1 0.5 645 387 19.5 15.8 75.0 / 62.1 52.7 / 51.4 0.512 44.0 54.0 4.2 3.34 1 645 387 23.48 65.8 99.5 0.127 130 100 1.47 1.45 1 208/1/60 9.7 15 244 1-4 A,B,C,D NOTES: 1 REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2 COIL, DRAIN AND MOTOR SIDE ACCESS TO BE FIELD CONFIRMED PRIOR TO SUBMITTING FOR APPROVAL
3 MAXIMUM COIL FACE VELOCITY SHALL NOT EXCEED SCHEDULED VALUES
4 ALL CONTROLS SENSORS, ACTUATORS AND WIRING PROVIDED AND INSTALLED BY DDC CONTRACTOR
ACCESSORIES: A FAN SHALL BE DIRECT DRIVE ECM TYPE. SEE EQUIPMENT SCHEDULE FOR SIZES AND QUANTITIES.
B PROVIDE UNIT WITH FACTORY PROVIDED 2 INCH ANGLE FILTER MIXING BOX WITH MERV 8 FILTERS.
C 1" INSULATED GALVANIZED STEEL CONSTRUCTION
D STAINLESS STEEL DRAIN PAN
ELECTRIC HEATER SCHEDULE
DRAWING CODE DESCRIPTION ELECTRIC COIL SUPPLY AIR ELECTRICAL WEIGHT
(LBS)
MOUNTING
HEIGHT
(FT)
NOTES ACCESSORIES
CAPACITY
(KW)
STEPS AIRFLOW
(CFM)
TEMP RISE
(F)
THROW
(FT)
POWER
(V/PH/HZ)
FLA MCA MOCP
TYPE FAN DISCHARGE
EUH01 UNIT HEATER PROPELLER HORIZONTAL 1.9 1 275.0 21.0 16 208/1/60 9.0 - - 32 10 1 A,B
NOTES: 1 REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATING, AND COOLING SYSTEM FOR FURTHER INFORMATION.
ACCESSORIES: A FACTORY INSTALLED THERMOSTAT, OVERHEAT SWITCH AND FAN DELAY SWITCH.
B MOUNTING HARDWARE
DIFFUSERS, REGISTERS AND GRILLES SCHEDULE
DRAWING CODE TYPE SERVICE NECK SIZE
(IN.)
BRANCH
CONN.
SIZE (IN.)
MODULE
SIZE (IN.)
MATERIAL FINISH MOUNTING NOTES ACCESSORIES
S1 SQUARE CEILING DIFFUSER SUPPLY 6Ø 6 24 X 24 ALUMINUM WHITE T-BAR 1,2 A
S2 SQUARE CEILING DIFFUSER SUPPLY 8Ø 8 24 X 24 ALUMINUM WHITE T-BAR 1,2 A
S3 RECTANGULAR CEILING DIFFUSER SUPPLY - - 12 X 4 ALUMINUM WHITE CEILING SURFACE 1,2 A,D
S4 RECTANGULAR CEILING DIFFUSER SUPPLY - 12 X 6 ALUMINUM WHITE CEILING SURFACE 1,2 A,D
S5 FIXED FACE GRILLE SUPPLY - - 12 X 10 ALUMINUM WHITE WALL SURFACE 1,2 A,D
S6 SPIRAL DUCT GRILLE SUPPLY - - 18 X 8 ALUMINUM MILL DUCT SURFACE 1 B,C
S7 FIXED FACE GRILLE SUPPLY - - 12 X 4 ALUMINUM WHITE WALL SURFACE 1,2 A,D
R1 SQUARE CEILING DIFFUSER RETURN - - 24 X 24 ALUMINUM WHITE T-BAR 1,2 E
R2 FIXED FACE GRILLE RETURN - - 54 x 54 ALUMINUM WHITE WALL SURFACE 1,2,3 F E1 RECTANGULAR CEILING DIFFUSER EXHAUST - - 12 x 4 ALUMINUM WHITE CEILING SURFACE 1,2 D E1 RECTANGULAR CEILING DIFFUSER EXHAUST - - 10 x 10 ALUMINUM WHITE CEILING SURFACE 1,2 D NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
2. DUCT BRANCH CONNECTION SIZE TO BE EQUAL TO THE NECK SIZE OF DIFFUSER UNLESS NOTED OTHERWISE ON PLANS.
3. USE FOR SEPARATE GRILLES EQUALLING 54 X 54. MOUNT WITH MOUNTING CHANNELS FASTENED WITH SCREWS TO DIVIDE OPENING.
ACCESSORIES: A. VOLUME DAMPER.
B. AIR SCOOP.
C. PAINT GRIP FINISH TO MATCH DUCTWORK.
D. CONCEALED MOUNTING BRACKET.
E. PROVIDE FILTER FRAME.
F. PROVIDE MEDIUM VELOCITY SILENCER WITH 22GA GALVANIZED PERFORATED LINER AND GLASS FIBER ACCOUSTIC MEDIA.
POWER VENTILATOR SCHEDULE
DRAWING CODE FAN TYPE SERVICE CAPACITIES ELECTRICAL SONES WEIGHT
(LBS.)
NOTES ACCESSORIES
AIRFLOW
(CFM)
ESP
(IN. WG.)
DRIVE
ARRANGEMENT
FAN
RPM
MOTOR
RPM
MOTOR
TYPE
MOTOR
SIZE (HP)
V/PH/HZ MCA MOCP
PV01 IN-LINE CENTRIFUGAL FANS EXHAUST 325 0.25 DIRECT 1,201 1,170 ECM 1/10 120/1/60 - - 4.8 49 1,2 A,B
PV02 CEILING-MOUNTED VENTILATORS EXHAUST 50 0.25 DIRECT 808 808 ECM 6 W 120/1/60 - - 0.7 12 1,2 A,B
PV03 CENTRIFUGAL ROOF VENTILATORS EXHAUST 975 0.25 DIRECT 867 867 ECM 1/4 120/1/60 - - 6.2 44 1,3 B,C,D
NOTES: 1 REFER TO SPECIFICATION FOR FURTHER INFORMATION.
2 UNIT TO RUN ON OCCUPIED SCHEDULE. REFER TO CONTROL SEQUENCE FOR ADDITIONAL INFORMATION.
3 REFER TO CONTROL DIAGRAMS
ACCESSORIES: A GRAVITY DAMPER
B UNIT MOUNTED SPEED CONTROLLER
C BIRD SCREEN
D ROOF CURB W/ SEAL
LOUVER SCHEDULE
DRAWING CODE TYPE FRAME DESCRIPTION MATERIAL LOUVER
DEPTH
SIZE (W x H) SERVICE AIRFLOW
(CFM)
PERFORMANCE RATINGS NOTES ACCESSORIES
FREE AREA S.P. LOSS WATER PENETRATION
(IN.) (IN.) (SF) (IN.H20) (OZ./SF)
L01 FIXED EXTERIOR FLANGE HORIZONTAL, WIND-DRIVEN-RAIN-RESISTANT ALUMINUM 7 12 x 12 EXHAUST 325 0.29 0.35 - 1,2 A,B
L02 FIXED EXTERIOR FLANGE HORIZONTAL, WIND-DRIVEN-RAIN-RESISTANT ALUMINUM 7 12 x 12 EXHAUST 50 0.29 0.03 - 1,2 A,B,C
L03 FIXED EXTERIOR FLANGE HORIZONTAL, WIND-DRIVEN-RAIN-RESISTANT ALUMINUM 7 24 x 24 INTAKE 975 1.77 0.09 1.46 1,2 A,B,C
L04 FIXED EXTERIOR FLANGE HORIZONTAL, WIND-DRIVEN-RAIN-RESISTANT ALUMINUM 7 36 x 24 INTAKE 1,405 2.78 0.08 1.59 1,2 A,B
NOTES: 1 REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATING, AND COOLING SYSTEM FOR FURTHER INFORMATION.
2 FINISH AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLOR AND GLOSS.
ACCESSORIES: A BIRD SCREENING (MATERIAL TO MATCH LOUVER MATERIAL)
B AMCA 550 LISTED (WATER PENETRATION)
C LOW LEAK MOTORIZED ALUMINUM DAMPER WITH END PROVING SWITCH.
SINGLE ZONE VAV AIR HANDLER SCHEDULE
DRAWING CODE
(IDU/ODU)
SYSTEM
TYPE
AIRFLOW COOLING COIL REHEAT COIL PREHEAT COIL ELECTRICAL WEIGHT (LBS.) NOTES ACCESSORIES
SUPPLY MAX.
AIRFLOW (CFM)
SUPPLY MIN.
AIRFLOW (CFM)
OUTSIDE
AIRFLOW (CFM)
NUMBER
OF FANS
POWER
(HP)
ESP
(IN.WG.)
AIRFLOW VELOCITY TOTAL CAP SENSIBLE CAP EAT LAT EWT LWT FLOW WPD PIPE RUNOUT AIRFLOW VELOCITY TOTAL CAP EAT LAT EWT LWT FLOW WPD PIPE RUNOUT AIRFLOW VELOCITY TOTAL CAP EAT LAT EWT LWT FLOW WPD PIPE RUNOUT POWER SUPPLY
(V/PH/HZ)
INDOOR UNIT
(CFM) (FPM) (MBH) (MBH) (°F db/wb) (°F db/wb) (°F) (°F) (GPM) (FT. H2O) (IN) (CFM) (FPM) (MBH) (°F) (°F) (°F) (°F) (GPM) (FT. H2O) (IN) (CFM) (FPM) (MBH) (°F) (°F) (°F) (°F) (GPM) (FT. H2O) (IN) (MCA) (MOCP)
AH01 4-PIPE 7,200 2,200 1,400 2 5 1.5 7,200 428.0 322.2 205.6 77.2/66.2 51.3/51.1 44.0 54.0 64.2 17.5 2 1/2 7,200 480.0 195.2 50.0 85.0 130.0 100.0 18.3 0.7 2 1/2 3,000 200.0 70 33.5 55.0 130.0 100.0 4.7 0.1 1 1/2 208/3/60 46.0 80 3288 1-5 A-J NOTES: 1 REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATING, AND COOLING SYSTEM FOR FURTHER INFORMATION.
2 COIL, DRAIN AND MOTOR SIDE ACCESS TO BE FIELD CONFIRMED PRIOR TO SUBMITTING FOR APPROVAL.
3 MAXIMUM COIL FACE VELOCITY SHALL NOT EXCEED SCHEDULED VALUES.
4 ALL CONTROLS SENSORS, THERMAL DISPERSION AIRFLOW METER, ACTUATORS, WIRING AND VFD SPEED CONTROL PROVIDED AND INSTALLED BY DDC CONTRACTOR.
5 REFER TO PLANS AND SECTION FOR UNIT ARRANGEMENTS.
ACCESSORIES: A COOLING COIL SECTIONS SHALL BE PROVIDED WITH AN INSULATED, DOUBLE WALL, 201 STAINLESS STEEL DRAIN PAN WITH POSITIVE DRAINAGE MEETING INDOOR AIR QUALITY (IAQ) IN ACCORDANCE WITH ASHRAE 62.1.
B COPPER COIL, ALUMINUM FIN, STAINLESS STEEL COIL CASING.
C UNIT PANELS SHALL BE MINIMUM 2" DOUBLE WALL FOAM R-13 CONSTRUCTION WITH ASHRAE 111 CLASS 6 CASING LEAKAGE.
D AHU PANELS SHALL BE PROVIDED WITH A MID-SPAN, NO-THRU-METAL, INTERNAL THERMAL BREAK. ENTIRE UNIT SHALL BE MADE OF GALVANIZED STEEL.
E PROVIDE 2" MERV 8 PLEATED MEDIA FILTERS, THREE SETS OF EACH TYPE. PROVIDE ONE SET IN UNIT, PROVIDE ONE SET FOR INSTALLATION AFTER SYSTEM IS BALANCED AND BUILDING IS CLEANED, AND ONE SET FOR TURN OVER TO OWNER.
F PROVIDE RETURN AIR AND OUTDOOR AIR DAMPERS. ALL DAMPERS INTERNAL TO BE PREMIUM LOW LEAK, ALUMINUM DAMPERS.
G HINGED ACCESS DOORS, MOTOR SIDE ONLY. ACCESS DOORS SHALL BE 2" DOUBLE WALL CONSTRUCTION. SURFACE MOUNTED HANDLES SHALL BE PROVIDED TO ALLOW QUICK ACCESS TO THE INTERIOR OF THE UNIT.
H FAN SHALL BE VFD TYPE. SEE EQUIPMENT SCHEDULE FOR SIZES AND QUANTITIES.
I PROVIDE UNIT WITH FACTORY PROVIDED 2 INCH ANGLE FILTER MIXING BOX.
J PROVIDE HYDRONIC COILS WITH SEA COAST PROTECTION TO MEET ASTM B117 5000 HOUR RATING.
DUCTLESS SPLIT SYSTEM SCHEDULE
DRAWING CODE ARI COOLING
80/67/95
ARI HEATING
70/47
MIN
SEER
MIN
HSPF
INDOOR UNIT OUTDOOR UNIT REFRIGERANT PIPING NOTES ACCESSORIES
FAN ELECTRICAL WEIGHT ELECTRICAL WEIGHT MAXIMUM
LENGTH (FT.)
MAXIMUM HEIGHT
DIFFERENTIAL
(FT.)
TOTAL MIN. TOTAL SA MIN-MAX VOLTAGE MCA VOLTAGE MCA MOCP
(IDU / ODU) (MBH) (MBH) (MBH) (CFM) (V/PH/HZ) (AMPS) (LBS) (V/PH/HZ) (AMPS) (AMPS) (LBS)
DAH01 / DHP01 21.0 6.5 30.0 21.0 12.5 194-376 208/1/60 1 29 208/1/60 18 20 118 100 50 1 A,B,C,D
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - HEATING, VENTILATION, AND COOLING SYSTEM FOR FURTHER REQUIREMENTS.
ACCESSORIES: A. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTOR FROM OUTDOOR UNIT TO INDOOR UNIT.
B. HEAT PUMP COILS TO BE COATED FOR EXPOSURE TO ASTM B117-90 3000 HOUR SALT SPRAY RESISTANCE TEST WITH NO DEGRADATION.
C. PROVIDE BACNET MSTP DDC CONTROL SYSTEM INTERFACE
D. PROVIDE ASPEN MINI WHITE CONDENSATE PUMP AND RESERVOIR OR EQUAL WITH CAPACITY OF 1.6 GAL/HR AT 33 FT OF HEAD. INTERLOCK TO SHUTDOWN UNIT.
1 AMENDMENT 03 08/10/20231
08/10/2023