This document provides details for a federal solicitation seeking HVAC maintenance services. The solicitation was issued by the Naval Facilities Engineering Command for HVAC maintenance and repair services at a critical facilities located at Naval Air Station Jacksonville in Florida. The contractor shall perform all required labor, management, supervision, tools, materials and equipment to maintain HVAC systems, including boilers excluding those in the Central Utility Plant. The solicitation includes maintenance, repairs and alterations to HVAC equipment such as chillers, air handling units, variable air volume boxes, exhaust fans, pumps and related systems. The response date and award date are not specified. Pricing and contract terms are also not outlined.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Section J – 1502000 Facility Investment Section J - 1502000 Facility Investment
| Attachment Number |
| Attachment Title |
| J-1502000-01 |
| Definitions and Acronyms |
| J-1502000-02 |
| Facilities Description |
| J-1502000-03 |
| Site Maps |
| J-1502000-04 |
| Not Used |
| J-1502000-05 |
| Uniformat Classification |
| J-1502000-06 |
| Uniformat General Direct Condition Rating Guidance |
| J-1502000-07 |
| Uniformat Condition Rating Guidance Specific to Each Meter Group |
| J-1502000-08 |
| Temperature Standards for HVAC and Refrigeration Systems |
| J-1502000-09 |
| Unfired Pressure Vessels (UPV) |
| J-1502000-10 |
| HVAC/HVAC Inventory |
Attachment J-1502000-01 Definitions and Acronyms
| Definition |
| Description |
| Crane, Category 1 |
| Portal cranes, Hammerhead cranes, Locomotive cranes, Derricks, Floating cranes (YD), Tower cranes, Container cranes, Mobile cranes (except those indicated as category 4), including truck, cruiser, crawler, warehouse/industrial cranes, and cranes used for dragline, pile driving, clamshell, magnet, bucket work, and Aircraft crash cranes. |
| Crane, Category 2 & 3 |
| Cranes with rated capacities of 20,000 pounds or greater are category 2. Examples are Overhead traveling cranes, Gantry cranes (rail mounted), Wall cranes, Jib cranes, Pillar cranes, Pillar jib cranes, Monorails and associated hoists, Fixed hoists including chain falls. Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities less than 2,000 pounds. |
| Crane, Category 4 |
| Commercial truck mounted cranes, Truck mounted articulating boom cranes, Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities of 2,000 pounds and greater. Commercial truck mounted cranes and truck mounted articulating boom cranes with OEM capacities of 2,000 pounds and greater require a licensed operator even if the cranes are down rated below 2,000 pounds capacity for administrative purposes. |
| Equipment, Collateral |
| Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project. |
| Equipment, Installed |
| Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial. |
| Equipment, Personal Property |
| Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed. |
| Facilities Life Cycle |
| A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal. |
| Facilities Maintenance Management |
| The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.” |
| Integrated Maintenance Program (IMP) |
| IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness. Service Orders will not be issued for accomplishment of repairs on systems and equipment maintained under IMP. |
| Life-Cycle Costs |
| A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life. |
| Maintenance, Preventive |
| Maintenance designed to increase the availability of the facilities/equipment by reducing the number of unexpected breakdowns or service interruptions. It is any planned maintenance activity that improves equipment life and avoid any unplanned maintenance requirements. |
| Management Information Systems-Maintenance |
| A computerized system that will provide sufficient information for management to evaluate differences between budgets and actual costs and evaluate performance. |
| Repair |
| Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition. |
| Replacement |
| Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance. |
| Restoration |
| Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes. |
| Sustainment |
| Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities. |
| Weight Handling Equipment (WHE) |
| Weight handling equipment consists of cranes (e.g., portal cranes, jib cranes), rigging gear (e.g., slings, shackles), and associated equipment (e.g., portable hoists, dynamometers). For purposes of this technical sub-annex, WHE does not include mobile or transportable truck, crawler, and railway mounted locomotive cranes covered in 1700000 BSVE. |
| Acronym |
| Title |
| ACO |
| Administrative Contracting Officer |
| BPVC |
| Boiler and Pressure Vessel Code |
| BW |
| Biweekly |
| CDR |
| Contract Discrepancy Report |
| CIA |
| Controlled Industrial Area |
| CMMS |
| Computerized Maintenance Management System |
| COR |
| Condition of Readiness |
| DBH |
| Diameter at Breast Height |
| DoD |
| Department of Defense |
| DoN |
| Department of Navy |
| DRMO |
| Defense Reutilization Management Office |
| EPA |
| Environmental Protection Agency |
| EPCRA |
| Emergency Planning and Community Right-to-Know Act |
| FAR |
| Federal Acquisition Regulation |
| FFP |
| Firm Fixed Price |
| FIFRA |
| Federal Insecticide, Fungicide, and Rodenticide Act |
| FSC |
| Facility Support Contract |
| GFE |
| Government-furnished Equipment |
| GFF |
| Government-furnished Facilities |
| GFM |
| Government-furnished Materials |
| GPWS |
| Guide Performance Work Statements |
| HCA |
| Head Contracting Agency |
| HVAC |
| Heating, Ventilation, and Air Conditioning |
| HSR |
| Heavy Solids Removal |
| ICAP |
| Infrastructure Condition Assessment Program |
| ICP |
| Integrated Contingency Plan |
| IDIQ |
| Indefinite Delivery Indefinite Quantity |
| IFLOLS |
| Improved Fresnel Lens Optical Landing System |
| IPM |
| Integrated Pest Management |
| IPMIS |
| Integrated Pest Management Information System |
| IPMP |
| Integrated Pest Management Plan |
| KO |
| Contracting Officer |
| LAN |
| Local Area Network |
| M |
| Monthly |
| MSDS |
| Material Safety Data Sheets |
| NFPA |
| National Fire Protection Association |
| NAVFAC |
| Naval Facilities Engineering Command |
| NMCI |
| Navy Marine Corps Intranet |
| NOSC |
| Navy-On-Scene Coordinator |
| PAP |
| Performance Assessment Plan |
| PAR |
| Performance Assessment Representative |
| PAW |
| Performance Assessment Worksheet |
| PEO |
| Program Executive Officer |
| PM |
| Project Manager |
| PRCSP |
| Permit Required Confined Space Program |
| PWS |
| Performance Work Statement |
| Q |
| Quarterly |
| QC |
| Quality Control |
| RPIE |
| Real Property Inventory Equipment |
| SC |
| Security Clearances |
| SCADA |
| Supervisory Control And Data Acquisition |
| SM |
| Semimonthly |
| SOP |
| Standard Operating Procedures |
| SPAR |
| Senior Performance Assessment Representative |
| SRM |
| Sustainment, Restoration and Modernization |
| TE |
| Technical Evaluation |
| UFC |
| Unified Facilities Criteria |
| UPV |
| Unfired Pressure Vessel |
| VIQ |
| Variation in Quantity |
| WBS |
| Work Breakdown Structure |
J-1502000-02 Facilities Description
| Location |
| Facility Number |
| Description |
| Area |
| Unit of Measure |
| Constructed |
| NAS Jacksonville |
| 512 |
| Integrated Training Center |
| 168,294 |
| SF |
| Aug-11 |
| NAS Jacksonville |
| 513 N |
| P-8A Training Facility |
| 58,265 |
| SF |
| Feb-14 |
| NAS Jacksonville |
| 513 S |
| Triton UAS Operator Training Facility |
| 8,970 |
| SF |
| Feb-14 |
| NAS Jacksonville |
| 514 |
| BAMS Mission Control Complex |
| 51,931 |
| SF |
| Nov-15 |
| NAS Jacksonville |
| 1003 |
| Fleet Support Facility |
| 10,311 |
| SF |
| Jul-08 |
J-1502000-03 Site Maps
Attachment J-1502000-03 Site Maps provided as a separate attachment (Provided as file name: J-1502000-03 Site Maps – NAS Jacksonville.pdf).
J-1502000-04 Not Used
Attachment J-1502000-05 Uniformat Classification
| Uniformat Classification & Description |
| Meter & Description |
D3020130 - Boiler, Cast Iron, Hot Water, Gas
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5370 - Record the condition of the Flue
CR-5380 - Record the condition of the Fuel System
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
CR-5690 - Record the condition of the Wiring/Connections
D3020134 - Boiler, Cast Iron, Steam, Gas
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5520 - Record the condition of the Pipes/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5380 - Record the condition of the Fuel System
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
CR-5690 - Record the condition of the Wiring/Connections
D3020138 - Boiler, Cast Iron, Steam, Gas/Oil
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5345 - Record the condition of the Feed Water System
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5370 - Record the condition of the Flue
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
D3020901 - Boiler, Cast Iron, HW, Oil
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5370 - Record the condition of the Flue
CR-5380 - Record the condition of the Fuel System
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
CR-5690 - Record the condition of the Wiring/Connections
D3020902 - Boiler, Cast Iron, Steam, Oil
CR-5060 - Record the condition of the Burner Assembly
CR-5200 - Record the condition of the Controls
CR-5365 - Record the condition of the Firebox/Fire Tubes
CR-5520 - Record the condition of the Pipes/Fittings/Valves
CR-5540 - Record the condition of the Pressure Vessel
D3030130 - Chiller, Reciprocating, Water Cooled
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5200 - Record the condition of the Controls
CR-5295 - Record the condition of the Enclosure
CR-5305 - Record the condition of the Evaporator
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5565 - Record the condition of the Receiver Tank
D3030135 - Chiller, Reciprocating, Air Cooled
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5295 - Record the condition of the Enclosure
CR-5305 - Record the condition of the Evaporator
CR-5520 - Record the condition of the Pipes/Fittings/Valves
CR-5565 - Record the condition of the Receiver Tank
CR-5690 - Record the condition of the Wiring/Connections
D3030140 - Chiller, Centrifugal, Water Cooled
CR-5110 - Record the condition of the Centrifugal Motor
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5210 - Record the condition of the Controls/Sensors
CR-5295 - Record the condition of the Enclosure
CR-5305 - Record the condition of the Evaporator
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5565 - Record the condition of the Receiver Tank
D3030145 - Chiller, Gas Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5200 - Record the condition of the Controls
CR-5295 - Record the condition of the Enclosure
CR-5305 - Record the condition of the Evaporator
CR-5430 - Record the condition of the Heat Generator
CR-5520 - Record the condition of the Pipes/Fittings/Valves
CR-5555 - Record the condition of the Receiver
D3030150 - Chiller, Steam Absorption, Water Cooled
CR-5000 - Record the condition of the Absorber
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5200 - Record the condition of the Controls
CR-5295 - Record the condition of the Enclosure
CR-5305 - Record the condition of the Evaporator
CR-5430 - Record the condition of the Heat Generator
CR-5520 - Record the condition of the Pipes/Fittings/Valves
CR-5555 - Record the condition of the Receiver
| D3030310 - Cooling Tower, Galvanized |
| CR-5025 - Record the condition of the Basin/Sump |
CR-5280 - Record the condition of the Electrodes
CR-5325 - Record the condition of the Fan Assembly
CR-5350 - Record the condition of the Fill Material
CR-5520 - Record the condition of the Pipes/Fittings/Valves
D3030320 - Cooling Tower, Fiberglass
CR-5025 - Record the condition of the Basin/Sump
CR-5280 - Record the condition of the Electrodes
CR-5325 - Record the condition of the Fan Assembly
CR-5350 - Record the condition of the Fill Material
CR-5520 - Record the condition of the Pipes/Fittings/Valves
D3030330 - Cooling Tower, Stainless Steel
CR-5025 - Record the condition of the Basin/Sump
CR-5280 - Record the condition of the Electrodes
CR-5325 - Record the condition of the Fan Assembly
CR-5350 - Record the condition of the Fill Material
CR-5520 - Record the condition of the Pipes/Fittings/Valves
D3030902 - Condenser, DX, Evaporative
CR-5325 - Record the condition of the Fan Assembly
CR-5495 - Record the condition of the Louvers
CR-5515 - Record the condition of the Nozzles
CR-5615 - Record the condition of the Sump Pump
CR-5690 - Record the condition of the Wiring/Connections
D3030903 - Packaged DX Refrigerant System
CR-5140 - Record the condition of the Compressor
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5185 - Record the condition of the Condensing Coils
CR-5200 - Record the condition of the Controls
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3040106 - Air Handling Unit, Field Fabricated
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5145 - Record the condition of the Condensate Piping
CR-5210 - Record the condition of the Controls/Sensors
CR-5235 - Record the condition of the Dampers
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5530 - Record the condition of the Piping/Fittings/Valves
D3040110 - Air Handling Unit, Central Station
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5200 - Record the condition of the Controls
CR-5235 - Record the condition of the Dampers
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5340 - Record the condition of the Fan(s) Assembly
CR-5495 - Record the condition of the Louvers
CR-5530 - Record the condition of the Piping/Fittings/Valves
D3040114 - Air Handling Unit, Rooftop
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5200 - Record the condition of the Controls
CR-5235 - Record the condition of the Dampers
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5340 - Record the condition of the Fan(s) Assembly
CR-5495 - Record the condition of the Louvers
CR-5530 - Record the condition of the Piping/Fittings/Valves
D3040220 - Fan System, Centrifugal In-Line
CR-5200 - Record the condition of the Controls
CR-5235 - Record the condition of the Dampers
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5690 - Record the condition of the Wiring/Connections
D3040230 - Fan System, Utility Set
CR-5330 - Record the condition of the Fan Assy
CR-5630 - Record the condition of the Switches Controls
CR-5690 - Record the condition of the Wiring/Connections
D3040240 - Fan System, Roof Exhaust
CR-5200 - Record the condition of the Controls
CR-5235 - Record the condition of the Dampers
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5690 - Record the condition of the Wiring/Connections
| D3040330 - Circulating Pump, End Suction |
| CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir |
| D3040340 - Circulating Pump, Double Suction |
| CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir |
D3040610 - Heat Exchanger, Plate Type
CR-5200 - Record the condition of the Controls
CR-5375 - Record the condition of the Frame/Supports
CR-5465 - Record the condition of the Insulation
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5570 - Record the condition of the Relief Valve
CR-5590 - Record the condition of the Steam Modulating Valve
D3040620 - Heat Exchanger, Shell Tube
CR-5200 - Record the condition of the Controls
CR-5375 - Record the condition of the Frame/Supports
CR-5465 - Record the condition of the Insulation
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5570 - Record the condition of the Relief Valve
CR-5590 - Record the condition of the Steam Modulating Valve
D3050170 - Split Systems With Air Cooled Condensing Units
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5460 - Record the condition of the Indoor Fan Motor Assembly
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050185 - Computer Room Cooling Units
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5150 - Record the condition of the Condensate Pump
CR-5210 - Record the condition of the Controls/Sensors
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5450 - Record the condition of the Humidifier
CR-5530 - Record the condition of the Piping/Fittings/Valves
D3050201 - Packaged A/C, Air Cooled, Elec Heat
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5275 - Record the condition of the Duct Connectors
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050203 - Packaged A/C, Air Cooled, HW Heat
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5275 - Record the condition of the Duct Connectors
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050210 - Packaged A/C, Water Cooled, Elec Heat
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050220 - Packaged A/C, Water Cooled, HW Heat
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5295 - Record the condition of the Enclosure
CR-5330 - Record the condition of the Fan Assy
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050255 - Thru-Wall A/C Unit
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5460 - Record the condition of the Indoor Fan Motor Assembly
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
D3050260 - Thru-Wall Heat Pump
CR-5120 - Record the condition of the Coils (Cooling)
CR-5125 - Record the condition of the Coils (Heating)
CR-5140 - Record the condition of the Compressor
CR-5155 - Record the condition of the Condenser
CR-5175 - Record the condition of the Condenser Fan(s) Assembly
CR-5200 - Record the condition of the Controls
CR-5260 - Record the condition of the Drain Pan
CR-5460 - Record the condition of the Indoor Fan Motor Assembly
CR-5530 - Record the condition of the Piping/Fittings/Valves
CR-5690 - Record the condition of the Wiring/Connections
CR-5035 - Record the condition of the Battery Rack
CR-5195 - Record the condition of the Control Panel
CR-5295 - Record the condition of the Enclosure
CR-5680 - Record the condition of the UPS Alarm System
Attachment J-1502000-06 Uniformat General Direct Condition Rating Guidance
| Rating |
| SRM Needs |
| Rating Definition |
| Green (+) |
| Sustainment consisting of possible preventive maintenance (where Applicable). |
| Entire component-section or component-section sample free of observable or known distress. |
| Green |
| Sustainment consisting of possible preventive maintenance (where applicable) and minor repairs (corrective maintenance) to possibly few or some subcomponents. |
| No component-section or sample serviceability* or reliability* reduction. Some, but not all, minor (non-critical) subcomponents may suffer from slight degradation or few major (critical) subcomponents may suffer from slight degradation. |
Green (-)
Slight or no serviceability or reliability reduction overall to the component-section or sample. Some, but not all, minor (non-critical) subcomponents may suffer from minor degradation or more than one major (critical) subcomponent may suffer from slight degradation.
| Amber (+) |
| Sustainment or restoration to any of the following: Minor repairs to several subcomponents; or Significant repair, rehabilitation, or replacement of one or more subcomponents, but not enough to encompass the component-section as a whole; or Combination thereof. |
| Component-section or sample serviceability or reliability is degraded, but adequate. A very few, major (critical) subcomponents may suffer from moderate deterioration with perhaps a few minor (non-critical) subcomponents suffering from severe deterioration. |
Amber
Component-section or sample serviceability or reliability is definitely impaired. Some, but not a majority, major (critical) subcomponents may suffer from moderate deterioration with perhaps many minor (non-critical) subcomponents suffering from severe deterioration.
Amber (-)
Component-section or sample has significant serviceability or reliability loss. Most subcomponents may suffer from moderate degradation or a few major (critical) subcomponents may suffer suffering from severe degradation.
| Red (+) |
| Sustainment or restoration required consisting of major repair, rehabilitation, or replacement to the component-section as a whole. |
| Significant serviceability or reliability reduction in component-section or sample. A majority of subcomponents are severely degraded and others may have varying degrees of degradation. |
Red
Severe serviceability or reliability reduction to the component-section or sample such that it is barely able to perform. Most subcomponents are severely degraded.
Red (-)
Overall component-section degradation is total. Few, if any, subcomponents are salvageable. Complete loss of component-section or sample serviceability.
Attachment J-1502000-07 Uniformat Condition Rating Guidance to Each Meter Group
| Meter |
| Direct Condition Rating Guidance |
| CR-5000 |
| GREEN: Absorber has minimal damage and corrosion, but no leaks |
AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired
| CR-5025 |
| GREEN: Sump has minimal damage or corrosion, no leaking |
AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, operationally impaired
| CR-5035 |
| GREEN: Battery Rack shows little to no signs of corrosion or damage. |
AMBER: Battery Rack shows minimal to noticeable corrosion or damage, but rack is structurally sound RED: Battery Rack shows significant signs of corrosion and/or the rack is significantly damaged, rack is structurally unsound.
| CR-5045 |
| GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational |
AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
| CR-5060 |
| GREEN: Burners have minimal damage or corrosion, but is fully operational |
AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound
| CR-5110 |
| GREEN: Motor operates properly, free of excessive noise/vibration, or overheating |
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
| CR-5115 |
| GREEN: Hook has minimal damage or wear, and is fully secured |
AMBER: Hook has noticeable damage or wear, but is still securely fastened RED: Hook has significant damage, connections not secure
| CR-5120 |
| GREEN: Coils have minimal scaling and free of debris. |
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
| CR-5125 |
| GREEN: Coils have minimal scaling and free of debris. |
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
| CR-5140 |
| GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational |
AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired
| CR-5145 |
| GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion |
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
| CR-5150 |
| GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational |
AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
| CR-5155 |
| GREEN: Minimal corrosion or fouling of the condenser/coils, no damage |
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired
| CR-5175 |
| GREEN: Motor operates properly, free of excessive noise/vibration, or overheating |
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
| CR-5185 |
| GREEN: Coils have minimal scaling and free of debris. |
AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.
RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.
| CR-5195 |
| GREEN: Controls function properly |
AMBER: Controls need calibrating RED: Controls are damaged and/or not operational
| CR-5200 |
| GREEN: Controls function properly |
AMBER: Controls need calibrating RED: Controls are damaged and/or not operational
| CR-5210 |
| GREEN: Controls function properly |
AMBER: Controls need calibrating RED: Controls are damaged and/or not operational
| CR-5225 |
| GREEN: Crane Unit shows minimal signs of wear, no loose components, structurally sound, fully operational |
AMBER: Crane Unit shows noticeable signs of damage or wear, but no loose or missing components, and still operational RED: Crane Unit shows significant signs of damage or wear, may have missing or loose components, comprised structural integrity, or is operationally impaired
| CR-5235 |
| GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational |
AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired
| CR-5260 |
| GREEN: Drain Pan has minimal damage or corrosion |
AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks
| CR-5275 |
| GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages |
AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired
| CR-5280 |
| GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional |
AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired
| CR-5290 |
| GREEN: Encasement/Deflector has minimal damage or deterioration, and is fully secured |
AMBER: Encasement/Deflector has noticeable damage or deterioration, some panels may be loose or displaced RED: Encasement/Deflector has significant damage, panels are displaced or missing
| CR-5295 |
| GREEN: Minimal damage and corrosion on Enclosure, fully secured |
AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing
| CR-5305 |
| GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage |
AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired
| CR-5325 |
| GREEN: Fan blades are in balance and free of damage or corrosion |
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
| CR-5330 |
| GREEN: Fan blades are in balance and free of damage or corrosion |
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
| CR-5340 |
| GREEN: Fan blades are in balance and free of damage or corrosion |
AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired
| CR-5345 |
| GREEN: Feed Water System has no damage or leaks, fully operational |
AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly
| CR-5350 |
| GREEN: Filter has minimal to no dirt and debris, free of damage |
AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips
| CR-5365 |
| GREEN: Firebox has minimal damage or corrosion |
AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present
| CR-5370 |
| GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational |
AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired
| CR-5375 |
| GREEN: Supports have minimal damage and corrosion, are fully stable and secure |
AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured
| CR-5380 |
| GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational |
AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired
| CR-5410 |
| GREEN: Guide Wheels show little to no wear or damage, are securely fastened, and fully functional |
AMBER: Guide Wheels have noticeable wear, may have slight damage, but are secure and still operational RED: Guide Wheels have significant damage, may be loose, displaced, missing, or operationally impaired
| CR-5430 |
| GREEN: Heating Element has little to no damage or corrosion, and is fully operational |
AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, operationally impaired
| CR-5445 |
| GREEN: Motor operates properly, free of excessive noise/vibration, or overheating |
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
| CR-5450 |
| GREEN: Pan has minimal damage or corrosion |
AMBER: Pan has noticeable damage or corrosion, but no leaks RED: Pan has significant damage or corrosion, and noticeable leaks
| CR-5460 |
| GREEN: Motor operates properly, free of excessive noise/vibration, or overheating |
AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired
| CR-5465 |
| GREEN: Insulation has minimal deterioration, and is mostly in place where necessary |
AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing
| CR-5495 |
| GREEN: Louvers have minimal damage and corrosion, fully secured |
AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired
| CR-5515 |
| GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational |
AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired
| CR-5520 |
| GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion |
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
| CR-5530 |
| GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion |
AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs
| CR-5540 |
| GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure |
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
| CR-5555 |
| GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure |
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
| CR-5565 |
| GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure |
AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured
| CR-5570 |
| GREEN: Valve has little to no damage or corrosion, is fully operational |
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired
| CR-5590 |
| GREEN: Valve has little to no damage or corrosion, is fully operational |
AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired
| CR-5610 |
| GREEN: Structural Frame has minimal damage and corrosion, is square and securely fastened |
AMBER: Structural Frame has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety RED: Structural Frame has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation
| CR-5615 |
| GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational |
AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired
| CR-5630 |
| GREEN: Switches function properly |
AMBER: None RED: Switches do not function properly
| CR-5660 |
| GREEN: Trolley Drive has minimal to no damage, operation is smooth, fully functional |
AMBER: Trolley Drive has noticeable damage, wear, may require adjustments but is fully functional RED: Trolley Drive has significant damage or wear, operation is significantly impaired
| CR-5680 |
| GREEN: UPS Alarm System functions properly |
AMBER: None RED: UPS Alarm System does not function properly
| CR-5690 |
| GREEN: Wiring is protected/insulated and connections are secure |
AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding
J-1502000-08 Temperature Standards for HVAC and Refrigeration Systems
HVAC Systems
Degrees Fahrenheit dry bulb
| Area |
| Cooling Season |
| Heating Season |
| Living & Admin. Areas (Inactive Employment) |
| 73 |
| 68 |
| Working Areas (Active Employment) |
| 78 |
| 68 |
| Storage Areas |
| 78 |
| 40 |
| Computer Areas |
| 70 |
| 68 |
| Training Areas |
| 75 |
| 68 |
Refrigeration Systems
| Type |
| Degrees Fahrenheit |
| Frozen Meat |
| 0 to 5 |
| Fresh Meat |
| 30 to 34 |
| Ice Storage |
| 28 to 30 |
| Dairy Products |
| 32 to 34 |
| Ice Cream |
| 0 to 5 |
| Beer |
| 35 to 39 |
| Fruits and Vegetables |
| 36 to 42 |
| Chill Room |
| 35 to 39 |
J-1502000-09 Not Used
J-1502000-10
HVAC INVENTORY
HVAC and Refrigeration Systems commence at and include the utility isolation point of connection and terminate at the conditioned air point of delivery. The Contractor shall develop and implement an IMP for the HVAC and Refrigeration Systems and all mechanically and electrically interlocked ancillary parts, equipment, and components of the HVAC and Refrigeration Systems such as: air handling units, blowers, boilers, chillers, compressors (including air compressors), condensers, controls (excluding TRACER ES), cooling towers, dehumidifiers, diffusers, driers, ducts, electrical disconnects, evaporators, fans, fan coil units, filters, fire dampers, fresh air dampers, heaters, heat exchangers, heat pumps, hoods, humidification systems, insulation, intakes, package units, piping, pumps, refrigeration boxes, registers, returns, strainers, ultraviolet lighting, valves, VAV boxes, variable frequency drives, water treatment systems, monitoring, control, and instrumentation systems, etc.
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 512 |
| CRACU |
| 01 |
| Liebert |
| CW106CDVA24727S |
| C10M140066 |
| TD 111 |
| 322 |
| 512 |
| CRACU |
| 02 |
| Leibert |
| CW106DCVA24727S |
| C10M140065 |
| TD 111 |
| 322 |
| 512 |
| CRACU |
| 03 |
| Leibert |
| CW181DC1A14726A |
| C10M170028 |
| TD 112 |
| 619 |
| 512 |
| CRACU |
| 04 |
| Leibert |
| CW181DC1A14726A |
| C10M170027 |
| TD 112 |
| 619 |
| 512 |
| CRACU |
| 05 |
| Leibert |
| CW060DCVA24727S |
| C10M140086 |
| TD 114 |
| 200 |
| 512 |
| CRACU |
| 06 |
| Leibert |
| CW060DCVA24727S |
| C10M140086 |
| TD 114 |
| 200 |
| 512 |
| CRACU |
| 07 |
| Leibert |
| CW181DC1A14726A |
| C10M170029 |
| TD 115 |
| 586 |
| 512 |
| CRACU |
| 08 |
| Leibert |
| CW060DCVA24727S |
| C10M140140 |
| TD 117 |
| 200 |
| 512 |
| CRACU |
| 09 |
| Leibert |
| CW060DCVA24727S |
| C10M140085 |
| TD 117 |
| 200 |
| 512 |
| CRACU |
| 10 |
| Leibert |
| CW114DCVA24727S |
| C10M140070 |
| TD 127 |
| 472 |
| 512 |
| CRACU |
| 10A |
| Leibert |
| CW114DCVA24727S |
| C10M140068 |
| TD 127 |
| 472 |
| 512 |
| CRACU |
| 11 |
| Leibert |
| CW114DCVA24727S |
| C10M140077 |
| TD 127 |
| 472 |
| 512 |
| CRACU |
| 11A |
| Leibert |
| CW114DCVA24727S |
| C10M140071 |
| TD 127 |
| 472 |
| 512 |
| CRACU |
| 12 |
| Leibert |
| CW114DCVA24727S |
| C10M140072 |
| TD 128 |
| 472 |
| 512 |
| CRACU |
| 12A |
| Leibert |
| CW114DCVA24727S |
| C10M140069 |
| TD 128 |
| 472 |
| 512 |
| CRACU |
| 13 |
| Leibert |
| CW114DCVA24727S |
| C10M140078 |
| TD 128 |
| 472 |
| 512 |
| CRACU |
| 13A |
| Leibert |
| CW114DCVA24727S |
| C10M140067 |
| TD 128 |
| 472 |
| 512 |
| CRACU |
| 14 |
| Leibert |
| CW181DC1A14726A |
| C10M170026 |
| SAPF 110 |
| 588 |
| 512 |
| CRACU |
| 15 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205902 |
| TD 139 |
| 49.6 |
| 512 |
| CRACU |
| 16 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205959 |
| TD 138 |
| 49.6 |
| 512 |
| CRACU |
| 17 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205895 |
| TD 140 |
| 49.6 |
| 512 |
| CRACU |
| 18 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205918 |
| AC 116 |
| 49.6 |
| 512 |
| CRACU |
| 19 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205955 |
| TD 141 |
| 49.6 |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 512 |
| CRACU |
| 20 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205921 |
| TD 255 |
| 49.6 |
| 512 |
| CRACU |
| 21 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205966 |
| TD 252 |
| 49.6 |
| 512 |
| CRACU |
| 22 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205899 |
| TD 253 |
| 49.6 |
| 512 |
| CRACU |
| 23 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205909 |
| TD 254 |
| 49.6 |
| 512 |
| CRACU |
| 24 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205919 |
| TD 251 |
| 49.6 |
| 512 |
| CRACU |
| 25 |
| Leibert |
| CW038DCVA24727S |
| C10M140138 |
| TD 240 |
| 106 |
| 512 |
| CRACU |
| 26 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205926 |
| SAPF 122 |
| 49.6 |
| 512 |
| CRACU |
| 27 |
| Leibert |
| MMD92C2A0EHB |
| 1046N205961 |
| SAPF 111 |
| 49.6 |
| CRACU Telecom |
| Total= 10 |
On Trane inventory list – All accounted
| CRACU Data Center |
| Total= 21 |
On Trane inventory list – All accounted
| 512 |
| AHU |
| 01 |
| MCCB057UA0DOUB000 |
| K10G71076 |
| 3rd Floor Equip. Rm. Platform |
| 512 |
| AHU |
| 02 |
| MCCB080UA0COUA000 |
| K10G71085 |
| 3rd Floor Equip. Rm. Platform |
| 512 |
| AHU |
| 03 |
| MCCB021UA0DOUA000 |
| K10G71120 |
| Mechanical Rm. AC 112 |
| 512 |
| AHU |
| 04 |
| MCCB080UA0COUA000 |
| K10G71093 |
| 3rd Floor Equip. Rm. Platform |
| 512 |
| AHU |
| 05 |
| MCCB080UA0COUB000 |
| K10G71164 |
| 3rd Floor Equip. Rm. Platform |
| 512 |
| AHU |
| 06 |
| MCCB050UA0DOUA000 |
| K10G71102 |
| Mechanical Rm. AC 114 |
| 512 |
| AHU |
| 07 |
| MCCB021UA0DOUA000 |
| K10G71154 |
| SAPH |
| 512 |
| AHU |
| 08 |
| MCCB017UA0DOUA000 |
| K10G71129 |
| Mechanical Rm. AC 114 |
| 512 |
| AHU |
| 09 |
| MCCB012UA0D0UA000 |
| K10G71138 |
| 3rd Floor Equip. Platform |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 512 |
| AHU |
| 10 |
| MCCB008UA0DOUB000 |
| K10G711147 |
| 512 CEP |
| 512 |
| Boiler |
| 01 |
| Benchmark |
| BMK 1.5 |
| G-10-2167 |
| 512 CEP |
| 512 |
| Boiler |
| 02 |
| Benchmark |
| BMK 1.5 |
| G-10-2168 |
| 512 CEP |
| 512 |
| Chiller |
| 01 |
| Trane |
| CVHF058FA4A0PCT2698ABE8TBC0000000HE00070L00000 |
| L10J04971 |
| 512 CEP |
| 512 |
| Chiller |
| 02 |
| Trane |
| CVHF058FA4A0PCT2698ABE8TBC0000000HE00070L00000 |
| L10J04972 |
| 512 CEP |
| 512 |
| Chiller |
| 03 |
| Trane |
| CVHF058FA4A0PCT2698ABE8TBC0000000HE00070L00000 |
| L10J04973 |
| 512 CEP |
| 512 |
| Cooling Tower |
| 01 |
| 512 |
| Cooling Tower |
| 02 |
| 512 |
| Cooling Tower |
| 03 |
| 512 |
| VAV |
| Total= 59 |
| 512 |
| Fan Power Boxes |
| Total= 75 |
| 512 |
| DOA MAU |
| 01 |
| MCCB050 |
| K10G71110 |
| 3rd Floor Equip. Platform |
| 512 |
| CHWP |
| 01 |
| 512 |
| CHWP |
| 02 |
| 512 |
| CHWP |
| 03 |
| 512 |
| PCWP |
| 01 |
| 512 |
| PCWP |
| 02 |
| 512 |
| PCWP |
| 03 |
| 512 |
| SCWP |
| 04 |
| 512 |
| SCWP |
| 05 |
| 512 |
| SCWP |
| 06 |
| 512 |
| SCWP |
| 07 |
| 512 |
| PHWP |
| 01 |
| 512 |
| PHWP |
| 02 |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 512 |
| PHWP |
| 03 |
| 512 |
| Tracer Controls |
| Total= 3 |
| 512 |
| Exhaust Fans |
| Total= 3 |
| 512 |
| In Line Fan |
| 01 |
AHU 6
| 512 |
| In Line Fan |
| 02 |
DOAS
| 512 |
| In Line Fan |
| 03 |
AC 211
| 512 |
| In Line Fan |
| 04 |
AHU 7
| 512 |
| In Line Fan |
| 05 |
Dty. Offc.
| 512 |
| VFD |
| AHU-01 |
512 CEP
| 512 |
| VFD |
| AHU-02 |
| 512 |
| VFD |
| AHU-03 |
| 512 |
| VFD |
| AHU-04 |
| 512 |
| VFD |
| AHU-05 |
| 512 |
| VFD |
| AHU-06 |
| 512 |
| VFD |
| AHU-06 BF |
| 512 |
| VFD |
| AHU-07 SPLY |
| 512 |
| VFD |
| AHU-07 RETN |
| 512 |
| VFD |
| AHU-07 BF |
| 512 |
| VFD |
| AHU-08 |
| 512 |
| VFD |
| AHU-09 |
| 512 |
| VFD |
| DOAS SPLY |
| 512 |
| VFD |
| DOAS EXHST |
| 512 |
| Chill Water Treatment |
| 1 |
512 CEP
| 512 |
| Hot Water Treatment |
| 1 |
512 CEP
| 514 |
| CHW AHU |
| 01 |
| Trane |
| TR 200 |
| 672804Y055 |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 514 |
| CHW AHU |
| 02 |
| Trane |
| TR 200 |
| 672904Y055 |
| 514 |
| CHWP |
| 01 |
| Trane |
| TR 200 |
| 667604Y055 |
| 514 |
| CHWP |
| 02 |
| Trane |
| TR 200 |
| 996802G315 |
| 514 |
| SHWP |
| 01 |
| Trane |
| TR 200 |
| 667304Y055 |
| 514 |
| SHWP |
| 02 |
| Trane |
| TR 200 |
| 667404Y055 |
| 514 |
| PHWP |
| 01 |
| 514 |
| PHWP |
| 02 |
| 514 |
| Air Cooled Chiller |
| 01 |
| Arctic Cool Chiller Ltd. |
| ACA165BT3010F - 165 TON |
| AC1405284 |
| Chiller yard |
| 514 |
| Air Cooled Chiller |
| 02 |
| Arctic Cool Chiller Ltd. |
| ACA165BT3010F - 165 TON |
| AC14005285 |
| Chiller yard |
| 514 |
| FCU |
| 01 |
| 514 |
| FCU |
| 02 |
| 514 |
| FCU |
| 03 |
| 514 |
| FCU |
| 04 |
| 514 |
| FCU |
| 05 |
Boiler
| Raypak Xfyre |
| H7-0700A |
| D1140400022 |
| Mech. Rm. |
| 514 |
| Boiler |
| Raypak Xfryre |
| H7-0700A |
| D1140400033 |
| Mech. Rm. |
| 514 |
| VAV |
| Total= 50 |
| 514 |
| Controls |
| 1 |
| Trane Tracer |
| 514 |
| VFD |
| Total= 6 |
| 514 |
| ERV |
| Total= 1 |
| 514 |
| Split DX Units |
| Total= 3 |
| 514 |
| Chill Water Treatment |
| 1 |
| 514 |
| Hot Water Treatment |
| 1 |
| 514 |
| Air Cooled Chiller |
| 01/ labeled #3 |
| Trane- 60 ton |
| J18H69631 |
| Chiller Yard |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| 514 |
| Air Cooled Chiller |
| 02/ labeled #4 |
| Trane- 60 ton |
| U18H69630 |
| Chiller yard |
| 514 |
| CHW AHU |
| 01 |
| 514 |
| CHW AHU |
| 02 |
| 514 |
| CHW AHU |
| 03 |
| 514 |
| Boiler |
| 01 |
| Weil-McLain |
| EVG-220 / 220 MBH |
| 514 |
| Boiler |
| 02 |
| Weil-McLain |
| EVG-220 / 220 MBH |
| 514 |
| ERU |
| 01 |
| 514 |
| VAV |
| Total= 13 |
| 1003 |
| MAU |
| 01 |
| 1003 |
| FCU |
| 01 |
| 1003 |
| FCU |
| 02 |
| 1003 |
| FCU |
| 03 |
| 1003 |
| FCU |
| 04 |
| 1003 |
| FCU |
| 05 |
| 1003 |
| FCU |
| 06 |
| 1003 |
| FCU |
| 07 |
| 1003 |
| FCU |
| 08 |
| 1003 |
| FCU |
| 09 |
| 1003 |
| FCU |
| 10 |
| 1003 |
| FCU |
| 11 |
| 1003 |
| FCU |
| 12 |
| 1003 |
| FCU |
| 13 |
| 1003 |
| FCU |
| 14 |
| 1003 |
| FCU |
| 16 |
| 1003 |
| CHWP |
| 01 |
| 1003 |
| CHWP |
| 02 |
| 1003 |
| Air Cooled Chiller |
| 01 |
| York International |
| YCAL-0041EC - 40 TON |
| SFTM-000320 |
| 1003 |
| CHW AHU |
| Total= 16 |
| 1003 |
| DX Split Systems |
| Total= 3 |
| Facility # |
| Name/ Description |
| Equipment # |
| Manufacturer |
| Model # |
| Serial # |
| Location |
| Total KBTUH |
| 1003 |
| Pump |
| 01 |
| 1003 |
| Pump |
| 02 |
| 1003 |
| Exhaust fan |
| Total= 2 |
| 1003 |
| Water Treatment |
| 01 |
| 1003 |
| Tracer Control |
| Total= 2 |
NAS Jacksonville Vital HVAC Mission Critical Solicitation Page 1 of 23
File details come from the government source that posted it. Updated .