Amen02 dwg 60039115r1.pdf

PDF 460 KB Posted

Attached to
Repair By Replacement TC601 Federal contract opportunity
Solicitation number
N4008523R2850
Issued by
Department of the Navy Naval Facilities Engineering Command

About this file

This document contains mechanical drawings and specifications for a boiler plant controls system for a federal facility. Key details include specifications for a dual boiler plant with lead-lag control and variable frequency drives on secondary pumps for balancing. The system will provide hot water for heating and freeze protection below 38 degrees Fahrenheit. Alarms are specified for high and low supply temperatures, pump failures, and emergency gas shutoff. The related federal contract opportunity is a solicitation from the Department of the Navy to repair by replacement of a boiler plant controls system at Naval Facilities Engineering Command Contract Center TC601. The solicitation number and name of the project are provided.

View the file

Other files for this federal contract opportunity

Other files attached to Repair By Replacement TC601, newest first.
File Type Posted
Amen 07 Photos3of3.pdf PDF
Amen07 Photos1of3.pdf PDF
Amen07 Photos2of3.pdf PDF
Amen07 220049.pdf PDF
Amen06 Dwg SKS-1.pdf PDF
Amen06 220049.pdf PDF
Amen05 220049.pdf PDF
Amen04 220049.pdf PDF
Amen04 Spec 23 07 00r1.pdf PDF
Amen04 dwg 60039100r2.pdf PDF
Amen04 dwg 60039111r1.pdf PDF
Amen03 220049.pdf PDF
Amen02 220049.pdf PDF
Amen02 220049.pdf PDF
Amen02 dwg 60039105r1.pdf PDF
Amen02 dwg 60039100r1.pdf PDF
Amen01 220049.pdf PDF
22-0049 APPD.pdf PDF
22-0049 PIS.pdf PDF
22-0049 Design Analysis.pdf PDF
22-0049 Geotechnical Report.pdf PDF
N4008522B0049 DRWGS.pdf PDF
RFP 220049.pdf PDF
N4008522B0049 SPECS.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

043801

TROY O. GRADY

SEAL

R

EENI GN

P R

OF E S S I ON

A

E

L

NO

RT H CAROL I NA

SEE DISCLOSURE OF INFORMATION STATEMENT ON SHEET G-001

2246 Yaupon Drive Wilmington, NC 28401

Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2023CBHF Engineers, PLLC

Engineers, PLLC

06-08-2023

151 Poole Rd. Suite 100 | Leland, NC, 28451

TEL (910) 383-1044 | FAX (910) 383-1045

www.capefearengineering.com | N.C. LICENSE # C-1621

M-802

MECHANICAL

CONTROLS

NOT TO SCALE1 BOILER PLANT CONTROLS

BOILER PLANT SEQUENCE OF OPERATION

AI

HWS

AI HOT WATER RETURN

TEMPERATURE

HOT WATER SUPPLY

TEMPERATURE

OUTSIDE AIR TEMPERATURE

HOT WATER PUMP 1

HOT WATER PUMP 2

BI

BO

BOILER 1

ENABLE/DISABLE

BOILER 1

ALARM

BOILER 1 CIRCULATING

PUMP

BOILER - 1

BI

BO

BOILER 2

ENABLE/DISABLE

BOILER 2

ALARM

BOILER 2 CIRCULATING

PUMP

BOILER - 2

AI

SECONDARY LOOP HOT WATER

PUMP 1 START/STOP

SECONDARY LOOP HOT WATER

PUMP 1 STATUS

BI

BO

HWR

HOT WATER SUPPLY TEMPERATURE

BY BOILER MANUFACTURER

WIRED TO BOILER 1

AI

AI

PLANT HW

FLOW METER

AI

PRIMARY HOT WATER

RETURN TEMPERATURE

AI

PRIMARY HOT WATER

SUPPLY TEMPERATURE

VFD

SECONDARY LOOP HOT WATER

PUMP 1 SPEED

AO

SECONDARY LOOP HOT WATER

PUMP 2 START/STOP

SECONDARY LOOP HOT WATER

PUMP 2 STATUS

BI

BO

VFD

SECONDARY LOOP HOT WATER

PUMP 2 SPEED

AO

PRIMARY-SECONDARY LOOP CONSTANT FLOW BOILER PLANT

GENERAL DESCRIPTION:

THE HOT WATER SYSTEM CONSISTS OF (2) BOILERS, THEIR ASSOCIATED CIRCULATION PUMPS AND TWO SECONDARY PUMPS. THE BUILDING AUTOMATION SYSTEM (BAS) CONTROLLER SHALL PROVIDE THE ENABLE SIGNAL TO THE BOILER PLANT AND THE START THE A SECONDARY PUMP. THE FACTORY BOILER CONTROLS SHALL PROVIDE CONTROL OF THE SUPPLY HEATING WATER TEMPERATURE SETPOINT (ADJ.) AND CONTROL THE BOILER'S CIRCULATION PUMP. ONLY TWO (2) BOILERS, THEIR CIRCULATION PUMPS AND (1) SECONDARY PUMP SHALL RUN

AT A TIME. VFD'S ON SECONDARY PUMPS MUST BE UTILIZED FOR BALANCING.

HEATING SYSTEM ENABLE/DISABLE:

THE HEATING SYSTEM SHALL BE ENABLED WHEN A DEFINABLE NUMBER (ADJ.) OF HOT WATER COILS NEED HEATING OR THE OUTSIDE AIR TEMPERATURE FALLS BELOW 60.0 DEG. F (ADJ.) OR ON A COMMAND FOR DEHUMIDIFICATION. WHEN ENABLED, THE BAS CONTROLLER SHALL START THE LEAD SECONDARY PUMP, AND ENABLE THE BOILER PLANT. THE BOILER FACTORY CONTROL SHALL OPERATE THE BOILERS INCLUDING THE

BOILER CIRCULATION PUMPS, TO MAINTAIN ITS LOCAL SUPPLY SETPOINT.

THE BOILERS SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.

THE BOILER PLANT SHALL ALSO RUN FOR FREEZE PROTECTION WHENEVER THE OUTSIDE AIR TEMPERATURE IS

LESS THAN 38°F (ADJ.).

BOILER CONTROL:

THE TWO BOILERS SHALL OPERATE IN A LEAD/LAG FASHION WHEN CALLED TO RUN AND FLOW IS PROVEN. THE

BOILERS SHALL CONTROL ITS CIRCULATION PUMP.

· THE LEAD BOILER SHALL RUN FIRST. IF NEEDED THE BOILER FACTORY CONTROLS SHALL ENABLE THE LAG

BOILER TO MAINTAIN SETPOINT.

· ON FAILURE OF THE LEAD BOILER, THE STANDBY BOILER SHALL RUN AND THE LEAD BOILER SHALL TURN OFF.

IF THE HOT WATER DISTRIBUTION SYSTEM SUPPLY TEMPERATURE FALLS MORE THAN 25.0 DEG. F (ADJ.) BELOW SETPOINT FOR A PERIOD LONGER THAN 15 MINUTES (ADJ.), OR IF AN ACTIVE BOILER SIGNALS A FAILURE ALARM, THE BAS CONTROLLER SHALL SEND AN ALARM TO THE BAS WORKSTATION. WHEN A BOILER FAILURE EXISTS, LEAD/LAG AUTOMATION SHALL BE DISABLED AND THE CURRENTLY RUNNING BOILER SHALL BECOME THE LEAD BOILER. ONCE THE PROBLEM IS CORRECTED, THE OPERATOR SHALL BE ABLE TO CLEAR THE ALARM FAILURE AND

THIS SHALL RE-ENABLE THE LEAD/LAG SEQUENCE.

THE FACTORY BOILER CONTROLS SHALL ROTATE THE LEAD/LAG SEQUENCE OF THE BOILERS.

THE BAS SHALL ROTATE THE LEAD/STANDBY SEQUENCE OF THE SECONDARY PUMPS ON THE 1ST AND THE 15TH

OF EACH MONTH.

BOILER ALARMS SHALL BE PROVIDED AS FOLLOWS:

· FAILURE: COMMANDED ON BUT THE STATUS IS OFF.

· RUNNING IN HAND: COMMANDED OFF BUT THE STATUS IS ON.

· RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.

SECONDARY HOT WATER DISTRIBUTION PUMP LEAD/STANDBY OPERATION:

THE TWO HOT WATER PUMPS SHALL OPERATE IN A LEAD/STANDBY FASHION. THE LEAD PUMP SHALL RUN FIRST.

ON FAILURE OF THE LEAD PUMP, THE STANDBY PUMP SHALL RUN AND THE LEAD PUMP SHALL TURN OFF. THE

LEAD PUMP DESIGNATION SHALL BE ROTATED ON THE 1ST AND 15TH OF EACH MONTH.

SECONDARY HOT WATER DISTRIBUTION PUMP ALARMS SHALL BE PROVIDED AS FOLLOWS:

· FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

· RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

· RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.

BOILER CIRCULATION PUMP 1:

THE CIRCULATION PUMP 1 SHALL RUN ANYTIME BOILER 1 IS CALLED TO RUN AND SHALL HAVE A USER DEFINABLE

DELAY (ADJ.) ON STOP.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

· CIRCULATION PUMP 1 FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

· CIRCULATION PUMP 1 RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

· CIRCULATION PUMP 1 RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER-DEFINABLE LIMIT.

BOILER CIRCULATION PUMP 2:

THE CIRCULATION PUMP 2 SHALL RUN ANYTIME BOILER 2 IS CALLED TO RUN AND SHALL HAVE A USER DEFINABLE

DELAY (ADJ.) ON STOP.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

· CIRCULATION PUMP 2 FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

· CIRCULATION PUMP 2 RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

· CIRCULATION PUMP 2 RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER-DEFINABLE LIMIT.

HOT WATER SUPPLY TEMPERATURE SETPOINT RESET:

THE FACTORY BOILER CONTROLS SHALL RESET THE HOT WATER SUPPLY TEMPERATURE SETPOINT BASED ON

OUTSIDE AIR TEMPERATURE.

AS OUTSIDE AIR TEMPERATURE RISES FROM 35°F (ADJ.) TO 70°F (ADJ.) THE HOT WATER SUPPLY TEMPERATURE SETPOINT SHALL RESET DOWNWARDS BY SUBTRACTING FROM 0°F (ADJ.) TO 30°F

(ADJ.) FROM THE CURRENT BOILER SETPOINT 130°F (ADJ.).

HOT WATER SUPPLY TEMPERATURE MONITORING:

· HOT WATER SUPPLY.

· HOT WATER RETURN.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

HIGH HOT WATER SUPPLY TEMP: IF GREATER THAN 160°F (ADJ.).

LOW HOT WATER SUPPLY TEMP: IF LESS THAN 80°F (ADJ.).

FREEZE PROTECTION:

WHEN THE OUTDOOR AIR TEMPERATURE FALLS BELOW 38.0 DEG. F (ADJ.), THE HOT WATER DISTRIBUTION PUMP SHALL OPERATE CONTINUOUSLY TO PROVIDE HOT WATER CIRCULATION TO ALL ASSOCIATED HOT WATER COILS.

EMERGENCY GAS SHUTOFF:

IF THE EMERGENCY GAS SHUTOFF BUTTON IS ACTIVATED, THE NATURAL GAS VALVE SHALL CLOSE AND THE HOT WATER SYSTEM SHALL BE DISABLED. BUTTON SHALL BE HARD-WIRED TO SHUT OFF NATURAL GAS DELIVERY TO BOILER AND SEND A CONTROL SIGNAL TO THE BUILDING DDC SYSTEM TO GENERATE AN ALARM.

AI

OUTSIDE AIR TEMPERATURE

NOTE: HARDWIRE OUTDOOR AIR

TEMPERATURE SENSOR TO LEAD BOILER

BO

BP2 START/STOP

BO

BP1 START/STOP

BOILER POINTS LIST

HARDWARE POINTS SOFTWARE POINTS

POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC

PLANT HOT WATER FLOW METER X X

PRIMARY HOT WATER RETURN TEMP X X

PRIMARY HOT WATER SUPPLY TEMP X X

HOT WATER RETURN TEMP X X X

HOT WATER SUPPLY TEMP X X X

BOILER 1 HOT WATER SUPPLY TEMP SETPOINT RESET X X X

BOILER 2 HOT WATER SUPPLY TEMP SETPOINT RESET X X X

BOILER 1 ENABLE X X

BOILER 2 ENABLE X X

BOILER 1 STATUS X X X

BOILER 2 STATUS X X X

BOILER 1 FLOW / CIRCULATION PUMP 1 STATUS X X X

BOILER 2 FLOW / CIRCULATION PUMP 2 STATUS X X X

CIRCULATION PUMP 1 START/STOP X X X

CIRCULATION PUMP 2 START/STOP X X X

HOT WATER PUMP 1 STATUS X X X

HOT WATER PUMP 2 STATUS X X X

HOT WATER PUMP 1 SPEED X X X

HOT WATER PUMP 2 SPEED X X X

HOT WATER PUMP 1 START/STOP X X

HOT WATER PUMP 2 START/STOP X X

OUTSIDE AIR TEMP X X

EMERGENCY SHUTDOWN X X X X

BOILER 1 FAILURE X

BOILER 1 HIGH HOT WATER SUPPLY TEMP X

BOILER 1 LOW HOT WATER SUPPLY TEMP X

BOILER 1 RUNNING IN HAND X

BOILER 1 RUNTIME EXCEEDED X

BOILER 2 FAILURE X

BOILER 2 HIGH HOT WATER SUPPLY TEMP X

BOILER 2 LOW HOT WATER SUPPLY TEMP X

BOILER 2 RUNNING IN HAND X

BOILER 2 RUNTIME EXCEEDED X

CIRCULATION PUMP 1 FAILURE X

CIRCULATION PUMP 1 RUNNING IN HAND X

CIRCULATION PUMP 1 RUNTIME EXCEEDED X

CIRCULATION PUMP 2 FAILURE X

CIRCULATION PUMP 2 RUNNING IN HAND X

CIRCULATION PUMP 2 RUNTIME EXCEEDED X

HIGH PRIMARY HOT WATER SUPPLY TEMP X

HOT WATER PUMP 1 FAILURE X

HOT WATER PUMP 1 RUNNING IN HAND X

HOT WATER PUMP 1 RUNTIME EXCEEDED X

HOT WATER PUMP 2 FAILURE X

HOT WATER PUMP 2 RUNNING IN HAND X

HOT WATER PUMP 2 RUNTIME EXCEEDED X

HIGH HOT WATER SUPPLY TEMP X

LOW HOT WATER SUPPLY TEMP X

BI

BOILER 2

FLOW

BI

BOILER 2

FLOW

HARDWIRED - EMERGENCY SHUT DOWNE

NOTE: BUTTON SHALL BE HARD-WIRED TO SHUT

OFF NATURAL GAS DELIVERY TO BOILER,

SHUTDOWN BOILERS AND SEND A CONTROL

SIGNAL TO THE BUILDING DDC SYSTEM TO

GENERATE AN ALARM.

1 REVISED PER RFI 02 08/08/2023