This is an electrical requirements specification document (DG 415-1) from June 2011 that establishes lighting standards and outlet requirements for the Iowa Department of Public Defense's Boone Army Aviation Support Facility (AASF) modernization project. The document provides detailed functional area specifications for 30 distinct spaces within the facility, including assembly halls, classrooms, training centers, administrative offices, and maintenance areas. Each functional area is assigned specific footcandle (FC) lighting levels ranging from 20 FC in storage areas to 70 FC in classrooms and learning centers, with corresponding electrical outlet requirements based on linear footage or square footage measurements. The specification includes specialized requirements for high-security areas such as the SIPRNET Room (50 FC with 1 duplex per wall), flammable materials storage (30 FC, explosion-proof), and the indoor firing range with tiered lighting demands of 50 FC for general lighting, 60 FC at the firing line, and 100 FC for direct/indirect target lighting. All electrical systems must comply with NFPA 70 (National Electrical Code) and IESNA Lighting Handbook standards, with lighting power densities meeting ANSI/ASHRAE/IESNA Standard 90.1-2004 for energy efficiency.

The specification establishes that general administrative and support areas should utilize T-8 fluorescent lamps with high-efficiency electronic ballasts to achieve 0.85 Watts/square foot lighting power density targets. Specialized areas designated as classified or explosion-proof zones require construction meeting those specifications for both lighting and power outlets. The document mandates multi-level switching or dimming capabilities in applicable spaces and notes that additional power provisions should be made for programmed equipment. Ground fault circuit interrupter (GFCI) protection is required for moisture-prone areas such as toilets, showers, and locker rooms. This electrical specification document serves as a technical foundation for the LED retrofit project encompassing 34,185 square feet at the facility, providing detailed parameters that contractors must meet during the modernization and installation of energy-efficient lighting systems and controls.

View the file

Other files

File Type Posted
L7 ldn6.pdf PDF
L1 blt-2x4.pdf PDF
Typical Office-Classroom Fixture.pdf PDF
OC1 BCS-WS-CS-DT-300.pdf PDF
L4 clx-strip-light-spec-sheet.pdf PDF
SOW BooneAASF_ReLighting.docx DOCX document
R1_LED Downlight.pdf PDF
LB1 dl_pgn_spec_WallPack.pdf PDF
F1-2_LED Flat Panel.pdf PDF
19A25-AASF1-001-11x17.pdf PDF
L6 LED_V70269_CS51922.pdf PDF
R4_LED Retrofit.pdf PDF
1370207-event.pdf PDF
Boone_AASF_Lighing_Data.xlsx XLSX spreadsheet
R2-3_LED Linear Recessed.pdf PDF
L5 - AVX_led.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DG 415-1

01 JUNE 2011

Table 5. Electrical Requirements

FUNCTIONAL AREA LIGHTING OUTLETS NOTES

1 Assembly Hall 50 FC 1 duplex per 10 LF of wall

2 Classrooms 70 FC 1 duplex per 10 LF of wall

3 Library/Classroom 70 FC 1 duplex per 10 LF of wall

4 Learning Center 70 FC 1 duplex per workstation 3

5 Distance Learning Center 70 FC 1 duplex per workstation 3

6 Indoor Firing Range - 2 duplex 1 7 Training

Device/Simulation Center 50 FC REF: Vender Data 2

8 Training Aid Storage 20 FC 1 duplex per 20 LF of wall 9 Kitchen 50 FC minimum of 1 duplex per 10 LF of wall 10 Break Room 50 FC 1 duplex per 10 LF of wall

11 Vending Area 30 FC 1 duplex per 10 LF of wall 2

12 Toilets/Shower 30 FC 1 duplex GFCI per 2 sinks 13 Flammable Materials

Storage 30 FC 1 duplex XP

14 Family Readiness Office 50 FC 1 duplex per wall

15 RAPIDS Office 50 FC 1 duplex per wall 16 Recruiting/Retention 50 FC 1 duplex per wall

17 Audio/Visual Storage 35 FC 1 duplex per 20 LF of wall

18 Table/Chair Storage 20 FC 1 duplex per 20 LF of wall

19 Physical Fitness 50 FC 2 duplex per 8 LF of wall 2 20 Controlled Waste

Handling Facility 30 FC 1 duplex per 20 LF of wall

21 Unit Administration 50 FC 2 duplex per 50 ft2

22 Unit Storage (Heated) 30 FC 1 duplex per 20 LF of wall

23 Locker Room Space 30 FC 1 duplex GFCI 24 Maintenance Training

Workbays 50 FC 1 duplex per 10 LF of wall 2

25 Supervisor’s Office 50 FC 1 duplex per wall

26 Inspection and Library 50 FC 1 duplex per 10 LF of wall

27 Tool Room 30 FC 1 duplex per 20 LF of wall

28 Supply Room 30 FC 1 duplex per 20 LF of wall

29 Vault 30 FC 1 duplex

30 SIPRNET Room 50 FC 1 duplex per wall 2

___ 40

DG 415-1

01 JUNE 2011

TABLE 5 – ABBREVIATIONS

FC foot-candles

GFCI ground fault circuit interrupter

LF linear feet

XP explosion proof

TABLE 5 – NOTES

All Electrical Power Systems/Service outlets in spaces must be designed and constructed in accordance with NFPA 70, National Electrical Code to accommodate the actual equipment layout. All Classified areas must be explosion proof construction to include lighting and power.

Lighting Systems must be designed in accordance with IESNA Lighting Handbook. The Lighting Power Densities in Watts/ST input must be in accordance with ANSI/ASHRAE/IESNA Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings. General Administrative and support areas lighting fixtures should be T-8 fluorescent lamps and high efficiency electronic ballasts to achieve a 0.85 Watts/SF lighting power density.

1. INDOOR FIRING RANGE LIGHTING FC REQUIREMENTS:

General lighting Behind Shooter 50 FC; Task Lighting @ Firing Line 60 FC; Direct/Indirect Lighting on Targets 100 FC.

2. Additional power for programmed equipment should be provided.

3. Multi-level switching or dimming should be provided.