This notice solicits proposals for design-build construction services for Hurricane Florence Recovery MILCON Package 4 at Marine Corps Base Camp Lejeune in North Carolina. The package includes replacement of the Onslow Beach Bridge over the Intracoastal Waterway and replacement of the 2,500 linear foot White Oak River Trestle and 60 linear foot Queens Creek Trestle. Construction is to be completed within 1,826 calendar days of award. Proposals will be evaluated based on technical approach, corporate experience, past performance, safety, technical solution, project management, and small business utilization. Price will also be considered. The solicitation will be issued on October 7, 2019. The contract is valued between $100-250 million and will be awarded by July 20, 2020. The solicitation is unrestricted and open to all. The NAICS code is 237310 and small business size standard is $39.5 million.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared by:
3802 Cherry Ave.
Wilmington, NC 28403
Tel: (910) 763-3445
Fax: (910-763-3415
Pre Demolition Asbestos/Lead
Paint/Creosote/Mercury/PCB Survey
At: Onslow Beach Bridge
Jacksonville, NC
Prepared for: Kimley-Horn
11818 Rock Landing Dr. Suite 100
Newport News, VA 23608
PEI Project No.: 5269-20-0001-2AL
Date:
Inspector:
March 23, 2020
Jonathan Guetta
NC Asbestos Inspector Accreditation # 11936
NC Lead Inspector/Risk Assessor Certification # 120097
3802 Cherry Ave. Wilmington, NC 28403 Tel: 910-763-3445 Fax: 910-763-3415 www.precision-enviro.com
Kimley-Horn
Attn: Scott Borges, PE
Re: Limited Asbestos Bulk Sampling & Analysis at:
Onslow Beach Bridge
PEI Project No.: 5269-20-0001-2AL
On February 28, 2020 Jonathan Guetta (NC Asbestos Building Inspector Accreditation No. 11936) of Precision
Environmental, Inc. (Precision) conducted an asbestos inspection within and on the exterior of the above referenced structure.
The purpose of the survey was to verify the presence or absence of asbestos-containing materials (ACM) associated with the structure prior to demolition procedures.
Prior to sample collection, a visual inspection was conducted in order to determine homogeneous materials/areas and sample locations. Asbestos-containing materials are defined as materials that contain greater than 1% asbestos via
Polarized Light Microscopy (PLM). Homogeneous Areas (HGA) are determined by the material’s color and texture.
Asbestos-containing materials are defined by the following descriptions: surfacing material (SM), thermal system insulation (TSI) and miscellaneous materials (M). Both friable and non-friable materials were included in the inspection.
Friable materials are defined as those that can be pulverized by hand pressure.
Bulk sampling of suspect ACM was conducted in accordance with the sampling requirements promulgated by the United
States Environmental Protection Agency’s “Asbestos-Containing Materials in Schools Rule” (40 CFR 763, Subpart E), commonly referred to as the “Asbestos Hazard Emergency Response Act” or AHERA regulations. Specific compliance to these requirements include, but are not limited to, the type and number of samples to be collected. Sample locations were selected at random.
As a result, a total of twenty-two (22) bulk samples were collected from eleven (11) suspect asbestos-containing materials.
A listing of identified suspect ACM materials and the number of samples collected from each homogeneous area (HGA) is provided in Table 1 below:
Table 1: Identified Suspect Asbestos Materials
Suspect Material (HGA)
Description
Friable/Non-friable
Sample Location No. of Samples
Collected
1. 12 x 12 floor tile/mastic
Tan. Mottled M NF 1st floor 2
2. 12 x 12 floor tile/mastic
Off white with gray specks M NF Patch 1st floor 2
3. Base mastic M NF 1st floor 2
4. Exterior door caulk M NF Exterior door 2
5. Exterior window caulk M NF Exterior window 2
6. Foundation caulk M NF Control tower base perimeter 2
7. Parapet mastic M NF Parapet Control Tower lower roof 2
Onslow Beach Bridge Pre-Demolition Survey
Precision No. 5269-20-0001-2AL
March 23, 2020
Suspect Material (HGA)
Friable/Non-friable
Sample Location No. of Samples
Collected
8. Parapet sheet material M NF Parapet Control Tower lower roof 2
9. Built up roofing M NF Control Tower lower roof 2
10. Built up roofing M NF Generator room roof 2
11. Cement board (ceiling material) M NF Generator room 2
SM=Surfacing material/TSI=Thermal system insulation/M= Miscellaneous material/F=Friable/NF=Non-friable
Collected samples were given a unique identification number, which included the date, building acronym (OBB) and sample number, logged onto a chain of custody form and shipped to an accredited laboratory for analysis. All samples were analyzed by Polarized Light Microscopy (PLM) via EPA method 600/M4/82/020. Multi layered samples were separated prior to analysis and analyzed separately per EPA protocol. In an effort to reduce cost, Precision instructed the laboratory to STOP analysis at the first positive sample for each suspect material HGA and not to analyze the remaining samples from the same HGA. As a result, a total of twenty-four (24) samples were analyzed.
Results
Laboratory analysis of the bulk samples collected revealed that suspect materials 7 and 9 contain asbestos in quantities greater than 1% and are considered to be asbestos-containing materials.
The remaining suspect materials revealed no asbestos detected and may be treated as NON-ACM.
Listing of identified ACM and NON-ACM materials is provided in Table 2 below:
Table 2: Identified ACM and NON-ACM Materials
Material
Friable/
Non-friable
Location
Laboratory
Result
Approx.
Quantity
1. 12 x 12 floor tile/mastic
Tan. Mottled M NF 1st floor and 2nd floor None detected N/A
2. 12 x 12 floor tile/mastic
Off white with gray specks M NF 1st floor as a patch None detected N/A
3. Base mastic M NF Throughout None detected N/A
4. Exterior door caulk M NF Exterior doors None detected N/A
5. Exterior window caulk M NF Exterior windows None detected N/A
6. Foundation caulk M NF Throughout exterior None detected N/A
7. Parapet mastic M NF Parapet Control Tower lower roof
3.5% Chrysotile asbestos 16 SF
8. Parapet sheet material M NF Parapet Control Tower lower roof None detected N/A
9. Built up roofing M NF Control Tower lower roof
3% Chrysotile asbestos 180 SF
10. Built up roofing M NF Generator room roof None detected N/A
11. Cement board (ceiling material) M NF Generator room (ceiling)
None detected N/A
SF = Square Feet N/A = Not Applicable
Based on the sample analysis, the following materials should be considered to be Asbestos-Containing Materials:
• Parapet mastic located at the Control Tower lower roof
• Built up roofing located at the Control Tower lower roof
Onslow Beach Bridge Pre-Demolition Survey
Precision No. 5269-20-0001-2AL
March 23, 2020
A physical/visual inspection revealed the following:
• The walls and ceilings are non-suspect concrete.
• The HVAC ducts are uninsulated metal.
• No window glaze was noted on the window systems
• No suspect material (i.e. cement board panels (transite)) was noted within the electrical control boxes.
• The control tower upper roof is non-suspect metal with no sealant associated with the metal sheeting.
• No suspect materials were noted under the bridge associated with the swing mechanisms.
Asbestos-containing materials are regulated materials and must be handled accordingly. If the materials are to be disturbed/removed, the materials must be removed in accordance with all applicable Federal, State and Local regulations.
In addition, the materials must be disposed of as asbestos-containing waste and may not be disposed of as construction debris.
If additional materials not addressed during this inspection are to be disturbed, Precision strongly recommends that those materials either be assumed to be asbestos-containing, or that bulk samples be collected to determine the materials asbestos content prior to their disturbance.
All bulk samples analytical results as well sample locations are outlined in detail on the attached “BULK SAMPLE DATA
AND CHAIN OF CUSTODY” form and laboratory’s “BULK ASBESTOS ANALYSIS RESULTS” form.
Attached please find the following:
• Bulk Asbestos Analysis Sheet
• Bulk Sample Data and Chain of Custody Form
• Laboratory and Personnel Certificates
If you have any questions or require additional information, please do not hesitate to contact me at (910) 763-3445.
Sincerely, Precision Environmental, Inc.
NC Asbestos Inspector Accreditation #11936
Re: Lead Paint Bulk Sampling & Analysis at:
PEI Project No.:5269-20-0001-2AL
Precision Environmental Inc. (Precision) was retained by Kimley-Horn to conduct a lead paint survey and analysis of coated surfaces associated with the above referenced structure. The inspection included all materials scheduled to be disturbed/removed during the upcoming demolition procedures.
The purpose of the survey was to determine if lead painted components exist on painted components prior to upcoming demolition procedures.
The bulk sampling was performed by Precision’s representative, Jonathan Guetta (NC Risk Assessor/ Lead Inspector
Certificate No. 120097) on February 28, 2020.
OSHA defines any detectable level of lead in paint a concern when renovations/demolition will impact lead coated surfaces.
As a result, a total of seventeen (17) different suspect lead based paint (LBP) coatings were identified. A listing of the identified LBP coatings and the number of bulk samples collected per suspect material is provided in Table 1 below:
Table 1: Identified suspect LBP coatings materials
Suspect Material Location No. of Samples
Collected
1. Cream painted concrete interior wall 1st floor control room 2
2. Cream painted concrete ceiling Control room 2
3. Cream painted metal interior door system Control room 2
4. Cream painted metal HVAC duct Control room 2
5. Gray painted metal spiral stair system Control room 2
6. Gray painted concrete interior wall 2nd floor control room 2
7. White painted concrete exterior wall Control room 2
8. Red painted metal exterior door system 2nd floor 2
9. White painted concrete overhang Front roof 2
10. White painter cinderblock exterior wall Generator room 2
11. White painted wood exterior soffit/fascia Generator room 2
12. White painted metal exterior door system Generator room 2
13. Gray painted metal bridge railing/guard rail Bridge 2
Lead Paint Survey Results
Precision No.5269-20-0001-2AL
No. of Samples
Collected
14. Gray painted metal swing bridge railing/guard rail Bridge 2
15. Gray painted metal swing bridge stringer Bridge 2
16. Gray painted metal horizontal I-beam Bridge under roadway 2
17. Black painted metal vertical I-beam Pylons within waterway 2
Collected samples were given a unique identification number, which included the date, structure acronym (OBB), element abbreviation (Pb) and sample number, logged onto a lead paint chip chain of custody form and shipped to an accredited laboratory for analysis. The bulk samples collected from the above listed materials (Table 1) were analyzed by Flame
Atomic Absorption (AA) via EPA SW-846 7420 and 3050B Method.
Analysis of the samples revealed that multiple suspect coatings contain lead in concentrations above the Detection Limit.
Laboratory results obtained are provided in detail in the attached laboratory report and summarized in the Table 2 below:
Table 2: Summary of Laboratory Results
Highest Lead
Concentration % by weight
Detection Limit
% by weight
1. Cream painted concrete interior wall 1st floor control room 0.4818 0.0006
2. Cream painted concrete ceiling Control room 0.0055 0.0006
3. Cream painted metal interior door system Control room 0.6780 0.0009
4. Cream painted metal HVAC duct Throughout 0.0187 0.0014
5. Gray painted metal spiral stair system Control room spiral staircase 6.1110 0.0011
6. Gray painted concrete interior wall 2nd floor control room 0.5565 0.0007
7. White painted concrete exterior wall Throughout 0.5565 0.0007
8. Red painted metal exterior door system 2nd floor exterior door Below detection limit 0.0025
9. White painted concrete overhang Exterior front overhang 0.0293 0.0011
10. White painted cinderblock exterior wall Generator room 0.0039 0.0015
11. White painted wood exterior soffit/fascia Generator room 0.0022 0.0007
12. White painted metal exterior door system Generator room
Below detection limit 0.0018
13. Gray painted metal bridge railing/guard rail Throughout 0.0269 0.0013
14. Gray painted metal swing bridge railing/guard rail Throughout
Below detection limit 0.0022
15. Gray painted metal swing bridge stringer Throughout 0.0024 0.0006
16. Gray painted metal horizontal I-beam Throughout 0.0019 0.0006
17. Black painted metal vertical I-beam Throughout 0.0021 0.0007
Lead Paint Survey Results
Precision No.5269-20-0001-2AL
Based on the laboratory analysis, the following components associated with the structure are confirmed to be coated with lead containing paint and shall be handled in accordance will all applicable regulations:
• All cream painted concrete interior walls
• All cream painted concrete ceilings
• All cream painted interior door systems
• All cream painted metal HVAC ducts
• The gray painted metal spiral stair system
• All gray painted concrete interior walls
• All white painted concrete exterior walls
• The white painted concrete overhang
• All white painted cinderblock exterior walls
• All white painted wood exterior soffit/fascia
• All gray painted metal bridge guards/railings
• All gray painted metal swing bridge stringers
• All gray painted metal horizontal I-beams under the bridge roadway
• All black painted metal vertical I-beams within the waterway associated with the wood pedestrian walkway
Note: All the painted surfaces sampled are in deteriorated condition
A visual assessment revealed the following:
• The interior walls of the generator room are unpainted cinderblock
• The ceiling of the generator room is unpainted structural wood
• The floor of the generator room is unpainted concrete
• Window systems throughout the control room are unpainted vinyl window systems
Recommendations/Control Options
If renovation or demolition activities are to impact lead coated surfaces, all work should be conducted by workers trained in “lead safe work practices” as outlined by the Occupational Safety and Health Administration (OSHA). In addition, all lead coated components or paint removed from lead coated components should be disposed of in accordance with all
Federal, State, and Local regulations.
If additional materials not addressed during this inspection are to be disturbed, Precision strongly recommends that those materials either be assumed to be coated with lead based paint or that sampling is conducted to confirm the presence of absence of lead based paint prior to the disturbance of the materials.
If you have any questions or require additional information, please do not hesitate to contact me at (910) 763-3445
PRECISION ENVIRONMENTAL INC.
NC Lead Inspector/Risk Assessor #: 120097
Attachments: Paint Chip Sample Data and Chain of Custody
Laboratory Data Sheets
Laboratory and Inspector Certificates
Certificate of Analysis: Lead In Paint by EPA SW-846 7420 and 3050B*
Client Project :
557280
03/04/2020
03/04/2020
Date Reported :
Date Analyzed :
Date Received :
AAT Project :
Phone :
Email :
Fax :
jguetta@precision-enviro.com
910-763-3445
J. Guetta
Precision Environmental
Attn :
Client :
ONSLOW BEACH BRIDGE NCProject Location :
5269-20-0001-2AL
Wilmington, NC 28403
3802 Cherry Ave.
3/5/2020 7:22:54AM
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
Sampling Date : 02/28/2020
Lab Sample ID Result Lead
(% by weight) PPMSample DescriptionClient Code
Calculated R L
(% by weight)
22820-OBB-PB-01 1ST FL INT WALL CTRL RM CREAM5368792 4818 0.4818 0.0006
22820-OBB-PB-02 1ST FL INT WALL CTRL RM CREAM5368793 113 0.0113 0.0005
22820-OBB-PB-03 CEILING CTRL RM CREAM5368794 40 0.0040 0.0005
22820-OBB-PB-04 CEILING CTRL RM CREAM5368795 55 0.0055 0.0006
22820-OBB-PB-05 INT DOOR STM CTRL RM CREAM5368796 6780 0.6780 0.0009
22820-OBB-PB-06 INT DOOR DTM CTRL RM CREAM5368797 182 0.0182 0.0008
22820-OBB-PB-07 HVAC DUCT CTRL RM CREAM5368798 187 0.0187 0.0014
22820-OBB-PB-08 HVAC DUCT CTRL RM CREAM5368799 69 0.0069 0.0014
22820-OBB-PB-09 SPIRAL STR STM CTRL RM GRAY5368800 6640 0.6640 0.0006
22820-OBB-PB-10 SPIRAL STR STM CTRL RM GRAY5368801 61110 6.1110 0.0011
22820-OBB-PB-11 2ND FL INT WALL CTRL RM GRAY5368802 5565 0.5565 0.0007
22820-OBB-PB-12 2ND FL INT WALL CTRL RM GRAY5368803 3959 0.3959 0.0010
22820-OBB-PB-13 EXT WALL CTRL RM WHITE5368804 205 0.0205 0.0011
22820-OBB-PB-14 EXT WALL CTRL RM WHITE5368805 35 0.0035 0.0009
22820-OBB-PB-15 2ND FL EXT DOOR STM RED5368806 <15 <0.0015 0.0015
22820-OBB-PB-16 2ND FL EXT DOOR STM RED5368807 <25 <0.0025 0.0025
22820-OBB-PB-17 FRONT OVERHANG ROOF WHITE5368808 145 0.0145 0.0013
22820-OBB-PB-18 FRONT OVERHANG ROOF WHITE5368809 293 0.0293 0.0011
22820-OBB-PB-19 EXT WALL GEN RM WHITE5368810 21 0.0021 0.0012
22820-OBB-PB-20 EXT WALL GEN RM WHITE5368811 39 0.0039 0.0015
22820-OBB-PB-21 EXT SOFFIT FACIA GEN RM WHITE5368812 18 0.0018 0.0010
557280 AAT Project:Date Printed: 03/05/2020 7:22AM
RL= Reporting Limit * For true values assume (2) significant figures. The method and batch QC is acceptable unless otherwise stated. Current
EPA/HUD Interim Standard for lead in paint samples is: 5000 PPM (parts per million) or ug/g which is equivalent to 0.5% by weight. AAT internal sop
S203. The laboratory operates in accord with ISO 17025 guidelines and holds limited scopes of accreditation under AIHA-LAP and NY State DOH
ELAP programs. These results are submitted pursuant to AAT LLC current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions.Analytical results relate to the samples as received by the lab. AAT will not assume any liability or responsibility for the manner in which the results are used or interpreted. Reproduction of this document other than in its entirety is not permitted. All Quality control requirements for the samples this report contains have been met. AAT does not blank correct reported values. Sample data apply only to items analyzed. Samples are stored for 15 days following report date. *= Validated modified method
AIHA LAP- Lab ID #100986, NY State DOH ELAP -Lab ID #11864, State of Ohio- Lab ID # 10042
Lab Sample ID Result Lead
(% by weight) PPMSample DescriptionClient Code
Calculated R L
(% by weight)
22820-OBB-PB-22 EXT SOFFIT FACIA GEN RM WHITE5368813 22 0.0022 0.0007
22820-OBB-PB-23 EXT DOOR STM GEN RM WHITE5368814 <18 <0.0018 0.0018
22820-OBB-PB-24 EXT DOOR STM GEN RM WHITE5368815 <11 <0.0011 0.0011
22820-OBB-PB-25 BRIDGE RAILING GUARD RAIL GRAY5368816 235 0.0235 0.0014
22820-OBB-PB-26 BRIDGE RAILING GUARD RAIL GRAY5368817 269 0.0269 0.0013
22820-OBB-PB-27 SWING BRIDGE RLG GUARD RL GRAY5368818 14 0.0014 0.0011
22820-OBB-PB-28 SWING BRIDGE RLG GUARD RL GRAY5368819 <22 <0.0022 0.0022
22820-OBB-PB-29 SWING BRIDGE STRINGER GRAY5368820 24 0.0024 0.0006
22820-OBB-PB-30 SWING BRIDGE STRINGER GRAY5368821 27 0.0027 0.0006
22820-OBB-PB-31 HZTL I BEAM UNDR RDWAY GRAY5368822 13 0.0013 0.0007
22820-OBB-PB-32 HZTL I BEAM UNDR RDWAY GRAY5368823 19 0.0019 0.0006
22820-OBB-PB-33 VTL I BEAM PLNS IN WTRWAY BLACK5368824 18 0.0018 0.0005
22820-OBB-PB-34 VTL I BEAM PLNS IN WTRWAY BLACK5368825 21 0.0021 0.0007
Analyst Signature
Elyse Bidle
557280 AAT Project:Date Printed: 03/05/2020 7:22AM
RL= Reporting Limit * For true values assume (2) significant figures. The method and batch QC is acceptable unless otherwise stated. Current
EPA/HUD Interim Standard for lead in paint samples is: 5000 PPM (parts per million) or ug/g which is equivalent to 0.5% by weight. AAT internal sop
S203. The laboratory operates in accord with ISO 17025 guidelines and holds limited scopes of accreditation under AIHA-LAP and NY State DOH
ELAP programs. These results are submitted pursuant to AAT LLC current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions.Analytical results relate to the samples as received by the lab. AAT will not assume any liability or responsibility for the manner in which the results are used or interpreted. Reproduction of this document other than in its entirety is not permitted. All Quality control requirements for the samples this report contains have been met. AAT does not blank correct reported values. Sample data apply only to items analyzed. Samples are stored for 15 days following report date. *= Validated modified method
Precision EnvironmentalTo :
Attn :
Phone :
AAT Project :
Client Project :
Date Reported :
Project Location :
Email :J. Guetta
910-763-3445 jguetta@precision-enviro.com
557280
3/5/2020 7:22:54AM
5269-20-0001-2AL
ONSLOW BEACH BRIDGE NC
3802 Cherry Ave.
Wilmington, NC 28403
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
Sample CompletedAnalysis RequestedClient Code Analyst
5368792 03/04/2020Lead Paint22820-OBB-PB-01 Elyse Bidle
5368793 03/04/2020Lead Paint22820-OBB-PB-02 Elyse Bidle
5368794 03/04/2020Lead Paint22820-OBB-PB-03 Elyse Bidle
5368795 03/04/2020Lead Paint22820-OBB-PB-04 Elyse Bidle
5368796 03/04/2020Lead Paint22820-OBB-PB-05 Elyse Bidle
5368797 03/04/2020Lead Paint22820-OBB-PB-06 Elyse Bidle
5368798 03/04/2020Lead Paint22820-OBB-PB-07 Elyse Bidle
5368799 03/04/2020Lead Paint22820-OBB-PB-08 Elyse Bidle
5368800 03/04/2020Lead Paint22820-OBB-PB-09 Elyse Bidle
5368801 03/04/2020Lead Paint22820-OBB-PB-10 Elyse Bidle
5368802 03/04/2020Lead Paint22820-OBB-PB-11 Elyse Bidle
5368803 03/04/2020Lead Paint22820-OBB-PB-12 Elyse Bidle
5368804 03/04/2020Lead Paint22820-OBB-PB-13 Elyse Bidle
5368805 03/04/2020Lead Paint22820-OBB-PB-14 Elyse Bidle
5368806 03/04/2020Lead Paint22820-OBB-PB-15 Elyse Bidle
5368807 03/04/2020Lead Paint22820-OBB-PB-16 Elyse Bidle
5368808 03/04/2020Lead Paint22820-OBB-PB-17 Elyse Bidle
5368809 03/04/2020Lead Paint22820-OBB-PB-18 Elyse Bidle
5368810 03/04/2020Lead Paint22820-OBB-PB-19 Elyse Bidle
5368811 03/04/2020Lead Paint22820-OBB-PB-20 Elyse Bidle
5368812 03/04/2020Lead Paint22820-OBB-PB-21 Elyse Bidle
5368813 03/04/2020Lead Paint22820-OBB-PB-22 Elyse Bidle
5368814 03/04/2020Lead Paint22820-OBB-PB-23 Elyse Bidle
5368815 03/04/2020Lead Paint22820-OBB-PB-24 Elyse Bidle
5368816 03/04/2020Lead Paint22820-OBB-PB-25 Elyse Bidle
5368817 03/04/2020Lead Paint22820-OBB-PB-26 Elyse Bidle
5368818 03/04/2020Lead Paint22820-OBB-PB-27 Elyse Bidle
557280 AAT Project:Date Printed: 03/05/2020 7:22AM
This report is intended for use solely by the individual or entity to which it is addressed. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify AAT immediately. Thank you.
Sample CompletedAnalysis RequestedClient Code Analyst
5368819 03/04/2020Lead Paint22820-OBB-PB-28 Elyse Bidle
5368820 03/04/2020Lead Paint22820-OBB-PB-29 Elyse Bidle
5368821 03/04/2020Lead Paint22820-OBB-PB-30 Elyse Bidle
5368822 03/04/2020Lead Paint22820-OBB-PB-31 Elyse Bidle
5368823 03/04/2020Lead Paint22820-OBB-PB-32 Elyse Bidle
5368824 03/04/2020Lead Paint22820-OBB-PB-33 Elyse Bidle
5368825 03/04/2020Lead Paint22820-OBB-PB-34 Elyse Bidle
Quality Assurance Coordinator - Stephen NorthcottReviewed By
557280 AAT Project:Date Printed: 03/05/2020 7:22AM
This report is intended for use solely by the individual or entity to which it is addressed. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify AAT immediately. Thank you.
Re: Creosote Bulk Sampling & Analysis at:
Precision Environmental Inc. (Precision) was retained by Kimley-Horn to conduct a creosote survey and analysis of wood components associated with the above referenced structure. The inspection included all materials scheduled to be disturbed/removed during the upcoming demolition procedures.
The purpose of the survey was to determine if wood components associated with the structure are treated with creosote prior to upcoming demolition procedures.
The bulk sampling was performed by Precision’s representative Jonathan on February 28, 2020.
As a result, a total of two creosote treated components were identified. A listing of the identified components and the number of bulk samples collected per suspect material is provided in Table 1 below:
Table 1: Identified suspect LBP coatings materials
No. of Samples
Collected
1. Wood platform (walkways) Under swing bridge 2
2. Horizontal bumpers Within waterway 2
Collected samples were given a unique identification number, which included the date, structure acronym (OBB), and sample number, logged onto a creosote bulk chain of custody form and shipped to an accredited laboratory for analysis.
The bulk samples collected from the above listed materials (Table 1) were analyzed for creosote in bulk material via EPA
Method 8015D
Analysis of the samples revealed that none of the samples contained detectable levels of creosote.
Laboratory results obtained are provided in detail in the attached laboratory report and summarized in the Table 2 below:
Table 2: Summary of Laboratory Results
Highest
Concentration mg/Kg
Detection Limit
Mg/Kg
1. Wood platform (walkways) Under swing bridge None detected
83 mg/kg and 93 mg/kg
2. Horizontal bumpers Within waterway None detected
91 mg/Kg and 90 mg/kg
Creosote Survey Results
Precision No.5269-20-0001-2AL
All efforts were made to identify and access all components associated with the structure that are treated with creosote. If additional materials not addressed during this inspection are to be disturbed, Precision strongly recommends that those materials either be assumed to be treated with creosote or that sampling is conducted to confirm the presence of absence of creosote prior to the disturbance of the materials.
If you have any questions or require additional information, please do not hesitate to contact me at (910) 763-3445
Attachments: Creosote Sample Data and Chain of Custody
Laboratory Data Sheets
Wood platform
(Walkway)
Wood platform
(Walkway)
Horizontal bumpers within waterway
Phillip Worby, Environmental Chemistry Laboratory Director
Approved By:
Fax: (910) 763-3415 Phone: (910) 763-3445
The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 3/3/2020. The results are tabulated on the attached data pages for the following client designated project:
Pre Demo Survey for Onslow Beach Bridge
The reference number for these samples is EMSL Order #012002408. Please use this reference when calling about these samples. If you have any questions, please do not hesitate to contact me at (856) 303-2500.
3/11/2020Attn: Jonathan Guetta Precision Environmental Inc.
3802 Cherry Ave.
Wilmington, NC 28403
The test results contained within this report meet the requirements of NELAP and/or the specific certification program that is applicable, unless otherwise noted.
NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, CA ELAP 1877
The samples associated with this report were received in good condition unless otherwise noted. This report relates only to those items tested as received by the laboratory. The QC data associated with the sample results meet the recovery and precision requirements established by the NELAP, unless specifically indicated. All results for soil samples are reported on a dry weight basis, unless otherwise noted. This report may not be reproduced except in full and without written approval by EMSL Analytical, Inc.
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone: (856) 303-2500 Fax: (856) 858-4571 Email: EnvChemistry2@emsl.com
EMSL Analytical does not hold SHW certification in the state of North Carolina.
mailto:EnvChemistry2@emsl.com
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 858-4571 http://www.EMSL.com EnvChemistry2@emsl.com
012002408 CustomerID: PREN34 CustomerPO:
ProjectID:
EMSL Order:
Analytical Results
Attn: Jonathan Guetta Precision Environmental Inc.
3802 Cherry Ave.
Wilmington, NC 28403
Received: 03/03/20 9:40 AM
Pre Demo Survey for Onslow Beach Bridge
Fax: (910) 763-3415 Phone: (910) 763-3445
Project:
Client Sample Description Lab ID:022820-OBB-01 012002408-0001 Wood platform under swing bridge
Collected: 2/28/2020
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
GC-SVOA
8015D Modified Creosote ACND mg/Kg 03/10/20 0:0083 3/5/2020 AF
Client Sample Description Lab ID:022820-OBB-02 012002408-0002 Wood platform under swing bridge
Collected: 2/28/2020
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
GC-SVOA
8015D Modified Creosote ACND mg/Kg 03/10/20 0:0093 3/5/2020 AF
Client Sample Description Lab ID:022820-OBB-03 012002408-0003 Horizontal bumpers. In waterway
Collected: 2/28/2020
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
GC-SVOA
8015D Modified Creosote ACND mg/Kg 03/10/20 0:0091 3/5/2020 AF
Client Sample Description Lab ID:022820-OBB-04 012002408-0004 Horizontal bumpers. In waterway
Collected: 2/28/2020
Method Parameter Result Units Analysis
Date & AnalystRL Prep
Date & Analyst
GC-SVOA
8015D Modified Creosote ACND mg/Kg 03/10/20 0:0090 3/5/2020 AF
MDL - method detection limit J - Result was below the reporting limit, but at or above the MDL ND - indicates that the analyte was not detected at the reporting limit RL - Reporting Limit (Analytical) D - Dilution Sample required a dilution which was used to calculate final results
Definitions:
Page 2 of 2ChemSmplw/RDL/NELAC-7.52.0 Printed: 3/11/2020 4:46:16 PM http://www.EMSL.com mailto:EnvChemistry2@emsl.com
OrderID: 012002408
Re: Mercury and Polychlorinated
Biphenyls - Visual assessment at:
Onslow Beach Bridge
Precision Environmental Inc. (Precision) was retained by Kimley-Horn to conduct a visual assessment for Mercury and
Polychlorinated Biphenyls (PCBs) at the above referenced structure.
The purpose of the survey was to determine if components associated with the structure contain or have the potential to contain Mercury or PCBs prior to demolition procedures.
Mercury
The following components have the potential to contain Mercury and must be handled and disposed of in accordance with all Federal, State and Local regulations:
• Fluorescent light tubes within and on the exterior of the control tower and associated generator room (Assumed to contain mercury vapors)
Generator room Control room exterior
Mercury/PCBs
Precision No.5269-20-0001-2AL
Control room interior
The thermostat associated with the control room is digital and is not likely to contain Mercury.
In accordance with EPA regulations, Mercury containing components must be disposed of in accordance with
EPA regulations.
Precision No.5269-20-0001-2AL
Polychlorinated Biphenyls
Concern over the toxicity and persistence in the environment of Polychlorinated Biphenyls (PCBs) led
Congress in 1976 to enact §6(e) of the Toxic Substances Control Act (TSCA) that included among other things, prohibitions on the manufacture, processing, and distribution in commerce of PCBs. Actual cessation of production occurred in 1977. Based on this information, structures constructed after 1977 can be assumed to be free of PCB’s.
The following components have the potential to contain PCB’s and must be handled and disposed of in accordance with all Federal, State and Local regulations:
• Light ballasts within fluorescent light tubes (see photos above).
In accordance with EPA regulations, components containing PCBs must be disposed of as hazardous waste.
Other potentially hazardous wastes
The following components were observed which may contain potentially hazardous wastes and should be addressed prior to demolition procedures:
• Freon associated with the control tower HVAC compressor
• Fuels and oils associated with the generator within the generator room
• Hydraulic fluids associated with the swing bridge located under the roadway
HVAC compressor (Freon)
Precision No.5269-20-0001-2AL
Generator (Fuels and Oils)
Hydraulic fluid associated with the swing bridge mechanism (located under the roadway)
All efforts were made to identify and access all components associated with the structure that may contain Mercury or
PCBs. If additional materials not addressed during this inspection are to be disturbed, Precision strongly recommends that those materials either be assumed to contain Mercury or PCB’s.
If you have any questions or require additional information, please do not hesitate to contact me at (910) 763-3445
A
IH
A
L ab o ra to ry
A cc re d it at io n
P ro g ra m s, L L
C a ck n o w le d g es t h t cc u ra te A n a ly ti ca l
T es ti n g L
B ev er ly R o ad
R o m u lu s M
I ab o ra to ry
I D al o n g w it h a ll p re m is es f ro m w h ic h k e y a ct iv it ie s ar e p er fo rm ed as l is te d a b o v e, h as f u lf il le d t h e re q u ir e m en ts o f th e
A
IH
A L ab o ra to ry A cc re d it at io n
P ro g ra m s
(A
IH
A -L
A P
L
L C a cc re d it at io n t o t h e
IS
O
/I E
C
:2 i n te rn at io n al s ta n d ar d
G en er a l R eq u ir em en ts f o r th e C o m p et en ce o f
T es ti n g a d li b ra ti o n
L a b o ra to ri es i n t h e fo ll o w in g
B O
R A
T O
R Y
A C
C R
E D
IT
A
T
IO
N P
R O
G R
A M
S
IN
D
U S
T R
IA
L
H Y
G
IE
N E re d it at io n E x p ir es
V
IR
O N
M E
N T
A L
L E re d it at io n E x p ir es
A u g u st
V
IR
O N
M E
N T
A L
M
IC
R O
B
IO
L O
G Y re d it at io n E x p ir
F O
O re d it at io n E x p ir
U
IQ
U
E S
C O
P re d it at io n E x p ir p ec if ic F ie ld
(s o f
T es ti n g
F o
T
M et h o d (s w it h in e ac h A cc re d it at io n P ro g ra m f o r w h ic h t h e ab o v e n a m ed l ab o ra to ry m ai n ta in s ac cr ed it at io n i s o u tl in ed o n t h e at ta ch ed
S co p e o f A cc re d it a ti o n
C o n ti n u ed a cc re d it at io n i s co n ti n g en t u p o n s u cc e ss fu l o n -g o in g c o m p li a n ce w it h I
S O
/I E
C
:2 an d
A
IH
A -L
A P
L
L C r eq u ir e m en ts
T h is c er ti fi ca te i s n o t v al id w it h o u t th e at ta ch ed
S c o p e o f
A cc re d it a ti o n
P le as e re v ie w t h e
A
IH
A -L
A P
L w eb si te w w w
.a ih aa cc re d it ed la b s.
o rg fo r th e m o st c u rr en t
S co p e.
li za b et h
B ir h a ir p er so n
A n a ly ti ca l
A cc re d it a ti o n B o rd h er yl
O
M o rt o
M n a g in g D ir ec to r, A
IH
A L a b o ra to ry
A cc re d it a ti o n P ro g ra m s, L
R ev is io n
/1
/2 at e Is su ed
/3
/2 http://www.aihaaccreditedlabs.org/
Effective: 10/14/2016
Scope_ELLAP_R7
AIHA Laboratory Accreditation Programs, LLC
SCOPE OF ACCREDITATION
Accurate Analytical Testing, LLC Laboratory ID: 100986
30105 Beverly Road, Romulus, MI 48174 Issue Date: 08/30/2019
The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory’s current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.
The EPA recognizes the AIHA-LAP, LLC ELLAP program as meeting the requirements of the National Lead Laboratory
Accreditation Program (NLLAP) established under Title X of the Residential Lead-Based Paint Hazard Reduction Act of 1992 and includes paint, soil and dust wipe analysis. Air and composited wipes analyses are not included as part of the NLLAP.
Environmental Lead Laboratory Accreditation Program (ELLAP)
Initial Accreditation Date: 02/01/2004
A complete listing of currently accredited Environmental Lead laboratories is available on the AIHA-LAP, LLC website at:
http://www.aihaaccreditedlabs.org
Field of Testing (FoT) Technology sub-type/
Detector Method
Method Description (for internal methods only)
Paint
EPA SW-846 3050B (Mod)
EPA SW-846 7000
EPA SW-846 7420
Soil
EPA SW-846 3050B (Mod)
EPA SW-846 7000
EPA SW-846 7420
Settled Dust by Wipe
EPA SW-846 7000
NIOSH 7082
Airborne Dust
EPA SW-846 7000
NIOSH 7082
| accurate analytical lead 2021.pdf |
| 100986_AccredAABApproval_2019_08_30 |
| 100986_Certificate_2019_08_30 |
| 100986_Scope_ELLAP_2019_08_30 |