DEMOLISH EXISTING ROOF
SCUTTLE. REPLACE WITH NEW
INSULATED ROOF SCUTTLE AND
FRAME WITH NEOPRENE SEAL ALL
SIDES. PROVIDE HINGED
CONDITION AND HASP FOR
PADLOCK (NIC)
SEE NOTE CUPOLA GENERAL
NOTES
SEE NOTES N1, N3, AND N4
FROM LEFT TO RIGHT:
1. SYNTHETIC PERMEABLE ICE &
SHIELD MEMBRANE (PERM 10
OR HIGHER)
2. FLASHING
3. CAP FLASHING
FROM BOTTOM TO TOP:
1. CLOSED CELL SPRAYED ON
INSULATION
2. SUBSTRATE
3. SYNTHETIC PERMEABLE ICE &
SHIELD MEMBRANE (PERM 10 OR
HIGHER)
4. SSMR
1. SSMR CLOSURE STRIP
VAPOR BARRIER OVERLAPED OVER
FLASHING
DEMOLISH TRIM AND REMOVE FRONT
PANEL/CLADDING AS NECESSARY TO ALLOW
THE REMOVAL OF THE LOUVER
EXIST LOUVER: REMOVE, REPAIR AND
PREPARE FOR RE-FINISH STORE FOR
RE-INSTALLATION. DISCARD IF DAMAGED
FLASHING: DEMO
DEMOLISH TRIM AND REMOVE FRONT
PANEL/CLDDING AS NECESSARY TO ALLOW THE
REMOVAL OF THE LOUVER
EXIST LOUVER: REMOVE, REPAIR AND PREPARE
FOR RE-FINISH STORE FOR RE-INSTALLATION.
DISCARD IF DAMAGED
INSTALL NEW THROUGH FLASHING. INSTALL
PANEL/CLADDING AND TRIM TO MATCH
LOUVER: RE-INSTALL, PAINT. REPLACE WITH
NEW TO MATCH EXISTING IF DAMAGED
1' ALUMINUM INSULATED PANEL OVER THE
ENTIRE LOUVER OPENING. INSTALL OVER
CONTINUOUS BEAD OF CAULKING AND FASTEN
AT 6" O.C. ALL SIDES. TYP AT ALL LOUVERS
INSTALL NEW VAPOR BARRIER AS NECESARY
INSTALL NEW THROUGH FLASHING. INSTALL
PANEL AND TRIM TO MATCH. PAINT
LOUVER: RE-INSTALL, PAINT. REPLACE WITH NEW
TO MATCH EXISTING IF DAMAGED
INSULATED PANEL SEE DETAIL
ABOVE
INSTALL NEW VAPOR BARRIER AS NECESARY
DEMOLISH TRIM AND REMOVE FRONT PANEL/AS
NECESSARY AS NECESSARY TO ALLOW THE
REMOVAL OF THE LOUVER
EXIST LOUVER: REMOVE, REPAIR AND PREPARE
FOR RE-FINISH STORE FOR RE-INSTALLATION.
DISCARD IF DAMAGED
INSTALL NEW THROUGH FLASHING. INSTALL
PANEL/CLADDING AND TRIM TO MATCH
LOUVER: RE-INSTALL, PAINT. REPLACE WITH
NEW TO MATCH EXISTING IF DAMAGED
INSTALL NEW VAPOR BARRIER AS NECESARY
INSULATED PANEL SEE DETAIL
ABOVE
BLDG. 1 CUPOLA ELEVATION1
CUPOLA BASE AT SSMR- RENO6
CONST. CONTR. NO.
DISCLOSURE OF INFORMATION CONTRACTOR SHALL COMPLY AS FOLLOWS:
A. THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S
ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE, DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO
THIS CON- TRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS:
(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR
(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE
DATE OF RELEASE.
B. REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE
MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL SUBMIT
ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE
FOR RELEASE.
C. THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT
UNDER THIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION
TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.
17 APRIL 2020 A110
GUSTAVO DE LUCA
GUSTAVO DE LUCA
GUSTAVO DE LUCA
GUSTAVO DE LUCA
THOMAS BURTON
PWO or OICC
BUILDING 1
CUPOLA ELEV, SEC, & DETAILS
XXXXX
19-0037
NOTED NA
10 10
ROOF EDGE & LOUVER HEAD - DEMO2
LOUVER SILL & ROOF FLASHING- DEMO4
ROOF EDGE & LOUVER HEAD- RENO3
LOUVER SILL & ROOF FLASHING - RENO5
LOUVER JAMB - DEMO7 LOUVER JAMB - RENO8
CUPOLA GENERAL NOTES
No.
NOTES (NOT KEYED IN SEC. & DET.)
N1
EXIST TRIM ITEMS, FASCIA, SOFFIT, PANELS, ETC.: FOR BIDING PURPOSES
ASSUME THAT 50% MUST BE REPLACED. ALL EXTERIOR CLADDING,
MOLDING, RIM, FASCIA BOARDS, LAP SIDING, SOFFIT MUST BE SOLID PVC
WITH A FLAME SPREAD INDEX OF LESS THAN 25, ASTM E 84.
N2
EXISTING ROOFING SUBSTRATE, NAILERS, BLOCKING, ETC.: REPLACE ALL
DAMAGED ITEMS. FOR BIDING PURPOSES ASSUME 50% NEW MATERIALS.
REPLACE WITH MOISTURE RESISTANT LUMBER, MATCH EXISTING
THICKNESS AND OTHER CONDITIONS
N3
EXISTING ROOFING MATERIAL: THE CONTRACTOR MUST VERIFY ITS
CONDITION. REPLACE WITH NEW IF NECESSARY. MATCH EXISTING
N4
APPLY CLOSED CELL SPRAY POLYURETHANE FOAM, 1” THICK TO THE
INSIDE FACE OF ALL THE CUPOLA'S COMPONENTS. APPLY TO ROOF
SUBSTRATE TO A MINIMUM OF 24" BEYOND THE CUPOLA'S OUTER EDGES
N5
EXISTING CLADDING, SIDING, ASSOCIATED TRIM, SUBSTRATE, VAPOR
BARRIER, ETC.: REMOVE AS NECESSARY TO ALLOW THE INSTALLATION OF
NEW FLASHING. REPLACE WITH NEW MOISTURE RESISTANT LUMBER AND
OTHER SUITABLE MATERIALS.
N6
EXISTING COATING AND SEALANT JOINTS: REMOVE ALL LOOSE COATING
AND JOINT SEALANTS. RE-FASTEN JOINTS AS NECESSARY. THE
CONTRACTOR MUST VERIFY FIELD THESE CONDITION. RE-COAT AND
RE-SEAL ALL CUPOLA, THE DESIGNER OF RECORD MUST PROVIDE
RECOMMENDATION AS TO THE TYPE OF MATERIAL BEST SUITED FOR THIS
APPLICATION
AutoCAD SHX Text NOTES: 1. THE CONTRACTOR MUST FIELD VERIFY ALL THE CONDITIONS SHOWN. THESE DETAILS THE CONTRACTOR MUST FIELD VERIFY ALL THE CONDITIONS SHOWN. THESE DETAILS AND RECOMMENDATIONS MUST NOT BE CONSIDERED THE FINAL DESIGN. IT IS THE CONTRACTORS RESPONSIBILITY TO REPRESENT THE SCOPE OF WORK IN SUFFICIENT DETAILS IN THE SHOP DRAWINGS, INCLUDING BUT NOT LIMITED TO ACTUAL DETAILS, MATERIALS SPECIFICATIONS, METHODS FOR REMOVAL AND REPLACEMENT WHILE MAINTAINING THE INTEGRITY OF THE BUILDING ENVELOPE, COLOR SELECTIONS FOR APPROVAL BY THE BEAP-REVIEW BOARD, ETC. 2. THESE BUILDINGS ARE REGISTERED HISTORICAL LANDMARKS. THE CONTRACTOR MUST THESE BUILDINGS ARE REGISTERED HISTORICAL LANDMARKS. THE CONTRACTOR MUST PRESENT THE PROPOSED SOLUTION(S) IN THE SHOP DRAWING SUBMITTAL OR WITH ANY OTHER METHOD SELECTED LEFT TO THE CONTRACTOR'S PREROGATIVE (FOR EXAMPLE: MOCK UPS, FIELD MEETINGS, ETC.) TO ENSURE THAT IT IS CONSISTENT WITH THE DESIGN INTENT OF THE MCBCL 3. ALL ENLARGED DETAILS SHOWN MAY HAVE SMALL VARIATIONS AMONG THE VARIOUS ALL ENLARGED DETAILS SHOWN MAY HAVE SMALL VARIATIONS AMONG THE VARIOUS CUPOLAS DESIGNS AND DETAILING. THESE DETAILS ARE NOT AN ACCURATE REPRESENTATION OF THE ACTUAL FIELD CONDITIONS. THE CONTRACTOR MUST BRING TO THE ATTENTION OF THE CM ANY DISCREPANCY FOUND IN THE FIELD. THE CONTRACTOR MUST PRESENT ALTERNATIVE DETAILING TO ACCOMMODATE THE EXISTING CONDITIONS.
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text ALL DIMENSIONS SHOWN ARE FROM EXISTING DRAWINGS AND HAVE NOT BEEN VERIFIED. FIELD CHECK
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text
AutoCAD SHX Text A107
AutoCAD SHX Text NOTES: 1. THE DESIGNER OF RECORD MUST FIELD VERIFY ALL THE CONDITIONS SHOWN. THESE DETAILS AND RECOMMENDATIONS MUST NOT BE CONSIDERED THE FINAL DESIGN. IT IS THE DESIGNER OF RECORD RESPONSIBILITY TO REPRESENT THE SCOPE OF WORK IN THE DESIGNER OF RECORD MUST FIELD VERIFY ALL THE CONDITIONS SHOWN. THESE DETAILS AND RECOMMENDATIONS MUST NOT BE CONSIDERED THE FINAL DESIGN. IT IS THE DESIGNER OF RECORD RESPONSIBILITY TO REPRESENT THE SCOPE OF WORK IN SUFFICIENT DETAILS IN THE DRAWINGS AND TO DESCRIBE IT IN SUFFICIENT DETAIL IN THE SPECIFICATIONS. THE SECTIONS AND DETAILS ARE GENERIC IN NATURE AND NOT THE FINAL CONFIGURATION. THE DESIGNER OF RECORD MUST PERFORM THE APPROPRIATE CALCULATIONS TO DETERMINE APPROPRIATE MATERIALS, LOADS, CODE COMPLIANCE REQUIREMENTS, ETC. 2. THE DESIGNER OF RECORD MUST PRESENT THE PROPOSED SOLUTION(S) DURING THE CDW TO ENSURE THAT IT IS CONSISTENT WITH THE DESIGN INTENT OF THE MCBCL THE DESIGNER OF RECORD MUST PRESENT THE PROPOSED SOLUTION(S) DURING THE CDW TO ENSURE THAT IT IS CONSISTENT WITH THE DESIGN INTENT OF THE MCBCL 3. THE DESIGNER OF RECORD MUST PERFORM THE APPROPRIATE CODE COMPLIANCE ANALYSIS BASED ON OCCUPANCY TO DETERMINE THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES, REQUIRED EXITS, ETC. ALL THE FLOOR PLAN LAYOUTS MUST BE THE DESIGNER OF RECORD MUST PERFORM THE APPROPRIATE CODE COMPLIANCE ANALYSIS BASED ON OCCUPANCY TO DETERMINE THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES, REQUIRED EXITS, ETC. ALL THE FLOOR PLAN LAYOUTS MUST BE APPROVED BY THE USER AT THE CDW. THIS APPLIES TO: THE SCOPE OF WORK (SOW) SHOWN WITHIN BLOCKED AREAS ON THE DRAWINGS DEVELOPED FLOOR PLAN LAYOUTS SHOWING FOR EXAMPLE: TOILET FIXTURES, FURNITURE, CABINETS, EXITS, ETC. ARE GENERIC IN NATURE AND NOT THE FINAL CONFIGURATION 4. NOTES SHOWN WITH TYPICAL (TYP) INDICATES CONDITIONS THAT OCCUR MULTIPLE TIMES NOTES SHOWN WITH TYPICAL (TYP) INDICATES CONDITIONS THAT OCCUR MULTIPLE TIMES 5. COMPLETE DEMOLITION OF INTERIOR CONDITIONS INCLUDES: WOOD OR METAL STUDS OR OTHER MATERIALS, GWB, PLASTER, FURRING FRAMING, FLOORING, BASE, CEILING, PLUMBING, HVAC, ELECTRICAL, SPRINKLER SYSTEMS, ETC. COMPLETE DEMOLITION OF INTERIOR CONDITIONS INCLUDES: WOOD OR METAL STUDS OR OTHER MATERIALS, GWB, PLASTER, FURRING FRAMING, FLOORING, BASE, CEILING, PLUMBING, HVAC, ELECTRICAL, SPRINKLER SYSTEMS, ETC. 6. THE BUILDINGS IN THIS PROJECT ARE HISTORICAL STRUCTURES. ALL EXTERIOR NEW EXTERIOR ITEMS MUST MATCH EXISTING DESIGN AESTHETICS. THE DESIGNER OF RECORD MUST SUBMIT DESIGN INTENT TO BE REVIEWED DURING THE CDW-PHASE THE BUILDINGS IN THIS PROJECT ARE HISTORICAL STRUCTURES. ALL EXTERIOR NEW EXTERIOR ITEMS MUST MATCH EXISTING DESIGN AESTHETICS. THE DESIGNER OF RECORD MUST SUBMIT DESIGN INTENT TO BE REVIEWED DURING THE CDW-PHASE 7. THE ASHRAE 90.1 -2016 REQUIREMENTS SHOWN IN SKEET A100 ARE APPLICABLE TO ALL THE BUILDINGS INCLUDED IN THIS PROJECTTHE ASHRAE 90.1 -2016 REQUIREMENTS SHOWN IN SKEET A100 ARE APPLICABLE TO ALL THE BUILDINGS INCLUDED IN THIS PROJECT
AutoCAD SHX Text
NTS
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110
AutoCAD SHX Text 3"'= 1'-0"
AutoCAD SHX Text A110