This document outlines room requirements for a five-story parking structure to be constructed at Marine Corps Air Station Cherry Point in North Carolina. Key details include specifications for parking spaces on each level, an elevator and elevator lobby, vestibule, mechanical and electrical rooms, and access stairs. Requirements cover dimensions, finishes, signage, doors and hardware, fire suppression, plumbing and electrical systems. The related federal contract opportunity is solicitation number N4008521R2516 for design and construction of a new aircraft maintenance hangar at MCAS Cherry Point, of which the parking structure would be a component. The response due date is not provided.

View the file

Other files

File Type Posted
Amendment 0012.pdf PDF
Amendment 0011.pdf PDF
P197_-_Price_Proposal_Form AMD11.pdf PDF
AMENDMENT 0010.pdf PDF
P197_-_Price_Proposal_Form AMD 10.pdf PDF
Amendment 0009.pdf PDF
Specification Section 41 22 13.55 .pdf PDF
ENCL 5 AND ENCL 6.pdf PDF
ENCL 3 MCAS Cherry Point P199-197 Permanent UFC Exemption Request (12 Jan 2021) - NAVFAC.pdf PDF
ENCL 4 NAVAIR ASW Approval Letter CPT-35.pdf PDF
ENCL 8 2020 FRD Idle Plume Decay Supplement Rev 2.pdf PDF
ENCL 7 Cherry Point Apron Temps.pdf PDF
M00146-E21-01_HQ_CHENG_FINAL.pdf PDF
P197_-_Price_Proposal_Form - Amendment 0008.pdf PDF
Amendment 0008.pdf PDF
ENCL 2 ML Endorsement UFC Exemption Cherry Point Hangars Sun Shades.pdf PDF
ENCL 1 M00146-E01-21 (P199 P197 AIRCRAFT MAINTENANCE HANGAR).pdf PDF
Amendment 0007.pdf PDF
AMD 07 Site Visit-Attendance Sheet.pdf PDF
PASS and ID_One Day Pass Request Form.xlsx XLSX spreadsheet
ROICC Florence Cherry Point - Google Maps - Office Location.pdf PDF
ROICC Florence Cherry Point - Base Maps - Office Location.pdf PDF
Amendment 0006.pdf PDF
P197_1620400 SIGN RFP_Parts 6 (2 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (11 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (4 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (6 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (9 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (1 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (3 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 2 - 5.pdf PDF
Amendment 0005 - Phase II.pdf PDF
P197_1620400 SIGN RFP_Parts 6 (7 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (5 of 11).pdf PDF
P197_1620400 SIGN RFP_Parts 6 (8 of 11).pdf PDF
P197_-_Price_Proposal_Form.pdf PDF
P197_1620400 SIGN RFP_Parts 6 (10 of 11).pdf PDF
Amendment 0004.pdf PDF
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
ATTACHMENT E SPCD.docx DOCX document
ATTACHMENT D HISTORICAL SMALL BUSINESS UTILIZATION.docx DOCX document
Amendment 0001.pdf PDF
ATTACHMENT B Past Performance Questionnaire.pdf PDF
Attachment A - PPI Inquiry Log.xls XLS spreadsheet
ATTACHMENT F SMALL BUSINESS SUBCONTRACTING PLAN.docx DOCX document
ATTACHMENT C Construction and Design Exp Project Data Sheet.pdf PDF
N4008521R2516.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 1

5.5 PARKING STRUCTURE (PS)

PARKING STRUCTURE POV PARKING

Space Characteristics

Function/adjacencies: Locate each floor of a five-story ramped facility. For the purpose of ROOM REQUIREMENTS, this description applies to POV PARKING on all five levels, MOTORCYLE PARKING and ACCESSIBLE PARKING.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height:

Acoustics: No acoustic requirements Access: From exterior Number of Occupants: None

Other/special requirements: Contractor’s Interior Designer to determine FF&E requirements based on in-depth interviews with the Activity at the Concept Design Workshop. Space must accommodate at a minimum: Fire Extinguishers (in cabinet). Design PS POV PARKING to allow no ponding of water anywhere on the structure.

Uniformat

Section Description Qty Size Specific Requirements

B2030 Exterior Doors AR 2 -3’ x 8-0” min.

Maximum-duty steel double door and frame, insulated.

Paint. Coordinate door sizes with equipment sizes.

B2030 Door Hardware AR AR Provide continuous hinge, full weather stripping, overhead holders, rain deflector, etc.

C103090 Other Specialties AR AR Provide an Avian Intrusion Prevention System

C3010 Wall Finish AR AR Exposed. Unpainted.

C3020 Floor Finish AR AR Sealed concrete.

C3030 Ceiling Finish AR AR Provide unpainted exposed prefab concrete panels.

D202002 Valves & Hydrants AR AR Hose bib

D4020 Fire Suppression Water Supply and Equipment

AR AR Fire Suppression Sprinkler Riser

D50 Electrical AR AR Per Part 3, Chapter 6, D50

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 2

PARKING STRUCTURE ELEVATOR

Function/adjacencies: Provide space for vertical circulation equipment. Locate adjacent to HANGAR structure and INTERNAL STAIR.

Special Dimensions: Ceiling Height: 8’-0” min. clear interior car height Acoustics:

Access: Provide direct access to all parking structure levels and elevator lobby Number of Occupants:

Other/special requirements: Provide passenger elevator designed to accommodate handicapped accessibility and emergency medical services including a 24” x 84” ambulance stretcher. See UFC 3-490-06 for Elevator Design. Provide connection to emergency generator. Provide protection from moisture, dust and corrosion.

Description Qty Size Specific Requirements

C1010 Interior Partitions AR AR Cast-in-place concrete elevator hoist way. Extend to underside of roof structure above or cap as required. Fire- Rated as required.

C102091 Interior Door AR 4’-0” x 7’-0” min.

Two-speed side sliding horizontal. Stainless steel doors and frames.

C103004 Identifying Devices AR AR Level identification at each stop.

Additional signage per code requirements.

C3010 Wall Finish AR AR Stainless steel panels with concealed fasteners and stainless steel handrails.

C3020 Floor Finish AR AR Rubber tile.

C3020 Wall Base AR AR Stainless steel.

C3030 Ceiling Finish AR AR Modular metal ceiling panels with integrated lighting.

D101002 Passenger Elevators AR AR

Electric Traction Four-stop (approx. 18’-0” floor to floor travel length) Rated Load: 4,500 lbs. minimum Rated Speed: 150 fpm minimum

D20 Elevator Sump Pump AR AR Sump Pump required. One per Elevator.

D50 Electrical AR AR In accordance UFC.

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 3

PARKING STRUCTURE ELEVATOR ENTRY VESTIBULE

Function/adjacencies: Locate on the top level. Provide an ELEVATOR ENTRY VESTIBULE as the main point of entry to the elevator from the top level of the parking structure.

Special Dimensions:

Acoustics: No special acoustic requirements.

Access: Provide access from the top level of the parking structure.

Number of Occupants:

Other/special requirements: Provide protection from moisture, dust and corrosion.

Description Qty Size Specific Requirements

B202003 Curtain Wall AR AR Prefinished aluminum-framed curtain wall system with laminated glass. Assembly to include integral aluminum-framed curtain wall entry double-door. (PR 3-0” x 8’0” min.)

C1010 Interior Partitions AR AR CMU. Extend to underside of floor/roof structure above.

C1020 Interior Doors AR 6’-0” x 7’-0” min.

Provide maximum-duty, Coordinate with curtain wall system– fire rated as required -- Coordinate door sizes with occupant load and associated equipment sizes.

C103014 Entrance Floor Grilles and

Mats

AR AR

Recessed walk-off floor grille/mat. System must be removable for servicing and cleaning.

C3010 Wall Finish AR AR CMU/concrete. Painted.

C3020 Floor Finish AR AR Rubber tile beyond entrance mat.

C3030 Ceiling Finish AR AR Provide painted exposed structure.

C3040 Interior Coatings AR AR Paint CMU/concrete walls and ceiling, including ductwork, conduit, piping, devices, etc.

D30 HVAC AR AR Heating, ventilation and air conditioning systems.

D30 HVAC AR AR Condition fire alarm panel ambient to NFPA 72 conditions.

D4010 Fire Alarm and Detection

Systems AR AR Fire Alarm System Components Fire Alarm Annunciator

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 4

PARKING STRUCTURE ELEVATOR EQUIPMENT ROOM

Function/adjacencies: Provide space for Elevator mechanical and electrical equipment. Locate on ground floor adjacent to ELEVATOR.

Special Dimensions:

Acoustics:

Access: Provide direct access from ground floor of parking structure.

Number of Occupants:0

Other/special requirements: See UFC 3-490-06 for Elevator Design and equipment. Provide connection to emergency generator. Provide protection from moisture, dust and corrosion.

Description Qty Size Specific Requirements

C1010 Interior Partitions AR AR Cast-in-place concrete. Extend to underside of roof structure above or cap as required. Fire-Rated as required.

C102091 Interior Door AR 4’-0” x 7’-0” min.

Provide maximum-duty, painted steel door, fire rated as required, with painted steel frame.

C3010 Wall Finish AR AR Concrete. Unpainted.

C103004 Interior/Exterior Signage AR AR Room number identification at each room entry.

C3020 Floor Finish AR AR Sealed concrete

C3020 Wall Base AR AR Utilize an epoxy based sealant caulking bead where concrete floor meets CMU wall.

C3030 Ceiling Finish AR AR Provide unpainted exposed structure.

D101002 Passenger Elevators AR AR

Electric Traction Four-stop (approx. 18’-0” floor to floor travel length) Rated Load: 4,500 lbs. minimum Rated Speed: 150 fpm minimum

D503001 Telecommunication

Systems 1 AR Wall phone outlet: (W).

D50 Electrical AR AR Per Part 3, Chapter 6, D50 for machine room.

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 5

PARKING STRUCTURE ACCESS/EXIT STAIR

Function/adjacencies: Locate each floor of five-story ramped facility.

Acoustics: No special requirements.

Access: From each POV PARKING area Number of Occupants: None

Other/special requirements: Provide skid, slip and stain resistant concrete floor finish. Provide feature element of Aluminum Storefront.

Provide exterior signage

Uniformat Section

Description Qty Size Specific Requirements

B202002 Aluminum-framed Exterior-grade Storefront Systems

AR AR

Provide full-width prefinished aluminum-framed storefront with tempered clear glass and transom.

B2030 Exterior Doors AR 3’ x 8-0” min.

Maximum-duty steel door and frame, insulated. Paint.

Coordinate door sizes with equipment sizes.

B2030 Door Hardware AR AR Provide continuous hinge, full weather stripping, overhead holders, rain deflector, etc.

C103004 Exterior Signage AR AR Room name, number, and level identification at each stair entry. Include graphic signage at each stair entrance.

C2010 Stair Construction AR AR Provide primed and painted steel with concrete filled pans or cast-in-place concrete

C201090 Stair Handrails Guardrails and Accessories AR AR Provide aluminum handrails.

C2020 Stair Finish AR AR Provide sealed concrete stairs with cast aluminum stair nosing at cast in place concrete. Paint all exposed steel components including stringers where applicable.

C3010 Wall Finish AR AR Exposed. Unpainted.

C3020 Floor Finish AR AR Sealed concrete

C3020 Wall Base AR AR Utilize an epoxy based sealant caulking bead where concrete floor meets CMU wall.

C3030 Ceiling Finish AR AR Provide exposed unpainted structure

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 6

PARKING STRUCTURE ELECTRICAL ROOM

Function/adjacencies: Locate first level of five-story ramped facility.

Acoustics: No acoustic requirements Access: From first level POV Parking Number of Occupants: None

Other/special requirements: Provide protection from moisture, dust and corrosion.

Description Qty Size Specific Requirements

B2030 Exterior Door AR 3’ x 8-0” min.

Maximum-duty steel door and frame, insulated. Paint.

Coordinate door sizes with equipment sizes.

B2030 Door Hardware AR AR Provide continuous hinge, full weatherstripping, overhead holders, rain deflector, etc.

C3010 Wall Finish AR AR Exposed. Unpainted.

C3020 Floor Finish AR AR Sealed concrete.

C3020 Wall Base AR AR Utilize an epoxy based sealant caulking bead where concrete floor meets CMU wall.

C3030 Ceiling Finish AR AR Provide unpainted exposed structure.

D305002 HVAC AR AR Unit Heater (Electric)

D4020 Fire Suppression Water Supply and Equipment

AR AR Fire Suppression Sprinkler Riser

D50 Electrical AR AR Per Part 3, Chapter 6, D50

D5010 Electrical Service and

Distribution

AR AR

Provide necessary equipment for Electrical Service and Distribution, including service entrance.

P197 - PART 3 - CHAPTER 5.5 – PARKING STRUCTURE REQUIREMENTS - Page 7

PARKING STRUCTURE MECHANICAL ROOM

Function/adjacencies: Locate on the top level. Provide non-secured support space for mechanical building systems. Consider equipment replacement and crane locations.

Special Dimensions: Ceiling Height: Exposed Acoustics: Provide partition and door construction with a minimum STC rating of 50.

Access: From top level of parking area via double doors.

Provide exterior access with through-the-wall access doors on building exterior for crane access - with removable hand and safety rails. In accordance with UFC 3-410-01 HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS, section 4‐2.4.5.

Number of Occupants:

Other/special requirements: Design the Mechanical space and the building to readily enable service or replacement of the largest piece of mechanical equipment. Provide protection from moisture, dust and corrosion.

Description Qty Size Specific Requirements

C1010 Interior Partitions AR AR CMU. Extend to underside of floor/roof structure above.

C1020 Interior Doors AR 6’-0” x 7’-0” min.

Provide maximum-duty, painted steel double door – fire rated as required -- with vision panel and painted steel frame. Coordinate door sizes with occupant load and associated equipment sizes.

B2030 Exterior Doors AR

6’-0” x 7’-0” min.

Provide maximum-duty, painted steel double doors – fire rated as required -- with painted steel frame. Coordinate door sizes with occupant load and associated equipment sizes.

C103004 Interior/Exterior Signage AR AR Room number identification at each room entry.

C3010 Wall Finish AR AR Exposed. Unpainted.

C3020 Floor Finish AR AR Sealed concrete.

C3020 Wall Base AR AR Utilize an epoxy based sealant caulking bead where concrete floor meets CMU wall.

C3030 Ceiling Finish AR AR Provide unpainted exposed structure.

D202002 Valves & Hydrants AR AR Hose bib Floor mounted drain

D203090 Other Sanitary Waste AR AR Hub drains for condensate.

D305002 HVAC AR AR Unit Heater

D50 Electrical AR AR Per Part 3, Chapter 6, D50

D503001 Telecommunication

Systems 1 AR Wall phone outlet: (W).

D503001 Telecommunication

Systems

1 AR

Dedicated Fiber Outlet for DDC Panel. Coordinate requirements with DDC Installer.