HHS0016943v2_Attach H-1_Project Drawings.pdf
PDF 5 MB Posted
- Attached to
- Water Improvements at El Paso Psychiatric Center
- Solicitation number
- HHS0016943v2
- Issued by
- El Paso County, Texas
About this file
This file comprises 100% construction documents for water improvements at El Paso Psychiatric Center (THHS), a state-owned facility operated by the Texas Health and Human Services Commission located at 4615 Alameda Avenue in El Paso, Texas. The project deliverables include comprehensive engineering plans prepared by Walter P. Moore and Associates, Inc., covering civil, mechanical, electrical, plumbing, fire protection, and architectural systems. The scope of work encompasses site water line improvements, including new domestic water service installation from the street to the building, backflow preventer installation in an enclosure with slab-mounted heater, water meter vault construction, pressure reducing valve installation, and associated demolition of existing water infrastructure from the street to the meter. Interior work includes new copper piping installation for domestic cold water supply, coordination with existing systems, ceiling modifications for pipe routing, and restoration of removed architectural elements including ceiling tiles, light fixtures, HVAC components, speakers, and smoke detectors. The construction documents indicate collaboration among multiple disciplines: Civil Engineer Walter P. Moore and Associates (601 North Mesa St., Suite 1475, El Paso, Texas), Electrical Engineer at 330 Eubank Court, and an Architect, with technical review and approval processes required from the Texas Health and Human Services Commission.
The construction documents dated May 2, 2025 (original issue) and November 18, 2025 (revisions) specify that contractor responsibilities include field verification of all existing conditions, coordination with El Paso Water for external demolition and system tie-ins, protection of existing utilities and structures, management of system shutdowns, and coordination across trades to resolve spatial conflicts in the constrained work environment. Materials specifications require copper Type K and L piping (ASTM B88) for domestic water systems, hubless cast iron soil pipe for sanitary sewer and vent, and galvanized steel ductwork. Critical requirements include minimum 4-foot pipe embedment depth, firestop sealing at penetrations, vibration isolation for equipment, seismic restraints per SMACNA guidelines, and compliance with 2021 International Building Codes, NFPA standards, and local authority amendments. The project mandates contractor coordination with utility companies for all tie-in costs, comprehensive submittals and shop drawings, temporary plumbing systems to maintain operations during phasing, and documentation of existing conditions through photographs before work begins.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment H-1
Project Drawings
EL PASO PSYCHIATRIC CENTER (THHS)
WATER IMPROVEMENTS
4615 ALAMEDA AVE., EL PASO, TEXAS
ENGINEERING PLANS
FOR
NORTH
MP ENGINEER
MAY 2, 2025
ARCHITECT
Texas Health and Human Services Commission P.O. Box 12668 Mail Code 2064
Austin, Texas 78711-2668
OWNER
CIVIL
ENGINEER
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
ELECTRICAL
ENGINEER
330 Burbank Ct, El Paso, Texas 79902
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
11-18-2025
ORIGINAL ISSUE
-N ov -2
- 1 :1
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
G N
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
GENERAL NOTES:
DIMENSION CONTROL AND PAVING:
GRADING NOTES:
UTILITY NOTES:
CONCRETE
Know what's below.
Callbefore you dig.
GENERAL NOTES
C0.2
STAT E OF TEXAS
PROFES S IO N A L E NGINEERL I C ENS ED
106776
GABRIELA RAMOS
Walter P. Moore and Associates, Inc.
TBPE Firm Registration No. 1856
11/18/2025
BO
LL
P L.
EL
P
AS
O
PS
YC
HI
AT
RI
C
CE
N
TE
R
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
11-18-2025
ORIGINAL ISSUE
-N ov -2
- 1 :2
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
D M
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
SCALE: 1"= 10'
0 10 2010
Edge of Pavement
FL41.07
R.O.W.
Electric
Storm Sewer/MH
Water Line/Fire Hydrant/Valve Sanitary Sewer/MH/Cleanout Curb Inlet/Grate Inlet
Slope Fence Phone
Flow Line
Gas
FL 42.25
1%
EXISTING
Curb
LEGEND
PROPOSED
Limit of Construction LOC
DEMOLITION PLAN
A. DEMOLITION FROM THE STREET UP TO THE METER WILL BE
PERFORMED BY EL PASO WATER.
B. COORDINATE WITH EL PASO WATER PRIOR TO DEMOLITION
WORK.
Sheet Notes:
FULL-DEPTH SAWCUT
PROTECT IN PLACE EXISTING UTILITY
REMOVE EXISTING CONCRETE
REMOVE EXISTING CONCRETE CURB
Key Notes:
PROTECT IN PLACE EXISTING TREE
REMOVE AND REUSE EXISTING BOULDER
CONTRACTOR TO PROTECT EXISTING PAVEMENT AND TO
REPLACE DAMAGED PAVEMENT TO ORIGINAL CONDITIONS
PROTECT IN PLACE EXISTING CURB
9 PROTECT IN PLACE CONCRETE
C1.0
STAT E OF TEXAS
PROFES S IO N A L E NGINEERL I C ENS ED
106776
GABRIELA RAMOS
Walter P. Moore and Associates, Inc.
P L.
240' TO
ALBERTA ST.
285' TO
ALAM
EDA ST.
5'
49.3'
12'
32.9'
12.9'
EL
P
AS
O
PS
YC
HI
AT
RI
C
CE
N
TE
R
21'
3'
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
11-18-2025
ORIGINAL ISSUE
-N ov -2
- 1 :3
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
U T.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
SCALE: 1"= 10'
0 10 2010
Edge of Pavement
FL41.07
R.O.W.
Electric
Storm Sewer/MH
Water Line/Fire Hydrant/Valve Sanitary Sewer/MH/Cleanout Curb Inlet/Grate Inlet
Slope Fence Phone
Flow Line
Gas
FL 42.25
1%
EXISTING
Curb
LEGEND
PROPOSED
Limit of Construction LOC
UTILITY PLAN
C2.0
A. CONTRACTOR TO MATCH EXISTING GRADES.
B. CONTRACTOR TO MATCH EXISTING SIDEWALK WIDTH AND
THICKNESS.
C. PIPE EMBEDMENT SHALL BE 4' MINIMUM TO THE TOP OF PIPE.
REF. SHEET C4.0. MAINTAIN PIPE EMBEDMENT OF 4' MINIMUM
FROM METER BOX TO THE BUILDING.
D. OFFSET ELECTRICAL CONDUIT A FOOT AWAY FROM THE WATER
LINE FROM THE BACKFLOW PREVENTER TO THE BUILDING. REF.
SHEET E1.0.
E. EXISTING UNDERGROUND ELECTRICAL LINES MAY BE PRESENT
ON SITE. CONTRACTOR SHALL SPOT OR CIRCUIT TRACE PRIOR
TO TRENCHING.
F. OTHER EXISTING UNDERGROUND UTILITIES MAY BE PRESENT
ON SITE.
G. CONTRACTOR SHALL TIE THE LOCATION OF THE PROPOSED
WATER LINE TO A NEARBY MONUMENT AND INCLUDE AS PART
OF THEIR RECORD DRAWINGS.
Sheet Notes:
STAT E OF TEXAS
PROFES S IO N A L E NGINEERL I C ENS ED
106776
GABRIELA RAMOS
Walter P. Moore and Associates, Inc.
P L.
EL
P
AS
O
PS
YC
HI
AT
RI
C
CE
N
TE
R
X
XX
X
X
X X
X X X
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
11-18-2025
ORIGINAL ISSUE
-N ov -2
- 1 :4
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
EC
P.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
SCALE: 1"= 10'
0 10 2010
LEGEND
REINFORCED FILTER FABRIC BARRIER
INLET PROTECTION BARRIER
RFB
IPB
NOTES:
1. ALL AFFECTED INLETS SHALL BE PROTECTED BEFORE
CONSTRUCTION ACTIVITIES BEGIN.
2. SEDIMENT AND EROSION CONTROLS INCLUDING
NON-STORMWATER DISCHARGES SHALL BE AS PER
THE SPECIFICATIONS.
EROSION CONTROL NOTES
1. REINFORCED SILT FENCES AND INLET PROTECTION TO BE
PROVIDED DURING CONSTRUCTION OF THIS PROJECT, AND
REMOVED UPON CONSTRUCTION COMPLETION (SEE SPECS. AND
DETAILS).
2. PRIOR TO REMOVAL OF EROSION CONTROL DEVICES, ALL AREAS
DISTURBED ARE TO BE RESTORED TO ORIGINAL CONDITIONS.
EROSION CONTROL
PLAN
C3.0
STAT E OF TEXAS
PROFES S IO N A L E NGINEERL I C ENS ED
106776
GABRIELA RAMOS
Walter P. Moore and Associates, Inc.
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 6 :3
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
EC
D
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
EROSION CONTROL
DETAILS
C3.1
STATE OF TEXAS
PROFESS IONA L ENGINEE
R
L ICENSED
154433
MIRIAM GONZALEZ
Walter P. Moore and Associates, Inc.
05/02/2025
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 6 :3
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
D T.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
DETAILS
C4.0
CUSTOMER
RESPONSIBILITY
CUSTOMER
RESPONSIBILITY
A
P
C E
B D
CONTRACTOR
RESPONSIBILITY
GI
F
D J
A
M
M
H
RESPONSIBILITY
K
CONTRACTOR
I H
B DC E GF E D J K
N N
O
L
12" MIN.
K
L K
#4 REBAR @ 6" O.C.
12"
24"
E
36" MAX.
Q
PAVED SURFACE
NATURAL GROUND
TOTAL AREA EQUALS AREA
1/4 PIPE DIAMETER
8" MINIMUM
MAX. SLOPE
AREA FOR TEE
13 SQ. FEET
23 SQ. FEET
29 SQ. FEET18"
16"
6 SQ. FEET
9 SQ. FEET 10"
12"
8"
12 SQ. FEET
15 SQ. FEET
3 SQ. FEET
5 SQ. FEET
7 SQ. FEET
TEE, DEAD END
90° BEND
WATER PIPE
4" & LESS
PIPE
SIZE
3 SQ. FEET
4 SQ. FEET 6"
22 1/2° BENDS
3 SQ. FEET
3 SQ. FEET
45° AND
Y
THRUST BLOCK
AREA (Y & W
)W
1/2 AREA REQUIRED
FOR 90° BEND
REQUIRED FOR TEE
A
A
A
1' MINIMUM
A
A
R
L ICENSED
154433
MIRIAM GONZALEZ
Walter P. Moore and Associates, Inc.
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 3 :5
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
D T.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
DETAILS
C4.1
R
L ICENSED
154433
MIRIAM GONZALEZ
Walter P. Moore and Associates, Inc.
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 1 1:
A
M
X:
\M
\2
5\
1-
T H
H S
W at er Im pr ov em en ts
El P as o\
C iv il\ 3-
Pr od uc tio n\
-S he et s\
M
-2
-0
0- G
N W
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
GENERAL NOTES:
I. DESIGN CRITERIA
II. NON-DESTRUCTIVE EVALUATION
III. SELECTIVE DEMOLITION
IV. SUBMITTALS
GENERAL WALL NOTES
R0.1
Abigailb Stamp
Abigailb Text Box
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 1 1:
A
M
X:
\M
\2
5\
1-
T H
H S
W at er Im pr ov em en ts
El P as o\
C iv il\ 3-
Pr od uc tio n\
-S he et s\
M
-2
-0
0- G
N W
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
GENERAL NOTES CONT.:
V. MISCELLANEOUS
VI. DRAWING INTERPRETATION
GENERAL WALL
NOTES 2
R0.2
Abigailb Stamp
Abigailb
1-1 2" 1"
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
M11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 6 :3
PM
X:
\M
\2
5\
1-
T
H H
S W at er
Im pr ov em en ts
El
P as o\ C iv il\
3- Pr od uc tio n\
-S he et s\ M
-2
-0 0-
D T
W
AL
LS
.d w g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
CONCRETE BASEMENT
WALL DETAILS
R1.0
Abigailb Stamp
Abigailb
SD
S
SD
S
S
SDSSDSSSD
S
SD
S
SD
S
S
SDSSDS
OPEN - NO CEILING. EXPOSED STRUCTURE
ACOUSTICAL LAY IN CEILING TILE TO BE
REINSTALLED
NO WORK IN THIS AREA.
DIFFUSER TO BE REINSTALLED
LIGHT FIXTURE TO BE REINSTALLED
FIRE SPRINKLER TO REMAIN UNDISTURBED
SPEAKER TO BE REINSTALLED
SMOKE DETECTOR TO BE REINSTALLED
SPOTLIGHT TO BE REINSTALLED
RCP LEGEND
S
ELEV.
E104E104
ELEV.
E101E101
ELEV.
E103E103
LIBRARY
00360036
CONFERENCE
00370037
OFFICE
00380038
COORD.
00310031
R.R.
00400040
R.R.
00390039
OFFICE
00430043
OFFICE
00440044
OFFICE
00450045
OFFICE
00460046
OFFICE
00470047
OFFICE
00480048
CONF.
00500050
OFFICE
00510051
OFFICE
00540054
OFFICE
N/AN/A
OFFICE
00530053
CONF.
00520052 OFFICE
00560056WORK RM.
00490049
OFFICE
00420042
STOR.
00410041
SPR.
00300030
MED.
RECORDS
00290029
CLERICAL
00280028
UTIL.
00270027
GARDEN
COURT
P101P101
OFFICE
00250025
WORKROOM
00240024
OFFICE
00090009
OFFICE
00050005
OFFICE
00100010
OFFICE
00070007
ACCTS.
00220022
OFFICE
00210021
OFFICE
00190019
OFFICE
00180018 CONF.
00170017
GARDEN
COURT
P102P102
OFFICE
00160016
OFFICE
00150015
OFFICE
00200020
R.R. WOM.
00130013
R.R. MENS
00120012
LOUNGE
00110011
PHARMACY
00580058
CONFERENCE
N/AN/A
TUNNEL
N/AN/A
HSKP
00600060
MECH.
00590059
CLEAN LINEN
00610061
STOR.
00620062
MAINTENANCE
00630063
DATA
00580058
MACH. RM.
00660066
M.I.S
0000100001WOMEN
00040004
R.R.
N/AN/A
R.R.
N/AN/A
MEN
00050005
STOR.
00060006
M.I.S.
00030003
SOIL
00330033
ELEC.
00570057 ELEC. RM.
00650065
M
EC
H
CH
A
SE
N A
N A
MECH.
00640064
SEC. AREA
00260026
CORRIDOR
N/AN/A
SYSTEMS
OFFICE
00320032
CORRIDOR
00770077
WAITING RM.
00350035
CORRIDOR
N/AN/A
OFFICE
00340034
SERVICE
LOBBY
00730073
CORRIDOR
00800080
COPY
0014A0014A
SECRETARY
00140014
OFFICE
N/AN/A
ELEV. LOBBY
00720072
CORRIDOR
00710071
TECH.
00020002
CONFERENCE
N/AN/A CONFERENCE
N/AN/A
WORKROOM
N/AN/A
REPORT
N/AN/A
LOCKER
N/AN/A
R.R.
N/AN/A
R.R.
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
MEN
N/AN/A
LOKER
N/AN/A
WOMEN
N/AN/A
CORRIDOR
N/AN/A
RECEPTIONIST
00750075
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
OFFICE
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
EXAM
N/AN/A
CORRIDOR
00740074
WAITING
N/AN/A
RECEPTIONIST
N/AN/A
OFFICE
N/AN/A
A1.0
A2.0
CORRIDOR
00760076
CORRIDOR
00740074
GENERAL NOTES
A.
B.
C.
CENTER SMOKE DETECTORS, FIRE SPRINKLER HEADS,
LIGHT FIXTURES, IN CENTER OF CEILING TILE, UNLESS
NOTED OTHERWISE.
ALL CEILING GRIDS SHALL BE CENTERED IN THE ROOM
U.N.O.
ALL CEILING HEIGHTS ARE FROM FINISHED FLOOR
ELEVATION.
-M ar -2
- 5 :3
PM
K:
\2
5-
TH
H S
EP
P sy ch ia tri c C en te r I m pr ov em en ts \0
C or re sp on de nc e\ C on su lta nt s\ C ar di na \2
Ti tle B lo ck
\T itl eb lo ck .d w g
Ed ua rd o
M ar qu ez
GENERAL NOTESA.B.C.CENTER SMOKE DETECTORS, FIRE SPRINKLER HEADS,LIGHT FIXTURES, IN CENTER OF CEILING TILE, UNLESSNOTED OTHERWISE.ALL CEILING GRIDS SHALL BE CENTERED IN THE ROOMU.N.O.ALL CEILING HEIGHTS ARE FROM FINISHED FLOORELEVATION.
S
SD
S
S
SDSSDS
S
SD
S
S
SDSSDS
SD
SSD
S
SD
PROJECT NO. DESIGNED BY REVIEWED BY DRAWN BY
M11-25001-00 OT RJ EM
ORIGINAL ISSUE DATE
TRUE NORTHPLAN NORTH KEYPLAN
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
NO. DATE REVISION
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
05/02/2025100% CONSTRUCTION DOCUMENTS
A0.0
REFERENCE BASEMENT RCP
05/02/2025
0 20'10'5'
SCALE: 3/32" = 1'-0"A0.0
01 REFERENCE BASEMENT REFLECTED CEILING PLAN
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
S
SD
S
S
SDSSDSSSD
S
SD
SD
GENERAL NOTES
A.
B.
C.
D.
E.
F.
THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
DIMENSIONS AND NEW WORK AND SHALL BE RESPONSIBLE
FOR THEIR ACCURACY,ANY DIFFERENCES FOUND SHALL
BE SUBMITTED TO THE ARCHITECT IN WRITING FOR
CLARIFICATION BEFORE PROCEEDING WITH THE WORK.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS OF
CONSTRUCTION AND NOTIFY THE ARCHITECT OF ANY
OUTSTANDING COST, MEANS, OR SCHEDULE. PRIOR TO BID
SUBMITTANCE.
PATCHING OF WALLS AND HARD CEILINGS WILL INCLUDE
REFINISHING ENTIRE SURFACE TO NEAREST TERMINATION
POINT, CORNER, CONTROL JOINT OR EXPANSION JOINT.
AT EXISTING FIRE RATED PARTITIONS PATCH AND SEAL ALL
PENETRATIONS AFTER REMOVAL OF DUCTS, CONDUITS,
PIPES, ETC. APPLY FIRE RESISTANT UL APPROVED
MATERIAL AND SEALANT.
THE CONTRACTOR MUST DOCUMENT EXISTING
CONDITIONS OF LIGHT FIXTURES, CEILING TILES, AND
OTHER REMOVED ELEMENTS WITH PHOTOGRAPHS
BEFORE STARTING WORK.
NOT ALL ARCHITECTURAL DEMOLITION SCOPE IS
INDICATED ON THE PLANS. CONTRACTOR IS TO REFER TO
ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS FOR
ADDITIONAL REQUIREMENTS. DEMOLITION REQUIRED FOR
THESE SYSTEMS WILL INCLUDE PATCHING FLOORS,
CEILINGS, WALLS, ETC., TO RESTORE EXISTING
CONSTRUCTION AND FINISH.
1 1
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
CORRIDORCORRIDOR
CORRIDOR
RECEPTIONIST
CORRIDOR
STAIRS
KEY NOTES
1. REMOVE LAY-IN CEILING TILES, GRID, LIGHTS, HVAC
SUPPLIES, RETURNS, SPEAKERS, SMOKE DETECTORS, AND
SPRINKLER HEADS AS NEEDED FOR PLUMBING WORK.
PROTECT DURING CONSTRUCTION TO BE REINSTALLED
WHEN PLUMBING WORK IS COMPLETED.
RCP LEGEND
OPEN - NO CEILING. EXPOSED STRUCTURE
NO WORK IN THIS AREA.
DIFFUSER TO BE REMOVED
LIGHT FIXTURE TO BE REMOVED
FIRE SPRINKLER TO REMAIN UNDISTURBED
SPEAKER TO BE REMOVED
SMOKE DETECTOR TO BE REMOVED
SPOTLIGHT TO BE REMOVED
ACOUSTICAL LAY IN CEILING TILE TO BE
REMOVED
S
-M ar -2
- 5 :3
PM
K:
\2
5-
TH
H S
EP
P sy ch ia tri c C en te r I m pr ov em en ts \0
C or re sp on de nc e\ C on su lta nt s\ C ar di na \2
Ti tle B lo ck
\T itl eb lo ck .d w g
Ed ua rd o
M ar qu ez
GENERAL NOTESA.B.C.CENTER SMOKE DETECTORS, FIRE SPRINKLER HEADS,LIGHT FIXTURES, IN CENTER OF CEILING TILE, UNLESSNOTED OTHERWISE.ALL CEILING GRIDS SHALL BE CENTERED IN THE ROOMU.N.O.ALL CEILING HEIGHTS ARE FROM FINISHED FLOORELEVATION.
S
SD
S
S
SDSSDS
S
SD
S
S
SDSSDS
SD
SSD
S
SD
PROJECT NO. DESIGNED BY REVIEWED BY DRAWN BY
M11-25001-00 OT RJ EM
ORIGINAL ISSUE DATE
TRUE NORTHPLAN NORTH KEYPLAN
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
NO. DATE REVISION
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
05/02/2025100% CONSTRUCTION DOCUMENTS
A1.0
DEMOLITION BASEMENT RCP
05/02/2025
0 20'10'5'
SCALE: 1/8" = 1'-0"A1.0
01 BASEMENT DEMOLITION REFLECTED CEILING PLAN
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
SSD
S
SD
S
SD
S
S
SDSSDS
OPEN - NO CEILING. EXPOSED STRUCTURE
ACOUSTICAL LAY IN CEILING TILE TO BE
REINSTALLED
NO WORK IN THIS AREA.
DIFFUSER TO BE REINSTALLED
LIGHT FIXTURE TO BE REINSTALLED
FIRE SPRINKLER TO REMAIN UNDISTURBED
SPEAKER TO BE REINSTALLED
SMOKE DETECTOR TO BE REINSTALLED
SPOTLIGHT TO BE REINSTALLED
RCP LEGEND
S
KEY NOTES
1. REINSTALL LAY-IN CEILING TILES AND REINSTALL ALL
FIXTURES AND SYSTEMS IN THEIR ORIGINAL LOCATIONS.
THE CONTRACTOR IS RESPONSIBLE FOR ANY PATCHING,
PAINTING, OR REPAIRS RESULTING FROM THE PLUMBING
WORK.
1 1
ACT
9' - 0"
ACT
9' - 0"
ACT
9' - 0"
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
EXIST.ACT
9' - 0"
CORRIDOR
00770077
RECEPTIONIST
00750075
CORRIDOR
00740074
STAIR
S103S103
CORRIDOR
00740074
CORRIDOR
00760076
GENERAL NOTES
A.
B.
C.
CENTER SMOKE DETECTORS, FIRE SPRINKLER HEADS,
LIGHT FIXTURES, IN CENTER OF CEILING TILE, UNLESS
NOTED OTHERWISE.
ALL CEILING GRIDS SHALL BE CENTERED IN THE ROOM
U.N.O.
ALL CEILING HEIGHTS ARE FROM FINISHED FLOOR
ELEVATION.
0 20'10'5'
SCALE: 1/8" = 1'-0"A2.0
01 BASEMENT REFLECTED CEILING PLAN
-M ar -2
- 5 :3
PM
K:
\2
5-
TH
H S
EP
P sy ch ia tri c C en te r I m pr ov em en ts \0
C or re sp on de nc e\ C on su lta nt s\ C ar di na \2
Ti tle B lo ck
\T itl eb lo ck .d w g
Ed ua rd o
M ar qu ez
GENERAL NOTESA.B.C.CENTER SMOKE DETECTORS, FIRE SPRINKLER HEADS,LIGHT FIXTURES, IN CENTER OF CEILING TILE, UNLESSNOTED OTHERWISE.ALL CEILING GRIDS SHALL BE CENTERED IN THE ROOMU.N.O.ALL CEILING HEIGHTS ARE FROM FINISHED FLOORELEVATION.
S
SD
S
S
SDSSDS
S
SD
S
S
SDSSDS
SD
SSD
S
SD
PROJECT NO. DESIGNED BY REVIEWED BY DRAWN BY
M11-25001-00 OT RJ EM
ORIGINAL ISSUE DATE
TRUE NORTHPLAN NORTH KEYPLAN
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
NO. DATE REVISION
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
05/02/2025100% CONSTRUCTION DOCUMENTS
A2.0
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
Z
05/02/2025
AT
T S
XETE FO
SA
R
EG
IS
TE
RED ARCHITECT
AR
M
EN
RENEE JIMEN
E
C
21 7 4 5
BASEMENT RCP
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-A pr -2
- 1 2:
P
M
C :\U se rs
\c ar di \C ar di na E ng in ee rin g C om m is si on in g\ C
AR
D
IN
A
Pr oj ec ts
-0
T H
H S
EP
P sy ch ia tri c C en te r I m pr ov em en ts \5
.0 _C
AD
_B
IM
\C
AD
\P
0.
0.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
PLUMBING LEGEND,
SCHEDULES AND NOTES
P0.0
GENERAL NOTES:PLUMBING NOTES:
MATERIALS
AutoCAD SHX Text
# OF SHEET ON WHICH CONDITION IS DRAWN
AutoCAD SHX Text
DETAIL #
AutoCAD SHX Text
NEW WORK INTERFACE
AutoCAD SHX Text
NATURAL GAS REGULATOR
AutoCAD SHX Text
WALL HYDRANT
AutoCAD SHX Text
NATURAL GAS METER
AutoCAD SHX Text
GM
AutoCAD SHX Text
DOMESTIC WATER METER
AutoCAD SHX Text M
AutoCAD SHX Text
VENT THRU ROOF
AutoCAD SHX Text
PIPING CAPPED
AutoCAD SHX Text
PIPING CONTINUATION
AutoCAD SHX Text
POUNDS PER SQUARE INCH
AutoCAD SHX Text
PSI
AutoCAD SHX Text A.F.F.
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXIST.
AutoCAD SHX Text B.O.P.
AutoCAD SHX Text
BOTTOM OF PIPE
AutoCAD SHX Text
POUNDS
AutoCAD SHX Text
LBS
AutoCAD SHX Text
NORTH DIRECTION
AutoCAD SHX Text
KEYED NOTES
AutoCAD SHX Text
EXISTING EQUIPMENT
AutoCAD SHX Text
NEW EQUIPMENT
AutoCAD SHX Text
ANGLE VALVE
AutoCAD SHX Text
"Y" TYPE STRAINER
AutoCAD SHX Text
3-WAY VALVE
AutoCAD SHX Text
EXISTING BALL VALVE
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
COLD WATER
AutoCAD SHX Text
VENT
AutoCAD SHX Text
HOT WATER
AutoCAD SHX Text
PIPING TURNING UP
AutoCAD SHX Text
TYPICAL PLUMBING FIXTURE CONNECTIONS
AutoCAD SHX Text
DIRECTION OF SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
PIPING TURNING DOWN
AutoCAD SHX Text
ISOLATION BALL VALVE
AutoCAD SHX Text
GAS SHUT-OFF VALVE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
VALVES AND FITTINGS
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
DEMOLITION / REMOVED
AutoCAD SHX Text
PLUMBING LEGEND
AutoCAD SHX Text
PLUMBING LEGEND
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
DCW
AutoCAD SHX Text
EDCW
AutoCAD SHX Text
DHW
AutoCAD SHX Text
DHR
AutoCAD SHX Text G
AutoCAD SHX Text
CD
AutoCAD SHX Text
SS
AutoCAD SHX Text
EG
AutoCAD SHX Text
ESS
AutoCAD SHX Text
SYMBOLS
AutoCAD SHX Text
NEW
AutoCAD SHX Text
AG
AutoCAD SHX Text
CO
AutoCAD SHX Text
DSN
AutoCAD SHX Text
DCO
AutoCAD SHX Text
GM
AutoCAD SHX Text
EWC(-H)
AutoCAD SHX Text
FD
AutoCAD SHX Text
FS
AutoCAD SHX Text
HB
AutoCAD SHX Text L(-H)
AutoCAD SHX Text
MSB
AutoCAD SHX Text
PRV
AutoCAD SHX Text
ORD
AutoCAD SHX Text
RD
AutoCAD SHX Text
RCP
AutoCAD SHX Text S
AutoCAD SHX Text
SH(-H)
AutoCAD SHX Text
TD
AutoCAD SHX Text
TP
AutoCAD SHX Text U(-H)
AutoCAD SHX Text
VTR
AutoCAD SHX Text
WC(-H)
AutoCAD SHX Text
WCO
AutoCAD SHX Text
BFP
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EVTR
AutoCAD SHX Text
EBFP
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DOMESTIC COLD WATER SUPPLY
AutoCAD SHX Text
DOMESTIC HOT WATER SUPPLY
AutoCAD SHX Text
DOMESTIC HOT WATER RETURN
AutoCAD SHX Text
NATURAL GAS LINE
AutoCAD SHX Text
CONDENSATE DRAIN LINE
AutoCAD SHX Text
SEWER UNDERGROUND
AutoCAD SHX Text
SANITARY SEWER
AutoCAD SHX Text
VENT LINE
AutoCAD SHX Text
AIR GAP
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
DOWN SPOUT NOZZLE
AutoCAD SHX Text
DOUBLE CLEAN OUT
AutoCAD SHX Text
GAS METER
AutoCAD SHX Text
ELECTRIC WATER COOLER (HANDICAPPED)
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
FLOOR SINK
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
LAVATORY (HANDICAPPED)
AutoCAD SHX Text
MOP SERVICE BASIN
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
OVERFLOW ROOF DRAIN
AutoCAD SHX Text
ROOF DRAIN
AutoCAD SHX Text
RECIRCULATION PUMP
AutoCAD SHX Text
SINK
AutoCAD SHX Text
SHOWER (HANDICAPPED)
AutoCAD SHX Text
TRENCH DRAIN
AutoCAD SHX Text
TRAP PRIMER
AutoCAD SHX Text
URINAL (HANDICAPPED)
AutoCAD SHX Text
VENT THRU ROOF
AutoCAD SHX Text
WATER CLOSET (HANDICAPPED)
AutoCAD SHX Text
WALL CLEAN OUT
AutoCAD SHX Text
BACKFLOW PREVENTER
AutoCAD SHX Text
EDHW
AutoCAD SHX Text
FU
AutoCAD SHX Text
SEWER FIXTURE UNIT COUNT
AutoCAD SHX Text
FU
AutoCAD SHX Text
UG
AutoCAD SHX Text
UNDERGROUND
AutoCAD SHX Text
EFD
AutoCAD SHX Text
EFS
AutoCAD SHX Text
EAG
AutoCAD SHX Text
ECO
AutoCAD SHX Text
EDSN
AutoCAD SHX Text
EDCO
AutoCAD SHX Text
EGM
AutoCAD SHX Text V
AutoCAD SHX Text
EMSB
AutoCAD SHX Text
ES
AutoCAD SHX Text
ESH(-H)
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETP
AutoCAD SHX Text
EWCO
AutoCAD SHX Text
EUG
AutoCAD SHX Text
EDHR
AutoCAD SHX Text
ECD
AutoCAD SHX Text
EV
AutoCAD SHX Text
EL
AutoCAD SHX Text
EEWC
AutoCAD SHX Text
DI WATER LINE (DIONIZED WATER)
AutoCAD SHX Text
DI
AutoCAD SHX Text
EDI
AutoCAD SHX Text
CFU
AutoCAD SHX Text
COLD WATER FIXTURE UNIT COUNT
AutoCAD SHX Text
CFU
AutoCAD SHX Text
HFU
AutoCAD SHX Text
HOT WATER FIXTURE UNIT COUNT
AutoCAD SHX Text
HFU
AutoCAD SHX Text
FCO
AutoCAD SHX Text
FLOOR CLEAN OUT
AutoCAD SHX Text
EFCO
AutoCAD SHX Text
EU
AutoCAD SHX Text
EWC
AutoCAD SHX Text
ERCP
AutoCAD SHX Text
ERD
AutoCAD SHX Text
EORD
AutoCAD SHX Text
EPRV
AutoCAD SHX Text
EHB
AutoCAD SHX Text
STORM DRAIN
AutoCAD SHX Text
SD
AutoCAD SHX Text
SS
AutoCAD SHX Text
SERVICE SINK
AutoCAD SHX Text
ESS
AutoCAD SHX Text W
AutoCAD SHX Text
EW
AutoCAD SHX Text
WATER SERVICE
AutoCAD SHX Text
HY
AutoCAD SHX Text
WALL HYDRANT
AutoCAD SHX Text
EHY
AutoCAD SHX Text
SUG
AutoCAD SHX Text
ESUG
AutoCAD SHX Text
CIRCUIT SETTER
AutoCAD SHX Text
BACKFLOW PREVENTER
AutoCAD SHX Text
COMBINED TEMPERATURE AND PRESSURE
AutoCAD SHX Text
RELIEF VALVE
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
RECIRCULATING PUMP
AutoCAD SHX Text
ESD
AutoCAD SHX Text
BACKWATER VALVE
AutoCAD SHX Text I.E.
AutoCAD SHX Text
INVERT ELEVATION
AutoCAD SHX Text
CIRCUIT SETTER (ISOMETRIC)
AutoCAD SHX Text X
AutoCAD SHX Text
XXX
AutoCAD SHX Text
AutoCAD SHX Text
WM
AutoCAD SHX Text
SP
AutoCAD SHX Text
WHA
AutoCAD SHX Text
EWM
AutoCAD SHX Text
WATER METER
AutoCAD SHX Text
SUMP PUMP
AutoCAD SHX Text
WATER HAMMER ARRESTOR
AutoCAD SHX Text
CSS
AutoCAD SHX Text
CLINICAL SERVICE SINK
AutoCAD SHX Text
ECSS
AutoCAD SHX Text
RM#
AutoCAD SHX Text
ROOM NUMBER
AutoCAD SHX Text
BP
AutoCAD SHX Text
EBP
AutoCAD SHX Text
BOOSTER PUMP
AutoCAD SHX Text
ESP
AutoCAD SHX Text
EWHA
AutoCAD SHX Text
ST
AutoCAD SHX Text
WATER STORAGE TANK
AutoCAD SHX Text
EST
AutoCAD SHX Text
HWP
AutoCAD SHX Text
HOT WATER PUMP
AutoCAD SHX Text
EHWP
AutoCAD SHX Text
WH
AutoCAD SHX Text
WATER HEATER
AutoCAD SHX Text
EWH
AutoCAD SHX Text
FP
AutoCAD SHX Text
FIRE PROTECTION WATER SUPPLY
AutoCAD SHX Text
EFP
AutoCAD SHX Text B
AutoCAD SHX Text
BOILER
AutoCAD SHX Text
EB
AutoCAD SHX Text
OS
AutoCAD SHX Text
OIL SEPARATOR
AutoCAD SHX Text
EOS
AutoCAD SHX Text
AS
AutoCAD SHX Text
AIR SEPARATOR
AutoCAD SHX Text
EAS
AutoCAD SHX Text
ET
AutoCAD SHX Text
EXPANSION TANK
AutoCAD SHX Text
EET
AutoCAD SHX Text
FC
AutoCAD SHX Text
FAN COIL
AutoCAD SHX Text
EFC
AutoCAD SHX Text
CP
AutoCAD SHX Text
CONDENSATE PUMP
AutoCAD SHX Text
ECP
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AIR HANDLER UNIT
AutoCAD SHX Text
EAHU
AutoCAD SHX Text
EU
AutoCAD SHX Text
EVAPORATIVE UNIT
AutoCAD SHX Text
EEU
AutoCAD SHX Text
OSD
AutoCAD SHX Text
SD
AutoCAD SHX Text
OVERFLOW STORM DRAIN
AutoCAD SHX Text
STORM DRAIN
AutoCAD SHX Text
ESD
AutoCAD SHX Text
EOSD
AutoCAD SHX Text
1. CONTRACTOR SHALL COMPLY WITH LOCAL, STATE AND FEDERAL CODE ORDINANCES, RULES AND CONTRACTOR SHALL COMPLY WITH LOCAL, STATE AND FEDERAL CODE ORDINANCES, RULES AND REGULATIONS. 2. CONTRACTOR IS SOLELY RESPONSIBLE FOR PHASING AND SEQUENCING WORK. CONTRACTOR IS SOLELY RESPONSIBLE FOR PHASING AND SEQUENCING WORK. 3. BEFORE COMMENCING WORK, GENERAL CONTRACTOR AND INSTALLING CONTRACTORS (JOINTLY BEFORE COMMENCING WORK, GENERAL CONTRACTOR AND INSTALLING CONTRACTORS (JOINTLY REFERRED TO HEREAFTER AS "CONTRACTOR") SHALL SECURE COPIES OF RECORD DRAWINGS SHOWING EXISTING BUILDING SYSTEMS AND FEATURES. RECORD DRAWINGS AND THESE PROJECT DRAWINGS MAY NOT REFLECT EXISTING CONDITIONS ACCURATELY, THEREFORE CONTRACTORS SHALL VERIFY EXISTING CONDITIONS BEFORE COMMENCING CONSTRUCTION. CONTRACTOR SHALL IDENTIFY THE LOCATION AND DETERMINE THE PURPOSE OF EXISTING EQUIPMENT, VALVES, CONTROLS, PIPES, ETC. BEFORE COMMENCING CONSTRUCTION. 4. SOME INFORMATION APPEARS ON ONE DOCUMENT BUT NOT ON OTHER DOCUMENTS, THEREFORE SOME INFORMATION APPEARS ON ONE DOCUMENT BUT NOT ON OTHER DOCUMENTS, THEREFORE DRAWINGS, SPECIFICATIONS, AND OTHER CONTRACT DOCUMENTS ARE TO BE READ TOGETHER. IN THE EVENT OF A CONFLICT BETWEEN DRAWINGS, SPECIFICATIONS, CODES, AND STANDARDS, THE MOST STRINGENT SHALL GOVERN. 5. SOME INFORMATION APPEARS ON MORE THAN ONE DOCUMENT. IF FEATURES ARE INDICATED SOME INFORMATION APPEARS ON MORE THAN ONE DOCUMENT. IF FEATURES ARE INDICATED DIFFERENTLY ON DIFFERENT DRAWINGS (EXAMPLE #1: DIFFERENT REFLECTED CEILING PLAN LAYOUTS ON ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS. EXAMPLE #2: ROOF CURBS AND FLASHING MAY BE SHOWN DIFFERENTLY ON MECHANICAL AND ARCHITECTURAL DRAWINGS.), CONTRACTOR SHALL REQUEST CLARIFICATION BY ARCHITECT/ENGINEER BEFORE COMMENCING CONSTRUCTION. 6. IF TWO SIZES ARE SHOWN FOR A PIPE OR DUCT (FOR EXAMPLE ONE SIZE ON THE PLAN VIEW IF TWO SIZES ARE SHOWN FOR A PIPE OR DUCT (FOR EXAMPLE ONE SIZE ON THE PLAN VIEW AND ONE SIZE ON THE ISOMETRIC VIEW), CONTRACTOR SHALL REQUEST CLARIFICATION FROM ARCHITECT/ENGINEER BEFORE PROCEEDING WITH INSTALLATION. 7. BECAUSE WORK SPACE IS LIMITED, IT IS IMPORTANT THAT CONTRACTOR COORDINATE WITH OTHER BECAUSE WORK SPACE IS LIMITED, IT IS IMPORTANT THAT CONTRACTOR COORDINATE WITH OTHER TRADES TO AVOID SPACE CONFLICTS. IT IS ANTICIPATED THAT SPACE COORDINATION WILL BE DIFFICULT, SO THE VARIOUS TRADE CONTRACTORS MUST IDENTIFY AND RESOLVE SPACE CONFLICTS BEFORE COMMENCING CONSTRUCTION. CONTRACTOR SHALL OFFSET DUCTWORK AND PIPING AS NECESSARY TO FIT EQUIPMENT AND MATERIALS IN SPACE ALLOTTED. 8. ALL PRODUCTS, MATERIALS, WORK, AND TECHNIQUES FOR THE MECHANICAL AND PLUMBING ALL PRODUCTS, MATERIALS, WORK, AND TECHNIQUES FOR THE MECHANICAL AND PLUMBING SYSTEMS SHALL COMPLY WITH THE MOST RIGID STANDARDS AND RECOMMENDATIONS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA); THE NATIONAL ELECTRIC CODE (NEC); 2021 INTERNATIONAL BUILDING CODES AS ADOPTED AND/OR AMENDED BY LOCAL AUTHORITIES, THE AMERICAN SOCIETY OF HEATING REFRIGERATION, AND AIR CONDITIONING ENGINEERS (ASHRAE); THE SHEET METAL AND AIR CONDITIONING CONTRACTORS (SMACNA); THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME); THE AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM); AND THE AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). ALL MATERIALS AND EQUIPMENT FOR THE ELECTRICAL PORTION OF THE MECHANICAL SYSTEM SHALL BEAR THE APPROVAL LABEL OF UNDERWRITERS LABORATORIES, INC. (UL). 9. CONTRACTOR SHALL PREPARE AND SUBMIT COORDINATION DRAWINGS TO ARCHITECT/ENGINEER FOR CONTRACTOR SHALL PREPARE AND SUBMIT COORDINATION DRAWINGS TO ARCHITECT/ENGINEER FOR REVIEW. SUCH DRAWINGS ARE REQUIRED WHEN WORK BY SEPARATE ENTITIES REQUIRES FABRICATION OF PRODUCTS AND MATERIALS WHICH MUST ACCURATELY INTERFACE AND WHEN SPACE PROVIDED FOR INSTALLATION IS TIGHT. 10. CONTRACTOR SHALL NOT CUT, DRILL, OR ALTER ANY BUILDING ELEMENT INCLUDING WALLS, FLOORS, CONTRACTOR SHALL NOT CUT, DRILL, OR ALTER ANY BUILDING ELEMENT INCLUDING WALLS, FLOORS, CEILINGS, AND ROOFS WITHOUT FIRST RECEIVING APPROVAL FROM ARCHITECT/ENGINEER. ALL CUTS SHALL BE MADE WITH ARCHITECT/ENGINEER APPROVED CUTTING TOOLS. 11. CONTRACTOR SHALL BRACE AND/OR REINFORCE SUPPORTING DEVICES TO AVOID DAMAGE TO CONTRACTOR SHALL BRACE AND/OR REINFORCE SUPPORTING DEVICES TO AVOID DAMAGE TO BUILDING STRUCTURE, SYSTEMS, AND SURFACES. 12. HVAC, PLUMBING, AND ELECTRICAL OUTAGES MUST BE MINIMIZED. CONTRACTOR SHALL COORDINATE HVAC, PLUMBING, AND ELECTRICAL OUTAGES MUST BE MINIMIZED. CONTRACTOR SHALL COORDINATE WITH OWNER BEFORE EACH OUTAGE. CONTRACTOR SHALL PROVIDE TEMPORARY HVAC, PLUMBING, AND ELECTRICAL SYSTEMS TO ACCOMPLISH WORK WITHOUT OBJECTIONABLE OUTAGES. 13. SOUND AND VIBRATION: EQUIPMENT SHALL BE PROTECTED BY VIBRATION CONTROL DEVICES SOUND AND VIBRATION: EQUIPMENT SHALL BE PROTECTED BY VIBRATION CONTROL DEVICES (VIBRATION ELIMINATORS, EQUIPMENT SUPPORTS, FLEXIBLE CONNECTIONS, ETC.) INSTALLED IN ACCORDANCE WITH EQUIPMENT MANUFACTURERS' RECOMMENDATIONS. PIPES SHALL BE ISOLATED FROM STUDS AND OTHER BUILDING SURFACES SO AS TO AVOID VIBRATION AND NOISE. ALL MECHANICAL PRODUCTS, EQUIPMENT, AND SYSTEMS MUST OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT ANY SOUND OR VIBRATION WHICH, IN THE SOLE OPINION OF THE ARCHITECT, IS OBJECTIONABLE. SOUND OR VIBRATION NOTICEABLE OUTSIDE THE SPACE OF A PRODUCT WILL BE CONSIDERED OBJECTIONABLE. VIBRATION WHICH, IN THE SOLE OPINION OF THE ARCHITECT/ENGINEER, WILL IMPACT ON THE LIFE, WARRANTY, OR PERFORMANCE OF A PRODUCT, WILL BE CONSIDERED OBJECTIONABLE. SOUND OR VIBRATION CONDITIONS CONSIDERED OBJECTIONABLE SHALL BE CORRECTED BY CONTRACTOR AT CONTRACTOR'S EXPENSE. 14. ACCESS FOR MAINTENANCE: CONTRACTOR SHALL LOCATE EQUIPMENT AND PRODUCTS WHICH ACCESS FOR MAINTENANCE: CONTRACTOR SHALL LOCATE EQUIPMENT AND PRODUCTS WHICH REQUIRE SERVICE, OPERATION, OBSERVATION, OR MAINTENANCE IN FULLY ACCESSIBLE POSITIONS. THIS APPLIES TO, BUT IS NOT LIMITED TO, VALVES, TRAPS, COILS, DX UNITS, FILTERS, CLEANOUTS, MOTORS, AND DAMPERS. IF DRAWINGS SHOW ITEMS IN INACCESSIBLE LOCATIONS, CONTRACTOR SHALL REQUEST INSTALLATION INSTRUCTIONS FROM ARCHITECT/ENGINEER BEFORE COMMENCING CONSTRUCTION. WHERE NECESSARY FOR ACCESS TO DEVICES, CONTRACTOR SHALL PROVIDE ARCHITECT/ENGINEER-APPROVED ACCESS PANELS. IN MECHANICAL ROOMS, CONTRACTOR SHALL INSTALL VALVES SO THEY ARE ACCESSIBLE BY A PERSON STANDING AT FLOOR LEVEL. 15. CONTRACTOR SHALL PROVIDE A TIGHT SEAL OF FIRESTOP MATERIAL AT DUCT AND PIPE CONTRACTOR SHALL PROVIDE A TIGHT SEAL OF FIRESTOP MATERIAL AT DUCT AND PIPE PENETRATIONS THROUGH WALLS, FLOORS, ROOFS, AND OTHER SURFACES. FIRESTOP SYSTEMS OTHER SURFACES. FIRESTOP SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE CODE OFFICIAL HAVING JURISDICTION. 16. VERTICAL HANGER ELEMENTS (RODS, WIRES, ETC.) SHALL BE LOCATED SUCH THAT AT LEAST SIX VERTICAL HANGER ELEMENTS (RODS, WIRES, ETC.) SHALL BE LOCATED SUCH THAT AT LEAST SIX INCHES OF HORIZONTAL SEPARATION EXISTS BETWEEN THE HANGER ELEMENT AND OTHER OBJECTS. 17. CONTRACTOR SHALL WEATHERPROOF EQUIPMENT, DUCTS, PIPES, AND OTHER DEVICES AND CONTRACTOR SHALL WEATHERPROOF EQUIPMENT, DUCTS, PIPES, AND OTHER DEVICES AND MATERIALS WHICH ARE EXPOSED TO THE WEATHER.
AutoCAD SHX Text
1. DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR IS TO VERIFY ALL LOCATIONS OF PLUMBING FIXTURES WITH DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR IS TO VERIFY ALL LOCATIONS OF PLUMBING FIXTURES WITH ARCHITECTURAL PLANS PRIOR TO ROUGH-IN AND ASSURE NECESSARY CLEARANCES ARE MAINTAINED. WHERE EXISTING CONDITIONS VARY FROM THOSE SHOWN ON DRAWINGS, CONTRACTOR SHALL MOVE/MODIFY EXISTING CONDITIONS OR REROUTE NEW FEATURES TO ACHIEVE PROJECT INTENT. PATCH ABANDONED PENETRATIONS. CONTRACTOR SHALL NOT BE ENTITLED TO EXTRA COMPENSATION FOR SAID MOVING, MODIFYING OR REROUTING. CONTRACTOR TO COORDINATE ALL LINES AND VENTS WITH OTHER DISCIPLINES (I.E. STRUCTURAL, ELECTRICAL, MECHANICAL, ETC.). 2. SEE FLOOR PLANS AND ISOMETRIC DIAGRAMS FOR MAIN PIPING SIZES. SEE PLUMBING FIXTURE SCHEDULE SEE FLOOR PLANS AND ISOMETRIC DIAGRAMS FOR MAIN PIPING SIZES. SEE PLUMBING FIXTURE SCHEDULE FOR INDIVIDUAL UNIT WATER, WASTE, AND VENT SIZES. 3. PLUMBING ITEMS NOT SHOWN ON THE PLUMBING DRAWINGS BUT SHOWN ON THE ARCHITECTURAL DRAWINGS PLUMBING ITEMS NOT SHOWN ON THE PLUMBING DRAWINGS BUT SHOWN ON THE ARCHITECTURAL DRAWINGS OR REQUIRED BY GOVERNING CODES SHALL BE PROVIDED BY CONTRACTOR AT NO ADDITIONAL COST TO OWNER. 4. FLASH ALL PIPE, CONDUIT, AND OTHER PENETRATIONS THRU THE ROOF WITH PORTAL PLUS FLASHING OR AN FLASH ALL PIPE, CONDUIT, AND OTHER PENETRATIONS THRU THE ROOF WITH PORTAL PLUS FLASHING OR AN APPROVED WATERTIGHT SYSTEM. REFER TO ARCHITECTURAL DRAWINGS FOR MORE INFORMATION. 5. VERIFY EXACT LOCATION OF EXISTING WATER MAINS. VERIFY EXACT LOCATION OF EXISTING WATER MAINS. 6. THE PLUMBING SYSTEM LAYOUT SHALL BE IN CAREFUL COORDINATION WITH THE DRAWINGS AND DETERMINING THE PLUMBING SYSTEM LAYOUT SHALL BE IN CAREFUL COORDINATION WITH THE DRAWINGS AND DETERMINING PROPER ELEVATIONS FOR ALL COMPONENTS OF THE SYSTEM. THE GENERAL LAYOUT SHALL BE FOLLOWED AS SHOWN ON THE DRAWINGS IN ALL CASES, EXCEPT WHERE OTHER DISCIPLINES MAY INTERFERE. 7. BEFORE INSTALLING NEW PIPES AND CONDUITS, AND BEFORE RELOCATING OR REMOVING EXISTING PIPES, BEFORE INSTALLING NEW PIPES AND CONDUITS, AND BEFORE RELOCATING OR REMOVING EXISTING PIPES, EQUIPMENT, AND CONDUITS, CONTRACTOR SHALL CAREFULLY DIG TO LOCATE ANY EXISTING COMMUNICATION, DATA, MECHANICAL, ELECTRICAL, AND PLUMBING LINES. EXTREME CARE SHALL BE REQUIRED. CONTRACTOR WILL BE HELD FINANCIALLY RESPONSIBLE FOR REPAIR OF DAMAGE TO EXISTING LINES. 8. PROVIDE ACCESS PANELS ON WALLS AND CHASES FOR ALL VALVES, TRAP PRIMER, WATER HAMMER PROVIDE ACCESS PANELS ON WALLS AND CHASES FOR ALL VALVES, TRAP PRIMER, WATER HAMMER ARRESTORS AND OTHER DEVICES REQUIRING ADJUSTMENT AND/OR MAINTENANCE. CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING ACCESS DOORS AND/OR PANELS IN ACCORDANCE WITH SPECIFICATIONS. ACCESS DOORS AND/OR PANELS MUST COMPLY WITH THE FIRE RATING OF THE SURFACE WHERE THEY ARE INSTALLED. 9. COORDINATE WITH CIVIL ON WALL CORING FOR PLUMBING SYSTEM PRIOR TO COMMENCING WORK. COORDINATE WITH CIVIL ON WALL CORING FOR PLUMBING SYSTEM PRIOR TO COMMENCING WORK. CONTRACTOR SHALL CAREFULLY MARK FINAL CORING LOCATIONS AND SUBMIT TO ARCHITECT/ENGINEER FOR APPROVAL. 10. ALL COLD, HOT AND HOT WATER RECIRCULATION LINES SHALL BE INSULATED. REFER TO SPECIFICATIONS FOR ALL COLD, HOT AND HOT WATER RECIRCULATION LINES SHALL BE INSULATED. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 11. CONTRACTOR IS SOLELY RESPONSIBLE FOR COORDINATING WITH UTILITY COMPANIES. THIS INCLUDES ORDERS, CONTRACTOR IS SOLELY RESPONSIBLE FOR COORDINATING WITH UTILITY COMPANIES. THIS INCLUDES ORDERS, FILLING OUT ALL FORMS, DEPOSITS, AND COORDINATING INSTALLATIONS OF GAS, WATER, SEWER, AND ELECTRICAL UTILITIES. CONTRACTOR SHALL PAY ALL COSTS ASSOCIATED WITH UTILITY TIE-INS. 12. PLUMBING CONTRACTOR SHALL COORDINATE WITH STRUCTURAL, ELECTRICAL, FIRE PROTECTION, AND PLUMBING CONTRACTOR SHALL COORDINATE WITH STRUCTURAL, ELECTRICAL, FIRE PROTECTION, AND MECHANICAL CONTRACTOR ON THE LAYOUT OF THE PIPING. INCLUDING, BUT NOT LIMITED TO, UNDER GROUND PIPING, DOMESTIC WATER, SEWER, FIRE PROTECTION, AND ELECTRICAL CONDUIT. 13. EXISTING UTILITIES AND PLUMBING SYSTEM WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXISTING UTILITIES AND PLUMBING SYSTEM WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK WITH ALL DISCIPLINES AND EXISTING CONDITIONS. 14. CONTRACTOR SHALL PHASE DEMOLITION AND NEW WORK AS PER CONSTRUCTION PHASING PLAN. CONTRACTOR CONTRACTOR SHALL PHASE DEMOLITION AND NEW WORK AS PER CONSTRUCTION PHASING PLAN. CONTRACTOR SHALL PROVIDE TEMPORARY PLUMBING PIPING TO MAINTAIN EXISTING PLUMBING AND MECHANICAL EQUIPMENT NOT BEING REMOVED IN OPERATION. CONTRACTOR SHALL NOT BE COMPENSATED EXTRA FOR OVERTIME OR EXTRA WORK REQUIRED FOR PHASING. 15. CAP OR PLUG PIPING THAT IS SPECIFICALLY CALLED OUT. CAPS AND PLUGS SHALL BE SAME MATERIAL AS CAP OR PLUG PIPING THAT IS SPECIFICALLY CALLED OUT. CAPS AND PLUGS SHALL BE SAME MATERIAL AS EXISTING PIPE MATERIAL. 16. EXAMINE SURFACES TO BE CUT AND PATCHED AND CONDITIONS UNDER WHICH CUTTING AND PATCHING ARE EXAMINE SURFACES TO BE CUT AND PATCHED AND CONDITIONS UNDER WHICH CUTTING AND PATCHING ARE TO BE PERFORMED. 17. CUT IN-PLACE BY SAWING, OR DRILLING USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS ADJOINING CUT IN-PLACE BY SAWING, OR DRILLING USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS ADJOINING CONSTRUCTION. IN GENERAL, USE POWER TOOLS DESIGNED FOR SAWING AND DRILLING, NOT HAMMERING AND CHOPPING. CUT HOLES AS SMALL AS POSSIBLE, NEATLY TO SIZE REQUIRED, AND WITH MINIMUM DISTURBANCE OF ADJACENT SURFACES. TEMPORARILY COVER OPENINGS WHEN NOT IN USE. 18. PATCH CONSTRUCTION BY FILLING, REPAIRING, REFINISHING, CLOSING UP, AND SIMILAR OPERATIONS PATCH CONSTRUCTION BY FILLING, REPAIRING, REFINISHING, CLOSING UP, AND SIMILAR OPERATIONS FOLLOWING PERFORMANCE OF NEW WORK AND DEMOLITION WORK. 19. CLEAN AREAS AND SPACES WHERE CUTTING AND PATCHING ARE PERFORMED. COMPLETELY REMOVE PAINT, CLEAN AREAS AND SPACES WHERE CUTTING AND PATCHING ARE PERFORMED. COMPLETELY REMOVE PAINT, MORTAR, OILS, PUTTY, AND SIMILAR MATERIALS. 20. PIPES SHALL BE SUPPORTED AND BRACED PER SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF PIPES SHALL BE SUPPORTED AND BRACED PER SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING PIPING SYSTEMS". 21. HOUSEKEEPING PADS SHALL BE 4" HIGH WITH A MINIMUM OF 6" BEYOND EQUIPMENT (INTERIOR AND HOUSEKEEPING PADS SHALL BE 4" HIGH WITH A MINIMUM OF 6" BEYOND EQUIPMENT (INTERIOR AND EXTERIOR). CONTRACTOR SHALL MODIFY CONCRETE BASES FOR ALL EQUIPMENT AS REQUIRED BY DIMENSIONS AND LAYOUT. 22. SHOULD A DISCREPANCY OR DISCOVERY OCCUR DURING CONSTRUCTION RELATED ACTIVITIES THAT INVOLVE SHOULD A DISCREPANCY OR DISCOVERY OCCUR DURING CONSTRUCTION RELATED ACTIVITIES THAT INVOLVE HAZARDOUS OR REGULATED MATERIALS, INCLUDING BUT NOT LIMITED TO ASBESTOS CONTAINING MATERIAL, THE CONTRACTOR AND/OR ITS SUBCONTRACTORS SHALL IMMEDIATELY CEASE OPERATIONS IN THE AFFECTED AREA(S) AND CONTACT CONSTRUCTION OFFICER REPRESENTATIVE FOR FURTHER INSTRUCTIONS. 23. CONTRACTOR SHALL COORDINATE RETURN AIR SYSTEM USED BY MECHANICAL HVAC SYSTEMS. IF AIR IS CONTRACTOR SHALL COORDINATE RETURN AIR SYSTEM USED BY MECHANICAL HVAC SYSTEMS. IF AIR IS RETURNED TO HVAC UNITS BY PLENUM RETURN, AND IF PLUMBING, SEWER AND VENT LINES ARE IN AIR PLENUMS, SUCH PIPING SHALL CONFORM TO NFPA 90A AND BE NONCOMBUSTIBLE. 24. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT CONNECTIONS. MODIFY HYDRONIC, WATER, VENT, SEWER, CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT CONNECTIONS. MODIFY HYDRONIC, WATER, VENT, SEWER, ELECTRICAL AND/OR GAS PIPING AS REQUIRED, FOR PROPER CONNECTION TO EQUIPMENT, OR TO EXISTING SYSTEMS.
AutoCAD SHX Text
(APPLIES TO ALL SHEETS)
AutoCAD SHX Text
(APPLIES TO ALL SHEETS)
AutoCAD SHX Text NEW WORK MATERIAL CONSISTS OF THE FOLLOWING: 1. DOMESTIC WATER INSIDE BUILDING: COPPER TYPE K AND L, ASTM B88 DOMESTIC WATER INSIDE BUILDING: COPPER TYPE K AND L, ASTM B88 2. DOMESTIC WATER OUTSIDE BUILDING: REFER TO CIVIL DOMESTIC WATER OUTSIDE BUILDING: REFER TO CIVIL MATERIAL FOR MODIFICATIONS TO EXISTING SYSTEMS SHALL CONSIST OF THE FOLLOWING: 1. CONDENSATE: COPPER TYPE L, ASTM B88 CONDENSATE: COPPER TYPE L, ASTM B88 2. SANITARY SEWER AND VENT: HUBLESS CAST IRON SOIL PIPE AND FITTINGS, ASTM A888 SANITARY SEWER AND VENT: HUBLESS CAST IRON SOIL PIPE AND FITTINGS, ASTM A888 3. DUCTWORK: GALVANIZED STEEL G90 DUCTWORK: GALVANIZED STEEL G90
AutoCAD SHX Text
(APPLIES TO ALL SHEETS)
AutoCAD SHX Text
PRESSURE REDUCING VALVE
CORRIDOR
RECEPTIONIST
CORRIDOR
STAIR
S103
CORRIDOR
CORRIDOR
SD
S
SD
S
S
SDSSDSS
S
SD
S
S
SDSSDS
76.0
CORRIDOR
SS
STAIR
76.0
Walter P. Moore and Associates, Inc.
601 North Mesa St., Suite 1475 El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-A pr -2
- 1 2:
P
M
C :\U se rs
\c ar di \C ar di na E ng in ee rin g C om m is si on in g\ C
AR
D
IN
A
Pr oj ec ts
-0
T H
H S
EP
P sy ch ia tri c C en te r I m pr ov em en ts \5
.0 _C
AD
_B
IM
\C
AD
\P
1.
0.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
SCALE: 1/8" = 1'-0"P1.0
01 BASEMENT PLUMBING IMPROVEMENT PLAN
SCALE: 1/4" = 1'-0"P1.0
02 BASEMENT PLUMBING IMPROVEMENT ENLARGED PLAN
P1.0
SCALE: 3/16" = 1'-0"P1.0
03 SITE PLUMBING IMPROVEMENT ENLARGED PLAN PLUMBING IMPROVEMENT
PLAN
AutoCAD SHX Text
4"DCW
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING 4"DCW
AutoCAD SHX Text
4"DCW
AutoCAD SHX Text
4"DCW
AutoCAD SHX Text
EXISTING 4"DCW
AutoCAD SHX Text
EXISTING 2"SS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6'-4"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1. C.O.P. AT APPROXIMATELY 10'-9"ABOVE FINISHED FLOOR. C.O.P. AT APPROXIMATELY 10'-9"ABOVE FINISHED FLOOR. FIELD COORDINATE. 2. OFFSET DOWN WITH 45° ELBOWS TO AVOID EXISTING OFFSET DOWN WITH 45° ELBOWS TO AVOID EXISTING SANITARY SEWER LINE. SUGGESTED HEIGHT 1'-3-1/4" ABOVE CEILING. FIELD COORDINATE. 3. INSTALL PIPE IN SPACE BETWEEN SANITARY SEWER PIPING INSTALL PIPE IN SPACE BETWEEN SANITARY SEWER PIPING AND FLEX DUCT SERVING HALLWAY DIFFUSER. 4. OFFSET PIPE WITH 45° ELBOWS TO AVOID VAV BOX. OFFSET PIPE WITH 45° ELBOWS TO AVOID VAV BOX. 5. DEMOLISH EXISTING PIPE HANGERS AS REQUIRED TO DEMOLISH EXISTING PIPE HANGERS AS REQUIRED TO ACCOMMODATE NEW PIPE. REPLACE DEMOLISHED HANGERS WITH TRAPEZE. REFER TO DETAIL 2 IN SHEET P2.0. 6. OFFSET PIPE EAST OF PARTITION WITH 45° ELBOWS AND OFFSET PIPE EAST OF PARTITION WITH 45° ELBOWS AND RUN PIPE ABOVE DUCT. 7. OFFSET DOWN WITH 45° ELBOWS TO AVOID CONCRETE BEAM. OFFSET DOWN WITH 45° ELBOWS TO AVOID CONCRETE BEAM. SUGGESTED C.O.P. HEIGHT 1'-11-1/2" ABOVE CEILING. FIELD COORDINATE AND RUN PARALLEL TO SUPPLY DUCT. 8. INSTALL PRESSURE REDUCING VALVE. INSTALL PRESSURE REDUCING VALVE. 9. SUGGESTED C.O.P. HEIGHT 5-1/2" ABOVE CEILING BEFORE SUGGESTED C.O.P. HEIGHT 5-1/2" ABOVE CEILING BEFORE CROSSING DOUBLE DOORS. INSTALL PIPE BELOW EXISTING DUCTWORK EAST OF DOUBLE DOORS. 10. RELOCATE EXISTING CABLES. MAINTAIN ACCESS TO RELOCATE EXISTING CABLES. MAINTAIN ACCESS TO DUCTWORK ACCESS PANELS. 11. REDUCE PIPE INSULATION THICKNESS IN PIPE SECTION REDUCE PIPE INSULATION THICKNESS IN PIPE SECTION BELOW EXISTING DUCTS AND FIT PIPE ABOVE CEILING. INSULATION TO COMPLY WITH R-VALUE AS REQUIRED BY CODE. 12. OFFSET PIPE UP WITH 45° ELBOWS, TO AVOID LIGHT OFFSET PIPE UP WITH 45° ELBOWS, TO AVOID LIGHT FIXTURE. 13. OFFSET DOWN AND CONNECT TO EXISTING DOMESTIC COLD OFFSET DOWN AND CONNECT TO EXISTING DOMESTIC COLD WATER MAIN. PROVIDE ISOLATION VALVE NEXT TO TEE. 14. REMOVE SECTION OF EXISTING WATER MAIN AS REQUIRED REMOVE SECTION OF EXISTING WATER MAIN AS REQUIRED TO ACCOMMODATE NEW TIE-IN. COORDINATE SYSTEM SHUT DOWN, WEEKEND AND OVERNIGHT WORK REQUIREMENTS WITH OWNER. 15. EXISTING 6" SANITARY SEWER LINE, FIELD VERIFY EXACT EXISTING 6" SANITARY SEWER LINE, FIELD VERIFY EXACT LOCATION. HAND DIG AS REQUIRED. 16. EXISTING ELECTRICAL CONDUIT, FIELD VERIFY EXACT EXISTING ELECTRICAL CONDUIT, FIELD VERIFY EXACT LOCATION. HAND DIG AS REQUIRED. REFER TO ELECTRICAL DRAWINGS. 17. PROVIDE 6" METAL SLEEVE AND LINK-SEAL. REFER TO PROVIDE 6" METAL SLEEVE AND LINK-SEAL. REFER TO CIVIL AND PLUMBING DETAILS. 18. NEW BACKFLOW PREVENTER IN ENCLOSURE WITH SLAB NEW BACKFLOW PREVENTER IN ENCLOSURE WITH SLAB MOUNTED HEATER. 19. FOR CONTINUATION REFER TO CIVIL DRAWINGS. FOR CONTINUATION REFER TO CIVIL DRAWINGS. 20. NEW WATER METER VAULT. REFER TO CIVIL DRAWINGS. NEW WATER METER VAULT. REFER TO CIVIL DRAWINGS. 21. INSTALL PRESSURE GAUGES ON EXISTING AND NEW LINES. INSTALL PRESSURE GAUGES ON EXISTING AND NEW LINES. 22. DRAIN PORT WITH ISOLATION VALVE, THREADED END FOR DRAIN PORT WITH ISOLATION VALVE, THREADED END FOR HOSE CONNECTION AND CAP. 23. MAINTAIN APPROPRIATE CLEARANCES FOR FIRE PROTECTION MAINTAIN APPROPRIATE CLEARANCES FOR FIRE PROTECTION VALVES AND ACCESSORIES. 24. TRANSITION FROM PVC TO COPPER USING RESTRAINED TRANSITION FROM PVC TO COPPER USING RESTRAINED FLANGE COUPLING ADAPTER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING 4"DCW
AutoCAD SHX Text
EXISTING 4"DCW
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1. FIRE PROTECTION SPRINKLER HEADS TO REMAIN IN FIRE PROTECTION SPRINKLER HEADS TO REMAIN IN EXISTING LOCATION, MAINTAIN ACTIVE AND PROTECT FROM ANY DAMAGE DURING CONSTRUCTION. 2. WORK SPACE IS LIMITED AND REQUIRES THAT WORK SPACE IS LIMITED AND REQUIRES THAT CONTRACTOR COORDINATE WITH OTHER TRADES TO AVOID SPACE CONFLICTS. IT IS ANTICIPATED THAT SPACE COORDINATION WILL BE DIFFICULT, SO THE VARIOUS TRADE CONTRACTORS MUST IDENTIFY AND RESOLVE SPACE CONFLICTS BEFORE COMMENCING CONSTRUCTION. CONTRACTOR SHALL OFFSET DUCTWORK AND PIPING AS NECESSARY TO FIT EQUIPMENT AND MATERIALS IN SPACE ALLOTTED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BFP-1
AutoCAD SHX Text
AutoCAD SHX Text
KEYED NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P1.0
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
AutoCAD SHX Text
P1.0
El Paso, Texas 79901
915.838.3100
DESIGNED BY
NO.
REVIEWED BY DRAWN BYPROJECT NO.
DATE REVISION
MG
Copyright © 2025 WALTER P MOORE AND ASSOCIATES, INC.
GRMGM11-25001-00
DATE
05-02-2025
ORIGINAL ISSUE
-M ay -2
- 8 :3
AM
C
:\U se rs \c ar di
\C ar di na
E ng in ee rin g
C om m is si on in g\
C
AR
D
IN
A Pr oj ec ts
-0
T
H H
S
EP
P sy ch ia tri c
C en te r I m pr ov em en ts
\5 .0
_C
AD
_B
IM
\C
AD
\P 2.
0.
dw g
EL PASO PSYCHIATRIC
CENTER:
THHS WATER
IMPROVEMENTS
4615 ALAMEDA AVE
EL PASO, TX 79905
100% CONSTRUCTION DOCUMENTS
CIVIL:
MEP:
ARCHITECT:
ELECTRICAL:
OWNER:
330 Eubank Ct, El Paso, Texas 79902 T.915.587.8023
PLUMBING DETAILS
0.3 MIN. 0.3 MIN.
0.3 MIN. 0.3 MIN.
SCALE: NONEP2.0
02 PIPE SUPPORT MODIFICATION AND INSTALLATION DETAIL
SCALE: NONEP2.0
03 PIPE CLEVIS HANGER DETAIL
SCALE: NONE
TYPICAL PIPE WALL AND FLOOR
PENETRATIONS DETAIL
P2.0
SCALE: NONEP2.0
04 PIPE PENETRATION DETAIL
SCALE: NONEP2.0
DOMESTIC WATER BACKFLOW
PREVENTER DETAIL
SCALE: NONEP2.0
THREADED ROD ATTACHMENTS FROM
DECK CONCRETE SLAB DETAIL
P2.0
AutoCAD SHX Text
EVERY 10'-0".
AutoCAD SHX Text
HANGER RODS TO OCCUR
AutoCAD SHX Text
DECK
AutoCAD SHX Text
STRUCTURAL
AutoCAD SHX Text
ALL THREADED HANGER,
AutoCAD SHX Text
AS REQUIRED
AutoCAD SHX Text
ARE IN CONFLICT WITH NEW
AutoCAD SHX Text
EXISTING PIPE
AutoCAD SHX Text
HEADER ANGLE
AutoCAD SHX Text
NEW PIPE
AutoCAD SHX Text
EXISTING PIPE
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
INSULATION SHIELD
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
HANGER
AutoCAD SHX Text
CLEVIS
AutoCAD SHX Text
CAULKING
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
WATER STOP
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
DEPTH AS REQUIRED*,
AutoCAD SHX Text
FIELD VERIFY ACTUAL DEPTH.
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
OUTSIDE
AutoCAD SHX Text
CONTINUOUS JACKETING THRU WALL PENETRATION.
AutoCAD SHX Text
MASTIC FINISH FLASHED AND COUNTER FLASHED INSIDE AND OUTSIDE
AutoCAD SHX Text
SEAL WITH FIRESTOP MATERIAL
AutoCAD SHX Text
B…
This is the start of the file's text. The full file is on GovTribe.