AHU 33 Terminal unit report.pdf

PDF 48 KB Posted

Attached to
Y1DA--648-349 Construct Space for the Surgical Service Minor Construction - Portland, OR VAMC
Solicitation number
IFB-36C77625B0017
Issued by

About this file

This document is a Delta Controls Report 24 showing detailed airflow measurements for multiple ventilation units (VVRs, VVUs, CVRs, CVUs) at a VA Medical Center. The report provides comprehensive flow data for 30 different devices, including their current cubic feet per minute (CFM) readings, setpoint values, minimum setpoint values, and flow error measurements. Each device is identified by a specific location code (e.g., 3C162c, C3-30 NORTH) and assigned a unique device number, with measurements ranging from as low as 0.0 cfm to as high as 2,435.1 cfm for the OR8 SUPPLY CVR 33 29 unit. The final entry shows a cooling demand of 3.5% for AHU33, with a total of 125 objects recorded in the report.

View the file

Other files

File Type Posted
Amendment 6 - 36C77625B0017 0006 8-12-2025.pdf PDF
20250811 - RFI TRACKING SHEET - SOLICITATION 36C77625B0017 - Project 648-349.pdf PDF
Amendment 5 - 36C77625B0017 0005 8-11-2025.pdf PDF
Wage rates Multnomah 8-8-2025.pdf PDF
20250807_RFI TRACKING SHEET - SOLICITATION 36C77625B0017 - Project 648-349.pdf PDF
Online Bid Opening Meeting Info.docx DOCX document
Amendment 4 - 36C77625B0017 0004 8-7-2025.pdf PDF
00 01 10 - Table of Contents.pdf PDF
Amendment 3 - 36C77625B0017 0003 7-30-25.pdf PDF
20250729_PVAMC Surgical Suite Expansion_Add001.pdf PDF
Wage rates Multnomah 7-25-2025.pdf PDF
As-Built Plan Roof Details.pdf PDF
RFI TRACKING SHEET - SOLICITATION 36C77625B0017 - Project 648-349.pdf PDF
100-SF-33 fan data.pdf PDF
Addendum 001 - MA Architects.pdf PDF
26 08 00 Commissioning of Electrical Systems.pdf PDF
Wage rates Multnomah 7-11-2025.pdf PDF
Amendment 2 - 36C77625B0017 0002 7-21-25.pdf PDF
Amendment 1 - 36C77625B0017 0001 7-10-25.pdf PDF
Wage rates Multnomah 7-4-2025.pdf PDF
Contractor sign in.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 4 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 3.pdf PDF
Attachment 1 - 648-349 VAPHCS Specs 100Pct BID Set REV 3.pdf PDF
Attachment 7 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 6.pdf PDF
Attachment 10 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 9.pdf PDF
Attachment 2 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 1.pdf PDF
Attachment 14 - Infection Control Risk Assessement - ICRA 648-349.pdf PDF
Attachment 11 - Brand Name Justification - Portland_Redacted.pdf PDF
Attachment 8 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 7.pdf PDF
Attachment 17 - RFI TRACKING SHEET - SOLICITATION 36C77625B0017 - Project 648-349.xlsx XLSX spreadsheet
Attachment 12 - Wage rates Multnomah 5-30-2025.pdf PDF
Attachment 5 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 4.pdf PDF
IFB 36C77625B0017.pdf PDF
Attachment 13 - PreConstruction Risk Assessment - PCRA 648-349.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 15 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 9 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 8.pdf PDF
Attachment 3 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 2.pdf PDF
Attachment 6 - 648-349 VAPHCS - Space for Surgical Service Plans BID Set Part 5.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Site:

17-Nov-2023 10:21:26 AMGenerated On:

VAMC

Report 24 av10 av11 av12 1v13 av14

3C162c_VVR_33_01 (2501)

Device Unit s

ValueObject IDName

VVR_33_01_FLOW_CFM 2501 2501.AV10 838.9 cfm

VVR_33_01_FLOW_SP 2501 2501.AV11 840.0 cfm

VVR_33_01_FLOW_MIN_S

P

2501 2501.AV12 840.0 cfm

VVR_33_01_FLOW_ERRO

R_CFM

2501 2501.AV14 1.1 cfm

3C162a_VVR_33_02 (2502)

Device Unit s

ValueObject IDName

VVR_33_02_FLOW_CFM 2502 2502.AV10 395.2 cfm

VVR_33_02_FLOW_SP 2502 2502.AV11 400.0 cfm

VVR_33_02_FLOW_MIN_S

P

2502 2502.AV12 420.0 cfm

VVR_33_02_FLOW_ERRO

R_CFM

2502 2502.AV14 8.4 cfm

3C161a_VVR_33_03 (2503)

Device Unit s

ValueObject IDName

VVR_33_03_FLOW_CFM 2503 2503.AV10 139.2 cfm

VVR_33_03_FLOW_SP 2503 2503.AV11 140.0 cfm

VVR_33_03_FLOW_MIN_S

P

2503 2503.AV12 140.0 cfm

VVR_33_03_FLOW_ERRO

R_CFM

2503 2503.AV14 0.8 cfm

C3_30_NORTH_VVR_33_04 (2504)

Device Unit s

ValueObject IDName

VVR_33_04_FLOW_CFM 2504 2504.AV10 280.5 cfm

VVR_33_04_FLOW_SP 2504 2504.AV11 280.0 cfm

VVR_33_04_FLOW_MIN_S

P

2504 2504.AV12 280.0 cfm

VVR_33_04_FLOW_ERRO

R_CFM

2504 2504.AV14 0.5 cfm

Rev 1.0

Generated by ORCAview

Unit s

ValueObject IDNameDevice

C3-30_SOUTH_VVR_33_05 (2505)

Device Unit s

ValueObject IDName

VVR_33_05_FLOW_CFM 2505 2505.AV10 428.4 cfm

VVR_33_05_FLOW_SP 2505 2505.AV11 420.0 cfm

VVR_33_05_FLOW_MIN_S

P

2505 2505.AV12 420.0 cfm

VVR_33_05_FLOW_ERRO

R_CFM

2505 2505.AV14 7.7 cfm

3C162J_VVR_33_06 (2506)

Device Unit s

ValueObject IDName

3C162J_VVR_33_06_FLO

W_CFM

2506 2506.AV10 945.7 cfm

3C162J_VVR_33_06_FLO

W_SP

2506 2506.AV11 965.0 cfm

3C162J_VVR_33_06_FLO

W_MIN_SP

2506 2506.AV12 965.0 cfm

3C162J_VVR_33_06_FLO

W_ERROR_CFM

2506 2506.AV14 19.3 cfm

3C162e_VVR_33_07 (2507)

Device Unit s

ValueObject IDName

VVR_33_07_FLOW_CFM 2507 2507.AV10 831.4 cfm

VVR_33_07_FLOW_SP 2507 2507.AV11 901.0 cfm

VVR_33_07_FLOW_MIN_S

P

2507 2507.AV12 700.0 cfm

VVR_33_07_FLOW_ERRO

R_CFM

2507 2507.AV14 69.6 cfm

3C Room 156 VVR 3308 (2508)

Device Unit s

ValueObject IDName

FLOW_CFM 2508 2508.AV10 319.0 cfm

FLOW_SP 2508 2508.AV11 320.0 cfm

FLOW_MIN_SP 2508 2508.AV12 140.0 cfm

FLOW_ERROR_CFM 2508 2508.AV14 1.0 cfm

C3-39_WEST_VVU_33_09 (2509)

Device Unit s

ValueObject IDName

VVU_33_09_FLOW_CFM 2509 2509.AV10 193.3 cfm

VVU_33_09_FLOW_SP 2509 2509.AV11 200.0 cfm

VVU_33_09_FLOW_MIN_S

P

2509 2509.AV12 0.0 cfm

ValueObject IDNameDevice

VVU_33_09_FLOW_ERRO

R_CFM

2509 2509.AV14 6.7 cfm

3C162_CVU_33_10 (2510)

Device Unit s

ValueObject IDName

CVU_33_10_FLOW_CFM 2510 2510.AV10 525.8 cfm

CVU_33_10_FLOW_SP 2510 2510.AV11 540.0 cfm

CVU_33_10_FLOW_MIN_S

P

2510 2510.AV12 0.0 cfm

CVU_33_10_FLOW_ERRO

R_CFM

2510 2510.AV14 14.2 cfm

3C159_CVR_33_11 (2511)

Device Unit s

ValueObject IDName

CVR_33_11_FLOW_CFM 2511 2511.AV10 222.1 cfm

CVR_33_11_FLOW_SP 2511 2511.AV11 220.0 cfm

CVR_33_11_FLOW_MIN_S

P

2511 2511.AV12 220.0 cfm

CVR_33_11_FLOW_ERRO

R_CFM

2511 2511.AV14 2.1 cfm

3C159 _VVR_33_12 (2512)

Device Unit s

ValueObject IDName

VVR_33_12_FLOW_CFM 2512 2512.AV10 439.0 cfm

VVR_33_12_FLOW_SP 2512 2512.AV11 436.0 cfm

VVR_33_12_FLOW_MIN_S

P

2512 2512.AV12 235.0 cfm

VVR_33_12_FLOW_ERRO

R_CFM

2512 2512.AV14 3.0 cfm

3C159_CVR_33_13 (2513)

Device Unit s

ValueObject IDName

CVR_33_13_FLOW_CFM 2513 2513.AV10 155.4 cfm

CVR_33_13_FLOW_SP 2513 2513.AV11 320.0 cfm

CVR_33_13_FLOW_MIN_S

P

2513 2513.AV12 320.0 cfm

CVR_33_13_FLOW_ERRO

R_CFM

2513 2513.AV14 164.6 cfm

3C159_CVR_33_14 (2514)

Device Unit s

ValueObject IDName

CVR_33_14_FLOW_CFM 2514 2514.AV10 218.1 cfm

CVR_33_14_FLOW_SP 2514 2514.AV11 220.0 cfm

ValueObject IDNameDevice

CVR_33_14_FLOW_MIN_S

P

2514 2514.AV12 220.0 cfm

CVR_33_14_FLOW_ERRO

R_CFM

2514 2514.AV14 1.9 cfm

3C141_VVU_33_15 (2515)

Device Unit s

ValueObject IDName

VVU_33_15_FLOW_CFM 2515 2515.AV10 46.3 cfm

VVU_33_15_FLOW_SP 2515 2515.AV11 46.0 cfm

VVU_33_15_FLOW_MIN_S

P

2515 2515.AV12 0.0 cfm

VVU_33_15_FLOW_ERRO

R_CFM

2515 2515.AV14 0.3 cfm

3C137_VVU_33_16 (2516)

Device Unit s

ValueObject IDName

VVU_33_16_FLOW_CFM 2516 2516.AV10 60.0 cfm

VVU_33_16_FLOW_SP 2516 2516.AV11 50.0 cfm

VVU_33_16_FLOW_MIN_S

P

2516 2516.AV12 50.0 cfm

VVU_33_16_FLOW_ERRO

R_CFM

2516 2516.AV14 10.0 cfm

C3-31_VVU_33_17 (2517)

Device Unit s

ValueObject IDName

VVU_33_17_FLOW_CFM 2517 2517.AV10 25.2 cfm

VVU_33_17_FLOW_SP 2517 2517.AV11 0.0 cfm

VVU_33_17_FLOW_MIN_S

P

2517 2517.AV12 0.0 cfm

VVU_33_17_FLOW_ERRO

R_CFM

2517 2517.AV14 25.2 cfm

C3-28_VVU_33_18 (2518)

Device Unit s

ValueObject IDName

VVU_33_18_FLOW_CFM 2518 2518.AV10 146.2 cfm

VVU_33_18_FLOW_SP 2518 2518.AV11 140.0 cfm

VVU_33_18_FLOW_MIN_S

P

2518 2518.AV12 0.0 cfm

VVU_33_18_FLOW_ERRO

R_CFM

2518 2518.AV14 6.2 cfm

C3-28_WEST_VVU_33_19 (2519)

Device Unit s

ValueObject IDName

VVU_33_19_FLOW_CFM 2519 2519.AV10 0.0 cfm

ValueObject IDNameDevice

VVU_33_19_FLOW_SP 2519 2519.AV11 0.0 cfm

VVU_33_19_FLOW_MIN_S

P

2519 2519.AV12 0.0 cfm

VVU_33_19_FLOW_ERRO

R_CFM

2519 2519.AV14 0.0 cfm

C3-28_MID_VVU_33_20 (2520)

Device Unit s

ValueObject IDName

VVU_33_10_FLOW_CFM 2520 2520.AV10 20.0 cfm

VVU_33_10_FLOW_SP 2520 2520.AV11 0.0 cfm

VVU_33_10_FLOW_MIN_S

P

2520 2520.AV12 0.0 cfm

VVU_33_10_FLOW_ERRO

R_CFM

2520 2520.AV14 20.0 cfm

3C163_VVU_33_21 (2521)

Device Unit s

ValueObject IDName

3C163_VVU_33_21_FLOW

_CFM

2521 2521.AV10 79.6 cfm

3C163_VVU_33_21_FLOW

_SP

2521 2521.AV11 0.0 cfm

3C163_VVU_33_21_FLOW

_MIN_SP

2521 2521.AV12 0.0 cfm

3C163_VVU_33_21_FLOW

_ERROR_CFM

2521 2521.AV14 79.6 cfm

3C100g_VVU_33_22 (2522)

Device Unit s

ValueObject IDName

3C100g_VVU_33_22_FLO

W_CFM

2522 2522.AV10 0.0 cfm

3C100g_VVU_33_22_FLO

W_SP

2522 2522.AV11 380.0 cfm

3C100g_VVU_33_22_FLO

W_MIN_SP

2522 2522.AV12 0.0 cfm

3C100g_VVU_33_22_FLO

W_ERROR_CFM

2522 2522.AV14 380.0 cfm

3C100vestibule_VVU_33_23 (2523)

Device Unit s

ValueObject IDName

VVU_33_23_FLOW_CFM 2523 2523.AV10 104.8 cfm

VVU_33_23_FLOW_SP 2523 2523.AV11 50.0 cfm

VVU_33_23_FLOW_MIN_S

P

2523 2523.AV12 50.0 cfm

VVU_33_23_FLOW_ERRO

R_CFM

2523 2523.AV14 54.8 cfm

ValueObject IDNameDevice

3C150_VVU_33_24 (2524)

Device Unit s

ValueObject IDName

VVU_33_24_FLOW_CFM 2524 2524.AV10 205.5 cfm

VVU_33_24_FLOW_SP 2524 2524.AV11 200.0 cfm

VVU_33_24_FLOW_MIN_S

P

2524 2524.AV12 200.0 cfm

VVU_33_24_FLOW_ERRO

R_CFM

2524 2524.AV14 5.5 cfm

3C145_VVR_33_25 (2525)

Device Unit s

ValueObject IDName

3C145_VVR_33_25_FLOW

_CFM

2525 2525.AV10 110.3 cfm

3C145_VVR_33_25_FLOW

_SP

2525 2525.AV11 115.0 cfm

3C145_VVR_33_25_FLOW

_MIN_SP

2525 2525.AV12 100.0 cfm

3C145_VVR_33_25_FLOW

_ERROR_CFM

2525 2525.AV14 4.7 cfm

3C100d_VVU_33_26 (2526)

Device Unit s

ValueObject IDName

3C100d_VVU_33_26_FLO

W_CFM

2526 2526.AV10 0.0 cfm

3C100d_VVU_33_26_FLO

W_SP

2526 2526.AV11 0.0 cfm

3C100d_VVU_33_26_FLO

W_MIN_SP

2526 2526.AV12 0.0 cfm

3C100d_VVU_33_26_FLO

W_ERROR_CFM

2526 2526.AV14 0.0 cfm

3C-100C Exam/Treat/Proc #2_VVR_33-27 (2527)

Device Unit s

ValueObject IDName

RM_3C_100C_FLOW_CFM 2527 2527.AV10 179.2 cfm

RM_3C_100C_FLOW_SP 2527 2527.AV11 180.0 cfm

RM_3C_100C_FLOW_MIN_

SP

2527 2527.AV12 180.0 cfm

RM_3C_100C_FLOW_ERR

OR_CFM

2527 2527.AV14 0.8 cfm

3C115_VVR_33_28 (2528)

Device Unit s

ValueObject IDName

VVR_33_28_FLOW_CFM 2528 2528.AV10 195.4 cfm

VVR_33_28_FLOW_SP 2528 2528.AV11 200.0 cfm

ValueObject IDNameDevice

VVR_33_28_FLOW_MIN_S

P

2528 2528.AV12 200.0 cfm

VVR_33_28_FLOW_ERRO

R_CFM

2528 2528.AV14 4.6 cfm

OR8 SUPPLY CVR_33_29 (2529)

Device Unit s

ValueObject IDName

VVR_33_29_FLOW_CFM 2529 2529.AV10 2435.1 cfm

VVR_33_29_FLOW_SP 2529 2529.AV11 2400.0 cfm

VVR_33_29_FLOW_MIN_S

P

2529 2529.AV12 2400.0 cfm

VVR_33_29_FLOW_ERRO

R_CFM

2529 2529.AV14 35.1 cfm

OR8 EXHAUST 33_30 (2530)

Device Unit s

ValueObject IDName

VVR_33_30_FLOW_CFM 2530 2530.AV10 1954.0 cfm

VVR_33_30_FLOW_SP 2530 2530.AV11 2000.0 cfm

VVR_33_30_FLOW_ERRO

R_CFM

2530 2530.AV14 46.0 cfm

VVU-3C RM-123 -IT CLOSET (2537)

Device Unit s

ValueObject IDName

FLOW_CFM_ 2537 2537.AV10 68.6 cfm

FLOW__SP 2537 2537.AV11 65.0 cfm

FLOW_MIN_SP 2537 2537.AV12 65.0 cfm

FLOW_ERRORCFM_ 2537 2537.AV14 3.6 cfm

B100_AHU33 (2599)

Device Unit s

ValueObject IDName

Cooling Demand 2599 2599.AV11 3.5 %

AHU33_SF_FLOW 2599 2599.AV12 1.8

Total : 125 objects