AUTONOMOUS CONTROL UNIT (FRONT VIEW)
COMBINATION FIRE ALARM / MASS NOTIFICATION
AUTONOMOUS CONTROL UNIT (SIDE VIEW)
COMBINATION FIRE ALARM / MASS NOTIFICATION
REMOTE POWER SUPPLY (FRONT VIEW)
VISUAL NOTIFICATION APPLIANCE
REMOTE POWER SUPPLY (SIDE VIEW)
VISUAL NOTIFICATION APPLIANCE
46.0000
24.0000
46.0000
6.0000
15.0000
14.5000
15.0000
3.0000
NEW FIRE ALARM CONTROL UNIT AND
AUTONOMOUS CONTROL UNIT WITH
AUDIO AMPLIFIERS, DISPLAY &
HANDHELD MICROPHONE
(DIMENSIONS APPROXIMATE AND MAY
VARY DEPENDING ON MANUFACTURER)
FIRE ALARM / MASS NOTIFICATION SYSTEM GENERAL NOTES
FIRE ALARM / MASS NOTIFICATION SYSTEM SUBMITTAL NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING AND SUBMITTING A FIRE ALARM / MNS SYSTEM PRE-INSTALLATION
SUBMITTAL PACKAGE FOR APPROVAL BY THE ENGINEER. THE PRE-INSTALLATION SUBMITTAL PACKAGE SHALL INCLUDE (AT A
MINIMUM) THE FOLLOWING ITEMS:
a. PRODUCT DATA SHEETS FOR ALL FIRE ALARM SYSTEM EQUIPMENT TO BE INSTALLED.
b. EQUIPMENT LIST IDENTIFYING THE TYPE, QUANTITY, MAKE AND MODEL NUMBER OF EACH PIECE OF EQUIPMENT TO BE USED.
c. SHOP DRAWING PLANS SHOWING THE PROPOSED FIRE ALARM SYSTEM EQUIPMENT, DEVICE AND APPLIANCE LOCATIONS.
d. POINT-TO-POINT FIRE ALARM CONTROL EQUIPMENT INSTALLATION DIAGRAMS INCLUSIVE OF INFORMATION REQUIRED BY
NFPA 72 REQUIREMENTS.
e. BATTERY CALCULATIONS FOR ALL NEW FIRE ALARM SYSTEM CONTROL EQUIPMENT.
f. VOLTAGE DROP CALCULATIONS FOR ALL NOTIFICATION APPLIANCE CIRCUITS.
g. SPEAKER CIRCUIT AND AMPLIFIER LOADING CALCULATIONS.
h. SEQUENCE OF OPERATIONS MATRIX THAT DESCRIBES HOW THE SYSTEM WILL RESPOND DURING ALL TYPES OF ALARM, TROUBLE AND SUPERVISORY CONDITIONS.
i. STATEMENT OF EQUIPMENT LIFECYCLE SIGNED BY A REPRESENTATIVE OF THE EQUIPMENT MANUFACTURER STATING THAT
THE EQUIPMENT TO BE SUPPLIED IS NOT AT OR NEAR THE END OF ITS LIFECYCLE AND THAT REPLACEMENT PARTS WILL BE
AVAILABLE FROM THE MANUFACTURER FOR THE FORESEEABLE FUTURE.
2. UPON COMPLETION OF THE INSTALLATION, THE CONTRACTOR SHALL SUBMIT CLOSEOUT DOCUMENTATION INCLUDING DETAILED
AS-BUILT DRAWINGS TO THE ENGINEER. THE AS-BUILT DRAWINGS SHALL INDICATE THE EXACT LOCATION OF ALL CONTROL
EQUIPMENT, DEVICES AND APPLIANCES AND THE EXACT LOCATION OF ALL INSTALLED WIRING AND RACEWAY, INCLUDING THE
NUMBER OF CONDUCTORS IN EACH PORTION OF THE CIRCUIT AND THE LOCATION OF JUNCTION BOXES AND TERMINAL CABINETS.
CLOSEOUT DOCUMENTATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS.
1. PROVIDE AN AUTOMATIC, COMBINATION FIRE ALARM AND MASS NOTIFICATION SYSTEM THROUGHOUT THE BUILDING. INSTALL A
NEW FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION SYSTEM AUTONOMOUS CONTROL UNIT (FMCU). THE FIRE ALARM
SYSTEM CONTROLS AND DISPLAY SHALL BE LOCATED BEHIND A LOCKED DOOR ON THE CABINET, SUCH THAT BUILDING
OCCUPANTS CANNOT ACCESS THE FIRE ALARM SYSTEM CONTROLS. THE MASS NOTIFICATION SYSTEM CONTROLS AND
MICROPHONE SHALL BE LOCATED IN A SEPARATE SECTION OF THE MAIN ENCLOSURE/CABINET, OR A SEPARATE CABINET
ALTOGHER, WHICH IS NOT LOCKED AND IS ACCESSIBLE TO ALL BUILDING OCCUPANTS.
2. THE NEW FIRE ALARM / MASS NOTIFICATION SYSTEM CONTROL EQUIPMENT SHALL BE MANUFACTURED BY NOTIFIER. ALL
EQUIPMENT, DEVICES, APPLIANCES AND CIRCUITRY SHALL BE COMPATIBLE WITH THE NEW NOTIFIER CONTROL EQUIPMENT.
3. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING A UL FIRESTOP SYSTEM FOR ALL
PENETRATIONS MADE THROUGH FIRE RATED WALLS AND FLOOR/CEILING ASSEMBLIES AS PART OF THE FIRE ALARM / MASS
NOTIFICATION SYSTEM INSTALLATION.
4. ALL FIRE ALARM/MASS NOTIFICATION SYSTEM WORK SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72-2019, "NATIONAL FIRE
ALARM AND SIGNALING CODE,” NFPA 70-2017, “NATIONAL ELECTRICAL CODE,” UFC 3-600-01, "DESIGN: FIRE PROTECTION
ENGINEERING FOR FACILITIES - 25-MAR-2018," UFC 4-021-01, "DESIGN AND O&M: MASS NOTIFICATION SYSTEMS - 01-JAN-2010," AND
THE PROJECT SPECIFICATIONS.
5. ALL FIRE ALARM SYSTEM WIRING, CABLES, AND CONDUCTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS
OF NFPA 70-2017, “NATIONAL ELECTRICAL CODE,” THE PUBLISHED INSTRUCTIONS OF THE FIRE ALARM EQUIPMENT
MANUFACTURER, AND THE PROJECT SPECIFICATIONS.
6. THE SCOPE OF WORK INCLUDES COORDINATING THE FIRE ALARM SYSTEM INSTALLATION WITH THE NAVAL FACILITIES
ENGINEERING COMMAND, NAVAL WAR COLLEGE, AND JENSEN HUGHES.
7. THE SCOPE OF WORK INCLUDES REUSING THE EXISTING AES ALARM TRANSCEIVER (#7788-F8) FOR TRANSMITTING SIGNALS TO
THE BASE RECEIVING STATION. THE CONTRACTOR SHALL FURNISH AND INSTALL THREE (3) ADDRESSABLE CONTROL MODULES
FOR RELAYING GENERAL ALARM, GENERAL SUPERVISORY, AND GENERAL TROUBLE SIGNALS TO THE BASE RECEIVING STATION.
THE CONTRACTOR SHALL FURNISH AND INSTALL AN ADDRESSABLE MONITOR MODULE TO SUPERVISE THE MASTER BOX FOR A
TROUBLE CONDITION.
8. THE SCOPE OF WORK INCLUDES INTERFACING TO THE EXISTING SMOKE GUARD MODEL M2100 FIRE CURTAIN LOCATED AT THE
INTERFACE BETWEEN MAHAN HALL AND THE PEDESTRIAN BRIDGE WHICH CONNECTS MAHAN AND LUCE HALLS. ALL COMPONENTS
AND WIRING ASSOCIATED WITH THE FIRE CURTAIN, WITH THE EXCEPTION OF THE CONTROL MODULE FOR RELEASE, SHALL REMAIN
AS CURRENTLY INSTALLED. THE CONTRACTOR SHALL FURNISH AND INSTALL A NEW ADDRESSABLE CONTROL MODULE FOR FIRE
CURTAIN RELEASE UPON A GENERAL ALARM CONDITION.
9. THE EXISTING OSID BEAM SMOKE DETECTOR IMAGER AND EMITTER ARE TO REMAIN. THE SCOPE OF WORK INCLUDES
INTERFACING TO THE EXISTING OSID BEAM SMOKE DETECTOR IMAGER WITH A CONSTANT 24VDC POWER SOURCE FROM THE NEW
FIRE ALARM SYSTEM. THE CONTRACTOR SHALL FURNISH AND INSTALL TWO (2) ADDRESSABLE MONITOR MODULES TO SUPERVISE
THE IMAGER FOR ALARM AND TROUBLE CONDITIONS.
10. THE SCOPE OF WORK INCLUDES INTERFACING THE EXISTING BUILDING SECURITY SYSTEM TO TRANSMIT A GENERAL ALARM
SIGNAL UPON RECEIPT OF ALARM CONDITION BY THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR NECESSARY TO TIE INTO THE ELECTRONIC LOCK CONTROLS TO
FACILITATE THIS INTERFACE. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH THE NAVAL WAR COLLEGE AND/OR
SECURITY SYSTEM VENDOR TO FACILITATE THIS INTERFACE. THE NEW FIRE ALARM / MNS SYSTEM WILL NOT BE INTERFACED WITH
THE EXISTING ALERTUS SYSTEM AND COMPONENTS.
11. THE SCOPE OF WORK INCLUDES INTERFACING THE NEW FIRE ALARM SYSTEM WITH THE ELEVATOR CONTROLLER, ELEVATOR
SHUNT TRIP BREAKER, BUILDING HVAC UNITS, ELECTRONIC LOCKING MECHANISMS, AND FIRE PUMP CONTROLLER AS NOTED ON
THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR
NECESSARY TO TIE INTO THE SYSTEMS INDICATED TO FACILITATE THE INTERFACES.
12. THE SCOPE OF WORK INCLUDES REMOVING ALL EXISTING FIRE ALARM SYSTEM EQUIPMENT, WIRING AND RACEWAY, UNLESS
NOTED AS EXISTING TO REMAIN ON THE DRAWINGS. THERE MAY BE ADDITIONAL DEVICES LOCATED IN THE FIELD THAN WHAT IS
SHOWN ON THE DEMOLITION DRAWINGS. THE DEMOLITION DRAWINGS ARE INTENDED TO ASSIST THE CONTRACTOR, BUT DO NOT
SHOW THE FULL EXTENT OF THE DEMOLITION WORK REQUIRED.
13. ALL CONDUCTORS AND CABLES SHALL BE INSTALLED IN MINIMUM 3_
" CONDUIT (EMT MINIMUM) IN A MANNER THAT COMPLIES
WITH NFPA 70-2017. ALL RACEWAY SHALL BE PAINTED TO MATCH EXISTING CONDITIONS. SPECIFIC APPROVAL SHALL BE OBTAINED
FROM NAVFAC AND JENSEN HUGHES PRIOR TO THE USE OF MC CABLE. ALL NEW CONDUIT AND WIRING IN PUBLIC SPACES SHALL
BE CONCEALED TO GREATEST EXTENT POSSIBLE.
14. ALL CONTROL EQUIPMENT, INITIATING DEVICES AND NOTIFICATION APPLIANCES SHALL BE UL LISTED.
15. THE FIRE ALARM CONTROL UNIT SHALL BE PROVIDED WITH BYPASS BUTTONS FOR FIRE CURTAIN RELEASE, SPRINKLER SYSTEM /
FIRE PUMP MONITORING DEVICES, ELEVATOR RECALL, NOTIFICATION APPLIANCES, HVAC SHUTDOWN, RADIO MASTER BOX
SIGNAL TRANSMISSION AND MAGNETIC DOOR HOLD-OPEN DEVICES.
16. SURGE SUPPRESSION SHALL BE PROVIDED WHERE ANY CIRCUIT EXITS OR RE-ENTERS THE EXTERIOR OF THE BUILDING, WITH
THE EXCEPTION OF DEVICES MOUNTED DIRECTLY TO THE FACILITY EXTERIOR.
17. ALL SIGNALING LINE CIRCUITS (SLC) AND NOTIFICATION APPLIANCE CIRCUITS (NAC) SHALL BE INSTALLED TO MEET THE
REQUIREMENTS OF CLASS B CIRCUITS AS DEFINED BY NFPA 72-2019.
18. POWER-LIMITED FIRE ALARM CIRCUITS SHALL NOT BE INSTALLED IN THE SAME RACEWAY AS NON POWER-LIMITED CIRCUITS.
19. PROVIDE A MINIMUM OF ONE VISUAL NOTIFICATION APPLIANCE CIRCUIT AND A MINIMUM OF ONE AUDIBLE NOTIFICATION
APPLIANCE PER FLOOR. EACH NOTIFICATION APPLIANCE CIRCUIT MUST INCLUDE 25 PERCENT SPARE CAPACITY.
20. WIRING MAY BE SOLID COPPER OR STRANDED AS PERMITTED BY NFPA 70. UNLESS THE FIRE ALARM CONTROL UNIT
MANUFACTURE SPECIFIES MORE STRINGENT REQUIREMENTS, SIGNALING LINE CIRCUITS SHALL BE MINIMUM 18 AWG.
NOTIFICATION APPLIANCE CIRCUITS MUST BE MINIMUM 16 AWG. ALL FIRE ALARM SYSTEM CIRCUITRY SHALL BE APPROPRIATELY
LABELED IN THE FIELD TO REFLECT ITS USE AND CIRCUIT IDENTIFICATION.
21. ALL DEVICES MUST HAVE SCREW TERMINALS. WHERE DEVICES ARE ONLY PROVIDED WITH PIGTAILS FROM THE MANUFACTURER, PIGTAILS MUST BE LANDED ON TERMINAL STRIPS WITHIN THE JUNCTION BOX.
22. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP OR THE DEVICE SCREW TERMINALS. TERMINAL STRIPS ARE ONLY PERMITTED
WHERE DIRECT CONNECTION TO A DEVICE IS NOT POSSIBLE, AND SHALL BE LOCATED WITHIN JUNCTION/BACK BOXES.
23. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS, WHEN PROVIDED, MUST BE FACTORY PAINTED RED IN
UNFINISHED AREAS (E.G., ABOVE CEILINGS, MECHANICAL ROOMS, ETC.)
24. ALL EXPOSES CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS, WHEN PROVIDED, ARE PERMITTED TO BE PAINTED TO
MATCH THE ROOM FINISHING IN FINISHED AREAS. THE INSIDE COVER OF ALL JUNCTION BOXES MUST BE IDENTIFIED AS "FIRE ALARM".
ALL EXPOSED CONDUIT LOCATED IN BACK OF HOUSE SPACES MUST HAVE PAINTED RED BANDS 3/4-IN. WIDE AT 20 FEET INTERVALS
AND ON BOTH SIDES OF ALL FLOOR, WALL AND CEILING PENETRATIONS.
25. ALL FIRE ALARM INITIATING DEVICES AND NOTIFICATION APPLIANCES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72-2019, THE PROJECT DRAWINGS, AND THE PROJECT SPECIFICATIONS.
26. ALL WALL-MOUNTED AUDIBLE/VISIBLE NOTIFICATION APPLIANCES SHALL BE INSTALLED WITH THE BOTTOM OF THE LENS OF THE
VISIBLE NOTIIFICATION APPLIANCE AT NO LESS THAN 80-INCHES ABOVE THE FINISHED FLOOR AND THE TOP OF THE LENS AT NO
MORE THAN 96-IN ABOVE THE FINISHED FLOOR. WHERE FINISHED CEILING HEIGHTS ARE LESS THAN 86-IN MOUNT THE APPLIANCE
WITH THE TOP OF THE LENS 6-IN DOWN FROM THE CEILING.
27. AS A STARTING POINT, ALL SPEAKER NOTIFICATION APPLIANCES SHALL BE SET TO 1-WATT IN BOILER AND MECHANICAL ROOMS.
ALL SPEAKER NOTIFICATION APPLIANCES SHALL BE SET TO 1/2-WATT IN COMMON CORRIDORS, LOBBIES, MEETING/CONFERENCE
ROOMS, EXHIBITION HALLS, CLASSROOMS, ROTUNDA, STACK AREAS, AND OTHER PUBLIC AREAS. ALL SPEAKER NOTIFICATION
APPLIANCES SHALL BE SET TO 1/4-WATT IN STORAGE ROOMS, OFFICES AND RESTROOMS. THE CONTRACTOR SHALL CARRY A
MINIMUM OF 4 HOURS TO MAKE ANY NECESSARY SPEAKER WATTAGE SETTING ADJUSTMENTS DURING ACCEPTANCE TESTING.
28. ALL SPEAKER NOTIFICATION APPLIANCE CIRCUITS AND AMPLIFIERS SHALL BE CONFIGURED FOR FOR 70.7 VRMS INPUT.
29. ALL NEW MANUAL FIRE ALARM BOXES SHALL BE MOUNTED SUCH THAT THE HEIGHT FROM THE FLOOR TO THE TOP OF THE
OPERABLE ELEMENT IS IN THE RANGE OF 42 TO 48 INCHES ABOVE THE FINISHED FLOOR.
30. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING (AND MODIFYING/UPDATING AS NECESSARY) THAT ALL EXISTING AND
NEW BUILDING SYSTEMS / EQUIPMENT TO BE INTERFACED WITH THE FIRE ALARM SYSTEM, INCLUDING BUT NOT LIMITED TO THE
ELEVATORS, FIRE PUMP, SPRINKLER SYSTEM, HVAC UNITS, SECURITY SYSTEM, ELECTRONIC LOCKS, ETC., ARE PROVIDED WITH
MEANS TO FACILITATE MONITORING OR CONTROL BY THE NEW FIRE ALARM SYSTEM PER THE CONTRACT DOCUMENTS, AND
PROVIDING SUCH MEANS IF NOT EXISTING AT NO ADDITIONAL COST. THIS INCLUDES PROVIDING ALL PARTS, LABOR, AND
PROGRAMMING FOR THE FIRE ALARM SYSTEM OR OTHER BUILDING SYSTEMS REQUIRED TO COMPLETE ALL INTERFACES LISTED IN
THE FIRE ALARM SYSTEM OPERATIONS MATRIX AND AS OUTLINED IN THE CONTRACT DOCUMENTS.
31. SECONDARY POWER: PROVIDE RECHARGEABLE BATTERIES PER NFPA 72 TO OPERATE THE FIRE ALARM SYSTEM UNDER
SUPERVISORY CONDITIONS FOR 48 HOURS AND ALL ALARM DEVICES FOR AN ADDITIONAL 15 MINUTES. ADDITIONALLY, THE
SECONDARY POWER SHALL PROVIDE A MINIMUM OF 60 MINUTES OF MASS NOTIFICATION AT THE MAXIMUM CONNECTED LOAD, IMMEDIATELY UPON LOSS OF NORMAL AC POWER. PROVIDE RECHARGEABLE BATTERIES FOR SECONDARY POWER AND SIZE
ACCORDINGLY TO OPERATE THE AES ALARM TRANSCEIVER IN NORMAL STANDBY STATUS FOR A MINIMUM OF 72 HOURS AND BE
CAPABLE OF TRANSMITTING ALARMS DURING THAT PERIOD.
32. AN ACTIVE FIRE ALARM SYSTEM (EITHER THE EXISTING FIRE ALARM SYSTEM OR A TEMPORARY FIRE ALARM SYSTEM) SHALL
REMAIN OPERATIONAL THROUGHOUT THE PERIOD OF CONSTRUCTION FOR THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR
SHALL INCLUDE THE APPROACH FOR THE ACTIVE FIRE ALARM SYSTEM DURING CONSTRUCTION IN THEIR CONSTRUCTION AND
PHASING PLAN TO BE APPROVED BY THE NAVAL WAR COLLEGE, NAVAL FACILITIES ENGINEERING COMMAND, AND JENSEN HUGHES.
33. UPON FINAL ACCEPTANCE OF THE NEW FIRE ALARM SYSTEM BY THE AHJ, DEMOLITION OF THE EXISTING SYSTEM IS PERMITTED
TO COMMENCE. THE EXISTING FIRE ALARM SYSTEM SHALL BE REMOVED IN ITS ENTIRETY, INCLUDING ALL DEVICES, APPLIANCES, CONDUIT, BOXES, WIRING, PANELS AND ASSOCIATED FIRE ALARM EQUIPMENT, UNLESS OTHERWISE NOTED AS EXISTING TO
REMAIN ON THE DRAWINGS. WALLS AND CEILINGS SHALL BE PATCHED AND PAINTED TO MATCH EXISTING CONDITIONS.
34. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FIRE ALARM SYSTEM CONSTRUCTION AND PHASING PLAN FOR
APPROVAL BY THE NAVAL WAR COLLEGE, NAVAL FACILITIES ENGINEERING COMMAND, AND JENSEN HUGHES PRIOR TO THE
COMMENCEMENT OF WORK.
35. THE CONTRACTOR SHALL BE REQUIRED TO CONDUCT A 100% PRE-ACCEPTANCE TEST OF THE FIRE ALARM SYSTEM IN
ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS.
36. THE CONTRACTOR SHALL BE REQUIRED TO CONDUCT AND SCHEDULE AN ACCEPTANCE TEST OF THE NEW FIRE ALARM / MNS
SYSTEM FOR APPROVAL BY THE NAVAL FACILITIES ENGINEERING COMMAND AND NAVSTA NEWPORT.
37. WHERE AN INTERPOSING RELAY IS REQUIRED TO INTERFACE THE FIRE ALARM SYSTEM TO BUILDING SYSTEMS OR EQUIPMENT, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING THIS EQUIPMENT, INCLUDING ANY EXTERNAL POWER
REQUIRED.
38. SMOKE DETECTORS LOCATED IN THE VICINITY OF A DOOR WHICH IS PROVIDED WITH A MAGNETIC DOOR HOLD-OPEN DEVICE
SHALL BE PROGRAMMED TO RELEASE ONLY ITS ASSOCIATED DOOR HOLD-OPEN DEVICE, UNLESS OTHERWISE NOTED ON THE .
DRAWINGS TO RELEASE MULTIPLE DEVICES. SMOKE DETECTORS SHALL ALSO PERFORM GENERAL ALARM FUNCTIONS.
TS
WF
WF(ST)
FP(RUN)
FP(PR)
FP(ACPL)
FP(CAS)
PRI
ALT
HAT
AHU
WP
ELR
FC
SEC
TRBL
ALRM
Z#
DH
SBO
M
S
I cd cd
MM
CM
TXT
FMCU
RTS
AMP
RPS
MB
DOC
ETH
EOL
ER
DD
SPRINKLER VALVE SUPERVISORY TAMPER SWITCH
SPRINKLER SYSTEM WATERFLOW SWITCH
SPRINKLER SYSTEM WATERFLOW SWITCH FOR ELEVATOR CONTROLLER SHUNT TRIP
FIRE PUMP RUNNING SIGNAL
FIRE PUMP PHASE REVERSAL SIGNAL
FIRE PUMP AC POWER LOSS SIGNAL
FIRE PUMP CONNECTED TO ALTERNATE SOURCE SIGNAL
PRIMARY ELEVATOR RECALL
ALTERNATE ELEVATOR RECALL
ELEVATOR FLASHING HAT
AIR HANDLING UNIT SHUTDOWN
WEATHER-PROOF NOTIFICATION APPLIANCE
ELECTRONIC DOOR LOCKING MECHANISM RELEASE
ACTIVATE CLOSING OF EXISTING FIRE CURTAIN
GENERAL ALARM SIGNAL OUTPUT TO BUILDING SECURITY SYSTEM
MASTER BOX OR BEAM DETECTOR IMAGER TROUBLE RELAY SUPERVISION
BEAM DETECTOR IMAGER ALARM RELAY SUPERVISION
RADIO MASTER BOX ZONE ACTIVATION RELAY (ZONE # AS INDICATED)
MAGNETIC DOOR HOLD-OPEN DEVICE RELAY
SUPPLIED BY OTHERS
SUBSCRIPT LEGEND
FIRE ALARM / MNS SYMBOLS LEGEND
ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
ADDRESSABLE DUCT SMOKE DETECTOR
ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR FOR ELEVATOR RECALL
ADDRESSABLE MANUAL FIRE ALARM BOX
COMBINATION FIRE ALARM / MNS SPEAKER/STROBE NOTIFICATION APPLIANCE
(CANDELA RATING AS NOTED)
COMBINATION FIRE ALARM / MNS SPEAKER NOTIFICATION APPLIANCE
COMBINATION FIRE ALARM / MNS STROBE NOTIFICATION APPLIANCE
(CANDELA RATING AS NOTED)
ADDRESSABLE MONITOR MODULE
ADDRESSABLE CONTROL MODULE
MNS LED TEXT SIGN
COMBINATION ADDRESSABLE FIRE ALARM / MASS NOTIFICATION
SYSTEM CONTROL PANEL
REMOTE TEST SWITCH W/ LED INDICATOR
SPEAKER NOTIFICATION APPLIANCE AMPLIFIER
VISUAL NOTIFICATION APPLIANCE REMOTE POWER SUPPLY
EXISTING RADIO MASTER BOX #0003 ( AES ALARM TRANSCEIVER #7788-F8)
FIRE ALARM DOCUMENTS CABINET
ISOLATION MODULE
MNS LED SIGN DEDICATED ETHERNET SWITCH LISTED TO UL 864
END OF LINE RESISTOR
STLP SHUNT TRIP LOSS OF 120V POWER SUPERVISION
HT SPRINKLER PIPE HEAT TRACE SUPERVISION
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886 O: 401.736.8992 C: 410.737.8677
As indicated
FA-001
B M
A H
A N
H A
L L
F
IR
E A
LA
R
M N
O
TE
S , L
E G
E N
D
D E
TA
IL
S
CMA
12828370
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T , R
I N
A V
A L
S T
A T
IO
N
N E
W P
O R
T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45132-415
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
0% S
U B
M
IT
T A
L
/1 7/
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L
/0 2/
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L
/3 0/
IS
S
U E
F O
R B
ID
/3 0/
A
B
STOR
B28
CRAWL
SPACE
B29D
NCC STORE
B29B
HALL
B32
STOR
B08
MECH
B29C
STOR
B29A
HALL
B29
STOR/
MECH
B31
STOR
B31A
SUMP PIT
B33A
STOR
B33C
STOR
B33
STOR
B33B
MECH
B11
CRAWL
SPACE
CHASE
ST19
CRAWL
SPACE
B12A
CRAWL
SPACE
B12C
MECH
B12
CRAWL
SPACE
B12B
CRAWL
SPACE
B33D
VEST
B32A
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-100.5
B M
A H
A N
H A
L L
B A
S E
M E
N T
D E
M O
LI
T
IO
N
P
LA
N
CMA
12828371
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45133-415
SCALE: 1/8" = 1'-0"
BASEMENT FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
M
M
A
B
FACU
CM
RPS
MM
CM
CM
CM
STAIR
ST02
OFFICE
M13
OFFICE
M11
STAIR
ST01
ARCHIVE
STORAGE
N18B
ELEV
ST31
ARCHIVE
STORAGE
M10A
ARCHIVE
STORAGE
M10B
CPO MESS
M14
OFFICE
N18
CLASSROOM
N18A
CORRIDOR
N14A
OFFICE
N19A
IT STORAGE
N19
OFFICE
N17
EXHIBIT
HALL
N14
OFFICE
N11
OFFICE
N12
VAULT
N12A
LOBBY
N10D
OFFICE
N9
HALL
N10C
LANDING
N10B
LOBBY
N10
JC
N10A
RPS
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-101.0
B M
A H
A N
H A
L L
LE
V
E L
D
E M
O
LI
T
IO
N P
LA
N
CMA
12828372
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45134-415
SCALE: 1/8" = 1'-0"
1ST LEVEL FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
A
B
STAIR
ST02
STAIR
ST01
ELEV
ST31
BREAK
ROOM
M23
OFFICE
M21
STUDENT
CUBICLES
M25
STUDENT
CUBICLES
M27
OFFICE
M26
OFFICE
M24
OFFICE
M22
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-101.5
B M
A H
A N
H A
L L
LE
V
E L
1.
D E
M O
LI
T
IO
N
P
LA
N
CMA
12828373
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45135-415
SCALE: 1/8" = 1'-0"
1.5 LEVEL FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
M
A
B
STAIR
ST02
STAIR
ST01
ELEV
ST31
LANDING
N24
KITCHENETTE
N21
OFFICE
N23
STO
N24C
OFFICE
N22
VESTIBULE
N24B
VESTIBULE
N24AMAHAN
ROTUNDA
N26
READING
ROOM
N27
STUDENT
CUBICLES
M32
OFFICE
M36
OFFICE
M34
OFFICE
M30
CONFERENCE
M37
WOMEN
M33
MEN
M31
JC
M35
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-102.0
B M
A H
A N
H A
L L
LE
V
E L
D
E M
O
LI
T
IO
N P
LA
N
CMA
12828374
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45136-415
SCALE: 1/8" = 1'-0"
2ND LEVEL FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
A
B
STAIR
ST02
STAIR
ST01
ELEV
ST31
STUDENT
CUBICLES
M40
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-102.5
B M
A H
A N
H A
L L
LE
V
E L
2.
D E
M O
LI
T
IO
N
P
LA
N
CMA
12828375
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45137-415
SCALE: 1/8" = 1'-0"
2.5 LEVEL FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
A
B
RTS
RTS
DD
DD
RTS
RTS
DD
DD
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FAD-103.0
B M
A H
A N
H A
L L
A
TT
IC
D
E M
O
LI
T
IO
N P
LA
N
CMA
12828376
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45138-415
SCALE: 1/8" = 1'-0"
ATTIC LEVEL FIRE ALARM DEMOLITION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
S
C
D
S
15CD
S
C
D
S
15CD
S
S
S
S
M
M
S
S
S
S
S
S
S
S
A
B
CRAWL
SPACE
B29D
FIRE PUMP
RM
B28B
STOR
B28
HALL
B32
NCC STORE
B29B
STOR
B29A
MECH
B29C
MECH
B11
CRAWL
SPACE
CHASE
B11A
MECH
B12
STOR
B31A
STOR/
MECH
B31
STOR
B33B
STOR
B33
ARCHIVE
QUARANTINE
ROOM
B30
VEST
B32A
MM FP(RUN)
MM FP(PR)
MM FP(ACPL)
MM FP(CAS)
MM
MM
WF
TSx9
MM
MM
WF
TS
WP
TXT
TXT
RTS
MM
AHU
MM
CM
RL
RTS
DD
MM
MMTRBL
ALRM
AHU
TRBL
ALRM
CRAWL
SPACE
B33D
CRAWL
SPACE
B33D
CRAWL
SPACE
B12B
CRAWL
SPACE
B12A
CRAWL
SPACE
B12C
CRAWL
SPACE
B12E
CRAWL
SPACE
B12D
CRAWL
SPACE
B12D
CRAWL
SPACE
B12E
CRAWL
SPACE
B12E
CRAWL
SPACE
B12F
DD
MMTSx3
MM TS
MM HT
DRAWING KEYNOTES:
THE NEW DEDICATED OUTSIDE AIR SYSTEM (DOAS) UNIT TO BE INSTALLED IN THIS
LOCATION IS PROPOSED TO HAVE A SUPPLY CAPACITY LESS THAN 2,000CFM, AND THUS
WILL NOT BE INTERFACED WITH THE NEW FIRE ALARM SYSTEM.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO RELEASE THE ELECTRONIC
LOCKING MECHANISM FOR THE DOOR FROM THE CONNECTOR TO THE COURTYARD, SUCH
THAT IT UNLOCKS DURING AN ALARM CONDITION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR NECESSARY
TO TIE INTO THE ELECTRONIC LOCK CONTROLS TO FACILITATE THIS INTERFACE.
CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE INSTALLATION WITH
ELECTRONIC LOCK VENDOR.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO SEND A GENERAL ALARM
SIGNAL TO THE BUILDING SECURITY SYSTEM UPON RECEIPT OF A FIRE ALARM CONDITION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS,
CIRCUITRY AND LABOR NECESSARY TO TIE INTO THE SECURITY SYSTEM TO FACILITATE
THIS INTERFACE. CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE
INSTALLATION WITH SECUIRTY SYSTEM VENDOR.
THE EXISTING RADIO MASTER BOX #0003 (AES ALARM TRANSCEIVER 7788-F8) IS TO REMAIN
AND SHALL CONTINUE TO SEND THREE (3) SIGNALS TO THE FIRE DEPARTMENT:
(1) GENERAL ALARM CONDITION
(2) GENERAL SUPERVISORY CONDITION
(3) GENERAL TROUBLE CONDITION
THE RADIO BOX SHALL ALSO BE SUPERVISED FOR TROUBLE CONDITIONS.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO INITIATE THE CLOSING OF THE
EXISTING FIRE CURTAIN LOCATED ON THE LANDING ABOVE BETWEEN MAHAN HALL AND
THE CONNECTOR TO LUCE HALL. CONTRACTOR TO FIELD LOCATE CONTROL RELAY.
SMOKE DETECTOR AND SPEAKER/STROBE TO BE LOCATED IN THE CONNECTOR WHICH
CONNECTS MAHAN HALL AND LUCE HALL.
EXISTING BATTERY POWERED OSID BEAM SMOKE DETECTOR EMITTER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING THE EXISTING BATTERIES (AND
REPLACING IF NECESSARY) TO VERIFY THAT THEY ARE PERFORMING WITHIN THE
MANUFACTURERS SPECIFICATIONS.
EXISTING 24VDC POWERED OSID BEAM SMOKE DETECTOR IMAGER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE UNIT WITH 24VDC POWER
FROM THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR SHALL FURNISH AND INSTALL
TWO (2) ADDRESSABLE MONITOR MODULES TO SUPERVISE THE IMAGER FOR ALARM AND
TROUBLE CONDITIONS. A BEAM SMOKE DETECTOR ALARM CONDITION SHALL BE
PROGRAMMED TO RELEASE DOOR HOLDERS TO VESTIBULE N24B, OFFICE N22, AND
ROTUNDA N26, IN ADDITION TO GENERAL ALARM FUNCTIONS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING TWO (2) NEW DUCT SMOKE
DETECTORS, COMPLETE WITH HOUSING AND SAMPLING TUBES, FOR EXISTING TO REMAIN
UNIT AHU-E2, ONE (1) ON THE SUPPLY SIDE AND ONE (1) ON THE RETURN SIDE. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING THE DUCTWORK WHERE THE
EXISTING DUCT SMOKE DETECTORS ARE REMOVED ONCE THE NEW FIRE ALARM SYSTEM
HAS BEEN ACCEPTED BY THE AHJ. THE CONTRACTOR SHALL PROVIDE ONE (1) CONTROL
MODULE WHICH SHALL AUTOMATICALLY SHUTDOWN THE UNIT UPON ACTIVATION OF A
DUCT SMOKE DETECTOR INSTALLED IN THE UNIT. THE FIRE ALARM CONTRACTOR SHALL
PROVIDE A REMOTE TEST SWITCH IN AN ACCESSIBLE LOCATION FOR EACH DUCT SMOKE
DETECTOR WHICH IS INSTALLED. THE INSTALLATION OF THIS EQUIPMENT SHALL BE
COORDINATED WITH THE MECHANICAL CONTRACTOR AND SHALL BE IN ACCORDANCE
WITH NFPA 72 & NFPA 90A. .
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING PRE-APPROVAL FOR THE
ROUTING OF ALL EXPOSED RACEWAY TO BE INSTALLED IN EXHIBIT HALL N14.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO LOBBY N10D
AND LOBBY N10, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N11,
OFFICE N12, AND EXHIBIT HALL N14, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N17
AND CLASSROOM N18A, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO IT STORAGE
N19 AND OFFICE N18, IN ADDITION TO GENERAL ALARM FUNCTIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING AN ADDRESSABLE MONITOR
MODULE TO SUPERVISE THE SPRINKLER PIPE HEAT TRACE CONTROLLER FOR AN OFF-
NORMAL CONDITION. INSTALLATION AND EXACT LOCATION TO BE COORDINATE WITH
SPRINKLER SYSTEM INSTALLING CONTRACTOR.
4' 8' 16'0' 1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886 O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-100.5
B M
A H
A N
H A
L L
B A
S E
M E
N T
LE
V
E L
C O
N S
TR
U
C T
IO
N
P
LA
N
CMA
12828377
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T , R
I N
A V
A L
S T
A T
IO
N
N E
W P
O R
T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45139-415
SCALE: 1/8" = 1'-0"
BASEMENT FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
0% S
U B
M
IT
T A
L
/1 7/
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L
/0 2/
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L
/3 0/
IS
S
U E
F O
R B
ID
/3 0/
C
D
S
15CD
S
C
D
S
C
D
S
15CD S
15CD
S
15CD
S
75CD
S
75CD
S
C
D
S
C
D
M
15CD
S
C
D
S
75CD
S
75CD
S
15CD
S
75CD
S
C
D
S
75CD
S
C
D
S
C
D
S
C
D
S
C
D
S
C
D
S
C
D
S
C
D
S
S
M
S
S
S
S
S
S
S
S
S
S
S
C
D
S
30CD
S
30CD
S
75CD
S
75CD
A
B
OFFICE
N9
LOBBY
N10D
LOBBY
N10
JC
N10A
LANDING
N10B
OFFICE/CONFERENCE
ROOM
N12A
OFFICE
N11
HALL
N10C
OFFICE
N12
EXHIBIT
HALL
N14
OFFICE
N17
IT STORAGE
N19
CORRIDOR
N14A
CLASSROOM
N18A
OFFICE
N18
RAMP
M15
CORR
M16
ELEV
MACHINE
ROOM
M17
ELEV
E01
LOBBY
M13
W.C.
M13A
JC
M13B
ER
M11
STAIR
ST02
STAIR
ST01STOR
M19
CORR
M10
CORR
M10
CPO MESS
M14
OFFICE
M14A
ARCHIVE
STORAGE
N18B
ARCHIVE
STORAGE
M10A
ARCHIVE
STORAGE
M10C
FMCU
MMWF
MMTS
MMWF
MMTS
MM WF
MM TS
MM TS
CM PRI
CM ALT
CM HAT
MB
E
#0003
ER
TXT
TXTCMZ1
CMZ2
CMZ3
ER
TXT
WP
MM WF(ST)
MM TS
MM TS
CMFC
AMP3x ETH
RPSCM
RPSMM
MMTRBL
CM SEC
CM ELR
DOC
DH
DH
DH
DH
DH
DH
DH
DH
WP
MM TS
DH
DH
DH
DH
DH
SWSW
121314
MM WF
CM
CM
MM STLP
CM
CM
CM
CM
CM
CM
CM
CMCM
CM
DRAWING KEYNOTES:
THE NEW DEDICATED OUTSIDE AIR SYSTEM (DOAS) UNIT TO BE INSTALLED IN THIS
LOCATION IS PROPOSED TO HAVE A SUPPLY CAPACITY LESS THAN 2,000CFM, AND THUS
WILL NOT BE INTERFACED WITH THE NEW FIRE ALARM SYSTEM.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO RELEASE THE ELECTRONIC
LOCKING MECHANISM FOR THE DOOR FROM THE CONNECTOR TO THE COURTYARD, SUCH
THAT IT UNLOCKS DURING AN ALARM CONDITION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR NECESSARY
TO TIE INTO THE ELECTRONIC LOCK CONTROLS TO FACILITATE THIS INTERFACE.
CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE INSTALLATION WITH
ELECTRONIC LOCK VENDOR.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO SEND A GENERAL ALARM
SIGNAL TO THE BUILDING SECURITY SYSTEM UPON RECEIPT OF A FIRE ALARM CONDITION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS,
CIRCUITRY AND LABOR NECESSARY TO TIE INTO THE SECURITY SYSTEM TO FACILITATE
THIS INTERFACE. CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE
INSTALLATION WITH SECUIRTY SYSTEM VENDOR.
THE EXISTING RADIO MASTER BOX #0003 (AES ALARM TRANSCEIVER 7788-F8) IS TO REMAIN
AND SHALL CONTINUE TO SEND THREE (3) SIGNALS TO THE FIRE DEPARTMENT:
(1) GENERAL ALARM CONDITION
(2) GENERAL SUPERVISORY CONDITION
(3) GENERAL TROUBLE CONDITION
THE RADIO BOX SHALL ALSO BE SUPERVISED FOR TROUBLE CONDITIONS.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO INITIATE THE CLOSING OF THE
EXISTING FIRE CURTAIN LOCATED ON THE LANDING ABOVE BETWEEN MAHAN HALL AND
THE CONNECTOR TO LUCE HALL. CONTRACTOR TO FIELD LOCATE CONTROL RELAY.
SMOKE DETECTOR AND SPEAKER/STROBE TO BE LOCATED IN THE CONNECTOR WHICH
CONNECTS MAHAN HALL AND LUCE HALL.
EXISTING BATTERY POWERED OSID BEAM SMOKE DETECTOR EMITTER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING THE EXISTING BATTERIES (AND
REPLACING IF NECESSARY) TO VERIFY THAT THEY ARE PERFORMING WITHIN THE
MANUFACTURERS SPECIFICATIONS.
EXISTING 24VDC POWERED OSID BEAM SMOKE DETECTOR IMAGER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE UNIT WITH 24VDC POWER
FROM THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR SHALL FURNISH AND INSTALL
TWO (2) ADDRESSABLE MONITOR MODULES TO SUPERVISE THE IMAGER FOR ALARM AND
TROUBLE CONDITIONS. A BEAM SMOKE DETECTOR ALARM CONDITION SHALL BE
PROGRAMMED TO RELEASE DOOR HOLDERS TO VESTIBULE N24B, OFFICE N22, AND
ROTUNDA N26, IN ADDITION TO GENERAL ALARM FUNCTIONS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING TWO (2) NEW DUCT SMOKE
DETECTORS, COMPLETE WITH HOUSING AND SAMPLING TUBES, FOR EXISTING TO REMAIN
UNIT AHU-E2, ONE (1) ON THE SUPPLY SIDE AND ONE (1) ON THE RETURN SIDE. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING THE DUCTWORK WHERE THE
EXISTING DUCT SMOKE DETECTORS ARE REMOVED ONCE THE NEW FIRE ALARM SYSTEM
HAS BEEN ACCEPTED BY THE AHJ. THE CONTRACTOR SHALL PROVIDE ONE (1) CONTROL
MODULE WHICH SHALL AUTOMATICALLY SHUTDOWN THE UNIT UPON ACTIVATION OF A
DUCT SMOKE DETECTOR INSTALLED IN THE UNIT. THE FIRE ALARM CONTRACTOR SHALL
PROVIDE A REMOTE TEST SWITCH IN AN ACCESSIBLE LOCATION FOR EACH DUCT SMOKE
DETECTOR WHICH IS INSTALLED. THE INSTALLATION OF THIS EQUIPMENT SHALL BE
COORDINATED WITH THE MECHANICAL CONTRACTOR AND SHALL BE IN ACCORDANCE
WITH NFPA 72 & NFPA 90A. .
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING PRE-APPROVAL FOR THE
ROUTING OF ALL EXPOSED RACEWAY TO BE INSTALLED IN EXHIBIT HALL N14.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO LOBBY N10D
AND LOBBY N10, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N11,
OFFICE N12, AND EXHIBIT HALL N14, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N17
AND CLASSROOM N18A, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO IT STORAGE
N19 AND OFFICE N18, IN ADDITION TO GENERAL ALARM FUNCTIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING AN ADDRESSABLE MONITOR
MODULE TO SUPERVISE THE SPRINKLER PIPE HEAT TRACE CONTROLLER FOR AN OFF-
NORMAL CONDITION. INSTALLATION AND EXACT LOCATION TO BE COORDINATE WITH
SPRINKLER SYSTEM INSTALLING CONTRACTOR.
4' 8' 16'0' 1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886 O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-101.0
B M
A H
A N
H A
L L
LE
V
E L
C
O N
S
TR
U C
T
IO
N P
LA
N
CMA
12828378
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T , R
I N
A V
A L
S T
A T
IO
N
N E
W P
O R
T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45140-415
SCALE: 1/8" = 1'-0"
1ST LEVEL FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
0% S
U B
M
IT
T A
L
/1 7/
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L
/0 2/
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L
/3 0/
S
C
D
S
C
D
S
75CDS
75CD
S
C
D
S
C
D
S
C
D S
C
D
S
C
D S
C
D
S
C
D
S
C
D
SSS
S
A
B
ER
LOBBY
M25
OFFICE
M21
ELEV
E01
STAIR
ST02
STAIR
ST01
OFFICE
M26
OFFICE
M24
OFFICE
M22
ARCHIVE
STORAGE
M27
TXT
TXT
MM WF
MM TS
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-101.5
B M
A H
A N
H A
L L
LE
V
E L
1.
C O
N S
T R
U C
T
IO
N P
LA
N
CMA
12828379
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45141-415
SCALE: 1/8" = 1'-0"
1.5 LEVEL FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
15CD
S
15CD
S
C
D
S
C
D
S
C
D
S
15CD
S
C
D
S
C
D
S
C
D
S
C
D
S
C
D
S
75CD
M
M
S
C
D
S
30CD
S
30CD
S
30CD
S
30CD
S
75CD
S
75CD
S
75CD
M
M
M
S
C
D
S
75CDS
75CD
S
C
D S
C
D S
C
D
S
C
D
S
15CD
S
S
S
SSS
S
75CD
M
A
B
KITCHENETTE
N21
OFFICE
N23
STO
N24C
LANDING
N24
VESTIBULE
N24A
VESTIBULE
N24B
MAHAN
ROTUNDA
N26
READING
ROOM
N27
ARCHIVE
STORAGE
M32A
ARCHIVE
STORAGE
M32
STOR
M32C
STAIR
ST01
STOR
M39B
STOR
M39A
CORR
M37A
CORR
M37A
STAIR
ST02
LOBBY
M37
ELEV
E01
W.C.
M33
JC
M35
W.C.
M31
OFFICE
M36
OFFICE
M34
OFFICE
M30
OFFICE
N22
TXT
ER
TXT
TXT
TXT
TXT
CLOSET
N23A
MM WF
MM TS
MM WF
MM TS
RPSCM
RPSMM
IM,E
EM,E
MMALRM
MMTRBL
DH
DH
DH
DH
DH
DH
DH
DH
DH
SW
SWSW
SW
SW
SW
CM
CM
CM
CM
CM
CM
CM
CM
CM
DRAWING KEYNOTES:
THE NEW DEDICATED OUTSIDE AIR SYSTEM (DOAS) UNIT TO BE INSTALLED IN THIS
LOCATION IS PROPOSED TO HAVE A SUPPLY CAPACITY LESS THAN 2,000CFM, AND THUS
WILL NOT BE INTERFACED WITH THE NEW FIRE ALARM SYSTEM.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO RELEASE THE ELECTRONIC
LOCKING MECHANISM FOR THE DOOR FROM THE CONNECTOR TO THE COURTYARD, SUCH
THAT IT UNLOCKS DURING AN ALARM CONDITION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR NECESSARY
TO TIE INTO THE ELECTRONIC LOCK CONTROLS TO FACILITATE THIS INTERFACE.
CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE INSTALLATION WITH
ELECTRONIC LOCK VENDOR.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO SEND A GENERAL ALARM
SIGNAL TO THE BUILDING SECURITY SYSTEM UPON RECEIPT OF A FIRE ALARM CONDITION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS,
CIRCUITRY AND LABOR NECESSARY TO TIE INTO THE SECURITY SYSTEM TO FACILITATE
THIS INTERFACE. CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE
INSTALLATION WITH SECUIRTY SYSTEM VENDOR.
THE EXISTING RADIO MASTER BOX #0003 (AES ALARM TRANSCEIVER 7788-F8) IS TO REMAIN
AND SHALL CONTINUE TO SEND THREE (3) SIGNALS TO THE FIRE DEPARTMENT:
(1) GENERAL ALARM CONDITION
(2) GENERAL SUPERVISORY CONDITION
(3) GENERAL TROUBLE CONDITION
THE RADIO BOX SHALL ALSO BE SUPERVISED FOR TROUBLE CONDITIONS.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO INITIATE THE CLOSING OF THE
EXISTING FIRE CURTAIN LOCATED ON THE LANDING ABOVE BETWEEN MAHAN HALL AND
THE CONNECTOR TO LUCE HALL. CONTRACTOR TO FIELD LOCATE CONTROL RELAY.
SMOKE DETECTOR AND SPEAKER/STROBE TO BE LOCATED IN THE CONNECTOR WHICH
CONNECTS MAHAN HALL AND LUCE HALL.
EXISTING BATTERY POWERED OSID BEAM SMOKE DETECTOR EMITTER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING THE EXISTING BATTERIES (AND
REPLACING IF NECESSARY) TO VERIFY THAT THEY ARE PERFORMING WITHIN THE
MANUFACTURERS SPECIFICATIONS.
EXISTING 24VDC POWERED OSID BEAM SMOKE DETECTOR IMAGER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE UNIT WITH 24VDC POWER
FROM THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR SHALL FURNISH AND INSTALL
TWO (2) ADDRESSABLE MONITOR MODULES TO SUPERVISE THE IMAGER FOR ALARM AND
TROUBLE CONDITIONS. A BEAM SMOKE DETECTOR ALARM CONDITION SHALL BE
PROGRAMMED TO RELEASE DOOR HOLDERS TO VESTIBULE N24B, OFFICE N22, AND
ROTUNDA N26, IN ADDITION TO GENERAL ALARM FUNCTIONS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING TWO (2) NEW DUCT SMOKE
DETECTORS, COMPLETE WITH HOUSING AND SAMPLING TUBES, FOR EXISTING TO REMAIN
UNIT AHU-E2, ONE (1) ON THE SUPPLY SIDE AND ONE (1) ON THE RETURN SIDE. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING THE DUCTWORK WHERE THE
EXISTING DUCT SMOKE DETECTORS ARE REMOVED ONCE THE NEW FIRE ALARM SYSTEM
HAS BEEN ACCEPTED BY THE AHJ. THE CONTRACTOR SHALL PROVIDE ONE (1) CONTROL
MODULE WHICH SHALL AUTOMATICALLY SHUTDOWN THE UNIT UPON ACTIVATION OF A
DUCT SMOKE DETECTOR INSTALLED IN THE UNIT. THE FIRE ALARM CONTRACTOR SHALL
PROVIDE A REMOTE TEST SWITCH IN AN ACCESSIBLE LOCATION FOR EACH DUCT SMOKE
DETECTOR WHICH IS INSTALLED. THE INSTALLATION OF THIS EQUIPMENT SHALL BE
COORDINATED WITH THE MECHANICAL CONTRACTOR AND SHALL BE IN ACCORDANCE
WITH NFPA 72 & NFPA 90A. .
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING PRE-APPROVAL FOR THE
ROUTING OF ALL EXPOSED RACEWAY TO BE INSTALLED IN EXHIBIT HALL N14.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO LOBBY N10D
AND LOBBY N10, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N11,
OFFICE N12, AND EXHIBIT HALL N14, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N17
AND CLASSROOM N18A, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO IT STORAGE
N19 AND OFFICE N18, IN ADDITION TO GENERAL ALARM FUNCTIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING AN ADDRESSABLE MONITOR
MODULE TO SUPERVISE THE SPRINKLER PIPE HEAT TRACE CONTROLLER FOR AN OFF-
NORMAL CONDITION. INSTALLATION AND EXACT LOCATION TO BE COORDINATE WITH
SPRINKLER SYSTEM INSTALLING CONTRACTOR.
4' 8' 16'0' 1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886 O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-102.0
B M
A H
A N
H A
L L
LE
V
E L
C
O N
S
TR
U C
T
IO
N P
LA
N
CMA
12828380
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T , R
I N
A V
A L
S T
A T
IO
N
N E
W P
O R
T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45142-415
SCALE: 1/8" = 1'-0"
2ND LEVEL FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
0% S
U B
M
IT
T A
L
/1 7/
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L
/0 2/
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L
/3 0/
IS
S
U E
F O
R B
ID
/3 0/
S
C
D
S
C
D
S
75CDS
75CD
S
C
D
S
C
D
S
C
D S
C
D
S
C
D S
C
D
S
C
D
S
C
D
S
S
75CD
S
75CD
A
B
TXT
TXT
ER
LOBBY
M41
ELEV
E01
STAIR
ST02
TR
M42
ARCHIVE
STORAGE
M40
STAIR
ST01
MM WF
MM TS
MM TS
MM WF
4' 8' 16'0'
1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886
O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-102.5
B M
A H
A N
H A
L L
LE
V
E L
2.
C O
N S
T R
U C
T
IO
N P
LA
N
CMA
12828381
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T
R I
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45143-415
SCALE: 1/8" = 1'-0"
2.5 LEVEL FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
S U
B M
IT
T
A L
/1
/2
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L /0
/2
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L /3
/2
IS
S
U E
F O
R B
ID
/3
/2
75CD
S
75CD
S
75CD
S
75CD S
75CD
S
75CD
A
B
RTS
DD
RTS
DD
AHUCM
DRAWING KEYNOTES:
THE NEW DEDICATED OUTSIDE AIR SYSTEM (DOAS) UNIT TO BE INSTALLED IN THIS
LOCATION IS PROPOSED TO HAVE A SUPPLY CAPACITY LESS THAN 2,000CFM, AND THUS
WILL NOT BE INTERFACED WITH THE NEW FIRE ALARM SYSTEM.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO RELEASE THE ELECTRONIC
LOCKING MECHANISM FOR THE DOOR FROM THE CONNECTOR TO THE COURTYARD, SUCH
THAT IT UNLOCKS DURING AN ALARM CONDITION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS, CIRCUITRY AND LABOR NECESSARY
TO TIE INTO THE ELECTRONIC LOCK CONTROLS TO FACILITATE THIS INTERFACE.
CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE INSTALLATION WITH
ELECTRONIC LOCK VENDOR.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO SEND A GENERAL ALARM
SIGNAL TO THE BUILDING SECURITY SYSTEM UPON RECEIPT OF A FIRE ALARM CONDITION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT, CONNECTIONS,
CIRCUITRY AND LABOR NECESSARY TO TIE INTO THE SECURITY SYSTEM TO FACILITATE
THIS INTERFACE. CONTRACTOR TO FIELD LOCATE CONTROL RELAY AND COORDINATE
INSTALLATION WITH SECUIRTY SYSTEM VENDOR.
THE EXISTING RADIO MASTER BOX #0003 (AES ALARM TRANSCEIVER 7788-F8) IS TO REMAIN
AND SHALL CONTINUE TO SEND THREE (3) SIGNALS TO THE FIRE DEPARTMENT:
(1) GENERAL ALARM CONDITION
(2) GENERAL SUPERVISORY CONDITION
(3) GENERAL TROUBLE CONDITION
THE RADIO BOX SHALL ALSO BE SUPERVISED FOR TROUBLE CONDITIONS.
ADDRESSABLE CONTROL RELAY SHALL BE CONFIGURED TO INITIATE THE CLOSING OF THE
EXISTING FIRE CURTAIN LOCATED ON THE LANDING ABOVE BETWEEN MAHAN HALL AND
THE CONNECTOR TO LUCE HALL. CONTRACTOR TO FIELD LOCATE CONTROL RELAY.
SMOKE DETECTOR AND SPEAKER/STROBE TO BE LOCATED IN THE CONNECTOR WHICH
CONNECTS MAHAN HALL AND LUCE HALL.
EXISTING BATTERY POWERED OSID BEAM SMOKE DETECTOR EMITTER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR TESTING THE EXISTING BATTERIES (AND
REPLACING IF NECESSARY) TO VERIFY THAT THEY ARE PERFORMING WITHIN THE
MANUFACTURERS SPECIFICATIONS.
EXISTING 24VDC POWERED OSID BEAM SMOKE DETECTOR IMAGER IS TO REMAIN. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE UNIT WITH 24VDC POWER
FROM THE NEW FIRE ALARM SYSTEM. THE CONTRACTOR SHALL FURNISH AND INSTALL
TWO (2) ADDRESSABLE MONITOR MODULES TO SUPERVISE THE IMAGER FOR ALARM AND
TROUBLE CONDITIONS. A BEAM SMOKE DETECTOR ALARM CONDITION SHALL BE
PROGRAMMED TO RELEASE DOOR HOLDERS TO VESTIBULE N24B, OFFICE N22, AND
ROTUNDA N26, IN ADDITION TO GENERAL ALARM FUNCTIONS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING TWO (2) NEW DUCT SMOKE
DETECTORS, COMPLETE WITH HOUSING AND SAMPLING TUBES, FOR EXISTING TO REMAIN
UNIT AHU-E2, ONE (1) ON THE SUPPLY SIDE AND ONE (1) ON THE RETURN SIDE. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING THE DUCTWORK WHERE THE
EXISTING DUCT SMOKE DETECTORS ARE REMOVED ONCE THE NEW FIRE ALARM SYSTEM
HAS BEEN ACCEPTED BY THE AHJ. THE CONTRACTOR SHALL PROVIDE ONE (1) CONTROL
MODULE WHICH SHALL AUTOMATICALLY SHUTDOWN THE UNIT UPON ACTIVATION OF A
DUCT SMOKE DETECTOR INSTALLED IN THE UNIT. THE FIRE ALARM CONTRACTOR SHALL
PROVIDE A REMOTE TEST SWITCH IN AN ACCESSIBLE LOCATION FOR EACH DUCT SMOKE
DETECTOR WHICH IS INSTALLED. THE INSTALLATION OF THIS EQUIPMENT SHALL BE
COORDINATED WITH THE MECHANICAL CONTRACTOR AND SHALL BE IN ACCORDANCE
WITH NFPA 72 & NFPA 90A. .
THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING PRE-APPROVAL FOR THE
ROUTING OF ALL EXPOSED RACEWAY TO BE INSTALLED IN EXHIBIT HALL N14.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO LOBBY N10D
AND LOBBY N10, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N11,
OFFICE N12, AND EXHIBIT HALL N14, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO OFFICE N17
AND CLASSROOM N18A, IN ADDITION TO GENERAL ALARM FUNCTIONS.
SMOKE DETECTOR SHALL BE PROGRAMMED TO RELEASE DOOR HOLDERS TO IT STORAGE
N19 AND OFFICE N18, IN ADDITION TO GENERAL ALARM FUNCTIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING AN ADDRESSABLE MONITOR
MODULE TO SUPERVISE THE SPRINKLER PIPE HEAT TRACE CONTROLLER FOR AN OFF-
NORMAL CONDITION. INSTALLATION AND EXACT LOCATION TO BE COORDINATE WITH
SPRINKLER SYSTEM INSTALLING CONTRACTOR.
4' 8' 16'0' 1/8" = 1'-0"
GRAPHIC SCALE:
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T
LA
N
TI
C
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
KEY PLAN
NAVSTA DRAWING NO.
JENSEN HUGHES
117 Metro Center Blvd Suite 1002
Warwick, Rhode Island 02886 O: 401.736.8992 C: 410.737.8677
1/8" = 1'-0"
FA-103.0
B M
A H
A N
H A
L L
A
TT
IC
C
O N
S
TR
U C
T
IO
N P
LA
N
CMA
12828382
EBJ EBJ
B.COLLARD
1637267
N E
W P
O R
T , R
I N
A V
A L
S T
A T
IO
N
N E
W P
O R
T
P U
B L
IC
W O
R K
S D
E P
A R
T M
E N
T
G.MONTANI
R.REGAN
P.BAKAJ
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N
E W
P O
R T
R
I
D E
S
IG
N O
F E
X
TE
R
IO
R A
N D
IN
TE
R
IO
R R
E P
A
IR
S , N
W C
45144-415
SCALE: 1/8" = 1'-0"
ATTIC LEVEL FIRE ALARM CONSTRUCTION PLAN
A1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S
U E
F O
R
0% S
U B
M
IT
T A
L
/1 7/
0%
P R
E -F
IN
A
L S
U B
M
IT
T A
L
/0 2/
IS
S
U E
F O
R F
IN
A
L S
U B
M
IT
T A
L
/3 0/
IS
S
U E
F O
R B
ID
/3 0/
SYSTEM INPUTS
REQUIRED SYSTEM OUTPUTS
MANUAL FIRE ALARM BOX
ACTIVATION
SUPERVISORY SIGNALS
OPEN CIRCUIT
TROUBLE SIGNALS
CIRCUIT GROUND FAULT
AC POWER FAILURE
ACTUATE A
UDIB
LE
/V
IS
IB
LE
A
LA
RM
IN
DIC
ATOR A
T FAMNSCP A
ND A
NNUNCIA
TOR
ACTUATE A
UDIB
LE
/V
IS
IB
LE
S
UPERVIS
ORY
IN
DIC
ATOR A
T FAMNSCP A
ND A
NNUNCIA
TOR
ACTUATE A
UDIB
LE
/V
IS
IB
LE
T
ROUBLE
IN
DIC
ATOR A
T FAMNSCP A
ND A
NNUNCIA
TOR
PROVID
E D
EVIC
E/C
IR
CUIT
IN
DIC
ATIO
N
AT FAMNSCP A
ND A
NNUNCIA
TOR
TRANSMIT ZONE 1
- MAHAN H
ALL
G
ENERAL
ALA
RM C
ONDIT
IO
N
TRANSFER F
IR
E A
LA
RM S
YSTEM T
O
SECONDARY P
OW
ER
ANNUNCIATION AND INDICATION
SIGNAL TRANSMISSION TO
RECEIVING STATION
(VIA EXISTING AES RADIO BOX #0003)
ANCILLARY FUNCTIONSFIRE ALARM MASS
NOTIFICATION
OPERATIONS…