This plumbing drawing package details the domestic water piping plan for a church facility renovation project. The drawings show the layout of water lines 1/2" or larger throughout the building, including lines routed under slab, above ceiling, and overhead. Notes specify that the contractor may use PEX-A piping for domestic water lines under slab if no joints are located under the slab. The related federal contract opportunity is a solicitation from the Department of the Navy to repair a facility by replacement of utility system TC601. No pricing, response dates, or other contract details are provided in the documents reviewed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amen 07 Photos3of3.pdf | ||
| Amen07 Photos1of3.pdf | ||
| Amen07 Photos2of3.pdf | ||
| Amen07 220049.pdf | ||
| Amen06 Dwg SKS-1.pdf | ||
| Amen06 220049.pdf | ||
| Amen05 220049.pdf | ||
| Amen04 220049.pdf | ||
| Amen04 Spec 23 07 00r1.pdf | ||
| Amen04 dwg 60039100r2.pdf | ||
| Amen04 dwg 60039111r1.pdf | ||
| Amen03 220049.pdf | ||
| Amen02 220049.pdf | ||
| Amen02 dwg 60039115r1.pdf | ||
| Amen02 220049.pdf | ||
| Amen02 dwg 60039105r1.pdf | ||
| Amen01 220049.pdf | ||
| 22-0049 APPD.pdf | ||
| 22-0049 PIS.pdf | ||
| 22-0049 Design Analysis.pdf | ||
| RFP 220049.pdf | ||
| 22-0049 Geotechnical Report.pdf | ||
| N4008522B0049 DRWGS.pdf | ||
| N4008522B0049 SPECS.pdf |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P
2"
3/4"
HB1
2"
1/2" 1-1/4"
SEE PW101 FOR
CONTINUATION
PIPING ROUTED
UNDER SLAB
2"
1/2" 1"
1/ 2"
1/ 2"
1"
2"
1"
2" 2"
PIPING ROUTED
UNDER SLAB
1/2" 1/2"
1/ 2" 1/ 2" 1-1/2"
1/2" 1/2"
1/2"
SK2
OB1
WC1
MB1
LAV1
2" 2"
2"
1/2"
3/ 4"
SEE PW101 FOR
CONTINUATION
SEE CIVIL UTILITY
PLAN FOR
CONTINUATION
1/ 2" 1/2"
CIRCUIT
SETTER
BALANCING
VALVE
"B"
TRAP
PRIMER
TRAP
PRIMER
SK1
2"
SHUTOFF
VALVE IN
RISER
GWH1
CP1
2"
3/ 4"
HB1
1" 1/2"1/2"
1"
RECIRC., DCW
AND DHW
PIPING DOWN
TO BELOW SLAB
1/ 2"
1/ 2"
3/4"
PIPING ROUTED
ABOVE CEILING
NORTH
TRANSEPT
BAND
PLATFORM
SACRISTY
CLOSET
EXIT
STORAGE
RISER
ROOM
MECH
SOUND
BOOTH
FELLOWSHIP
ENTRY
UNISEX
DRESSING
1/2"
1/2"
2" 2"
2"
1/2" 1-1/2"
1-1/2"
2"
2"
1/2"
1" 1"
PIPING
ROUTED
ABOVE
CEILING
1- 1/
4" 1-
1/ 4"
1- 1/
4" 1/
2" 1/
2" 1/
2"
RECIRC., DCW
AND DHW
PIPING DOWN
TO BELOW SLAB
RECIRC., DCW
AND DHW
PIPING DOWN
TO BELOW SLAB
1" 2"
1/ 2"
1/ 2"
1/ 2"
1/ 2"
1-1/2"
RPZ, MOUNT
OVERHEAD.
LOCATION WITH
MECHANICAL
CONTRACTOR
EW1
1"
PIPING ROUTED
UNDER SLAB
NOTE: CONTRACTOR
MAY USE PEX-A PIPING
FOR DOMESTIC WATER
PIPING UNDER SLAB.
WHEN USING PEX-A, NO
JOINTS ARE PERMITTED
TO BE UNDER THE SLAB.
1"
1-1/2"
2"
1/2" 3/4"
2"
1/ 2"
WC2
WC1
1/ 2"
1/2
2"
1/2"
2" 2"
1/2" 1/2"
MB2
2"
1"
1"1"
1/2"
1/ 2"
2"2" 2"
UR1
WC2
WC1
SEE PW101 FOR
CONTINUATION
PIPING UP TO
ABOVE CEILING
ROUTE PIPING
UNDER SLAB
1/2"1/2" 1/2"
3/4"
3/ 4"
3/ 4"
3/ 4"
1"
1"1"1-1/4"1-1/4"
HB1
HB1
PIPING ROUTED
ABOVE CEILING
HAMMER
ARRESTOR,
TYP.
"C"
"B"
1-1/2"
3/ 4"
1-1/2"1-1/2"
1- 1/
2"
EWC1
3/4"
LAV2LAV2
1/2"
LAV2LAV2
1-1/2"
1" 1"
ADMIN.
OFFICE
WOMEN
104 CLOSET
NARTHEX
MEN
PRAYER
ROOM
JANITOR
I.T.
ROOM
107A
3/ 4"
1/ 2"
1/ 2"
1/ 2"
NOTE: CONTRACTOR
MAY USE PEX-A PIPING
FOR DOMESTIC WATER
PIPING UNDER SLAB.
WHEN USING PEX-A, NO
JOINTS ARE PERMITTED
TO BE UNDER THE SLAB.
043801
TROY O. GRADY
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
SEE DISCLOSURE OF INFORMATION STATEMENT ON SHEET G-001
2246 Yaupon Drive Wilmington, NC 28401
Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2023CBHF Engineers, PLLC
Engineers, PLLC
06-08-2023
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
PW401
PLUMBING DOMESTIC WATER
FIRST ENLARGED FLOOR PLAN
1/4" = 1'-0" 0 4' 8'2'1 DOMESTIC WATER ENLARGED PLAN
PLAN
NORTH
1/4" = 1'-0" 0 4' 8'2'2 DOMESTIC WATER ENLARGED PLAN
PLAN
NORTH
1 REVISED PER RFI 02 08/08/2023
08/08/2023
| 2023-08-08T16:27:24-0400 | |
| Troy O Grady |