This solicitation package describes a federal construction contract opportunity for repair of MacDonough Hall at the United States Naval Academy in Annapolis, Maryland. The project involves replacing the training pool and treatment system, upgrading HVAC, electrical, and fire suppression systems, abating asbestos and lead paint, and performing structural, architectural, and envelope repairs. The estimated construction period is 1,090 calendar days. The Naval Facilities Engineering Systems Command Washington will utilize a two-phase source selection process, first prequalifying offerors based on corporate experience, safety, small business participation, and past performance, then evaluating final phase proposals on all factors. Final phase participants will receive full plans and specifications by amendment. Prequalification phase proposals are due May 28, 2021. Pricing should remain valid for 90 days and work must be completed within 1,097 calendar days of award. The primary point of contact is Tonja Jenkins and the solicitation number is N4008021R0033.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRJ_NAVFAC:29314.06:07:01 F-1 Stanley Consultants
Appendix F
Hazmat Inspection Report
Repair Macdonough Hall Building 102
United States Naval Academy Annapolis, Maryland
GER 130-6577
Prepared for
Stanley Consultants 6836 Austin Center Boulevard
Austin, Texas 78731
Prepared by H. Nelson Adcock, Jr., P.E.
Maryland Asbestos Inspector # 129703
REPORT OF
HAZARDOUS MATERIALS
CONSULTING SERVICES
Southern Professional Center 1 2712 Southern Boulevard, Suite 101 Virginia Beach, Virginia 23452
(757) 463-3200 Fax (757) 463-3080 E-mail germail@geronline.com
January 23, 2015
Stanley Consultants 6836 Austin Center Boulevard Austin, Texas 78731
Attention: Mr. Scott Hartford, P.E.
Subject: Hazardous Materials Consulting Services Repair Macdonough Hall Building 102 United States Naval Academy Annapolis, MD
GER 130-6577
GeoEnvironmental Resources, Inc. has completed our hazardous materials sampling of the subject facility. This work was completed in accordance with the scope of work and fee outlined in our proposal P14-130-6058 dated 5 September 2014. This report is relevant to the date of our field work and should not be relied upon for later dates.
We appreciate the opportunity of completing this work for Stanley Consultants. If there are any questions concerning this report, please contact us.
Sincerely, GeoEnvironmental Resources, Inc.
Brian T. Hyde H. Nelson Adcock Hazardous Materials Project Manager President
Attachments: (1) Hazardous Materials Report
(2) Sample Tables and Analytical Reports
(3) Sample Location Maps
(4) Photographs
(5) Licenses
Southern Professional Center I 2712 Southern Boulevard, Suite 101 Virginia Beach, Virginia 23452
(757) 463-3200 Fax (757) 463-3080 E-mail germail@geronline.com
TABLE OF CONTENTS
Section 2 Sample Tables & Analytical Reports
Section 1 Report
Section 3 Sample Location Maps
Section 4 Photograps
Section 5 Licenses
ACRONYMS
AAS Atomic absorption spectroscopy ACBM Asbestos-containing building materials ACM Asbestos-containing materials ACT Acoustical ceiling tile ADA Americans with Disability Act AHERA Asbestos Hazard Emergency Response Act ASHARA Asbestos Schools Hazard Abatement Reauthorization Act ASTM American Society of Testing and Materials CMU Cement masonry unit CFC Chlorofluoro carbons CHMM Certified Hazardous Materials Manager CFR Code of Federal Regulation CSP Certified Safety Professional DEHP Di (2-ethylhexyl) phthalate DRO Diesel Range Organics ECD Electron capture detectors EA Each EPA U.S. Environmental Protection Agency GC Gas chromatography GRO Gasoline Range Organics GWB Gypsum wall board HBM Hazardous building material HID High intensity discharge HM Homogeneous material HUD U.S. Housing and Urban Development LBP Lead-based paint LF Linear feet LS Lump sum MDL Minimum detection limit mg/cm2 Milligrams per square centimeter mg/kg Milligrams per kilogram mg/L Milligrams per Liter ND none detected NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PCB Polychlorinated biphenyl PLM Polarized light microscopy ppm Parts per million RCRA Resource Conservation and Recovery Act SAP Sample and Analysis Plan SF Square Feet TCLP Toxicity characteristic leaching procedure TPH Total Petroleum Hydrocarbons TSI Thermal System Insulation VAC Virginia Administration Code VOC Volatile Organic Compound XRF X-Ray Fluorescence
PROJECT UNDERSTANDING
According to the Statement of Architect-Engineer Services (SAES) dated 26 August 2014 provided by Stanley consultants with Attachment 6 only, the project is described as follows:
The AE shall provide Design and Engineering Services in accordance with Reference (a) Basic IQ Contract SAES, Reference (b) DD1391, and all supplementary and/or revised requirements contained in this T.O. SAES, to provide repair of MacDonough Hall.
The general details in the SAES describe the various repairs broken down in the following categories: MacDonough Pool, ATFP, Historic Preservation, Structural, Architectural, Life Safety, Mechanical, and Electrical.
Based on our review of the SAES it appears the repairs will be extensive and involve the entire building. The specific repair scope has not yet been finalized.
The proposed project will prepare a Design-Bid-Build (DBB) construction package consisting of full plans, specifications, detailed cost estimate and other services as requested by this T.O.
BUILDING DESCRIPTION
According to the Facility Assessment and Site Investigation Report prepared by Clark Nexsen in 2014, “MacDonough Hall was originally built to serve as a dry dock facility for the US Naval Academy. The building was extensively renovated in 1982 to provide athletic facilities. The building today encompasses 128, 000 square feet over six floors as shown on the building plans.
The first floor has the largest area and encompasses approximately 49,000 square feet.
The building actually consists of three floors of athletic facilities with the fourth, fifth and sixth “floors” serving as mezzanine and top of stairway spaces. Large mechanical rooms are located on the east and west ends of the fifth floor in the building.
The building is constructed of noncombustible materials such as steel structural members, masonry exterior walls, and concrete floors.
Exposed structural steel members are not provided with fire resistant coatings.
SAMPLING METHODOLOGIES
SUSPECT ASBESTOS-CONTAINING MATERIALS
(ACM)
The AHERA regulation, 40 Code of Federal Regulations (CFR) 763, is the primary governing regulation when performing asbestos surveys. This regulation was originally enacted for school buildings, but has since been applied to public and commercial buildings by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA) in 1994 and by the Occupational Safety and Health Administration’s (OSHA) worker protection regulations in 1995, specifically 29 CFR 1926.1101(k). The demolition of structures is also subject to 40 CFR Part 61 “National Emission Standards for Hazardous Air Pollutants” (NESHAPs).
ACM is specifically addressed in 40 CFR 61 Subpart M “National Emission Standard for Asbestos.”
ACM is generally divided into three primary classifications as follows: (a) Surfacing material, (b) Thermal System Insulation, and (c) Miscellaneous material. These classifications are defined in 40 CFR 763.83 as provided below.
Miscellaneous material means interior building on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Surfacing material means material in a school building that is sprayed-on, troweled-on, or
GER
Report of Hazardous Materials Study Repair Macdonough Hall
Building 102 United States Naval Academy
Annapolis, Maryland
GER 130-6577
otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
The sampling methodologies employed to address the ACM categories described above are as follows:
Surfacing material – An accredited inspector shall collect, in a statistically random manner that is representative of the homogeneous are, bulk samples from each homogeneous area of friable surfacing material that is not assumed to be ACM, and shall collect the samples as follows:
(1) At least three bulk samples shall be collected from each homogeneous area that is 1,000 SF or less.
(2) At least five bulk samples shall be collected from each homogeneous area that is greater than 1,000 SF but less than or equal to 5,000 SF.
(3) At least seven bulk samples shall be collected from each homogeneous area that is greater than 5,000 SF.
Thermal system insulation - An accredited inspector shall collect the samples as follows:
(1) At least three bulk samples, in a random distributed manner from each homogeneous area of thermal system insulation that is not assumed to be ACM.
(2) Collect at least one bulk sample from each homogeneous are of patched thermal system insulation that is not assumed to be ACM if the patched section is less than 6 linear or square feet.
(3) In a manner sufficient to determine whether the material is ACM or not ACM, collect bulk samples from each insulated mechanical system that is not assumed to be ACM where cement or plaster is used on fittings such as tees, elbows, or valves.
(4) Bulk samples are not required to be collected from any homogeneous area where the accredited inspector has determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACBM.
Miscellaneous material - An accredited inspector shall collect the samples as follows:
(1) In a manner sufficient to determine whether material is ACM or not ACM from each homogeneous area of friable miscellaneous material that is not assumed to be ACM.
Non friable suspected ACBM - An accredited inspector shall collect the samples as follows:
If any homogeneous area of non friable suspected ACBM is not assumed to be ACM, then an accredited inspector shall collect, in a manner sufficient to determine whether the material is ACM or not ACM, bulk samples from the homogeneous are of non friable suspected ACBM that is not assumed to be ACM.
LEAD BASED PAINT (LBP)
Testing of painted surfaces for lead, cadmium and chromium was conducted by collecting bulk paint chip samples from various painted surfaces. It is important to note that this inspection was not intended to meet the requirements of HUD sampling protocols for lead paint and was not a comprehensive, surface-by-surface evaluation, but rather a screening inspection of major painted components, which may contain LBP.
ANALYTICAL METHODS
SUSPECT ASBESTOS-CONTAINING MATERIALS
(ACM)
Suspect bulk ACM samples were analyzed using polarized light microscopy (PLM) and dispersion staining techniques and transmission electron microscopy. The analytical method was conducted in accordance with Method EPA-600/M4-82-020 and/or EPA 600/R-93/116.
Analysis was performed by EMSL Analytical, Inc., Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036.
LEAD BASED PAINT (LBP)
Paint chip samples were analyzed for lead using inductively coupled plasma (ICP) emission
Repair Macdonough Hall, Building 102 GER 130-6577 Page 3 USNA, Annapolis, MD
GER
spectroscopy (SW-846, 6010C). Analysis was performed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: 10896, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01.
PREVIOUS HAZARDOUS MATERIAL
REPORTS
Mr. Randolph Ghertler (NAVFAC Design Manager) provided two previous hazardous material reports associated with Macdonough Hall as follows. Each of these reports is included by reference.
1. Asbestos Identification Survey and Assessment, Contract #N62477-94-D-0117, Delivery Order #0009, prepared by Applied Environmental, Inc., dated 1997.
This report included the collection of 58 bulk samples of suspect ACM. The report identified the following ACM:
2,400 square feet of 9” square floor tile and associated black mastic in the swimming pool hallway and
1,500 square feet of dark gray spray-applied fireproofing on the structural support columns throughout the building. In addition, the report assumed the building’s roofing system to be ACM.
The inspection report did not address LBP or any other hazardous materials.
2. Hazardous Materials Inspection Report for the Macdonough and Scott Halls, prepared by Aerosol Monitoring & Analytical, Inc., dated 2010.
This report included the collection of 109 bulk samples of suspect ACM. The report identified the following ACM:
14 unit ventilators with ACM mastic.
1,100 square feet of black mirror mastic.
25 window systems with ACM window glazing.
In addition, the report assumed the following
ACM:
650 linear feet of pipe and fitting insulation.
51 fire doors.
130 window systems with ACM frame sealant and glazing.
52,500 square feet of roofing materials.
This report also identified LBP in the building as follows:
White wood interior window casing - Room 107.
Tan and white metal window casing - Rooms 203 and 305.
White wood interior window sills - Room 107.
Yellow wood window apron - Room 107.
Green wood exterior window sills and casings
- Throughout exterior.
White concrete interior window sills - Room 107.
Beige, black and tan metal I-beams - Rooms 312, 507, and 502.
Beige metal structural steel - Rooms 305, 306, 312, and 507.
White wood window sash - Room 227.
White wood window mullion - Room 227.
White wood walkway ceiling - Swimming pool.
Blue metal I-beam supports - Swimming pool.
Blue metal newel post - Swimming pool.
Tan and green plaster walls and ceilings - Throughout building.
Gold and white brick walls - Room 507.
Black concrete wall - Room 121.
Green wood door casing - 6th floor roof access.
White porcelain sinks - Rooms 121 and 241.
The previous hazardous materials reports are provided in Sections XX and XX of this report.
PREVIOUS RENOVATION DRAWING
REVIEW
The most recent major renovation to the building was performed in or about 1983. The project was titled “Rehabilitation of Physical Education
Repair Macdonough Hall, Building 102 GER 130-6577 Page 4
Facilities.” The Construction Contract number was N62477-79-C-0053. The drawing sheet index for the project did not specifically identify any sheets associated with hazardous materials. However, the Mechanical Demolition sheets contained symbols and notes indicating ACM insulation was present on mechanical equipment and or piping. The General Demolition Note on drawing #3028713 (M-1) stated “All pipe & duct insulation shall be removed.
Asbestos insulation shall be removed as specified prior to pipe removal.”
For purposes of this report, we assume the ACM was properly removed and disposed of by the contractor performing the work. We have not been provided with any additional documents to indicate otherwise.
FIELD SURVEY
ASBESTOS BULK SAMPLING
In December of 2014, eighty-three (83) bulk samples of suspect ACM were collected by H.
Nelson Adcock, a Maryland Licensed Asbestos Inspector. Additionally, four (4) bulk samples of suspect ACM were collected by Gayle, Inc., during the roofing inspection and forwarded to us for analysis. Samples were collected from accessible areas throughout the building.
The attached Table 1 is a summary of the sample materials, sample location, and laboratory results.
Laboratory results are contained in Section 2 of this report. Drawings showing the approximate sample locations, are contained in Section 3.
Destructive activities such as breaking into walls, chases, ceilings, or floors were not performed in order to obtain samples. Therefore, if during the demolition process suspect hazardous materials are uncovered, they must be properly addressed.
As the sample results indicate, the following materials were determined to contain asbestos:
Exterior window glazing on the roof.
INACCESSIBLE PORTIONS OF THE BUILDING
During our inspection there were portions of the building that were not accessible for various reasons. We were provided with a building key by Mr. Rich Miranda, Facilities Manager for the building. While the key provided access to many areas of the building, it did not open all locked areas. The list below identifies major areas of the building that were not accessible; however, the list should not be considered to be all inclusive.
1. Tunnel Area Beneath The Swimming Pool - This area appeared to be a confined space and was not entered for safety reasons.
2. Roof Area - The standing seam metal roof was not accessible by our inspector. Special safety requirements were required to be implemented to access the roof. The roof inspection was performed by Gayle Inc. They collected a limited number of bulk samples from the roofing components and provided them to us for analysis.
3. Swimming Pool Balcony - The entrance to the swimming pool balcony was locked at the time of our inspection. The key we were provided di not allow access to this area.
ASBESTOS DISCUSSION
The EPA defines ACM as any material which contains greater than 1% asbestos by weight.
Based on previous hazardous material inspection reports and our current inspection the following categories of ACM were identified in the buildings:
Presumed Friable ACM
Pipe and Fitting Insulation: ACM pipe and fitting insulation was identified on previous renovation drawings. It is presumed these ACM materials were removed in accordance with the drawings. However, as a precaution, we have assumed limited amounts of this ACM may be present in concealed areas. Estimated Quantity
- 2,000 linear feet.
Fire Doors: Fire doors within the building may contain ACM. These doors are generally not labeled as asbestos-containing. Destructive techniques were not used to inspect the doors within the building since that would impair the doors fire protection rating. Estimated Quantity
- 51 each.
Friable ACM
Exterior Roof Window Glazing (2% Chrysotile): Asbestos-containing exterior window glazing exists on the windows located on the roof. This material was in fair condition
Repair Macdonough Hall, Building 102 GER 130-6577 Page 5 at the time of the survey. Estimated Quantity - 4,000 linear feet.
Dark Gray Spray Applied Fireproofing (1%
- 5% Chrysotile): Asbestos-containing dark gray spray applied fireproofing exists on the structural steel above the 2nd floor intramural office according to previous reports. This material was in fair condition at the time of the survey. Estimated Quantity - 1,500 square feet.
Non-Friable ACM
9-inch Green Floor Tile and Mastic (10% - 15% Chrysotile in the tile, <1% Chrysotile in the mastic): Asbestos-containing floor tile and mastic is located on the pool balcony according to previous reports. This material is classified as Category I ACM and was presumed to be in fair condition at the time of the inspection.
Estimated Quantity - 2,400 square feet.
Unit Ventilator Mastic (3% - 10% Chrysotile): Asbestos-containing mastic was associated with the unit ventilators according to previous reports. This material is classified as Category II ACM and was presumed to be in fair condition at the time of the inspection.
Estimated Quantity - 14 units.
Black Mirror Mastic (15% Chrysotile):
Asbestos-containing black mirror mastic was identified in the building according to previous reports. This material is classified as Category II ACM and was presumed to be in fair condition at the time of the inspection.
Estimated Quantity - 1,100 square feet.
Gray/Black Window Glazing (2% Chrysotile): Asbestos-containing gray/black window glazing was identified in the building according to previous reports. This material is classified as Category II ACM and was presumed to be in fair condition at the time of the inspection. Estimated Quantity - 3,000 linear feet.
Materials Containing <1% Asbestos
Exterior Door Frame Sealant - (<1% Chrysotile: This material does not meet the Occupational Safety and Health Administration (OSHA) definition of ACM; however, since it does contain asbestos it must still be handled in accordance with 29 CFR 1926.1101.
Estimated quantity to be disturbed - 350 LF.
Under the National Emission Standard for Hazardous Air Pollutants (NESHAP) all friable ACM must be removed prior to disturbance through either renovation or demolition. No friable ACM which will be disturbed during the renovation project must also be removed.
All asbestos abatement activities should be performed by a Maryland Licensed Asbestos Abatement Contractor.
All asbestos abatement work shall be performed in accordance with local, state and Federal regulations including but not limited to:
29CFR1926.1101 - Asbestos.
40CFR61 - National Emission Standards for Hazardous Air Pollutants.
COMAR 26.04.07 - Solid Waste Management Regulations
COMAR 26.11.21 - Control of Asbestos
PAINT SAMPLING
As part of the building inspection process ten (10) paint chip samples were collected by GER. The attached Table 2 summarizes the samples collected and their laboratory results. The laboratory analytical results are contained in Section 2. The purpose of our sampling was to obtain representative data on the concentrations of lead, cadmium and chromium in the existing painted surfaces scheduled to be disturbed by the work.
Paint samples were collected from painted surfaces that may be disturbed by the planned renovation work.
PAINT DISCUSSION
There are two frequently used standards to define lead-based paint, the Consumer Product and Safety Commission (CPSC) and the Department of Housing and Urban Development (HUD). In 1978, the CPSC, acting under the authority of the Consumer Product Safety Act, banned the sale of paint containing more than 0.06% lead by weight to consumers. Paint which contains more than 0.06% lead by weight is defined as Lead-containing paint (LCP). The Department of Housing and Urban Development (HUD) defines Lead-based paint (LBP) as any paint, varnish, shellac, or other coating that contains lead equal to or greater than
1.0 mg/cm2 as measured by X-ray fluorescence
Repair Macdonough Hall, Building 102 GER 130-6577 Page 6
(XRF) analyzer or laboratory analysis, or 0.5% by weight as measured by laboratory analysis.
The Occupational Safety and Health Administration (OSHA) Lead in Construction Standard (29 CFR 1926.62) does not define lead-based paint.
However, to comply with OSHA, all painted surfaces with a lead concentration at or above the laboratory’s minimum detection limit (MDL) should be considered lead containing. Compliance with this standard is required even for paints with less than 0.5% or 0.06% lead by weight. Therefore, painted surfaces exceeding the MDL should not be disturbed without taking the appropriate precautions when performing certain high risk tasks. Activities such as scraping, sanding, welding/torching and disturbance of painted surfaces could potentially release leaded dust. OSHA has categorized the following high risks tasks into three groups:
Group 1: manual demolition manual scraping heat-gun applications power tool cleaning with dust collection system spray paint with lead-based paints
Group 2: lead burning using lead-containing mortar power tool cleaning without dust collection system rivet blasting cleanup activities where dry expendable abrasives are used movement and removal of abrasive blasting enclosures
Group 3: abrasive blasting welding, cutting and burning on steel structures
Analytical results for lead paint indicated that all of the samples collected and analyzed were found to have lead concentrations above the laboratory's minimum detection limit. Four of the ten samples analyzed were determined to be lead-based (>0.5%).
Paints containing cadmium and chromium are often found as protective coatings on structural steel or exterior coatings on metal surfaces. These paints tend to be red, yellow or orange and are typically the first layer. All of the bulk paint chip samples were also tested for cadmium and chromium.
Analytical results for cadmium and chromium indicate that all of the samples analyzed resulted in concentrations above the MDL for cadmium and chromium. The National Institute for Occupational Safety and Health (NIOSH) identifies chromium as a confirmed carcinogen and cadmium as a suspect carcinogen.
Therefore, all existing painted surfaces scheduled for demolition should be considered lead, cadmium and chromium containing for the purposes of complying with 29 CFR 1926.62, 29 CFR 1926.1126 and 29 CFR 1926.1127 in order to protect workers and the environment.
Construction Standards established by OSHA for lead, cadmium and chromium are:
Lead 29 CFR 1926.62 Cadmium 29 CFR 1926.1127 Chromium 29 CRF 1926.1126
The permissible exposure limits (PEL) established by OSHA are 5 ug/m3 for cadmium, 5 ug/m3 for chromium (chromates) and 50 ug/m3 for lead.
The PEL is an airborne measurement to address worker exposure. There is no direct correlation between lead, cadmium, and chromium concentrations in paint and worker exposure. Only when these concentrations are below the laboratory’s MDL, is worker exposure not an issue.
Appropriate precautions should be taken during the disturbance of all painted surfaces to ensure protection of workers and the environment.
All lead, cadmium and chromium paint work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
29CFR 1926.62 - Lead
29CFR 1926.1126 - Chromium
29CFR 1926.1127 - Cadmium
COMAR 26.04.07 - Solid Waste Management
COMAR 26.13 - Disposal of Controlled Hazardous Substances
COMAR 26.16 - Lead
Repair Macdonough Hall, Building 102 GER 130-6577 Page 7
POLYCHLORINATED BIPHENYLS (PCBS)
On January 1, 1979, the Environmental Protection Agency (EPA) banned the manufacturing of light ballasts which contain PCB’s and phased out most PCB uses. Therefore, all light ballasts manufactured prior to January 1, 1979 without “Non-PCB” markings must be considered PCB containing. The EPA’s actions subjects all substances containing over 50 ppm PCBs to regulatory control (with the exception of PCB-contaminated waste oil which is prohibited at any level).
Our field investigation of existing light fixtures indicated there were generally newer fluorescent light fixtures used in the buildings. The T8 fluorescent light fixtures observed in the building contained electronic ballasts. We also observed some older fluorescent light fixtures in the building.
We observed an electrical ballast manufactured by Advance in several of these fluorescent light fixtures. The Advance electrical ballasts were labeled “No PCBs.”
All fluorescent light ballasts, other than electronic ballast and those not marked as “No PCBs” must be considered to contain PCB’s. We recommend assuming that 10% of all light ballasts contain PCB's and all light tubes and lamps are assumed to be mercury containing.
All PCB and mercury containing light tube work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
40CFR761 - Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution In Commerce, and Use Prohibitions
COMAR 26.04.07 - Maryland Solid Waste Management Regulations.
MERCURY CONTAINING THERMOSTATS
We observed wall mounted thermostats throughout the building. Several of the thermostats were disassembled in order to determine whether the thermostat contained mercury. The wall mounted thermostats we observed appeared to be BI-metallic thermostats. If any mercury containing thermostats are discovered and replaced the mercury containing thermostat should be properly recycled to prevent the release of any mercury.
All mercury containing thermostat work shall be performed in accordance with all local, state and Federal regulations to protect workers and the environment, including but not limited to:
COMAR 26.04.07 - Maryland Solid Waste Management Regulations.
LIMITATIONS
This report has been prepared for the exclusive use of Stanley Consultants and/or their agents. This service was performed in accordance with generally accepted environmental practices. No other warranty, expressed or implied, is made. Our conclusions and recommendations are based, in part, upon information provided to us by others and our site observations. We have not verified the completeness or accuracy of the information provided by others, unless otherwise noted. Our observations and recommendations are based upon conditions readily visible at the time of our site visit, November of 2014, and upon current industry standards. During our inspection, accessible areas were visually inspected for the presence of asbestos and lead based paints. The findings at these locations area assumed to be representative throughout each building. Inaccessible areas were not visually inspected. Areas inspected for the above-referenced materials were limited to those designated by the client. The inspection did include the entire building and was limited to the areas described in the report.
Under this scope of services, GER assumes no responsibility regarding response actions (e.g. O&M Plans, Remediation, Notifications, etc.) initiated as a result of these findings. GER assumes no liability for the duties and responsibilities of the Client with respect to compliance with local, state and Federal regulations. Compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state and Federal regulations and should be performed by appropriately licensed personnel, as warranted.
REFERENCES
(1) Frederick. C. Peter and David P. O’Konski (1997). United States Naval Academy Annapolis, Maryland, Building Number 102, Asbestos Identification Survey and Assessment. Applied Environmental Inc.
Repair Macdonough Hall, Building 102 GER 130-6577 Page 8
(2) Aerosol Monitoring & Analysis, Inc. (2010).
Hazardous Materials Inspection Report For The Macdonough And Scott Halls At The United States Naval Academy, Annapolis, Maryland.
Repair Macdonough Hall, Building 102 GER 130-6577 Page 9
SECTION 2
Sample Tables and Analytical Reports
Table 1 - Asbestos Sample Results
Table 2 - Paint Sample Results
Repair Macdonough Hall, Building 102 GER 130-6577
NO. SAMPLE LOCATION SAMPLE MATERIAL % & TYPE OF ASBESTOS
M1-1 West elev., window Black exterior sealant None Detected
M1-2 West elev., window Black exterior sealant None Detected
M1-3 West elev., north metal panel at stone Green exterior sealant None Detected
M1-4 West elev., south metal panel at stone Green exterior sealant None Detected
M1-5 West elev., metal panel White exterior sealant None Detected
M1-6 West elev., metal panel White exterior sealant None Detected
M2-7 South side flashing at elevated walkway White exterior sealant None Detected
M2-8 South side flashing at elevated walkway White exterior sealant None Detected
M2-9 South side at door stone columns White exterior sealant None Detected
M2-10 South side at door stone columns White exterior sealant None Detected
M2-11 South side window White exterior glazing None Detected
M2-12 South side window White exterior glazing None Detected
M2-13 South side window, exterior Frame sealant None Detected
M2-14 South side window, exterior Frame sealant None Detected
M2-15 South side door, exterior Frame sealant None Detected
M2-16 South side door, exterior Frame sealant < 1% Chrysotile
M1-17 Lobby area ceiling Textured surfacing material None Detected
M1-18 Lobby area ceiling Textured surfacing material None Detected
M1-19 Lobby area ceiling 2'x 2' CT None Detected
M1-20 Lobby area above ceiling, HVAC duct with FG insulation Tan HVAC mastic None Detected
M1-21 Lobby area above ceiling GWB None Detected
M1-22 Lobby area above ceiling Grey spray applied fireproofing None Detected
M1-23 Lobby area above ceiling Joint compound None Detected
M1-24 Telephone Room 106 Blue floor tile and mastic None Detected
M1-25 Telephone Room 106 Blue covebase and mastic None Detected
M1-26 Telephone Room 106, wall Plaster None Detected
M1-27 Men's Room 111 Layer beneath blue floor None Detected
M1-28 Pool filtration Room 121 Layer beneath blue floor None Detected
M1-29 Pool filtration Room 121 Transition and mastic None Detected
Table 1 - Asbestos Bulk Sample Results
Table 1 - Asbestos Bulk Sample Results
M1-30 Telephone Room 102 Blue floor tile and mastic None Detected
M1-31 Telephone Room 102 Blue covebase and mastic None Detected
M1-32 Telephone Room 102 Plaster None Detected
M1-33 Vestibule Room 103A, ceiling GWB None Detected
M1-34 Room 110, wall above ceiling Joint compound None Detected
M1-35 Room 119 above ceiling White spray applied fireproofing None Detected
M1-36 Room 119, ceiling 2' x 4' CT None Detected
M1-37 Room 119, cold water pipe, above ceiling Mastic None Detected
M1-38 Room 119, cold water pipe, above ceiling Mastic None Detected
M1-39 Room 119 Tan 12" floor tile and mastic None Detected
M1-40 Room 119 Tan 12" floor tile and mastic None Detected
M1-41 Room 104 ceiling 2'x 2' CT None Detected
M1-42 Pool filtration, Room 121, exterior pool wall Plaster None Detected
M1-43 Pool filtration, Room 121, exterior pool wall Plaster None Detected
M1-44 Room 126, wall panels acoustical panel None Detected
M1-45 Room 126, wall panels acoustical panel None Detected
M1-46 127, stairs stair tread mastic None Detected
M1-47 127, stairs stair tread mastic None Detected
M1-48 Room 132 ceiling 2' x 4' ceiling tile None Detected
M1-49 Room 132D Tan 12" floor tile and mastic None Detected
M1-50 Room 132C Tan 12" floor tile and mastic None Detected
M1-51 Room 132E Tan covebase and mastic None Detected
M1-52 Room 132E 2' x 4' ceiling tile None Detected
M1-53 Room 132E above ceiling tile Tan HVAC mastic None Detected
M1-54 Room 132E Tan covebase and mastic None Detected
M1-55 Room 132D above ceiling tile Tan HVAC mastic None Detected
M1-56 Mech. Room, Storage Room 133 Tan HVAC mastic None Detected
Table 1 - Asbestos Bulk Sample Results
M1-57 Mech. Room, Storage Room 133, CWS pipe insulation White mastic None Detected
M1-58 Mech. Room, Storage Room 133, CWR pipe insulation White mastic None Detected
M1-59 Mech. Room, Storage Room 133, CWR Black wrap None Detected
M1-60 Mech. Room, Storage Room 133, CWS Black wrap None Detected
M5-61 East Mech. Room 507, ceiling Plaster, white top coat None Detected
M5-62 East Mech. Room 507, ceiling Plaster, brown base coat None Detected
M5-63 East Mech. Room 507, ceiling Plaster, white top coat None Detected
M5-64 East Mech. Room 507, ceiling Plaster, brown base coat None Detected
M5-65 South catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-66 North catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-67 South catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-68 South catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-69 North catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-70 North catwalk, ceiling top of gym White spray applied fireproofing None Detected
M5-71 East Mech. Room 505, north ceiling GWB None Detected
M5-72 East Mech. Room 505, south ceiling GWB None Detected
M5-73 East Mech. Room 505, AHU-3 duct Lagging and tape None Detected
M5-74 East Mech. Room 505, AHU-3 duct Lagging and tape None Detected
M5-75 East Mech. Room 505, AHU-1 duct Lagging and tape None Detected
M5-76 East Mech. Room 505, AHU-1 duct Lagging and tape None Detected
M4-77 Room 406, fencing storage Tan 12" floor tile and mastic None Detected
M4-78 Room 406A, fencing storage Tan 12" floor tile and mastic None Detected
M79 Roof Underlayment None Detected
M80 Roof Underlayment None Detected
M81 Roof Window glazing 2% Chrysotile
M82 Roof Window glazing 2% Chrysotile
NOTES
The sample number key is as follows:
The first character designates Macdonough Hall, the second character designates the floor, the third character after the dash represent the unique sample number.
NO. SAMPLE LOCATION SAMPLE MATERIAL
LEAD
CHROMIUM % CADMIUM
MP-1 West elev., wooden facade at windows Green exterior paint 0.046 0.0011 0.00022
MP-2 South side door, exterior Green paint 8.7 0.13 0.0017
MP-3 Room 306, heavy bags, arch beam Flesh paint 0.98 0.0067 0.0029
MP-4 Telephone Room 102, above ceiling tile White paint 0.19 0.0096 0.0016
MP-5 Vestibule 103A, brick wall Yellow paint 0.096 0.0029 0.001
MP-5A Room 122 ceiling White paint 0.017 0.00037 0.0013
MP-6 Pool filtration, Room 121, structural steel Yellow paint 0.28 3.8 0.0042
MP-7
Pool filtration, Room 121, exterior pool wall Blue paint 17 0.031 0.0072
MP-8 Room 128, metal door frame Grey paint 0.066 0.0045 0.00072
MP-9 East Mech. Room #505, catwalk stairs Tan paint 0.019 0.034 0.0006
MP-10 Stair #4, Room 506, brick wall Yellow paint 0.95 0.00078 0.0013
BOLD results indicate the sample is Lead Based Paint (LBP).
All samples exceeded the laboratory reporting limit (RL).
Table 2 - Paint Sample Results
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com cinnasblab@EMSL.com
041435867 CustomerID: GEOE25 CustomerPO: 130-6577 ProjectID:
EMSL Order:
Attn: Nelson Adcock GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 12/06/14 10:45 AM
#130-6577 / MacDonough Hall, USNA, Annapolis, MD
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
12/11/2014Analysis Date:
12/4/2014Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
M1-1
041435867-0001
West Elev., Window - Black Exterior Sealant
Gray/Black None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M1-2
041435867-0002
West Elev., Window - Black Exterior Sealant
Gray/Black None Detected Non-Fibrous Homogeneous
Cellulose1% Non-fibrous (other)99%
M1-3
041435867-0003
West Elev., North Metal Panel @ Stone - Green Exterior Sealant
Green None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M1-4
041435867-0004
West Elev., South Metal Panel @ Stone - Green Exterior Sealant
Green None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M1-5
041435867-0005
West Elev., Metal Panel - White Exterior Sealant
Tan/White/Green None Detected Non-Fibrous Heterogeneous
Cellulose2% Non-fibrous (other)98%
M1-6
041435867-0006
West Elev., Metal Panel - White Exterior Sealant
Tan/White/Green None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
M2-7
041435867-0007
South Side Flashing @ Elevated Walkway - White Exterior Sealant
Gray/White None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
1Test Report PLM-7.28.9 Printed: 12/11/2014 4:41:11 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Beltsville, MD
Initial report from 12/11/2014 16:41:11
George Malone (32) Matthew Daigneault (59)
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com cinnasblab@EMSL.com
041435867 CustomerID: GEOE25 CustomerPO: 130-6577 ProjectID:
EMSL Order:
Attn: Nelson Adcock GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 12/06/14 10:45 AM
#130-6577 / MacDonough Hall, USNA, Annapolis, MD
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
12/11/2014Analysis Date:
12/4/2014Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
M2-8
041435867-0008
South Side Flashing @ Elevated Walkway - White Exterior Sealant
Gray/White/Beige None Detected Non-Fibrous Heterogeneous
Cellulose2% Non-fibrous (other)98%
M2-9
041435867-0009
South Side @ Door Stone Columns - White Exterior Sealant
Gray/White/Beige None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
M2-10
041435867-0010
South Side @ Door Stone Columns - White Exterior Sealant
Gray/White None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
M2-11
041435867-0011
South Side Window - White Exterior Glazing
Gray/White/Beige None Detected Non-Fibrous Heterogeneous
Non-fibrous (other)100%
M2-12
041435867-0012
South Side Window - White Exterior Glazing
Gray/White/Beige None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M2-13
041435867-0013
South Side Window, Exterior - Frame Sealant
Beige None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M2-14
041435867-0014
South Side Window, Exterior - Frame Sealant
Gray/Beige None Detected Non-Fibrous Homogeneous
Non-fibrous (other)100%
M2-15
041435867-0015
South Side Door, Exterior - Frame Sealant
Green/Beige None Detected Non-Fibrous Heterogeneous
Synthetic3% Non-fibrous (other)97%
2Test Report PLM-7.28.9 Printed: 12/11/2014 4:41:11 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Beltsville, MD
Initial report from 12/11/2014 16:41:11
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com cinnasblab@EMSL.com
041435867 CustomerID: GEOE25 CustomerPO: 130-6577 ProjectID:
EMSL Order:
Attn: Nelson Adcock GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 12/06/14 10:45 AM
#130-6577 / MacDonough Hall, USNA, Annapolis, MD
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
12/11/2014Analysis Date:
12/4/2014Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
M2-16
041435867-0016
South Side Door, Exterior - Frame Sealant
Gray/Tan/Beige Non-Fibrous Heterogeneous
Chrysotile<1%Non-fibrous (other)100%
M1-17
041435867-0017
Lobby Area Ceiling - Textured Surfacing Material
White None Detected Non-Fibrous Homogeneous
Perlite10% Non-fibrous (other)90%
M1-18
041435867-0018
Lobby Area Ceiling - Textured Surfacing Material
White/Beige None Detected Non-Fibrous Heterogeneous
Perlite5% Non-fibrous (other)95%
M1-19
041435867-0019
Lobby Area Ceiling - 2'x2' CT
White None Detected Non-Fibrous Homogeneous
Glass60% Non-fibrous (other)40%
M1-20
041435867-0020
Lobby Area Above Ceiling, HVAC Duct w/ FG Insul. - Tan HVAC Mastic
Tan/Silver None Detected Fibrous Heterogeneous
Cellulose7% Glass5%
Non-fibrous (other)88%
M1-21
041435867-0021
Lobby Area Above Ceiling - GWB
Gray/Tan None Detected Fibrous Heterogeneous
Cellulose10% Glass7%
Gypsum75% Non-fibrous (other)8%
M1-22
041435867-0022
Lobby Area Above Ceiling - Grey Spray Applied Fireproofing
Brown/Gray None Detected Fibrous Homogeneous
Min. Wool40% Non-fibrous (other)60%
M1-23
041435867-0023
Lobby Area Above Ceiling - Joint Compound
Tan/White None Detected Fibrous Heterogeneous
Cellulose5% Mica15% Non-fibrous (other)80%
3Test Report PLM-7.28.9 Printed: 12/11/2014 4:41:11 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Beltsville, MD
Initial report from 12/11/2014 16:41:11
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com cinnasblab@EMSL.com
041435867 CustomerID: GEOE25 CustomerPO: 130-6577 ProjectID:
EMSL Order:
Attn: Nelson Adcock GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 12/06/14 10:45 AM
#130-6577 / MacDonough Hall, USNA, Annapolis, MD
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
12/11/2014Analysis Date:
12/4/2014Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
M1-24-Floor Tile
041435867-0024
Telephone M102A - Blue Floor Tile
Blue None Detected Non-Fibrous Homogeneous
Ca Carbonate20% Non-fibrous (other)80%
M1-24-Mastic
041435867-0024A
Telephone M102A - Mastic
Brown/Black None Detected Non-Fibrous Heterogeneous
Cellulose4% Non-fibrous (other)96%
M1-25-Cove Base
041435867-0025
Telephone M102A - Blue Cove Base
Blue None Detected Non-Fibrous Homogeneous
Ca Carbonate20% Non-fibrous (other)80%
M1-25-Mastic
041435867-0025A
Telephone M102A - Mastic
White None Detected Non-Fibrous Heterogeneous
Mica5% Non-fibrous (other)95%
M1-26
041435867-0026
Telephone M102A, Wall - Plaster
White None Detected Non-Fibrous Homogeneous
Quartz25% Non-fibrous (other)75%
M1-27
041435867-0027
Men's M107A - Layer Beneath Blue Floor
Brown/Gray None Detected Non-Fibrous Homogeneous
Quartz40% Non-fibrous (other)60%
M1-28
041435867-0028
Pool Filtration, M120 - Layer Beneath Blue Floor
Gray/Tan/Yellow None Detected
This is a composite of a Leveler and Mastic.
Fibrous Heterogeneous
Cellulose7% Non-fibrous (other)93%
M1-29-Transition
041435867-0029
Pool Filtration, M120 - Transition & Mastic
Black None Detected Non-Fibrous Homogeneous
Ca Carbonate15% Non-fibrous (other)85%
4Test Report PLM-7.28.9 Printed: 12/11/2014 4:41:11 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1% Samples analyzed by EMSL Analytical, Inc. Beltsville, MD
Initial report from 12/11/2014 16:41:11
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com cinnasblab@EMSL.com
041435867 CustomerID: GEOE25 CustomerPO: 130-6577 ProjectID:
EMSL Order:
Attn: Nelson Adcock GeoEnvironmental Resources 2712 Southern Blvd.
Suite 101 Virginia Beach, VA 23452
Received: 12/06/14 10:45 AM
#130-6577 / MacDonough Hall, USNA, Annapolis, MD
Fax: (757) 463-3080 Phone: (757) 463-3200
Project:
12/11/2014Analysis Date:
12/4/2014Collected:
Sample Description Appearance % Type AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
M1-29-Mastic
041435867-0029A
Pool Filtration, M120 - Transition & Mastic
Tan/Yellow None Detected Fibrous Homogeneous
Cellulose3% Synthetic4%
Non-fibrous (other)93%
M1-30-Floor Tile
041435867-0030
Telephone M101A - Blue Floor Tile
Blue None Detected Non-Fibrous Homogeneous
Ca Carbonate20% Non-fibrous (other)80%
M1-30-Mastic
041435867-0030A
Telephone M101A - Mastic
Brown/Tan None Detected Fibrous Heterogeneous
Cellulose3% Synthetic6%
Non-fibrous (other)91%
M1-31-Cove Base
041435867-0031
Telephone M101A - Blue Cove Base
Blue None Detected Non-Fibrous Homogeneous
Ca Carbonate15% Non-fibrous (other)85%
M1-31-Mastic
041435867-0031A
Telephone M101A - Mastic
White None Detected Non-Fibrous Heterogeneous
Mica5% Non-fibrous (other)95%
M1-32
041435867-0032
Telephone M101A - Plaster
White None Detected Non-Fibrous Homogeneous
Mica5% Non-fibrous (other)95%
M1-33
041435867-0033
Vestibule M101, Ceiling - GWB
Gray/Tan None Detected Fibrous Heterogeneous
Cellulose3% Glass2%
Non-fibrous (other)95%
MP-5
041435867-0034
Vestibule M101, Brick Wall - Yellow Paint
Not Submitted
5Test Report PLM-7.28.9 Printed: 12/11/2014 4:41:11 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government.