This document contains a plumbing plan and details for a federal construction project. The plan outlines the routing of domestic water piping both above and below slab for a church facility. Piping sizes range from 1/2 inch to 2 inches in diameter using materials such as PEX-A and copper. The plan specifies the location of fixtures including water closets, lavatories, and hose bibbs. It also shows the routing of recirculation lines and notes the required installation of insulation for below-slab piping. This project is solicited by the Naval Facilities Engineering Command under solicitation number N4008523R2850 for repair and replacement work at facility TC601.

View the file

Other files for this federal contract opportunity

Other files attached to Repair By Replacement TC601, newest first.
File Type Posted
Amen07 220049.pdf PDF
Amen07 Photos2of3.pdf PDF
Amen 07 Photos3of3.pdf PDF
Amen07 Photos1of3.pdf PDF
Amen06 220049.pdf PDF
Amen06 Dwg SKS-1.pdf PDF
Amen05 220049.pdf PDF
Amen04 220049.pdf PDF
Amen04 dwg 60039111r1.pdf PDF
Amen04 Spec 23 07 00r1.pdf PDF
Amen03 220049.pdf PDF
Amen02 220049.pdf PDF
Amen02 dwg 60039105r1.pdf PDF
Amen02 dwg 60039100r1.pdf PDF
Amen02 220049.pdf PDF
Amen02 dwg 60039115r1.pdf PDF
22-0049 Design Analysis.pdf PDF
22-0049 PIS.pdf PDF
Amen01 220049.pdf PDF
22-0049 APPD.pdf PDF
N4008522B0049 SPECS.pdf PDF
22-0049 Geotechnical Report.pdf PDF
N4008522B0049 DRWGS.pdf PDF
RFP 220049.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P

2"

3/4"

HB1

2"

1/2" 1-1/4"

SEE PW101 FOR

CONTINUATION

PIPING ROUTED

UNDER SLAB

2"

1/2" 1"

1/ 2"

1/ 2"

1"

2"

1"

2" 2"

PIPING ROUTED

UNDER SLAB

1/2" 1/2"

1/ 2" 1/ 2" 1-1/2"

1/2" 1/2"

1/2"

SK2

OB1

WC1

MB1

LAV1

2" 2"

2"

1/2"

3/ 4"

SEE PW101 FOR

CONTINUATION

SEE CIVIL UTILITY

PLAN FOR

CONTINUATION

1/ 2" 1/2"

CIRCUIT

SETTER

BALANCING

VALVE

"B"

TRAP

PRIMER

TRAP

PRIMER

SK1

2"

SHUTOFF

VALVE IN

RISER

GWH1

CP1

2"

3/ 4"

HB1

1" 1/2"1/2"

1"

RECIRC., DCW

AND DHW

PIPING DOWN

TO BELOW SLAB

1/ 2"

1/ 2"

3/4"

PIPING ROUTED

ABOVE CEILING

NORTH

TRANSEPT

BAND

PLATFORM

SACRISTY

CLOSET

EXIT

STORAGE

RISER

ROOM

MECH

SOUND

BOOTH

FELLOWSHIP

ENTRY

UNISEX

DRESSING

1/2"

1/2"

2" 2"

2"

1/2" 1-1/2"

1-1/2"

2"

2"

1/2"

1" 1"

PIPING

ROUTED

ABOVE

CEILING

1- 1/

4" 1-

1/ 4"

1- 1/

4" 1/

2" 1/

2" 1/

2"

RECIRC., DCW

AND DHW

PIPING DOWN

TO BELOW SLAB

RECIRC., DCW

AND DHW

PIPING DOWN

TO BELOW SLAB

1" 2"

1/ 2"

1/ 2"

1/ 2"

1/ 2"

1-1/2"

RPZ, MOUNT

OVERHEAD.

LOCATION WITH

MECHANICAL

CONTRACTOR

EW1

1"

PIPING ROUTED

UNDER SLAB

NOTE: CONTRACTOR MAY USE

PEX-A PIPING FOR DOMESTIC

WATER PIPING UNDER SLAB.

WHEN USING PEX-A, NO

JOINTS ARE PERMITTED TO BE

UNDER THE SLAB AND PIPING

IS TO BE INSULATED WITH 2"

OF FLEXIBLE UNICELLULAR

INSULATION.

1"

1-1/2"

2"

1/2" 3/4"

2"

1/ 2"

WC2

WC1

1/ 2"

1/2

2"

1/2"

2" 2"

1/2" 1/2"

MB2

2"

1"

1"1"

1/2"

1/ 2"

2"2" 2"

UR1

WC2

WC1

SEE PW101 FOR

CONTINUATION

PIPING UP TO

ABOVE CEILING

ROUTE PIPING

UNDER SLAB

1/2"1/2" 1/2"

3/4"

3/ 4"

3/ 4"

3/ 4"

1"

1"1"1-1/4"1-1/4"

HB1

HB1

PIPING ROUTED

ABOVE CEILING

HAMMER

ARRESTOR,

TYP.

"C"

"B"

1-1/2"

3/ 4"

1-1/2"1-1/2"

1- 1/

2"

EWC1

3/4"

LAV2LAV2

1/2"

LAV2LAV2

1-1/2"

1" 1"

ADMIN.

OFFICE

WOMEN

104 CLOSET

NARTHEX

MEN

PRAYER

ROOM

JANITOR

I.T.

ROOM

107A

3/ 4"

1/ 2"

1/ 2"

1/ 2"

NOTE: CONTRACTOR MAY USE

PEX-A PIPING FOR DOMESTIC

WATER PIPING UNDER SLAB.

WHEN USING PEX-A, NO

JOINTS ARE PERMITTED TO BE

UNDER THE SLAB AND PIPING

IS TO BE INSULATED WITH 2"

OF FLEXIBLE UNICELLULAR

INSULATION.

043801

TROY O. GRADY

SEAL

R

EENI GN

P R

OF E S S I ON

A

E

L

NO

RT H CAROL I NA

SEE DISCLOSURE OF INFORMATION STATEMENT ON SHEET G-001

2246 Yaupon Drive Wilmington, NC 28401

Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2023CBHF Engineers, PLLC

Engineers, PLLC

06-08-2023

151 Poole Rd. Suite 100 | Leland, NC, 28451

TEL (910) 383-1044 | FAX (910) 383-1045

www.capefearengineering.com | N.C. LICENSE # C-1621

PW401

PLUMBING DOMESTIC WATER

FIRST ENLARGED FLOOR PLAN

1/4" = 1'-0" 0 4' 8'2'1 DOMESTIC WATER ENLARGED PLAN

PLAN

NORTH

1/4" = 1'-0" 0 4' 8'2'2 DOMESTIC WATER ENLARGED PLAN

PLAN

NORTH