This document provides an overview for an Advanced Metering Infrastructure (AMI) project at Naval Support Activity Crane in Indiana. The project involves installing electric, water, and steam meters at the facility, with supporting hardware and communications infrastructure. Electric meters will be ION 8600 models and PM8 RTUs, measuring energy use in 15-minute intervals. Water meters up to 2 inches will use positive displacement models, while larger sizes will use turbine meters. Steam meters will be vortex shedding models capable of operating at high pressures and temperatures. Meter data will be collected through an AMI network using ION Enterprise software over a mesh network of 3eTI 523 radios. Metering enclosures and RTU cabinets conforming to NEMA 3R and UL-508A are specified for outdoor and indoor installations. The accompanying federal contract opportunity is an IDIQ MACC for minor construction projects at NSA Crane and a test facility, set aside for small businesses.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NSA Crane
NSA Crane AMI Project
5.0 Electric Metering
5.1 Overview
ION Meters are included in the design.
All meters are Class 20 and are rated ANSI C12.20 Accuracy Class 0.2.
For Polyphase installations including 4W Wye, 120/208V (FM 9S), 4 W Wye 277/480V (FM 9S), and 3W Delta 120 - 480V (FM 35S), the ION 8600 meter is used. For both 3W Single-phase 120/240V and 3W Network 120/208V applications, a specially programmed FM 9S ION 8600 meter is used. Control power for these enclosures is derived from line power.
For Meter-Interface-Unit (MIU) applications, the PM8 RTU is used. This device allows logging of mechanical meter data; however, it isn’t designed to directly measure an electric circuit and doesn’t include Voltage or Current inputs. Control power for these enclosures is provided by a nearby source, typically 120V.
5.2 Schneider Electric ION 8600
The ION 8600 is a multi-function socket-based meter that meets and exceeds ANSI C12.20 0.2.
The ION 8600 measures a comprehensive set of energy, power and harmonics parameters.
Events such as maximum harmonics and sags/swells are prioritized and recorded. The meter records up to 16 channels via data recorders and all are fully configurable to record any available parameter. Configured parameters are detailed in Section 5.3 Meter Configuration.
Figure 5-2-1 – ION8600 Front Display
Final Design
REDACTED
REDACTED DOCUMENT IS EXCERPT FROM ORIGINAL INSTALLATION OVERVIEW AND IS PROVDED
FOR INFORMATION ONLY. NOT DESIGN DIRECTION AND NOT SCOPE DIRECTION
The ION 8600 also allows ION, MV-90, Modbus and DNP hosts to talk through the Ethernet port and up to 31 downstream slave devices on the meter’s RS485 serial port. Standard communication ports are Ethernet, RS-232/485 port and a front mounted ANSI Optical Port.
Supported protocols are Modbus RTU, Modbus TCP, DNP 3.0, HTTP/XML, ION and MV-90.
The ION 8600 includes a web server and an Ethernet port for easy access to metering data over Ethernet and without specific software (only a browser such as Microsoft Internet Explorer is required).
The ION 8600 features on-board Inputs/Outputs (I/O) which allows for complete integration with 3rd party devices and systems. ION programmability enables scaling and totalizing to provide RTU like functionality in a power monitoring system. Applications include pulse counting, demand metering for other utilities (water, gas, etc), equipment status/position monitoring, demand synchronization, triggering conditional energy metering and equipment control or signaling. Meters provided include 4 digital inputs and 3 relay outputs (electromechanical). Additional I/O can be added through expansion modules. See section 5.6 ION 8600 Technical Details for further information.
Similar functionality is included in the PM8 RTU. The PM8 RTU is a panel mounted device.
The PM8 RTU has all the functionality of the PM8 meter excluding the capability to directly measure an electrical circuit. See section 5.7 PM8 RTU Technical Details for further information.
5.3 Meter Configuration
Meters will be programmed and will include Navy specified Device IDs. The meters will be programmed as secondary-rated units and the multiplier will be applied at the DAS. Meter programming conforms to the latest standard developed in conjunction with NFESC and based in large part on the July 2010 NAVFAC AMI Point Paper: A Call for Consistency. Additional display registers for Special Cases as detailed in the Call for Consistency document can be programmed as required.
Table 1: Displays of ION 8600 Electric Meter Modes (Rev 2g)
Display Code
REGISTER NORMAL ALTERNATE TEST
888 ALL SEGMENTS Yes Yes Yes
- DISK EMULATOR Yes Yes Yes
001 DATE Yes Yes No
002 TIME Yes Yes No
010 RATE A TOTAL KWH Yes No No
011 RATE A MAXIMUM KW Yes No No
012 RATE B TOTAL KWH Yes No No
Final Design
REDACTED
013 RATE B MAXIMUM KW Yes No No
014 RATE C TOTAL KWH Yes No No
015 RATE C MAXIMUM KW Yes No No
016 RATE D TOTAL KWH Yes No No
017 RATE D MAXIMUM KW Yes No No
018 TOTAL KWH Yes Yes Yes
019 MAXIMUM KW Yes Yes No
020 TOTAL KVARHr Yes No Yes
021 CUMULATIVE DEMAND (KW) Yes No No
030 BATTERY PERCENTAGE Yes Yes No
Owner: XX_LL_CCC_TT ID(A), Tag 1:
<facility>_S, Tag 3: FFBBnnnnn; etc. Yes No No
033 PT RATIO, CT RATIO, METER MULTIPLIER No Yes No
INSTANTANEOUS APPARENT POWER
(KVA)
No Yes No
VA (voltage magnitude) (Note: Line-to-Neutral for Wye and Single-phase applications No Yes Yes
VB (voltage magnitude) (Note: Line-to-Neutral for Wye No Yes No
VC (voltage magnitude) (Note: Line-to-Neutral for Wye and Single-phase applications;
No Yes No
045 IA (current magnitude) No Yes No
046 IB (current magnitude) No Yes No
047 IC (current magnitude) No Yes No
048 CURRENT ANGLE PHASE A No Yes No
049 CURRENT ANGLE PHASE B No Yes No
050 CURRENT ANGLE PHASE C No Yes No
051 INSTANTANEOUS POWER FACTOR Yes Yes Yes
052 INSTANTANEOUS POWER (KW) No Yes No
060 KH OF METER No Yes No
NUMBER OF PULSES RECEIVED FROM GAS
METER
No Yes No
071 CONSUMPTION OF GAS METER Yes No No
NUMBER OF PULSES RECEIVED FROM
WATER METER No Yes No
073 CONSUMPTION OF WATER METER Yes No No
NUMBER OF PULSES RECEIVED FROM
STEAM METER
No Yes No
075 CONSUMPTION OF STEAM METER Yes No No
080 TOTAL KWH PULSES Yes No Yes
090 INTERVAL LENGTH IN MINUTES Yes No No
Previous display data is also available from the meters. The meter performs an automated meter read and demand reset at 12:00 am on the first day of each month. This data is available locally or remotely until the next demand reset.
Final Design
REDACTED
The ION 8600 meter also has load profile recorder channels configured. Data is logged in the meter on an interval basis (15 minutes). This data is transmitted to the DAS periodically. Table 2 details the ION 8600 recorder channels and associated DAS Channel mapping.
Table 2: ION 8600 recorder channels and associated DAS Channel Mapping
DAS
Channel Number
Metering Data Type Note / Comment
101 KWHr Delivered 15 min use - LP Interval 102 KVARHr Delivered 15 min use - LP Interval 103 KWHr Received 15 min use - LP Interval 104 KVARHr Received 15 min use - LP Interval 110 Water Consumption LP Interval - thru KYZ pulses 120 Gas Consumption LP Interval - thru KYZ pulses
130 Steam Consumption LP Interval - thru KYZ pulses 140 Instantaneous Demand (KW) 201 Total KWH Delivered Total cumulative register since installation *** 203 Total KWH Received Total cumulative register since installation *** 301 Maximum Demand Delivered 501 Average Power Factor Average during LP interval 502 Total Harmonic Distortion Instantaneous 503 Average Voltage of A,B,C (V) Instantaneous 504 Average Current of A,B,C (A) Instantaneous 610 Current Angle for Phase A Instantaneous 701 Voltage Sag Event to trigger an alarm 702 Voltage Swell Event to trigger an alarm 703 Low PF Event to trigger an alarm 704 High Harmonic Event to trigger an alarm 705 High Neutral Current Event to trigger an alarm 706 Meter Reporting RAM Failure Event to trigger an alarm 707 Meter Reporting Low Battery Event to trigger an alarm 708 Loss of Any Phase Event to trigger an alarm 709 Number of Meter Power Down
Exceeds One Event to trigger an alarm
710 Reverse Power Observed on Any Phase
Event to trigger an alarm
Final Design
REDACTED
5.8 Instrument transformers
The current transformers (CTs) are ANSI accuracy class 0.3 revenue grade and are sized appropriately for each installation based on UFGS guidelines. Distance from the CTs to the meter will be minimized to limit burden in order to meet the 0.3 accuracy standard.
Metering potential transformers (PTs) will not be required on installations 600V or less.
Revenue grade PTs are provided for the medium installations, if applicable.
Final Design
REDACTED
6.0 Water Metering
For water monitoring, existing pulse devices will be used where feasible. For installations where water meters haven’t been installed or no pulse device is present, For 1”, 1.5” and 2” locations and up to 170 GPM, positive displacement meters will be used. For 3” or greater locations, turbine style meters will be provided. For new installations turbine meters will be equipped with an integral strainer or have a Y-type strainer installed a minimum of five (5) pipe diameters upstream of the meter. All meters will be accurate to within ±1.5% of flow rate. Meters will be supplied with a local display of water consumption in US gallons or 1,000 US gallons. Each meter will also be fitted with a pulse transmitter for integration to the AMI network.
The water meters will conform to applicable UFGS guidelines and applicable industry standards, including AWWA Series C700.
Final Design
REDACTED
REDACTED
DOCUMENT IS EXCERPT FROM ORIGINAL INSTALLATION OVERVIEW AND IS PROVDED
8.0 Steam Metering
Steam meters will be vortex shedding meters that include a stainless steel body with ANSI class 150 flanged ends and stainless steel sensing elements. Meters will be equipped with an explosion-proof type waterproof sending unit (register) housing capable of operating in a 0% to 100% (non-condensing) relative humidity environment from -20°F to 140°F. Meters will be internally temperature compensated. Meters will be rated to operate at temperatures from - 40°F to 750°F and be capable of operating with 150 psig continuous pressure. Meters will be supplied with a local electronic display which shall indicate steam flow in pounds per hour and totalized consumption in 1,000 pounds. Meter accuracy will be at least ±1.0% of flow rate.
The steam meters will conform to applicable UFGS guidelines and applicable industry standards.
Meters will be equipped with a digital pulse output with a programmable maximum pulse frequency of 100 Hz and shall have HART protocol.
9.0 Meter Interface Unit (MIU) Interfaces
When the mechanical flow meters are within range of an electric meter installation, signals from flow meters are hardwired to the inputs of the ION 8600. Otherwise, PM8 RTUs will be used to interface to the flow meters. PM8 RTUs will be mounted in a pre-wired UL-508A enclosure, along with a 3eTI 523 mesh radio, power supply, terminal blocks and antenna.
The ION 8600 and PM8 RTUs will count, scale, timestamp and log each pulse to an onboard energy interval log to be read by ION Enterprise.
Figure 9-1 - Pulse counting of flow meters to an ION8600 or PM8 RTU
Final Design
REDACTED
10.0 Hardware Enclosures
The following typical hardware enclosures are included in the design. A brief overview of each enclosure follows.
ION 8600 Meter with Radio PM8 RTU with Radio PM8 RTU with two Radios PM8 RTU Enclosure with Radio, RPT with RPT with RPT with Radio
REDACTED
REDA
CTEDREDACTED
10.1 8600 Enclosure with Radio
An enclosure equipped with an ION 8600 meter will be used for all electric metering installations. The enclosure is rated NEMA Type 3R and UL-508A approved. It will be used for installations on outdoor pad-mount transformers, wall mount and indoor locations where appropriate. The meters will be installed with test switches and fused disconnects to facilitate the isolation of the meters for service and maintenance as required.
Where wireless communications is permitted, the meter enclosure will include a 3ETi 3e-523.
Ethernet radio. The radio will be mounted inside the enclosure with integrated antennas, or the antennas will be separately mounted where necessary to provide adequate RF range. In some cases, a radio will not be included and the meter communications will be via a wired Ethernet connection to a separate radio point of other communications interface. See Figure 10-1-1: ION 8600 Meter Enclosure Layout
Figure 10-1-1: ION 8600 Meter Enclosure Layout
Final Design
REDACTED
10.2 PM8 RTU Enclosure with Radio
An enclosure equipped with an PM8 RTU will be used as a radio repeater or for collection of mechanical meter data where there isn’t an electric meter nearby. The enclosure is rated NEMA Type 3R and UL-508A approved. It will typically be installed in a wall mount configuration.
The RTU enclosure will be installed with fused disconnects, control power transformer, and terminal block for I/O. The meter enclosure will include a 3ETi 3e-523. Ethernet radio. The radio will be mounted inside the enclosure with integrated antennas, or the antennas will be separately mounted where necessary to provide adequate RF range. See Figure 10-3-1: PM8 RTU with Radio Enclosure Layout
Figure 10-2-1: PM8 RTU with Radio Enclosure Layout
Final Design
REDACTED
10.3 PM8 RTU Enclosure with 2 Radios
An enclosure equipped with an PM8 RTU, 2 Radios and Switch will be used for each mesh. One radio will function as the root node radio for the mesh. The other radio will be used for backhaul communications to the POP. The enclosure is rated NEMA Type 3R and UL-508A approved. It may be installed in either a pad-mount, wall mount, or roof mount configuration. The enclosure will be installed with fused disconnects, control power transformer, and switch. The meter enclosure will include two internally mounted 3ETi 3e-523 Ethernet radios. The antennas (2) will be separately mounted to provide adequate RF range. See Figure 10-4-1: PM8 RTU with Two Radios and Switch Enclosure Layout
Figure 10-3-1: PM8 RTU with Two Radios and Switch Enclosure Layout
10.5 RPT Enclosure with
An enclosure equipped with The enclosure is rated NEMA Type 3R and UL-508A approved. It may be installed in either a pad-mount, wall mount, or roof mount configuration. The enclosure will be installed with fused disconnects, control power transformer, and switch. See Figure 10-5-1: RPT Enclosure Layout.
Figure 10-5-1: RPT Enclosure Layout
REDACTED
REDA
CTED
REDACTED
REDACTED
10.6 RPT Enclosure with and Radio
An enclosure equipped with radio. The enclosure is rated NEMA Type 3R and UL-508A approved. It may be installed in either a pad-mount, wall mount, or roof mount configuration. The enclosure will be installed with fused disconnects, control power transformer, and switch. The meter enclosure will include a 3ETi 3e-523.
Ethernet radio. The radio will be mounted inside the enclosure with integrated antennas, or the antennas will be separately mounted where necessary to provide adequate RF range. See Figure 10-6-1: RPT and Radio Enclosure Layout.
Figure 10-6-1: RPT and Radio Enclosure Layout
REDACTED
REDA
CTED
REDACTED
REDACTED
10.7 RPT Enclosure with Radio
An enclosure equipped with a radio. Enclosure will be used as a radio repeater where there isn’t an electric meter or RTU nearby. The enclosure is rated NEMA Type 3R and UL-508A approved. It may be installed in either a pad-mount, wall mount, or roof mount configuration.
The enclosure will be installed with fused disconnects, control power transformer, and switch.
The meter enclosure will include a 3ETi 3e-523. Ethernet radio. The radio will be mounted inside the enclosure with integrated antennas, or the antennas will be separately mounted where necessary to provide adequate RF range. See Figure 10-7-1: RPT with Radio Enclosure Layout.
Figure 10-7-1: RPT with Radio Enclosure Layout
Final Design
REDACTED