This document contains specifications for pad-mounted distribution transformers and details for an indefinite delivery/indefinite quantity multiple award construction contract opportunity. The specifications provide requirements for dead-front construction, loop-feed capability with six bushings, load break switches, spare conduits, secondary voltage and current limits, winding configuration, and surge protection. The construction contract is a total small business set-aside for design-build and design-bid-build projects at the Naval Security Group Activity Crane in Indiana and the Glendora Test Facility in Sullivan, Indiana. The contract will have an indefinite quantity for minor construction, renovation, and repair projects over multiple years.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3-5 PAD-MOUNTED DISTRIBUTION TRANSFORMERS. (UFC 3-550-01)
3-5.2 Configuration.
Use dead-front construction for pad-mounted transformers unless not available within system parameters. Use pad-mounted transformers, separately protected with vacuum fault interrupter equipped switches for 34.5 kV systems. Three-phase pad-mounted transformers must be loop-feed capable with 6 bushings. Provide two-position, oil-immersed, load break switches that are appropriate for the application. If the transformer might be used as part of a loop-feed design, provide three switches to permit closed transition loop feed and sectionalizing. If the transformer will be installed at the end of a radial supply with no intention of future loop feed capability, provide a single on-off switch. Provide a spare conduit in the high voltage section extending 5 ft (1.5 m) out from the transformer pad.
3-5.3 Size and Secondary Voltage.
Do not use pad-mounted transformers with secondary currents exceeding 3,000 amperes because of the size and quantity of secondary conductors. Transformers rated above 1,000 kVA serving 208Y/120 volt loads and above 2,500 kVA serving 480Y/277 volt loads must be in a secondary unit substation configuration. UFC 3-550-01 1 September, 2016 9 Minimize double transformations to reduce energy consumption and to minimize items of equipment. Provide two oil-filled pad-mounted transformers in lieu of one 480Y/277 volt service if the required 208Y/120 volt load using dry-type transformers exceeds 40 percent of the 480 volt service transformer capability. Connect equipment at the highest available voltage to minimize the capital cost and energy losses of transformation equipment.
3-5.4 Winding Configuration.
Provide delta-wye connections for three phase systems.
3-5.5 Surge Protection.
Provide bushing-mounted elbow type arresters at the ends of all radials and in normally open locations in loops. Provide arresters for all voltage levels above 5 kV.